Power distribution unit (PDU) monitoring · BACnet points list

Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller) BACnet points list

Updated 6 November 2026

Short answer

The Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, output, panel and branch circuit electrical data, Binary Values carry events and Multi-state Values carry status, breaker states and resets. Panel and branch objects repeat per panel and branch, so the list is long.

This page lists 345 BACnet objects for the Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Equipment
Power distribution unit (PDU) monitoring
Equipment type
Other equipment
BACnet objects
345 (10 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 345 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 134717_1Acknowledge / reset eventsWrite
MV 124123_1Normal, warning or alarm stateRead
AV 435168_1Output load, %Read
AV 394209_1Output power, kVARead
AV 14097_1Input voltage, VRead
AV 274201_1Output voltage, VRead
AV 334204_1Output current, ARead

Network setup

Watch out for

Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

345 of 345 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller) BACnet Points List
DescriptionStates
BV14122_1Phase Loss (Input Power 1)ReadActive = alarm
BV24146_1Phase Rotation Error (Input Power 1)ReadActive = alarm
BV134122_2Phase Loss (Input Power 2)ReadActive = alarm
BV144146_2Phase Rotation Error (Input Power 2)ReadActive = alarm
BV255178_1Output Overvoltage (Output Power 1)ReadActive = alarm
BV265179_1Output Undervoltage (Output Power 1)ReadActive = alarm
BV275180_1Output Overcurrent (Output Power 1)ReadActive = alarm
BV285181_1Neutral Overcurrent (Output Power 1)ReadActive = alarm
BV295182_1Ground Overcurrent (Output Power 1)ReadActive = alarm
BV305183_1Output Voltage THD (Output Power 1)ReadActive = alarm
BV315184_1Frequency Deviation (Output Power 1)ReadActive = alarm
BV325432_1Transformer Overtemperature Power Off (Output Power 1)ReadActive = alarm
BV335433_1Transformer Overtemperature (Output Power 1)ReadActive = alarm
BV345434_1Transformer Temperature Sensor Fail (Output Power 1)ReadActive = alarm
BV455178_2Output Overvoltage (Output Power 2)ReadActive = alarm
BV465179_2Output Undervoltage (Output Power 2)ReadActive = alarm
BV475180_2Output Overcurrent (Output Power 2)ReadActive = alarm
BV485181_2Neutral Overcurrent (Output Power 2)ReadActive = alarm
BV495182_2Ground Overcurrent (Output Power 2)ReadActive = alarm
BV505183_2Output Voltage THD (Output Power 2)ReadActive = alarm
BV515184_2Frequency Deviation (Output Power 2)ReadActive = alarm
BV525432_2Transformer Overtemperature Power Off (Output Power 2)ReadActive = alarm
BV535433_2Transformer Overtemperature (Output Power 2)ReadActive = alarm
BV545434_2Transformer Temperature Sensor Fail (Output Power 2)ReadActive = alarm
BV655212_1Panel Summary Alarm (Panel 1)ReadActive = alarm
BV665213_1Panel Overvoltage (Panel 1)ReadActive = alarm
BV675214_1Panel Undervoltage (Panel 1)ReadActive = alarm
BV685215_1Panel Phase Overcurrent (Panel 1)ReadActive = alarm
BV695216_1Panel Neutral Overcurrent (Panel 1)ReadActive = alarm
BV705217_1Panel Ground Overcurrent (Panel 1)ReadActive = alarm
BV815226_1_1Branch Overcurrent (Panel 1 Branch 1)ReadActive = alarm
BV825227_1_1Branch Undercurrent Warning (Panel 1 Branch 1)ReadActive = alarm
BV935226_1_2Branch Overcurrent (Panel 1 Branch 2)ReadActive = alarm
BV945227_1_2Branch Undercurrent Warning (Panel 1 Branch 2)ReadActive = alarm
BV10775226_1_84Branch Overcurrent (Panel 1 Branch 84)ReadActive = alarm
BV10785227_1_84Branch Undercurrent Warning (Panel 1 Branch 84)ReadActive = alarm
BV10895212_2Panel Summary Alarm (Panel 2)ReadActive = alarm
BV10905213_2Panel Overvoltage (Panel 2)ReadActive = alarm
BV10915214_2Panel Undervoltage (Panel 2)ReadActive = alarm
BV10925215_2Panel Phase Overcurrent (Panel 2)ReadActive = alarm
BV10935216_2Panel Neutral Overcurrent (Panel 2)ReadActive = alarm
BV10945217_2Panel Ground Overcurrent (Panel 2)ReadActive = alarm
BV11055226_2_1Branch Overcurrent (Panel 2 Branch 1)ReadActive = alarm
BV11065227_2_1Branch Undercurrent Warning (Panel 2 Branch 1)ReadActive = alarm
BV11175226_2_2Branch Overcurrent (Panel 2 Branch 2)ReadActive = alarm
BV11185227_2_2Branch Undercurrent Warning (Panel 2 Branch 2)ReadActive = alarm
BV21015226_2_84Branch Overcurrent (Panel 2 Branch 84)ReadActive = alarm
BV21025227_2_84Branch Undercurrent Warning (Panel 2 Branch 84)ReadActive = alarm
BV31375212_4Panel Summary Alarm (Panel 4)ReadActive = alarm
BV31385213_4Panel Overvoltage (Panel 4)ReadActive = alarm
BV31395214_4Panel Undervoltage (Panel 4)ReadActive = alarm
BV31405215_4Panel Phase Overcurrent (Panel 4)ReadActive = alarm
BV31415216_4Panel Neutral Overcurrent (Panel 4)ReadActive = alarm
BV31425217_4Panel Ground Overcurrent (Panel 4)ReadActive = alarm
BV31535226_4_1Branch Overcurrent (Panel 4 Branch 1)ReadActive = alarm
BV31545227_4_1Branch Undercurrent Warning (Panel 4 Branch 1)ReadActive = alarm
BV31655226_4_2Branch Overcurrent (Panel 4 Branch 2)ReadActive = alarm
BV31665227_4_2Branch Undercurrent Warning (Panel 4 Branch 2)ReadActive = alarm
BV41495226_4_84Branch Overcurrent (Panel 4 Branch 84)ReadActive = alarm
BV41505227_4_84Branch Undercurrent Warning (Panel 4 Branch 84)ReadActive = alarm
BV41615245_1Subfeed Phase Overcurrent (Subfeed 1)ReadActive = alarm
BV41625246_1Subfeed Neutral Overcurrent (Subfeed 1)ReadActive = alarm
BV41635247_1Subfeed Ground Overcurrent (Subfeed 1)ReadActive = alarm
BV41745245_2Subfeed Phase Overcurrent (Subfeed 2)ReadActive = alarm
BV41755246_2Subfeed Neutral Overcurrent (Subfeed 2)ReadActive = alarm
BV41765247_2Subfeed Ground Overcurrent (Subfeed 2)ReadActive = alarm
BV49805245_64Subfeed Phase Overcurrent (Subfeed 64)ReadActive = alarm
BV49815246_64Subfeed Neutral Overcurrent (Subfeed 64)ReadActive = alarm
BV49825247_64Subfeed Ground Overcurrent (Subfeed 64)ReadActive = alarm
BV49935249_1Event State (Customer Event 1)ReadActive = alarm
BV50045249_2Event State (Customer Event 2)ReadActive = alarm
BV50925249_10Event State (Customer Event 10)ReadActive = alarm
BV51034213_1System Shutdown - EPOReadActive = alarm
BV51044214_1System Shutdown - REPOReadActive = alarm
BV51055422_1Transformer Overtemperature ShutdownReadActive = alarm
BV51064310_1Transformer Overtemperature (System)ReadActive = alarm
BV51074747_1Equipment Temperature Sensor FailReadActive = alarm
AVmin14097_1Input Voltage A-B (Input Power 1)VRead
AV24099_1Input Voltage B-C (Input Power 1)VRead
AV34101_1Input Voltage C-A (Input Power 1)VRead
AV144097_2Input Voltage A-B (Input Power 2)VRead
AV154099_2Input Voltage B-C (Input Power 2)VRead
AV164101_2Input Voltage C-A (Input Power 2)VRead
AVmin274201_1Output Voltage X-Y (Output Power 1)VRead
AV284202_1Output Voltage Y-Z (Output Power 1)VRead
AV294203_1Output Voltage Z-X (Output Power 1)VRead
AV304385_1Output Voltage Vx (Output Power 1)VRead
AV314386_1Output Voltage Vy (Output Power 1)VRead
AV324387_1Output Voltage Vz (Output Power 1)VRead
AVmin334204_1Output Current Ix (Output Power 1)ARead
AV344205_1Output Current Iy (Output Power 1)ARead
AV354206_1Output Current Iz (Output Power 1)ARead
AV365164_1Output Neutral Current (Output Power 1)ARead
AV375165_1Ground Current (Output Power 1)ARead
AV384207_1Output Frequency (Output Power 1)HzRead
AVmin394209_1Output Power (kVA) (Output Power 1)kVARead
AV404208_1Output Power (kW) (Output Power 1)kWRead
AV415166_1Output kW-Hrs (Output Power 1)kWhWrite
AV425167_1Output Power Factor (Output Power 1)Read
AVmin435168_1Output Percent Load (Output Power 1)%Read
AV445169_1Output Voltage Vx THD (Output Power 1)%Read
AV455170_1Output Voltage Vy THD (Output Power 1)%Read
AV465171_1Output Voltage Vz THD (Output Power 1)%Read
AV475172_1Output Current Ix THD (Output Power 1)%Read
AV485173_1Output Current Iy THD (Output Power 1)%Read
AV495174_1Output Current Iz THD (Output Power 1)%Read
AV505175_1Output Current Ix K-Factor (Output Power 1)Read
AV515176_1Output Current Iy K-Factor (Output Power 1)Read
AV525177_1Output Current Iz K-Factor (Output Power 1)Read
AV535250_1Output Current Ix Crest Factor (Output Power 1)Read
AV545251_1Output Current Iy Crest Factor (Output Power 1)Read
AV555252_1Output Current Iz Crest Factor (Output Power 1)Read
AV664201_2Output Voltage X-Y (Output Power 2)VRead
AV674202_2Output Voltage Y-Z (Output Power 2)VRead
AV684203_2Output Voltage Z-X (Output Power 2)VRead
AV694385_2Output Voltage Vx (Output Power 2)VRead
AV704386_2Output Voltage Vy (Output Power 2)VRead
AV714387_2Output Voltage Vz (Output Power 2)VRead
AV724204_2Output Current Ix (Output Power 2)ARead
AV734205_2Output Current Iy (Output Power 2)ARead
AV744206_2Output Current Iz (Output Power 2)ARead
AV755164_2Output Neutral Current (Output Power 2)ARead
AV765165_2Ground Current (Output Power 2)ARead
AV774207_2Output Frequency (Output Power 2)HzRead
AV784209_2Output Power (kVA) (Output Power 2)kVARead
AV794208_2Output Power (kW) (Output Power 2)kWRead
AV805166_2Output kW-Hrs (Output Power 2)kWhWrite
AV815167_2Output Power Factor (Output Power 2)Read
AV825168_2Output Percent Load (Output Power 2)%Read
AV835169_2Output Voltage Vx THD (Output Power 2)%Read
AV845170_2Output Voltage Vy THD (Output Power 2)%Read
AV855171_2Output Voltage Vz THD (Output Power 2)%Read
AV865172_2Output Current Ix THD (Output Power 2)%Read
AV875173_2Output Current Iy THD (Output Power 2)%Read
AV885174_2Output Current Iz THD (Output Power 2)%Read
AV895175_2Output Current Ix K-Factor (Output Power 2)Read
AV905176_2Output Current Iy K-Factor (Output Power 2)Read
AV915177_2Output Current Iz K-Factor (Output Power 2)Read
AV925250_2Output Current Ix Crest Factor (Output Power 2)Read
AV935251_2Output Current Iy Crest Factor (Output Power 2)Read
AV945252_2Output Current Iz Crest Factor (Output Power 2)Read
AV1055515_1Columns of Breakers (Panel 1)Read
AV1065516_1Number of Breakers (Panel 1)Read
AV1075187_1Panel Main Voltage X-Y (Panel 1)VRead
AV1085188_1Panel Main Voltage Y-Z (Panel 1)VRead
AV1095189_1Panel Main Voltage Z-X (Panel 1)VRead
AV1105190_1Panel Main Voltage X-N (Panel 1)VRead
AV1115191_1Panel Main Voltage Y-N (Panel 1)VRead
AV1125192_1Panel Main Voltage Z-N (Panel 1)VRead
AV1135193_1Panel Main Current Ix (Panel 1)ARead
AV1145194_1Panel Main Current Iy (Panel 1)ARead
AV1155195_1Panel Main Current Iz (Panel 1)ARead
AV1165196_1Panel Main Neutral Current (Panel 1)ARead
AV1175197_1Panel Main Ground Current (Panel 1)ARead
AV1185198_1Panel Main Output Power (kVA) (Panel 1)kVARead
AV1195199_1Panel Main Output Power (kW) (Panel 1)kWRead
AV1205200_1Panel Main Output kW-Hrs (Panel 1)kWhWrite
AV1215201_1Panel Main Output Power Factor (Panel 1)Read
AV1225202_1Panel Main Output Percent Load (Panel 1)%Read
AV1235203_1Panel Main Voltage Vx THD (Panel 1)%Read
AV1245204_1Panel Main Voltage Vy THD (Panel 1)%Read
AV1255205_1Panel Main Voltage Vz THD (Panel 1)%Read
AV1265206_1Panel Main Current Ix THD (Panel 1)%Read
AV1275207_1Panel Main Current Iy THD (Panel 1)%Read
AV1285208_1Panel Main Current Iz THD (Panel 1)%Read
AV1295209_1Panel Main Current Ix Crest Factor (Panel 1)Read
AV1305210_1Panel Main Current Iy Crest Factor (Panel 1)Read
AV1315211_1Panel Main Current Iz Crest Factor (Panel 1)Read
AV1425421_1_1Breaker position (Panel 1 Branch 1)Read
AV1435219_1_1Branch Current Phase 1 (Panel 1 Branch 1)ARead
AV1445220_1_1Branch Current Phase 2 (Panel 1 Branch 1)ARead
AV1455221_1_1Branch Current Phase 3 (Panel 1 Branch 1)ARead
AV1465222_1_1Branch Output Power (W) (Panel 1 Branch 1)kWRead
AV1475223_1_1Output kW-Hrs (Panel 1 Branch 1)kWhRead
AV1485224_1_1Branch Output Power Factor (Panel 1 Branch 1)Read
AV1495225_1_1Branch Output Percent Load (Panel 1 Branch 1)%Read
AV1605421_1_2Breaker position (Panel 1 Branch 2)Read
AV1615219_1_2Branch Current Phase 1 (Panel 1 Branch 2)ARead
AV1625220_1_2Branch Current Phase 2 (Panel 1 Branch 2)ARead
AV1635221_1_2Branch Current Phase 3 (Panel 1 Branch 2)ARead
AV1645222_1_2Branch Output Power (W) (Panel 1 Branch 2)kWRead
AV1655223_1_2Output kW-Hrs (Panel 1 Branch 2)kWhRead
AV1665224_1_2Branch Output Power Factor (Panel 1 Branch 2)Read
AV1675225_1_2Branch Output Percent Load (Panel 1 Branch 2)%Read
AV16365421_1_84Breaker position (Panel 1 Branch 84)Read
AV16375219_1_84Branch Current Phase 1 (Panel 1 Branch 84)ARead
AV16385220_1_84Branch Current Phase 2 (Panel 1 Branch 84)ARead
AV16395221_1_84Branch Current Phase 3 (Panel 1 Branch 84)ARead
AV16405222_1_84Branch Output Power (W) (Panel 1 Branch 84)kWRead
AV16415223_1_84Output kW-Hrs (Panel 1 Branch 84)kWhRead
AV16425224_1_84Branch Output Power Factor (Panel 1 Branch 84)Read
AV16435225_1_84Branch Output Percent Load (Panel 1 Branch 84)%Read
AV16545515_2Columns of Breakers (Panel 2)Read
AV16555516_2Number of Breakers (Panel 2)Read
AV16565187_2Panel Main Voltage X-Y (Panel 2)VRead
AV16575188_2Panel Main Voltage Y-Z (Panel 2)VRead
AV16585189_2Panel Main Voltage Z-X (Panel 2)VRead
AV16595190_2Panel Main Voltage X-N (Panel 2)VRead
AV16605191_2Panel Main Voltage Y-N (Panel 2)VRead
AV16615192_2Panel Main Voltage Z-N (Panel 2)VRead
AV16625193_2Panel Main Current Ix (Panel 2)ARead
AV16635194_2Panel Main Current Iy (Panel 2)ARead
AV16645195_2Panel Main Current Iz (Panel 2)ARead
AV16655196_2Panel Main Neutral Current (Panel 2)ARead
AV16665197_2Panel Main Ground Current (Panel 2)ARead
AV16675198_2Panel Main Output Power (kVA) (Panel 2)kVARead
AV16685199_2Panel Main Output Power (kW) (Panel 2)kWRead
AV16695200_2Panel Main Output kW-Hrs (Panel 2)kWhWrite
AV16705201_2Panel Main Output Power Factor (Panel 2)Read
AV16715202_2Panel Main Output Percent Load (Panel 2)%Read
AV16725203_2Panel Main Voltage Vx THD (Panel 2)%Read
AV16735204_2Panel Main Voltage Vy THD (Panel 2)%Read
AV16745205_2Panel Main Voltage Vz THD (Panel 2)%Read
AV16755206_2Panel Main Current Ix THD (Panel 2)%Read
AV16765207_2Panel Main Current Iy THD (Panel 2)%Read
AV16775208_2Panel Main Current Iz THD (Panel 2)%Read
AV16785209_2Panel Main Current Ix Crest Factor (Panel 2)Read
AV16795210_2Panel Main Current Iy Crest Factor (Panel 2)Read
AV16805211_2Panel Main Current Iz Crest Factor (Panel 2)Read
AV16915421_2_1Breaker position (Panel 2 Branch 1)Read
AV16925219_2_1Branch Current Phase 1 (Panel 2 Branch 1)ARead
AV16935220_2_1Branch Current Phase 2 (Panel 2 Branch 1)ARead
AV16945221_2_1Branch Current Phase 3 (Panel 2 Branch 1)ARead
AV16955222_2_1Branch Output Power (W) (Panel 2 Branch 1)kWRead
AV16965223_2_1Output kW-Hrs (Panel 2 Branch 1)kWhRead
AV16975224_2_1Branch Output Power Factor (Panel 2 Branch 1)Read
AV16985225_2_1Branch Output Percent Load (Panel 2 Branch 1)%Read
AV17095421_2_2Breaker position (Panel 2 Branch 2)Read
AV17105219_2_2Branch Current Phase 1 (Panel 2 Branch 2)ARead
AV17115220_2_2Branch Current Phase 2 (Panel 2 Branch 2)ARead
AV17125221_2_2Branch Current Phase 3 (Panel 2 Branch 2)ARead
AV17135222_2_2Branch Output Power (W) (Panel 2 Branch 2)kWRead
AV17145223_2_2Output kW-Hrs (Panel 2 Branch 2)kWhRead
AV17155224_2_2Branch Output Power Factor (Panel 2 Branch 2)Read
AV31855421_2_84Breaker position (Panel 2 Branch 84)Read
AV31865219_2_84Branch Current Phase 1 (Panel 2 Branch 84)ARead
AV31875220_2_84Branch Current Phase 2 (Panel 2 Branch 84)ARead
AV31885221_2_84Branch Current Phase 3 (Panel 2 Branch 84)ARead
AV31895222_2_84Branch Output Power (W) (Panel 2 Branch 84)kWRead
AV31905223_2_84Output kW-Hrs (Panel 2 Branch 84)kWhRead
AV31915224_2_84Branch Output Power Factor (Panel 2 Branch 84)Read
AV31925225_2_84Branch Output Percent Load (Panel 2 Branch 84)%Read
AV47525515_4Columns of Breakers (Panel 4)Read
AV47535516_4Number of Breakers (Panel 4)Read
AV47545187_4Panel Main Voltage X-Y (Panel 4)VRead
AV47555188_4Panel Main Voltage Y-Z (Panel 4)VRead
AV47565189_4Panel Main Voltage Z-X (Panel 4)VRead
AV47575190_4Panel Main Voltage X-N (Panel 4)VRead
AV47585191_4Panel Main Voltage Y-N (Panel 4)VRead
AV47595192_4Panel Main Voltage Z-N (Panel 4)VRead
AV47605193_4Panel Main Current Ix (Panel 4)ARead
AV47615194_4Panel Main Current Iy (Panel 4)ARead
AV47625195_4Panel Main Current Iz (Panel 4)ARead
AV47635196_4Panel Main Neutral Current (Panel 4)ARead
AV47645197_4Panel Main Ground Current (Panel 4)ARead
AV47655198_4Panel Main Output Power (kVA) (Panel 4)kVARead
AV47665199_4Panel Main Output Power (kW) (Panel 4)kWRead
AV47675200_4Panel Main Output kW-Hrs (Panel 4)kWhWrite
AV47685201_4Panel Main Output Power Factor (Panel 4)Read
AV47695202_4Panel Main Output Percent Load (Panel 4)%Read
AV47705203_4Panel Main Voltage Vx THD (Panel 4)%Read
AV47715204_4Panel Main Voltage Vy THD (Panel 4)%Read
AV47725205_4Panel Main Voltage Vz THD (Panel 4)%Read
AV47735206_4Panel Main Current Ix THD (Panel 4)%Read
AV47745207_4Panel Main Current Iy THD (Panel 4)%Read
AV47755208_4Panel Main Current Iz THD (Panel 4)%Read
AV47765209_4Panel Main Current Ix Crest Factor (Panel 4)Read
AV47775210_4Panel Main Current Iy Crest Factor (Panel 4)Read
AV47785211_4Panel Main Current Iz Crest Factor (Panel 4)Read
AV47895421_4_1Breaker position (Panel 4 Branch 1)Read
AV47905219_4_1Branch Current Phase 1 (Panel 4 Branch 1)ARead
AV47915220_4_1Branch Current Phase 2 (Panel 4 Branch 1)ARead
AV47925221_4_1Branch Current Phase 3 (Panel 4 Branch 1)ARead
AV47935222_4_1Branch Output Power (W) (Panel 4 Branch 1)kWRead
AV47945223_4_1Output kW-Hrs (Panel 4 Branch 1)kWhRead
AV47955224_4_1Branch Output Power Factor (Panel 4 Branch 1)Read
AV47965225_4_1Branch Output Percent Load (Panel 4 Branch 1)%Read
AV48075421_4_2Breaker position (Panel 4 Branch 2)Read
AV48085219_4_2Branch Current Phase 1 (Panel 4 Branch 2)ARead
AV48095220_4_2Branch Current Phase 2 (Panel 4 Branch 2)ARead
AV48105221_4_2Branch Current Phase 3 (Panel 4 Branch 2)ARead
AV48115222_4_2Branch Output Power (W) (Panel 4 Branch 2)kWRead
AV48125223_4_2Output kW-Hrs (Panel 4 Branch 2)kWhRead
AV48135224_4_2Branch Output Power Factor (Panel 4 Branch 2)Read
AV48145225_4_2Branch Output Percent Load (Panel 4 Branch 2)%Read
AV62835421_4_84Breaker position (Panel 4 Branch 84)Read
AV62845219_4_84Branch Current Phase 1 (Panel 4 Branch 84)ARead
AV62855220_4_84Branch Current Phase 2 (Panel 4 Branch 84)ARead
AV62865221_4_84Branch Current Phase 3 (Panel 4 Branch 84)ARead
AV62875222_4_84Branch Output Power (W) (Panel 4 Branch 84)kWRead
AV62885223_4_84Output kW-Hrs (Panel 4 Branch 84)kWhRead
AV62895224_4_84Branch Output Power Factor (Panel 4 Branch 84)Read
AV62905225_4_84Branch Output Percent Load (Panel 4 Branch 84)%Read
AV63015229_1Subfeed Current Ix (Subfeed 1)ARead
AV63025230_1Subfeed Current Iy (Subfeed 1)ARead
AV63035231_1Subfeed Current Iz (Subfeed 1)ARead
AV63045232_1Subfeed Neutral Current (Subfeed 1)ARead
AV63055233_1Subfeed Ground Current (Subfeed 1)ARead
AV63065234_1Subfeed Output Power (kVA) (Subfeed 1)kVARead
AV63075235_1Subfeed Output Power (kW) (Subfeed 1)kWRead
AV63085236_1Subfeed Output kW-Hrs (Subfeed 1)kWhWrite
AV63095237_1Subfeed Power Factor (Subfeed 1)Read
AV63105238_1Subfeed Output Percent Load (Subfeed 1)%Read
AV63115239_1Subfeed Current Ix THD (Subfeed 1)%Read
AV63125240_1Subfeed Current Iy THD (Subfeed 1)%Read
AV63135241_1Subfeed Current Iz THD (Subfeed 1)%Read
AV63145242_1Subfeed Current Ix Crest Factor (Subfeed 1)Read
AV63155243_1Subfeed Current Iy Crest Factor (Subfeed 1)Read
AV63165244_1Subfeed Current Iz Crest Factor (Subfeed 1)Read
AV63275229_2Subfeed Current Ix (Subfeed 2)ARead
AV63285230_2Subfeed Current Iy (Subfeed 2)ARead
AV63295231_2Subfeed Current Iz (Subfeed 2)ARead
AV63305232_2Subfeed Neutral Current (Subfeed 2)ARead
AV63315233_2Subfeed Ground Current (Subfeed 2)ARead
AV63325234_2Subfeed Output Power (kVA) (Subfeed 2)kVARead
AV63335235_2Subfeed Output Power (kW) (Subfeed 2)kWRead
AV63345236_2Subfeed Output kW-Hrs (Subfeed 2)kWhWrite
AV63355237_2Subfeed Power Factor (Subfeed 2)Read
AV63365238_2Subfeed Output Percent Load (Subfeed 2)%Read
AV63375239_2Subfeed Current Ix THD (Subfeed 2)%Read
AV63385240_2Subfeed Current Iy THD (Subfeed 2)%Read
AV63395241_2Subfeed Current Iz THD (Subfeed 2)%Read
AV63405242_2Subfeed Current Ix Crest Factor (Subfeed 2)Read
AV63415243_2Subfeed Current Iy Crest Factor (Subfeed 2)Read
AV63425244_2Subfeed Current Iz Crest Factor (Subfeed 2)Read
AV79395229_64Subfeed Current Ix (Subfeed 64)ARead
AV79405230_64Subfeed Current Iy (Subfeed 64)ARead
AV79415231_64Subfeed Current Iz (Subfeed 64)ARead
AV79425232_64Subfeed Neutral Current (Subfeed 64)ARead
AV79435233_64Subfeed Ground Current (Subfeed 64)ARead
AV79445234_64Subfeed Output Power (kVA) (Subfeed 64)kVARead
AV79455235_64Subfeed Output Power (kW) (Subfeed 64)kWRead
AV79465236_64Subfeed Output kW-Hrs (Subfeed 64)kWhWrite
AV79475237_64Subfeed Power Factor (Subfeed 64)Read
AV79485238_64Subfeed Output Percent Load (Subfeed 64)%Read
AV79495239_64Subfeed Current Ix THD (Subfeed 64)%Read
AV79505240_64Subfeed Current Iy THD (Subfeed 64)%Read
AV79515241_64Subfeed Current Iz THD (Subfeed 64)%Read
AV79525242_64Subfeed Current Ix Crest Factor (Subfeed 64)Read
AV79535243_64Subfeed Current Iy Crest Factor (Subfeed 64)Read
AV79545244_64Subfeed Current Iz Crest Factor (Subfeed 64)Read
AV79654293_1System Date and TimeWrite
MV14553_1Server ClassRead1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR
MVmin124123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MVmin134717_1System Event Acknowledge/ResetWrite1=Reset, 2=Acknowledge
Object ID lookup: Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)

How many BACnet points does the Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller) have?

This list has 345 BACnet objects: 265 analog values, 77 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller) BACnet points are writable?

10 of the 345 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller) BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)?

Start with MV 13 4717_1 (Acknowledge / reset events); MV 12 4123_1 (Normal, warning or alarm state); AV 43 5168_1 (Output load, %); AV 39 4209_1 (Output power, kVA); AV 1 4097_1 (Input voltage, V); AV 27 4201_1 (Output voltage, V); AV 33 4204_1 (Output current, A).

How do I check these points on the real Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.