Cooling unit group (Liebert SRC) · BACnet points list

Vertiv Liebert SRC (iCOM CMS card) BACnet points list

Updated 6 November 2026

Short answer

The Liebert SRC map is read through the iCOM CMS card and repeats one block of objects per unit (device address, state, temperature, alarms and on/off / fan controls) for up to eight units.

This page lists 88 BACnet objects for the Vertiv Liebert SRC (iCOM CMS card) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert SRC (iCOM CMS card)
Equipment
Cooling unit group (Liebert SRC)
Equipment type
Other equipment
BACnet objects
88 (32 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Liebert SRC, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 88 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert SRC (iCOM CMS card)

Integration in brief

Fit a Liebert iCOM CMS card (BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 102bc01_1Unit 1 on/off commandWrite
MV 103bc03_1Unit 1 fan speedWrite
MV 101bs02_1Unit 1 stateRead
AV 102bs03_1Unit 1 temperatureRead
BV 101ba01_1Unit 1 communication alarmRead
BV 104ba04_1Unit 1 errorRead

Network setup

Watch out for

Vertiv Liebert SRC (iCOM CMS card) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

88 of 88 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert SRC (iCOM CMS card) BACnet Points List
DescriptionStates
AV101bs01_1Device Address (Status Points (View))Read1
MVmin101bs02_1State (Status Points (View))ReadEnabled=1 StandbyOffline=2 Absent=3 UnavailableOffline=4
AVmin102bs03_1Temperature (Status Points (View))Read
AV201bs01_2Device Address (Status Points (View))Read2
MV201bs02_2State (Status Points (View))ReadEnabled=1 StandbyOffline=2 Absent=3 UnavailableOffline=4
AV202bs03_2Temperature (Status Points (View))Read
AV301bs01_3Device Address (Status Points (View))Read3
MV301bs02_3State (Status Points (View))ReadEnabled=1 StandbyOffline=2 Absent=3 UnavailableOffline=4
AV302bs03_3Temperature (Status Points (View))Read
AV401bs01_4Device Address (Status Points (View))Read4
MV401bs02_4State (Status Points (View))ReadEnabled=1 StandbyOffline=2 Absent=3 UnavailableOffline=4
AV402bs03_4Temperature (Status Points (View))Read
AV501bs01_5Device Address (Status Points (View))Read5
MV501bs02_5State (Status Points (View))ReadEnabled=1 StandbyOffline=2 Absent=3 UnavailableOffline=4
AV502bs03_5Temperature (Status Points (View))Read
AV601bs01_6Device Address (Status Points (View))Read6
MV601bs02_6State (Status Points (View))ReadEnabled=1 StandbyOffline=2 Absent=3 UnavailableOffline=4
AV602bs03_6Temperature (Status Points (View))Read
AV701bs01_7Device Address (Status Points (View))Read7
MV701bs02_7State (Status Points (View))ReadEnabled=1 StandbyOffline=2 Absent=3 UnavailableOffline=4
AV702bs03_7Temperature (Status Points (View))Read
AV801bs01_8Device Address (Status Points (View))Read8
MV801bs02_8State (Status Points (View))ReadEnabled=1 StandbyOffline=2 Absent=3 UnavailableOffline=4
AV802bs03_8Temperature (Status Points (View))Read
BVmin101ba01_1Communications (Alarm Points)ReadActive=1 Inactive=0
BV102ba02_1High Temperature (Alarm Points)ReadActive=1 Inactive=0
BV103ba03_1Low Temperature (Alarm Points)ReadActive=1 Inactive=0
BVmin104ba04_1Error (Alarm Points)ReadActive=1 Inactive=0
BV201ba01_2Communications (Alarm Points)ReadActive=1 Inactive=0
BV202ba02_2High Temperature (Alarm Points)ReadActive=1 Inactive=0
BV203ba03_2Low Temperature (Alarm Points)ReadActive=1 Inactive=0
BV204ba04_2Error (Alarm Points)ReadActive=1 Inactive=0
BV301ba01_3Communications (Alarm Points)ReadActive=1 Inactive=0
BV302ba02_3High Temperature (Alarm Points)ReadActive=1 Inactive=0
BV303ba03_3Low Temperature (Alarm Points)ReadActive=1 Inactive=0
BV304ba04_3Error (Alarm Points)ReadActive=1 Inactive=0
BV401ba01_4Communications (Alarm Points)ReadActive=1 Inactive=0
BV402ba02_4High Temperature (Alarm Points)ReadActive=1 Inactive=0
BV403ba03_4Low Temperature (Alarm Points)ReadActive=1 Inactive=0
BV404ba04_4Error (Alarm Points)ReadActive=1 Inactive=0
BV501ba01_5Communications (Alarm Points)ReadActive=1 Inactive=0
BV502ba02_5High Temperature (Alarm Points)ReadActive=1 Inactive=0
BV503ba03_5Low Temperature (Alarm Points)ReadActive=1 Inactive=0
BV504ba04_5Error (Alarm Points)ReadActive=1 Inactive=0
BV601ba01_6Communications (Alarm Points)ReadActive=1 Inactive=0
BV602ba02_6High Temperature (Alarm Points)ReadActive=1 Inactive=0
BV603ba03_6Low Temperature (Alarm Points)ReadActive=1 Inactive=0
BV604ba04_6Error (Alarm Points)ReadActive=1 Inactive=0
BV701ba01_7Communications (Alarm Points)ReadActive=1 Inactive=0
BV702ba02_7High Temperature (Alarm Points)ReadActive=1 Inactive=0
BV703ba03_7Low Temperature (Alarm Points)ReadActive=1 Inactive=0
BV704ba04_7Error (Alarm Points)ReadActive=1 Inactive=0
BV801ba01_8Communications (Alarm Points)ReadActive=1 Inactive=0
BV802ba02_8High Temperature (Alarm Points)ReadActive=1 Inactive=0
BV803ba03_8Low Temperature (Alarm Points)ReadActive=1 Inactive=0
BV804ba04_8Error (Alarm Points)ReadActive=1 Inactive=0
MVmin102bc01_1Unit Status (Control Points)WriteON=1 OFF=2
AV103bc02_1Temperature Setpoint (Control Points)Write
MVmin103bc03_1Fan Speed (Control Points)WriteLow=1 Middle=2 High=3 Auto=4 (r/o)
MV104bc04_1Operation Mode (Control Points)WriteCooling=1 Fan=2 AI=3 Heating=4
MV202bc01_2Unit Status (Control Points)WriteON=1 OFF=2
AV203bc02_2Temperature Setpoint (Control Points)Write
MV203bc03_2Fan Speed (Control Points)WriteLow=1 Medium=2 High=3 Auto=4 (r/o)
MV204bc04_2Operation Mode (Control Points)WriteCooling=1 Fan=2 AI=3 Heating=4
MV302bc01_3Unit Status (Control Points)WriteON=1 OFF=2
AV303bc02_3Temperature Setpoint (Control Points)Write
MV303bc03_3Fan Speed (Control Points)WriteLow=1 Medium=2 High=3 Auto=4 (r/o)
MV304bc04_3Operation Mode (Control Points)WriteCooling=1 Fan=2 AI=3 Heating=4
MV402bc01_4Unit Status (Control Points)WriteON=1 OFF=2
AV403bc02_4Temperature Setpoint (Control Points)Write
MV403bc03_4Fan Speed (Control Points)WriteLow=1 Medium=2 High=3 Auto=4 (r/o)
MV404bc04_4Operation Mode (Control Points)WriteCooling=1 Fan=2 AI=3 Heating=4
MV502bc01_5Unit Status (Control Points)WriteON=1 OFF=2
AV503bc02_5Temperature Setpoint (Control Points)Write
MV503bc03_5Fan Speed (Control Points)WriteLow=1 Medium=2 High=3 Auto=4 (r/o)
MV504bc04_5Operation Mode (Control Points)WriteCooling=1 Fan=2 AI=3 Heating=4
MV602bc01_6Unit Status (Control Points)WriteON=1 OFF=2
AV603bc02_6Temperature Setpoint (Control Points)Write
MV603bc03_6Fan Speed (Control Points)WriteLow=1 Medium=2 High=3 Auto=4 (r/o)
MV604bc04_6Operation Mode (Control Points)WriteCooling=1 Fan=2 AI=3 Heating=4
MV702bc01_7Unit Status (Control Points)WriteON=1 OFF=2
AV703bc02_7Temperature Setpoint (Control Points)Write
MV703bc03_7Fan Speed (Control Points)WriteLow=1 Medium=2 High=3 Auto=4 (r/o)
MV704bc04_7Operation Mode (Control Points)WriteCooling=1 Fan=2 AI=3 Heating=4
MV802bc01_8Unit Status (Control Points)WriteON=1 OFF=2
AV803bc02_8Temperature Setpoint (Control Points)Write
MV803bc03_8Fan Speed (Control Points)WriteLow=1 Medium=2 High=3 Auto=4 (r/o)
MV804bc04_8Operation Mode (Control Points)WriteCooling=1 Fan=2 AI=3 Heating=4
Object ID lookup: Vertiv Liebert SRC point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert SRC (iCOM CMS card) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert SRC (iCOM CMS card)

How many BACnet points does the Vertiv Liebert SRC (iCOM CMS card) have?

This list has 88 BACnet objects: 24 analog values, 32 binary values, 32 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert SRC (iCOM CMS card) BACnet points are writable?

32 of the 88 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert SRC (iCOM CMS card) BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert SRC (iCOM CMS card)?

Start with MV 102 bc01_1 (Unit 1 on/off command); MV 103 bc03_1 (Unit 1 fan speed); MV 101 bs02_1 (Unit 1 state); AV 102 bs03_1 (Unit 1 temperature); BV 101 ba01_1 (Unit 1 communication alarm); BV 104 ba04_1 (Unit 1 error).

How do I check these points on the real Liebert SRC (iCOM CMS card)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.