Precision cooling unit (computer room air handler) · BACnet points list

Vertiv Liebert DME2 precision cooling BACnet points list

Updated 6 November 2026

Short answer

The Liebert DME2 precision cooling reports to a BMS through a Liebert IntelliSlot card (IS-UNITY-DP, for BACnet IP or BACnet MS/TP). The object list has Binary Values for events, Analog Values for temperatures, humidity, setpoints and run hours, and Multi-state Values for states and control modes. Objects are created on the card when it discovers the unit, so only options fitted to the unit appear.

This page lists 64 BACnet objects for the Vertiv Liebert DME2 precision cooling — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert DME2 precision cooling
Equipment
Precision cooling unit (computer room air handler)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
64 (12 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
DME2, Liebert DME2, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 64 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert DME2 precision cooling

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 607536_1Monitoring on/off (1=on, 2=off)Write
AV 95333_1Return air temperature setpoint, °CWrite
AV 115029_1Humidity setpoint, %RHWrite
MV 717528_1Run / standby / off stateRead
AV 588078_1_1Return air temperature, °CRead
AV 2348080_1_1Return air humidity, %RHRead
AV 4235077_1_1Fan speed, %Read
AV 4574096_1Input voltage, VRead
BV 6534300_1Internal communication lostRead

Network setup

Watch out for

Vertiv Liebert DME2 precision cooling BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

64 of 64 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert DME2 precision cooling BACnet Points List
DescriptionStates
BV37559_1Loss of Airflow Sensor FailureReadActive = alarm
BV45034_1High Return HumidityReadActive = alarm
BV65036_1Low Return HumidityReadActive = alarm
BV75335_1Return Air Under TemperatureReadActive = alarm
BV117522_1Loss of AirflowReadActive = alarm
BV175023_1Return Air Over TemperatureReadActive = alarm
BV97537_1_1Filter Maintenance DueReadActive = alarm
BV615147_1_1Return Air Sensor IssueReadActive = alarm
BV2375902_1_1Return Humidity Sensor IssueReadActive = alarm
BV4267544_1_1High Compressor Discharge Temperature LockoutReadActive = alarm
BV4277543_1_1High Compressor Discharge TemperatureReadActive = alarm
BV4287542_1_1Low Compressor Pressure LockoutReadActive = alarm
BV4247541_1_1Low Compressor PressureReadActive = alarm
BV4297540_1_1High Compressor Presssure LockoutReadActive = alarm
BV4307539_1_1High Compressor PressureReadActive = alarm
BV4685054_1Fan Hours ExceededReadActive = alarm
BV6058412_1Condensate Pressure Sensor AlarmReadActive = alarm
BV6125568_1Input UndervoltageReadActive = alarm
BV6135569_1Input OvervoltageReadActive = alarm
BV6156186_1Input Frequency DeviationReadActive = alarm
BV6167518_1Surge Protection Device AlarmReadActive = alarm
BV6187519_1Power Opposite PhaseReadActive = alarm
BV6197520_1Power Loss Of PhaseReadActive = alarm
BV6307503_1Electrical Heater FailureReadActive = alarm
BV6427525_1Repeated Teamwork AddressReadActive = alarm
BV6437524_1Loss of Teamwork SlaveReadActive = alarm
BV6447523_1Teamwork Master is offline or not connected to the networkReadActive = alarm
BV6464723_1Water Under FloorReadActive = alarm
BV6485043_1Humidifier IssueReadActive = alarm
BV6495037_1Humidifier Hours ExceededReadActive = alarm
BVmin6534300_1Internal Communications FailureReadActive = alarm
BV6575500_1Ext Remote ShutdownReadActive = alarm
BV6584714_1Shutdown - Loss Of PowerReadActive = alarm
BV6917561_1_1Custom Alarm (Custom Alarm 1)ReadActive = alarm
BV7027561_1_2Custom Alarm (Custom Alarm 2)ReadActive = alarm
BV7137561_1_3Custom Alarm (Custom Alarm 3)ReadActive = alarm
AVmin95333_1Return Air Temperature Set Point°CWrite
AV100095333_1_deg_FReturn Air Temperature Set Point°FWrite
AVmin115029_1Humidity Set Point%RHWrite
AV125009_1Cooling Proportional Band°CWrite
AV100125009_1_deg_FCooling Proportional Band°FWrite
AV135030_1Humidification Proportional Band%RHWrite
AVmin588078_1_1Return Air Sensor Temperature°CRead
AV100588078_1_1_deg_FReturn Air Sensor Temperature°FRead
AVmin2348080_1_1Return Sensor Humidity%RHRead
AV4105267_1_1Compressor HourshWrite
AVmin4235077_1_1Fan Speed%Read
AV4225374_1_1Fan HourshWrite
AV4258413_1Condensate Fan HourshWrite
AVmin4574096_1System Input RMS A-NVRead
AV4594098_1System Input RMS B-NVRead
AV4614100_1System Input RMS C-NVRead
AV4654105_1System Input FrequencyHzRead
AV4718443_1Fan Power ConsumptionkWRead
AV4765366_1_1Electric Reheater HourshWrite
AV4885369_1_1Humidifier HourshWrite
MV14553_1Server ClassRead1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR
MV565388_1Humidifier StateRead1=off, 2=on
MV575387_1Dehumidifier StateRead1=off, 2=on
MV455386_1Electric Reheat StateRead1=off, 2=on
MV585382_1Cooling StateRead1=off, 2=on
MV597529_1Teamwork StatusRead1=Single, 2=TeamworkMode0, 3=TeamworkMode1, 4=TeamworkMode2, 5=TeamworkMode3
MVmin607536_1Monitoring ON/OFFWrite1=on, 2=off
MVmin717528_1System Operating StateRead1=Run, 2=Standby, 3=Display Off, 4=Remote Off, 5=Monitoring Off, 6=Lockout
Object ID lookup: Vertiv Liebert DME2 precision cooling point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert DME2 precision cooling and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert DME2 precision cooling

How many BACnet points does the Vertiv Liebert DME2 precision cooling have?

This list has 64 BACnet objects: 20 analog values, 36 binary values, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert DME2 precision cooling BACnet points are writable?

12 of the 64 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert DME2 precision cooling BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert DME2 precision cooling?

Start with MV 60 7536_1 (Monitoring on/off (1=on, 2=off)); AV 9 5333_1 (Return air temperature setpoint, °C); AV 11 5029_1 (Humidity setpoint, %RH); MV 71 7528_1 (Run / standby / off state); AV 58 8078_1_1 (Return air temperature, °C); AV 234 8080_1_1 (Return air humidity, %RH); AV 423 5077_1_1 (Fan speed, %); AV 457 4096_1 (Input voltage, V); BV 653 4300_1 (Internal communication lost).

How do I check these points on the real Liebert DME2 precision cooling?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.