 "manufacturer": "York",
 "manufacturer_slug": "york",
 "model": "YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)",
 "model_slug": "yvwa-sc-eq",
 "short_model": "YVWA",
 "aliases": [
  "YORK YVWA",
  "YVWA chiller",
  "YVWA heat pump",
  "SC-EQ",
  "SE-SCC1001-1"
 ],
 "equipment_type": "Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)",
 "applies_to": "YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.",
 "summary": "YVWA chillers connect to a BAS through the SC-EQ communication card on BACnet MS/TP (or Modbus RTU / N2). The BAS can start/stop the unit, write the chilled liquid setpoint, current limit and heating setpoint, and switch between chiller and heat pump mode. Read-only points cover chilled and condenser liquid temperatures, per-system pressures, % FLA, hours and starts, VSD values, valve positions and multistate operational and fault codes per system.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "SC-EQ software 3.3.0.18",
 "default_device_instance": "5000 + MAC address",
 "access_inferred": true,
 "notes": [
  "Access is inferred: the sheet has no read/write column. The remote block (AV 1, AV 2, AV 4, BV 1, BV 3, BV 4) is treated as commandable; everything else as read-only.",
  "System 2 points only report on two-compressor units. MV 2 / AV 502 are printed twice: Sys 1 fault code on two-compressor units and the unit fault code on one-compressor units, each with its own code table; they are merged here and both tables are given.",
  "Operational and fault code MVs are the printed code + 1, as the doc's status code tables say; the AV copies (AV 501-504) carry the raw code. Binary states are as printed.",
  "This list has no MV 65001 Units object. Units shown are the IP units.",
  "Spare and reserved objects are left out."
 ],
 "source": {
  "title": "YVWA SC-EQ BAS Points List",
  "doc_number": null,
  "revision_date": "Rev 2.1, 2019-11-05",
  "url": "https://docs.johnsoncontrols.com/chillers/api/khub/documents/GBppk5iQWBiKzUyxqfeOFA/content"
 },
 "integration": {
  "summary": "Put the chiller in remote control (BV 20 reads Remote), then start/stop it with BV 1 and write the chilled liquid setpoint (AV 1) and current limit (AV 2); heat pump units also take BV 3 (mode) and AV 4 (heating setpoint). Read BV 5 for chiller run, the leaving chilled liquid temperature, VSD frequency and BV 6 for the chiller alarm; the fault code MVs give the cause.",
  "minimum_points": [
   {
    "ref": "BV 1",
    "name": "REM START STOP CMD",
    "why": "Remote start/stop (1 = run)"
   },
   {
    "ref": "AV 1",
    "name": "REM CHILLED LIQ SETPOINT",
    "why": "Remote chilled liquid setpoint"
   },
   {
    "ref": "AV 2",
    "name": "REM CURRENT LIMIT SETP",
    "why": "Remote current limit, %"
   },
   {
    "ref": "BV 5",
    "name": "CHILLER RUN",
    "why": "Chiller running"
   },
   {
    "ref": "BV 20",
    "name": "LOCAL REMOTE CONTROL MODE",
    "why": "Must read Remote (1) for BMS control"
   },
   {
    "ref": "AV 5",
    "name": "LEAVING CHILLED LIQ TEMP",
    "why": "Leaving chilled liquid temperature"
   },
   {
    "ref": "AV 27",
    "name": "VSD OUTPUT FREQUENCY",
    "why": "Compressor VSD frequency (load indication)"
   },
   {
    "ref": "BV 6",
    "name": "CHILLER ALARM",
    "why": "Chiller alarm active"
   },
   {
    "ref": "MV 2",
    "name": "SYS 1 FAULT CODE / FAULT CODE",
    "why": "Fault/inhibit code, Sys 1 or unit (1 = none)"
   }
  ],
  "enable": "BV 20 shows Local or Remote control mode. The points list gives no point to change it and no write-enable point. On heat pump units BV 3 selects chiller or heat pump operation.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The BAS connects to the SC-EQ J12 port (RS-485: +, -, COM/REF, SHLD). The card detects BACnet MS/TP, Modbus RTU or N2 and the baud rate by itself; allow up to 120 seconds after power-up.",
   "The MAC address (1-127) is set on DIP switch SW1 (switch 8 unused). Cycle the card's power after changing it.",
   "The device instance defaults to 5000 + the MAC address (MAC 6 gives 5006). To use another number, set Device Instance Mode to Manual and enter the instance with the SC-AP / MAP tool, or write BV 65000 (mode) and AV 65000 (instance ID)."
  ],
  "gotchas": [
   "The remote (commandable) setpoints read as unreliable until the BAS writes them the first time.",
   "The SC-EQ only exposes the points that apply to the chiller it detects; if it replaces an E-Link, re-discover the device so old non-applicable points don't sit offline.",
   "The fault code table differs between one- and two-compressor units; check the compressor count before decoding MV 2."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 1,
   "name": "REM CHILLED LIQ SETPOINT",
   "description": "Remote Chilled Liquid Setpoint",
   "units": "°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "REM CURRENT LIMIT SETP",
   "description": "Remote Current Limit Setpoint",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "REM HEATING SETPOINT",
   "description": "Remote Heating Setpoint",
   "units": "°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "REM START STOP CMD",
   "description": "Remote Start / Stop Command",
   "units": "",
   "access": "C",
   "states": "0=Stop, 1=Run"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "REM OPERATING MODE",
   "description": "Remote Operating Mode",
   "units": "",
   "access": "C",
   "states": "0=Chiller, 1=Heatpump"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "HISTORY REQUEST",
   "description": "History buffer 1 request (live / history data)",
   "units": "",
   "access": "C",
   "states": "0=Live Data, 1=History 1 Data"
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "LEAVING CHILLED LIQ TEMP",
   "description": "Leaving Chilled Liquid Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "ENTERING CHILLED LIQ TEMP",
   "description": "Entering Chilled Liquid Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "VSD INT AMBIENT TEMP",
   "description": "VSD Internal Ambient Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "LEAVING COND LIQ TEMP",
   "description": "Leaving Condenser Liquid Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "SYS 1 DISCH TEMP",
   "description": "Sys 1 Discharge Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "ENTERING COND LIQ TEMP",
   "description": "Entering Condenser Liquid Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "SYS 1 OIL PRESS",
   "description": "Sys 1 Oil Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "SYS 1 EVAP PRESS",
   "description": "Sys 1 Evaporator Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "SYS 1 DISCH PRESS",
   "description": "Sys 1 Discharge Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "SYS 1 COMP PCT FLA",
   "description": "Sys 1 Compressor % Full Load Amps",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "SYS 1 HOURS",
   "description": "Sys 1 Total Run Hours",
   "units": "Hr",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "SYS 1 STARTS",
   "description": "Sys 1 Total Number of Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "SYS 1 HIGHEST MOTOR TEMP",
   "description": "Sys 1 Highest Motor Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "SYS 2 HIGHEST MOTOR TEMP",
   "description": "Sys 2 Highest Motor Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "SYS 1 ECON TEMP",
   "description": "Sys 1 Economizer Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "SYS 2 OIL PRESS",
   "description": "Sys 2 Oil Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "SYS 2 EVAP PRESS",
   "description": "Sys 2 Evaporator Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "SYS 2 DISCH PRESS",
   "description": "Sys 2 Discharge Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "SYS 2 COMP PCT FLA",
   "description": "Sys 2 Compressor % Full Load Amps",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "SYS 2 HOURS",
   "description": "Sys 2 Total Run Hours",
   "units": "Hr",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "SYS 2 STARTS",
   "description": "Sys 2 Total Number of Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "VSD OUTPUT FREQUENCY",
   "description": "VSD Output Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "SYS 1 COND LEVEL VALVE PCT",
   "description": "Sys 1 Condenser Level Control Valve % Open",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "SYS 2 COND LEVEL VALVE PCT",
   "description": "Sys 2 Condenser Level Control Valve % Open",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "CHILLER RUN",
   "description": "Chiller Run",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "CHILLER ALARM",
   "description": "Chiller Alarm (0=No Alarm, 1=Alarm Active)",
   "units": "",
   "access": "R",
   "states": "0=No Alarm, 1=Alarm Active"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "VSD AUX COOLANT PUMP",
   "description": "VSD aux coolant pump (aux pump control enabled)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "EVAP COND PUMP STATUS",
   "description": "Evaporator/Condenser Pump Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "SYS 1 COMP RUN STATUS",
   "description": "Sys 1 Compressor Run Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "SYS 2 COMP RUN STATUS",
   "description": "Sys 2 Compressor Run Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "SYS 1 VI STEP SOL VALVE 1 STATUS",
   "description": "Sys 1 VI Step Solenoid Valve 1 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "SYS 2 VI STEP SOL VALVE 1 STATUS",
   "description": "Sys 2 VI Step Solenoid Valve 1 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "SYS 1 VI STEP SOL VALVE 2 STATUS",
   "description": "Sys 1 VI Step Solenoid Valve 2 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "SYS 2 VI STEP SOL VALVE 2 STATUS",
   "description": "Sys 2 VI Step Solenoid Valve 2 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "SYS 1 OIL LEVEL SWITCH STATUS",
   "description": "Sys 1 oil level switch status (oil level option)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "SYS 2 OIL LEVEL SWITCH STATUS",
   "description": "Sys 2 oil level switch status (oil level option)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "SYS 1 LIQ REF INJ VALVE STATUS",
   "description": "Sys 1 Liquid Refrigerant Injection Valve Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "SYS 2 LIQ REF INJ VALVE STATUS",
   "description": "Sys 2 Liquid Refrigerant Injection Valve Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "COOLING TYPE",
   "description": "Cooling Type",
   "units": "",
   "access": "R",
   "states": "0=Water, 1=Glycol"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "LOCAL REMOTE CONTROL MODE",
   "description": "Local Remote Control Mode",
   "units": "",
   "access": "R",
   "states": "0=Local, 1=Remote"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "DISPLAY UNITS",
   "description": "Display Units",
   "units": "",
   "access": "R",
   "states": "0=Imperial, 1=SI"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "SYS 1 HOT GAS BYPASS VALVE STATUS",
   "description": "Sys 1 hot gas bypass valve status (hot gas option)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "SYS 2 HOT GAS BYPASS VALVE STATUS",
   "description": "Sys 2 hot gas bypass valve status (hot gas option)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "HEATPUMP",
   "description": "Heatpump",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "SYS 1 OPERATIONAL CODE",
   "description": "Sys 1 Operational Code",
   "units": "",
   "access": "R",
   "states": "64=Manual Override, 65=Daily Schedule Shutdown, 66=Unit Switch OFF, 67=Remote Controlled Shutdown, 69=Chilled Evap Water Flow Switch Shutdown, 70=VSD Cooling Shutdown, 71=Invalid Serial Number, 72=Condenser Liquid Flow Switch Shutdown, 73=VSD Shutdown - Requesting Fault Data, 75=No Run Permissive, 76=Anti-Recycle Timer Active, 77=System Switch OFF, 78=System Not Running, 79=System Running, 80=Discharge Pressure Limiting, 81=Evaporator Pressure Limiting, 82=Motor Current Limiting, 83=OPD Mitigation, 84=BAS Motor Current Limiting, 85=Remote Motor Current Limiting, 86=System Shutting Down, 87=VSD PreCharging, 88=VSD Baseplate Temperature Limiting, 89=VSD Internal Ambient Temperature Limiting, 90=Leaving Chilled Liquid Temperaure Limiting, 91=Oil Filter Clogged, 93=Pulldown Motor Current Limiting, 94=Cooling Demand Shutdown"
  },
  {
   "type": "AV",
   "instance": 501,
   "name": "SYS 1 OPERATIONAL CODE AV",
   "description": "Sys 1 Operational Code AV",
   "units": "",
   "access": "R",
   "states": "63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 68=Chilled Evap Water Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Invalid Serial Number, 71=Condenser Liquid Flow Switch Shutdown, 72=VSD Shutdown - Requesting Fault Data, 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Evaporator Pressure Limiting, 81=Motor Current Limiting, 82=OPD Mitigation, 83=BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD PreCharging, 87=VSD Baseplate Temperature Limiting, 88=VSD Internal Ambient Temperature Limiting, 89=Leaving Chilled Liquid Temperaure Limiting, 90=Oil Filter Clogged, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "SYS 1 FAULT CODE / FAULT CODE",
   "description": "Sys 1 fault code (two-compressor units) or unit fault code (one-compressor units)",
   "units": "",
   "access": "R",
   "states": "Two-compressor units: 1=No Faults/Inhbits Present, 4=Low Chilled Liquid Temperature, 6=Low RTC Battery Voltage, 7=Invalid Number of Compressors Selected, 8=VSD Communications Failure, 9=Pre-charge Low DC Bus Voltage, 10=Pre-charge DC Bus Voltage Imbalance, 11=High DC Bus Voltage, 12=Low DC Bus Voltage, 13=DC Bus Voltage Imbalance, 14=High VSD Ambient Temperature, 15=Single Phase Input, 16=VSD Power Supply Fault, 17=VSD Logic Board Fault, 18=Motor Current Overload, 19=CT Plug Fault, 20=High Leaving Condenser Liquid Temp, 21=VSD Initialization Failure, 28=High Discharge Pressure, 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Evaporator Pressure, 32=High Discharge Temperature, 33=Low Evap Pressure Smart Freeze, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=Pre-charge Low DC Bus Voltage, 39=Pre-charge DC Bus Voltage Imbalance, 40=High DC Bus Voltage, 41=Low DC Bus Voltage, 42=DC Bus Voltage Imbalance, 43=High Motor Current, 44=Motor Current Overload, 45=IGBT Gate Driver Fault, 46=High Baseplate Temperature, 47=Single Phase Input, 48=VSD Run Signal Fault, 49=High Discharge Press (HPCO), 50=Sys Low Evap Press Refrig Temp, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Economizer Superheat, 54=Oil Level Low, 55=Sys Low Evap Press LCHLT. One-compressor units: 1=No Faults/Inhbits Present, 4=Low Chilled Liquid Temperature, 6=Low RTC Battery Voltage, 7=High Leaving Condenser Liquid Temp, 8=VSD Communications Failure, 9=VSD Initialization Failure, 10=Filter - High Heatsink Temperature, 11=Filter - High DC Bus Voltage, 12=Filter - High Phase C Current, 13=Filter - High Phase B Current, 14=Filter - High Phase A Current, 15=Filter - Phase Locked Loop, 16=Filter - Logic Board Power Supply, 17=Filter - Precharge - Low DC Bus Voltage 2, 18=Filter - Precharge - Low DC Bus Voltage 1, 19=Filter - Low DC Bus Voltage, 20=Filter - DC Bus Voltage Imbalance, 21=Filter - Input Current Overload, 22=Filter - Run Signal, 23=Filter - DC Current Transformer 1, 24=Filter - DC Current Transformer 2, 25=Filter - High Baseplate Temperature (Vyper), 26=IEEE-519 Filter Fault, 28=High Discharge Pressure (Software), 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Evaporator Pressure, 32=High Discharge Temperature, 33=Low Evap Pressure Smart Freeze, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=VSD - Precharge - Low DC Bus Voltage 1, 39=VSD - Precharge - DC Bus Voltage Imbalance, 40=VSD - High DC Bus Voltage, 41=VSD - Low DC Bus Voltage, 42=VSD - DC Bus Voltage Imbalance, 43=VSD - 105 % Motor Current Overload, 44=VSD - 105 % Motor Current Overload, 45=VSD - Motor Current Imbalance, 46=VSD - High Inverter Baseplate Temperature, 47=VSD - Single Phase Input Voltage, 48=VSD - Run Signal, 49=High Discharge Press ( HPCO), 50=Low Evaporator Press Refrig Temp, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Economizer Superheat, 54=Oil Level Low, 55=Low Evap Press LCHLT, 59=VSD - Precharge - Low DC Bus Voltage 2, 60=VSD - Precharge Lockout, 61=VSD - Serial Receive, 62=VSD - High Phase A Motor Current, 63=VSD - High Phase B Motor Current, 101=VSD - High Phase C Motor Current, 102=VSD - Phase A Gate Driver, 103=VSD - Phase B Gate Driver, 104=VSD - Phase C Gate Driver, 105=VSD - High Phase A Inverter Baseplate Temperature, 106=VSD - High Phase B Inverter Baseplate Temperature, 107=VSD - High Phase C Inverter Baseplate Temperature, 108=VSD - High Converter Heatsink Temperature, 109=VSD - Low Inverter Baseplate Temperature, 110=VSD - Low Phase A Inverter Baseplate Temperature, 111=VSD - Low Phase B Inverter Baseplate Temperature, 112=VSD - Low Phase C Inverter Baseplate Temperature, 113=VSD - Low Converter Heatsink Temperature, 114=VSD - High Internal Ambient Temperature, 115=VSD - Logic Board Power Supply, 116=VSD - Invalid Current Scale Selection, 117=VSD - High Phase A Inverter Heatsink Temperature, 118=VSD - High Phase B Inverter Heatsink Temperature, 119=VSD - High Phase C Inverter Heatsink Temperature, 120=VSD - Low Phase A Inverter Heatsink Temperature, 121=VSD - Low Phase B Inverter Heatsink Temperature, 122=VSD - Low Phase C Inverter Heatsink Temperature, 123=VSD - Logic Board Processor, 124=VSD – Undefined Fault"
  },
  {
   "type": "AV",
   "instance": 502,
   "name": "SYS 1 FAULT CODE AV / FAULT CODE AV",
   "description": "Sys 1 / unit fault code, raw value (see MV 2)",
   "units": "",
   "access": "R",
   "states": "Two-compressor units: 0=No Faults/Inhbits Present, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage, 9=Pre-charge DC Bus Voltage Imbalance, 10=High DC Bus Voltage, 11=Low DC Bus Voltage, 12=DC Bus Voltage Imbalance, 13=High VSD Ambient Temperature, 14=Single Phase Input, 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload, 18=CT Plug Fault, 19=High Leaving Condenser Liquid Temp, 20=VSD Initialization Failure, 27=High Discharge Pressure, 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Evaporator Pressure, 31=High Discharge Temperature, 32=Low Evap Pressure Smart Freeze, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage, 38=Pre-charge DC Bus Voltage Imbalance, 39=High DC Bus Voltage, 40=Low DC Bus Voltage, 41=DC Bus Voltage Imbalance, 42=High Motor Current, 43=Motor Current Overload, 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input, 47=VSD Run Signal Fault, 48=High Discharge Press (HPCO), 49=Sys Low Evap Press Refrig Temp, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Economizer Superheat, 53=Oil Level Low, 54=Sys Low Evap Press LCHLT. One-compressor units: 0=No Faults/Inhbits Present, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=High Leaving Condenser Liquid Temp, 7=VSD Communications Failure, 8=VSD Initialization Failure, 9=Filter - High Heatsink Temperature, 10=Filter - High DC Bus Voltage, 11=Filter - High Phase C Current, 12=Filter - High Phase B Current, 13=Filter - High Phase A Current, 14=Filter - Phase Locked Loop, 15=Filter - Logic Board Power Supply, 16=Filter - Precharge - Low DC Bus Voltage 2, 17=Filter - Precharge - Low DC Bus Voltage 1, 18=Filter - Low DC Bus Voltage, 19=Filter - DC Bus Voltage Imbalance, 20=Filter - Input Current Overload, 21=Filter - Run Signal, 22=Filter - DC Current Transformer 1, 23=Filter - DC Current Transformer 2, 24=Filter - High Baseplate Temperature (Vyper), 25=IEEE-519 Filter Fault, 27=High Discharge Pressure (Software), 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Evaporator Pressure, 31=High Discharge Temperature, 32=Low Evap Pressure Smart Freeze, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=VSD - Precharge - Low DC Bus Voltage 1, 38=VSD - Precharge - DC Bus Voltage Imbalance, 39=VSD - High DC Bus Voltage, 40=VSD - Low DC Bus Voltage, 41=VSD - DC Bus Voltage Imbalance, 42=VSD - 105 % Motor Current Overload, 43=VSD - 105 % Motor Current Overload, 44=VSD - Motor Current Imbalance, 45=VSD - High Inverter Baseplate Temperature, 46=VSD - Single Phase Input Voltage, 47=VSD - Run Signal, 48=High Discharge Press ( HPCO), 49=Low Evaporator Press Refrig Temp, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Economizer Superheat, 53=Oil Level Low, 54=Low Evap Press LCHLT, 58=VSD - Precharge - Low DC Bus Voltage 2, 59=VSD - Precharge Lockout, 60=VSD - Serial Receive, 61=VSD - High Phase A Motor Current, 62=VSD - High Phase B Motor Current, 100=VSD - High Phase C Motor Current, 101=VSD - Phase A Gate Driver, 102=VSD - Phase B Gate Driver, 103=VSD - Phase C Gate Driver, 104=VSD - High Phase A Inverter Baseplate Temperature, 105=VSD - High Phase B Inverter Baseplate Temperature, 106=VSD - High Phase C Inverter Baseplate Temperature, 107=VSD - High Converter Heatsink Temperature, 108=VSD - Low Inverter Baseplate Temperature, 109=VSD - Low Phase A Inverter Baseplate Temperature, 110=VSD - Low Phase B Inverter Baseplate Temperature, 111=VSD - Low Phase C Inverter Baseplate Temperature, 112=VSD - Low Converter Heatsink Temperature, 113=VSD - High Internal Ambient Temperature, 114=VSD - Logic Board Power Supply, 115=VSD - Invalid Current Scale Selection, 116=VSD - High Phase A Inverter Heatsink Temperature, 117=VSD - High Phase B Inverter Heatsink Temperature, 118=VSD - High Phase C Inverter Heatsink Temperature, 119=VSD - Low Phase A Inverter Heatsink Temperature, 120=VSD - Low Phase B Inverter Heatsink Temperature, 121=VSD - Low Phase C Inverter Heatsink Temperature, 122=VSD - Logic Board Processor, 123=VSD – Undefined Fault"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "SYS 2 OPERATIONAL CODE",
   "description": "Sys 2 Operational Code",
   "units": "",
   "access": "R",
   "states": "64=Manual Override, 65=Daily Schedule Shutdown, 66=Unit Switch OFF, 67=Remote Controlled Shutdown, 69=Chilled Evap Water Flow Switch Shutdown, 70=VSD Cooling Shutdown, 71=Invalid Serial Number, 72=Condenser Liquid Flow Switch Shutdown, 73=VSD Shutdown - Requesting Fault Data, 75=No Run Permissive, 76=Anti-Recycle Timer Active, 77=System Switch OFF, 78=System Not Running, 79=System Running, 80=Discharge Pressure Limiting, 81=Evaporator Pressure Limiting, 82=Motor Current Limiting, 83=OPD Mitigation, 84=BAS Motor Current Limiting, 85=Remote Motor Current Limiting, 86=System Shutting Down, 87=VSD PreCharging, 88=VSD Baseplate Temperature Limiting, 89=VSD Internal Ambient Temperature Limiting, 90=Leaving Chilled Liquid Temperaure Limiting, 91=Oil Filter Clogged, 93=Pulldown Motor Current Limiting, 94=Cooling Demand Shutdown"
  },
  {
   "type": "AV",
   "instance": 503,
   "name": "SYS 2 OPERATIONAL CODE AV",
   "description": "Sys 2 Operational Code AV",
   "units": "",
   "access": "R",
   "states": "63=Manual Override, 64=Daily Schedule Shutdown, 65=Unit Switch OFF, 66=Remote Controlled Shutdown, 68=Chilled Evap Water Flow Switch Shutdown, 69=VSD Cooling Shutdown, 70=Invalid Serial Number, 71=Condenser Liquid Flow Switch Shutdown, 72=VSD Shutdown - Requesting Fault Data, 74=No Run Permissive, 75=Anti-Recycle Timer Active, 76=System Switch OFF, 77=System Not Running, 78=System Running, 79=Discharge Pressure Limiting, 80=Evaporator Pressure Limiting, 81=Motor Current Limiting, 82=OPD Mitigation, 83=BAS Motor Current Limiting, 84=Remote Motor Current Limiting, 85=System Shutting Down, 86=VSD PreCharging, 87=VSD Baseplate Temperature Limiting, 88=VSD Internal Ambient Temperature Limiting, 89=Leaving Chilled Liquid Temperaure Limiting, 90=Oil Filter Clogged, 92=Pulldown Motor Current Limiting, 93=Cooling Demand Shutdown"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "SYS 2 FAULT CODE",
   "description": "Sys 2 Fault Code",
   "units": "",
   "access": "R",
   "states": "1=No Faults/Inhbits Present, 4=Low Chilled Liquid Temperature, 6=Low RTC Battery Voltage, 7=Invalid Number of Compressors Selected, 8=VSD Communications Failure, 9=Pre-charge Low DC Bus Voltage, 10=Pre-charge DC Bus Voltage Imbalance, 11=High DC Bus Voltage, 12=Low DC Bus Voltage, 13=DC Bus Voltage Imbalance, 14=High VSD Ambient Temperature, 15=Single Phase Input, 16=VSD Power Supply Fault, 17=VSD Logic Board Fault, 18=Motor Current Overload, 19=CT Plug Fault, 20=High Leaving Condenser Liquid Temp, 21=VSD Initialization Failure, 28=High Discharge Pressure, 29=High Differential Oil Pressure, 30=Low Differential Oil Pressure, 31=Low Evaporator Pressure, 32=High Discharge Temperature, 33=Low Evap Pressure Smart Freeze, 34=Eductor Clog Fault, 35=Sensor Failure, 36=Low Motor Current, 37=High Motor Temperature, 38=Pre-charge Low DC Bus Voltage, 39=Pre-charge DC Bus Voltage Imbalance, 40=High DC Bus Voltage, 41=Low DC Bus Voltage, 42=DC Bus Voltage Imbalance, 43=High Motor Current, 44=Motor Current Overload, 45=IGBT Gate Driver Fault, 46=High Baseplate Temperature, 47=Single Phase Input, 48=VSD Run Signal Fault, 49=High Discharge Press (HPCO), 50=Sys Low Evap Press Refrig Temp, 51=Control Voltage Fault, 52=Low Discharge Superheat, 53=Low Economizer Superheat, 54=Oil Level Low, 55=Sys Low Evap Press LCHLT"
  },
  {
   "type": "AV",
   "instance": 504,
   "name": "SYS 2 FAULT CODE AV",
   "description": "Sys 2 Fault Code AV",
   "units": "",
   "access": "R",
   "states": "0=No Faults/Inhbits Present, 3=Low Chilled Liquid Temperature, 5=Low RTC Battery Voltage, 6=Invalid Number of Compressors Selected, 7=VSD Communications Failure, 8=Pre-charge Low DC Bus Voltage, 9=Pre-charge DC Bus Voltage Imbalance, 10=High DC Bus Voltage, 11=Low DC Bus Voltage, 12=DC Bus Voltage Imbalance, 13=High VSD Ambient Temperature, 14=Single Phase Input, 15=VSD Power Supply Fault, 16=VSD Logic Board Fault, 17=Motor Current Overload, 18=CT Plug Fault, 19=High Leaving Condenser Liquid Temp, 20=VSD Initialization Failure, 27=High Discharge Pressure, 28=High Differential Oil Pressure, 29=Low Differential Oil Pressure, 30=Low Evaporator Pressure, 31=High Discharge Temperature, 32=Low Evap Pressure Smart Freeze, 33=Eductor Clog Fault, 34=Sensor Failure, 35=Low Motor Current, 36=High Motor Temperature, 37=Pre-charge Low DC Bus Voltage, 38=Pre-charge DC Bus Voltage Imbalance, 39=High DC Bus Voltage, 40=Low DC Bus Voltage, 41=DC Bus Voltage Imbalance, 42=High Motor Current, 43=Motor Current Overload, 44=IGBT Gate Driver Fault, 45=High Baseplate Temperature, 46=Single Phase Input, 47=VSD Run Signal Fault, 48=High Discharge Press (HPCO), 49=Sys Low Evap Press Refrig Temp, 50=Control Voltage Fault, 51=Low Discharge Superheat, 52=Low Economizer Superheat, 53=Oil Level Low, 54=Sys Low Evap Press LCHLT"
  },
  {
   "type": "AV",
   "instance": 409,
   "name": "LEAD SYSTEM NUMBER",
   "description": "Lead System Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "LOCAL LVG CHILL COND LIQ SETP",
   "description": "Local Leaving Chilled/Condenser Liquid Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "LOW LEAVING CHILL COND LIQ CUT",
   "description": "Low Leaving Chilled/Condenser Liquid Temp Cutout",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "SYS 1 ECON VALVE PCT",
   "description": "Sys 1 Economizer Valve % Open",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "SYS 2 ECON VALVE PCT",
   "description": "Sys 2 Economizer Valve % Open",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "SYS 2 ECON TEMP",
   "description": "Sys 2 Economizer Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "VSD DC BUS VOLT",
   "description": "VSD DC Bus Voltage",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "REM LVG CHILL COND LIQ SETP",
   "description": "Remote Leaving Chilled/Condenser Liquid Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "SYS 1 SUBCOOLED LIQ REF TEMP",
   "description": "Sys 1 Subcooled Liquid Refrigerant Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "COOLING HEATING RANGE",
   "description": "Cooling/Heating Range",
   "units": "°F (diff)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "SYS 1 ECON PRESS",
   "description": "Sys 1 Economizer Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "SYS 2 ECON PRESS",
   "description": "Sys 2 Economizer Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "SYS 2 DISCH TEMP",
   "description": "Sys 2 Discharge Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "SYS 2 SUBCOOLED LIQ REF TEMP",
   "description": "Sys 2 Subcooled Liquid Refrigerant Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "SYS 1 LOCKOUT",
   "description": "Sys 1 Lockout",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "SYS 2 LOCKOUT",
   "description": "Sys 2 Lockout",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "SYS 1 ECON DRAIN VALVE",
   "description": "Sys 1 economizer drain solenoid valve (CTS compressor)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "SYS 2 ECON DRAIN VALVE",
   "description": "Sys 2 economizer drain solenoid valve (CTS compressor)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/york/yvwa-sc-eq",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}