Ceiling-mounted precision split cooling unit · BACnet points list

Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card) BACnet points list

Updated 6 November 2026

Short answer

The Liebert Mini-Mate2 1-5 ton and 8 ton map is a short legacy list: unit status, temperature and humidity readings and setpoints, an on/off control word and alarm words where several alarms share one object as bits. Only use it with the card variant named in the title.

This page lists 48 BACnet objects for the Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Equipment
Ceiling-mounted precision split cooling unit
Equipment type
VRF & split air conditioners
BACnet objects
48 (11 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 48 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 4bc01_1Control word: unit on/off and lockouts (bit-coded)Write
AV 9bs10_1Return air temperature setpoint, °CWrite
AV 10bs12_1Humidity setpoint, %RHWrite
AV 5bs01_1Inlet air temperature, °CRead
AV 6bs02_1Return humidity, %RHRead
AV 8bs09_1Temperature control capacity, %Read
AV 1ba01_1Alarm word 1 (bit-coded)Read

Network setup

Watch out for

Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

48 of 48 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card) BACnet Points List
DescriptionStates
BV1ba21_1Internal Communications FailureReadActive = alarm
BV7ba27_1High TemperatureReadActive = alarm
BV8ba28_1Low TemperatureReadActive = alarm
BV9ba29_1High Return HumidityReadActive = alarm
BV10ba30_1Low Return HumidityReadActive = alarm
BV11ba31_1Humidifier ProblemReadActive = alarm
BV4ba24_1Loss of Air FlowReadActive = alarm
BV6ba26_1Clogged Air FilterReadActive = alarm
BV12ba32_1Smoke DetectedReadActive = alarm
BV5ba25_1Ext Standby Glycol Pump OnReadActive = alarm
BV14ba34_1Ext Standby Unit On (Not in 1-5 ton unit)ReadActive = alarm
BV13ba33_1Supply Chilled Water Loss of FlowReadActive = alarm
BV16ba36_1Loss Of PowerReadActive = alarm
BV17ba37_1Custom Alarm #1ReadActive = alarm
BV18ba38_1Custom Alarm #2ReadActive = alarm
BV19ba39_1Custom Alarm #3 (Not in 1-5 ton unit)ReadActive = alarm
BV20ba40_1Custom Alarm #4 (Not in 1-5 ton unit)ReadActive = alarm
BV2ba22_1Compressor 1 High PressureReadActive = alarm
BV3ba23_1Compressor 2 High Pressure (Not in 1-5 ton unit)ReadActive = alarm
BV15ba35_1Compressor Short CycleReadActive = alarm
AVmin1ba01_1Bit-packed: Combined DataReadCommunications Failure: Bit 0; Local Off: Bit 1; Remote Off: Bit 2; High Head Pressure 1: Bit 3 This event is not latching; High Head Pressure 2 (Not in 1-5 ton unit): Bit 4 This event is not latching; Loss of Air Flow: Bit 5; Standby Glycol Unit On (Not in 1-5 ton unit): Bit 6; Clogged Air Filter: Bit 8; High Temperature: Bit 9; Low Temperature: Bit 10
AV2ba02_1Bit-packed: Combined DataReadHigh Humidity: Bit 0; Low Humidity: Bit 1; Humidifier Problem: Bit 2; Compressor 1 Thermal Overload: Bit 4; Compressor 2 Thermal Overload (Not in 1-5 ton unit): Bit 5; Main Fan Overload: Bit 6; Smoke Detected: Bit 8; Loss of Water: Bit 9; Standby Unit On (Not in 1-5 ton unit): Bit 10
AV3ba03_1Bit-packed: Combined DataReadLow Suction Pressure: Bit 0; Short Cycle: Bit 1; Loss of Power: Bit 2; Local Alarm 1: Bit 6; Local Alarm 2: Bit 7; EPO Shutdown: Bit 8; High Water (1-5 Ton) Local Alarm 3 (8 Ton): Bit 9; High Water (8 Ton) (Not in 1-5 ton unit): Bit 10
AVmin4bc01_1Bit-packed: Combined DataWriteUnit On/Off: Bit 0 On=unit Off Bit 1 On= Unit ON (W); Reheat Lockout: Bit 2 On=RH Off Bit 3 On=RH On; Humidifier Lockout: Bit 4 On= HL Off Bit 5 On=HL On; Temperature and Tolerance: 0=No change (W); Humidity and Tolerance: 0=No change (W)
AV13bs03_1Cooling StateRead1=On /, 0=Off
AV14bs04_1Heating StateRead1=On /, 0=Off
AV15bs05_1Humidifier State (Combined Data)Read1=On /, 0=Off
AV16bs06_1Dehumidifier State (Combined Data)Read1=On /, 0=Off
AVmin5bs01_1Inlet Air Temperature°CRead
AVmin6bs02_1Return Humidity%RHRead
AVmin8bs09_1Temperature Control Capacity%Read
AV7bs08_1Cool/Heat StagesRead0=None, 1=Stage 1, 2=Stage 2
AV17bs07_1Glyco Pump On (System)Read0=off, 1=on
AVmin9bs10_1Return Air Temperature Set Point (Settings)°CWrite
AV11bc02_1Return Air Temperature Set Point (Settings)°CWrite
AV22bc25_1Air Temperature Proportional Band°CWrite
AVmin10bs12_1Humidity Set Point (Settings)%RHWrite
AV12bc03_1Humidity Set Point (Settings)%RHWrite
AV24bc27_1Humidity Proportional Band%RHWrite
AV18bs18_1System On/Off Control (Settings)Write0: off 1: on
MV6bs23_1Temp Control StateRead1=Idle, 2=Heating, 3=Cooling
MV9bs26_1Glyco Pump On (System)Read1=off, 2=on
MV10bs27_1Managed Device Operation StateRead1=UnitOn, 2=Reboot, 3=Unit Power Off, 4=RsdOff, 5=CommsOff
MV7bs24_1Humidifier State (System)Read1=off, 2=on
MV8bs25_1Dehumidifier State (System)Read1=off, 2=on
MV3bc21_1System On/Off Control (Settings)Write1=off, 2=on
MV4bc22_1Reheater LockoutWrite1=disabled, 2=enabled
MV5bc23_1Humidifier LockoutWrite1=disabled, 2=enabled
Object ID lookup: Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)

How many BACnet points does the Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card) have?

This list has 48 BACnet objects: 20 analog values, 20 binary values, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card) BACnet points are writable?

11 of the 48 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card) BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)?

Start with AV 4 bc01_1 (Control word: unit on/off and lockouts (bit-coded)); AV 9 bs10_1 (Return air temperature setpoint, °C); AV 10 bs12_1 (Humidity setpoint, %RH); AV 5 bs01_1 (Inlet air temperature, °C); AV 6 bs02_1 (Return humidity, %RH); AV 8 bs09_1 (Temperature control capacity, %); AV 1 ba01_1 (Alarm word 1 (bit-coded)).

How do I check these points on the real Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.