- Home
- BACnet points lists
- Vertiv
- Liebert NX 225-600 kVA UPS
UPS (uninterruptible power supply) · BACnet points list
Vertiv Liebert NX 225-600 kVA UPS BACnet points list
Updated 6 November 2026
The Liebert NX 225-600 kVA UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.
This page lists 147 BACnet objects for the Vertiv Liebert NX 225-600 kVA UPS — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert NX 225-600 kVA UPS
- Equipment
- UPS (uninterruptible power supply)
- Equipment type
- Other equipment
- BACnet objects
- 147 (0 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Liebert NX, NX 225-600 kVA, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert NX 225-600 kVA UPS
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 72 | 4123_1 | Normal, warning or alarm state | Read |
| MV 73 | 5971_1 | UPS operating state | Read |
| MV 36 | 4872_1 | Load on inverter, bypass or battery | Read |
| AV 87 | 4150_1 | Estimated battery runtime, min | Read |
| AV 118 | 5168_1 | Output load, % | Read |
| AV 108 | 4208_1 | Output power, kW | Read |
| AV 1 | 4097_1 | Input voltage, V | Read |
| AV 100 | 4201_1 | Output voltage, V | Read |
| AV 103 | 4204_1 | Output current, A | Read |
| BV 97 | 5113_1 | Unit shut down by an event | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert NX 225-600 kVA UPS BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | 4295_1 | Rectifier Failure | Read | Active = alarm | |
| BV | 2 | 4146_1 | System Input Phs Rotation Error | Read | Active = alarm | |
| BV | 3 | 4147_1 | System Input Current Limit | Read | Active = alarm | |
| BV | 4 | 4122_1 | System Input Power Problem | Read | Active = alarm | |
| BV | 15 | 4143_1 | Bypass Static Switch Unavailable | Read | Active = alarm | |
| BV | 16 | 5957_1 | Bypass Input Voltage Fault | Read | Active = alarm | |
| BV | 17 | 4135_1 | Bypass Not Available | Read | Active = alarm | |
| BV | 18 | 5798_1 | Bypass Overload | Read | Active = alarm | |
| BV | 29 | 4323_1 | Battery Test Failed | Read | Active = alarm | |
| BV | 30 | 4322_1 | Battery Test Passed | Read | Active = alarm | |
| BV | 31 | 5150_1 | Battery Terminals Reversed | Read | Active = alarm | |
| BV | 32 | 5874_1 | Battery Over Voltage | Read | Active = alarm | |
| BV | 33 | 5958_1 | Battery Temperature Out of Range | Read | Active = alarm | |
| BV | 34 | 4162_1 | Battery Low | Read | Active = alarm | |
| BV | 35 | 4219_1 | Battery Over Temperature | Read | Active = alarm | |
| BV | 36 | 4168_1 | Battery Discharging | Read | Active = alarm | |
| BV | 37 | 4172_1 | Battery Auto Test In Progress | Read | Active = alarm | |
| BV | 38 | 4171_1 | Battery Manual Test In Progress | Read | Active = alarm | |
| BV | 39 | 4222_1 | Battery Ground Fault | Read | Active = alarm | |
| BV | 40 | 5154_1 | DC Bus Abnormal | Read | Active = alarm | |
| BV | 51 | 4215_1 | System Output Off | Read | Active = alarm | |
| BV | 52 | 4299_1 | Output Load on Maint. Bypass | Read | Active = alarm | |
| BV | 53 | 4298_1 | UPS Output on Bypass | Read | Active = alarm | |
| BV | 64 | 4233_1 | Inverter Failure | Read | Active = alarm | |
| BV | 65 | 5960_1 | Inverter Overload | Read | Active = alarm | |
| BV | 66 | 4389_1 | System Output Fault | Read | Active = alarm | |
| BV | 67 | 5144_1 | Output Of/Uf | Read | Active = alarm | |
| BV | 68 | 5808_1 | System Shutdown - Output Short | Read | Active = alarm | |
| BV | 69 | 5968_1 | Inverter Desaturation | Read | Active = alarm | |
| BV | 80 | 6253_1 | Booster Failure | Read | Active = alarm | |
| BV | 81 | 6254_1 | Charger Failure | Read | Active = alarm | |
| BV | 92 | 4213_1 | System Shutdown - EPO | Read | Active = alarm | |
| BV | 93 | 5969_1 | Generic DIC Fault | Read | Active = alarm | |
| BV | 94 | 4294_1 | Inlet Air Over Temperature | Read | Active = alarm | |
| BV | 95 | 4551_1 | Generic Test Event | Read | Active = alarm | |
| BV | 96 | 5054_1 | Fan Hours Exceeded | Read | Active = alarm | |
| BVmin | 97 | 5113_1 | Unit Shutdown | Read | Active = alarm | |
| BV | 98 | 4753_1 | Main Controller Fault | Read | Active = alarm | |
| BV | 99 | 4310_1 | Equipment Over Temperature | Read | Active = alarm | |
| BV | 100 | 5851_1 | Maximum Load Alarm | Read | Active = alarm | |
| BV | 101 | 5970_1 | Ground Fault | Read | Active = alarm | |
| BV | 112 | 4325_1 | Backfeed Breaker Open | Read | Active = alarm | |
| BV | 113 | 5973_1 | Input Breaker Open | Read | Active = alarm | |
| BV | 114 | 5975_1 | Output Breaker Open | Read | Active = alarm | |
| BV | 115 | 5976_1 | Maintenance Bypass Breaker Closed | Read | Active = alarm | |
| BV | 116 | 5977_1 | Battery Breaker Open | Read | Active = alarm | |
| AVmin | 1 | 4097_1 | System Input RMS A-B | V | Read | |
| AV | 2 | 4099_1 | System Input RMS B-C | V | Read | |
| AV | 3 | 4101_1 | System Input RMS C-A | V | Read | |
| AV | 4 | 4113_1 | System Input RMS Current Phase A | A | Read | |
| AV | 5 | 4114_1 | System Input RMS Current Phase B | A | Read | |
| AV | 6 | 4115_1 | System Input RMS Current Phase C | A | Read | |
| AV | 7 | 4105_1 | System Input Frequency | Hz | Read | |
| AV | 18 | 6245_1_1 | Rectifier Phase A Temperature sensor (Rectifier Module Temperatures 1) | °C | Read | |
| AV | 10018 | 6245_1_1_deg_F | Rectifier Phase A Temperature sensor (Rectifier Module Temperatures 1) | °F | Read | |
| AV | 19 | 6246_1_1 | Rectifier Phase B Temperature sensor (Rectifier Module Temperatures 1) | °C | Read | |
| AV | 10019 | 6246_1_1_deg_F | Rectifier Phase B Temperature sensor (Rectifier Module Temperatures 1) | °F | Read | |
| AV | 20 | 6247_1_1 | Rectifier Phase C Temperature sensor (Rectifier Module Temperatures 1) | °C | Read | |
| AV | 10020 | 6247_1_1_deg_F | Rectifier Phase C Temperature sensor (Rectifier Module Temperatures 1) | °F | Read | |
| AV | 31 | 6245_1_2 | Rectifier Phase A Temperature sensor (Rectifier Module Temperatures 2) | °C | Read | |
| AV | 10031 | 6245_1_2_deg_F | Rectifier Phase A Temperature sensor (Rectifier Module Temperatures 2) | °F | Read | |
| AV | 32 | 6246_1_2 | Rectifier Phase B Temperature sensor (Rectifier Module Temperatures 2) | °C | Read | |
| AV | 10032 | 6246_1_2_deg_F | Rectifier Phase B Temperature sensor (Rectifier Module Temperatures 2) | °F | Read | |
| AV | 33 | 6247_1_2 | Rectifier Phase C Temperature sensor (Rectifier Module Temperatures 2) | °C | Read | |
| AV | 10033 | 6247_1_2_deg_F | Rectifier Phase C Temperature sensor (Rectifier Module Temperatures 2) | °F | Read | |
| AV | 57 | 6245_1_4 | Rectifier Phase A Temperature Sensor | °C | Read | |
| AV | 10057 | 6245_1_4_deg_F | Rectifier Phase A Temperature Sensor | °F | Read | |
| AV | 58 | 6246_1_4 | Rectifier Phase B Temperature Sensor | °C | Read | |
| AV | 10058 | 6246_1_4_deg_F | Rectifier Phase B Temperature Sensor | °F | Read | |
| AV | 59 | 6247_1_4 | Rectifier Phase C Temperature Sensor | °C | Read | |
| AV | 10059 | 6247_1_4_deg_F | Rectifier Phase C Temperature Sensor | °F | Read | |
| AV | 70 | 4125_1 | Bypass Input Voltage RMS A-B | V | Read | |
| AV | 71 | 4126_1 | Bypass Input Voltage RMS B-C | V | Read | |
| AV | 72 | 4127_1 | Bypass Input Voltage RMS C-A | V | Read | |
| AV | 73 | 4131_1 | Bypass Input Frequency | Hz | Read | |
| AV | 84 | 4148_1 | DC Bus Voltage | VDC | Read | |
| AV | 85 | 4155_1 | Battery Volts for Cabinet | VDC | Read | |
| AV | 86 | 4149_1 | DC Bus Current | A DC | Read | |
| AVmin | 87 | 4150_1 | Battery Time Remaining | min | Read | |
| AV | 88 | 4153_1 | Battery Percentage Charge | % | Read | |
| AV | 89 | 4156_1 | Battery Temperature for Cabinet | °C | Read | |
| AV | 10089 | 4156_1_deg_F | Battery Temperature for Cabinet | °F | Read | |
| AVmin | 100 | 4201_1 | System Output Voltage RMS A-B | V | Read | |
| AV | 101 | 4202_1 | System Output Voltage RMS B-C | V | Read | |
| AV | 102 | 4203_1 | System Output Voltage RMS C-A | V | Read | |
| AVmin | 103 | 4204_1 | System Output RMS Current Phs A | A | Read | |
| AV | 104 | 4205_1 | System Output RMS Current Phs B | A | Read | |
| AV | 105 | 4206_1 | System Output RMS Current Phs C | A | Read | |
| AV | 106 | 4207_1 | System Output Frequency | Hz | Read | |
| AV | 107 | 4209_1 | System Output Apparent Power | kVA | Read | |
| AVmin | 108 | 4208_1 | System Output Power | kW | Read | |
| AV | 109 | 5868_1 | System Output Apparent Power Phs A | kVA | Read | |
| AV | 110 | 5869_1 | System Output Apparent Power Phs B | kVA | Read | |
| AV | 111 | 5870_1 | System Output Apparent Power Phs C | kVA | Read | |
| AV | 112 | 5859_1 | System Output Power Phase A | kW | Read | |
| AV | 113 | 5860_1 | System Output Power Phase B | kW | Read | |
| AV | 114 | 5959_1 | System Output Power Phase C | kW | Read | |
| AV | 115 | 4223_1 | System Output Pct Power Phase A | % | Read | |
| AV | 116 | 4224_1 | System Output Pct Power Phase B | % | Read | |
| AV | 117 | 4225_1 | System Output Pct Power Phase C | % | Read | |
| AVmin | 118 | 5168_1 | Output Percent Load | % | Read | |
| AV | 119 | 6248_1 | Temperature | °C | Read | |
| AV | 10119 | 6248_1_deg_F | Temperature | °F | Read | |
| AV | 130 | 4232_1 | Inverter Overload Time Remaining | s | Read | |
| AV | 141 | 6249_1_1 | Inverter Phase A Temperature Sensor (Inverter Module Temperatures 1) | °C | Read | |
| AV | 10141 | 6249_1_1_deg_F | Inverter Phase A Temperature Sensor (Inverter Module Temperatures 1) | °F | Read | |
| AV | 142 | 6250_1_1 | Inverter Phase B Temperature Sensor (Inverter Module Temperatures 1) | °C | Read | |
| AV | 10142 | 6250_1_1_deg_F | Inverter Phase B Temperature Sensor (Inverter Module Temperatures 1) | °F | Read | |
| AV | 143 | 6251_1_1 | Inverter Phase C Temperature Sensor (Inverter Module Temperatures 1) | °C | Read | |
| AV | 10143 | 6251_1_1_deg_F | Inverter Phase C Temperature Sensor (Inverter Module Temperatures 1) | °F | Read | |
| AV | 154 | 6249_1_2 | Inverter Phase A Temperature Sensor (Inverter Module Temperatures 2) | °C | Read | |
| AV | 10154 | 6249_1_2_deg_F | Inverter Phase A Temperature Sensor (Inverter Module Temperatures 2) | °F | Read | |
| AV | 155 | 6250_1_2 | Inverter Phase B Temperature Sensor (Inverter Module Temperatures 2) | °C | Read | |
| AV | 10155 | 6250_1_2_deg_F | Inverter Phase B Temperature Sensor (Inverter Module Temperatures 2) | °F | Read | |
| AV | 156 | 6251_1_2 | Inverter Phase C Temperature Sensor (Inverter Module Temperatures 2) | °C | Read | |
| AV | 10156 | 6251_1_2_deg_F | Inverter Phase C Temperature Sensor (Inverter Module Temperatures 2) | °F | Read | |
| AV | 180 | 6249_1_4 | Inverter Phase A Temperature Sensor (Inverter Module Temperatures 4) | °C | Read | |
| AV | 10180 | 6249_1_4_deg_F | Inverter Phase A Temperature Sensor (Inverter Module Temperatures 4) | °F | Read | |
| AV | 181 | 6250_1_4 | Inverter Phase B Temperature Sensor (Inverter Module Temperatures 4) | °C | Read | |
| AV | 10181 | 6250_1_4_deg_F | Inverter Phase B Temperature Sensor (Inverter Module Temperatures 4) | °F | Read | |
| AV | 182 | 6251_1_4 | Inverter Phase C Temperature Sensor (Inverter Module Temperatures 4) | °C | Read | |
| AV | 10182 | 6251_1_4_deg_F | Inverter Phase C Temperature Sensor (Inverter Module Temperatures 4) | °F | Read | |
| AV | 193 | 5987_1 | Battery Recharge Voltage | VDC | Read | |
| AV | 194 | 6252_1 | Max Charge Current | A DC | Read | |
| AV | 205 | 5963_1_1 | Booster-Charger Temperature (Booster Charger Module Temperatures 1) | °C | Read | |
| AV | 10205 | 5963_1_1_deg_F | Booster-Charger Temperature (Booster Charger Module Temperatures 1) | °F | Read | |
| AV | 216 | 5963_1_2 | Booster-Charger Temperature (Booster Charger Module Temperatures 2) | °C | Read | |
| AV | 10216 | 5963_1_2_deg_F | Booster-Charger Temperature (Booster Charger Module Temperatures 2) | °F | Read | |
| AV | 238 | 5963_1_4 | Booster-Charger Temperature (Booster Charger Module Temperatures 4) | °C | Read | |
| AV | 10238 | 5963_1_4_deg_F | Booster-Charger Temperature (Booster Charger Module Temperatures 4) | °F | Read | |
| AV | 249 | 4264_1 | Output Apparent Power Rating | kVA | Read | |
| AV | 250 | 4102_1 | System Input Nominal Voltage | V | Read | |
| AV | 251 | 4103_1 | System Input Nominal Frequency | Hz | Read | |
| MV | 1 | 4748_1 | Rectifier Status | Read | 1=Off, 2=On | |
| MV | 12 | 4736_1 | Static Bypass Switch | Read | 1=Off, 2=On | |
| MV | 13 | 4737_1 | Bypass Qualification Status | Read | 1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High | |
| MV | 24 | 4743_1 | DC Bus Qualification Status | Read | 1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High | |
| MV | 25 | 4871_1 | UPS battery1 status | Read | 1=Unknown, 2=Normal, 3=Low, 4=Depleted | |
| MVmin | 36 | 4872_1 | UPS Output Source | Read | 1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer | |
| MV | 37 | 4319_1 | Load Power Source | Read | 1=Load Off, 2=Ups, 3=Maintenance Bypass | |
| MV | 48 | 4746_1 | Inverter On/Off State | Read | 1=Off, 2=On | |
| MV | 49 | 5961_1 | Inverter Synchronization Source | Read | 1=External, 2=Self Clock (Internal), 3=Output, 4=Bypass | |
| MV | 60 | 6255_1 | Booster On/Off State | Read | 1=Off, 2=On | |
| MV | 61 | 6256_1 | Charger On/Off State | Read | 1=Off, 2=On | |
| MVmin | 72 | 4123_1 | System Status | Read | 1=Normal Operation, 2=Startup, 3=Normal With Warning, 4=Normal With Alarm, 5=Abnormal Operation | |
| MVmin | 73 | 5971_1 | UPS Operating Mode | Read | 1=Idle, 2=Double Conversion Mode (Vfi), 3=Interactive Mode (Vi), 4=Stand-by Mode (Vfd), 5=Cr Mode (Cr), 6=Eco Mode (Dim) | |
| MV | 74 | 5454_1 | ECO Mode Operation State | Read | 1=Disabled, 2=Enabled |
No points match these filters.
Object ID lookup: Vertiv Liebert NX 225-600 kVA UPS point IDs by name
BV14295_1BV24146_1BV34147_1BV44122_1BV154143_1BV165957_1BV174135_1BV185798_1BV294323_1BV304322_1BV315150_1BV325874_1BV335958_1BV344162_1BV354219_1BV364168_1BV374172_1BV384171_1BV394222_1BV405154_1BV514215_1BV524299_1BV534298_1BV644233_1BV655960_1BV664389_1BV675144_1BV685808_1BV695968_1BV806253_1BV816254_1BV924213_1BV935969_1BV944294_1BV954551_1BV965054_1BV975113_1BV984753_1BV994310_1BV1005851_1BV1015970_1BV1124325_1BV1135973_1BV1145975_1BV1155976_1BV1165977_1AV14097_1AV24099_1AV34101_1AV44113_1AV54114_1AV64115_1AV74105_1AV186245_1_1AV100186245_1_1_deg_FAV196246_1_1AV100196246_1_1_deg_FAV206247_1_1AV100206247_1_1_deg_FAV316245_1_2AV100316245_1_2_deg_FAV326246_1_2AV100326246_1_2_deg_FAV336247_1_2AV100336247_1_2_deg_FAV576245_1_4AV100576245_1_4_deg_FAV586246_1_4AV100586246_1_4_deg_FAV596247_1_4AV100596247_1_4_deg_FAV704125_1AV714126_1AV724127_1AV734131_1AV844148_1AV854155_1AV864149_1AV874150_1AV884153_1AV894156_1AV100894156_1_deg_FAV1004201_1AV1014202_1AV1024203_1AV1034204_1AV1044205_1AV1054206_1AV1064207_1AV1074209_1AV1084208_1AV1095868_1AV1105869_1AV1115870_1AV1125859_1AV1135860_1AV1145959_1AV1154223_1AV1164224_1AV1174225_1AV1185168_1AV1196248_1AV101196248_1_deg_FAV1304232_1AV1416249_1_1AV101416249_1_1_deg_FAV1426250_1_1AV101426250_1_1_deg_FAV1436251_1_1AV101436251_1_1_deg_FAV1546249_1_2AV101546249_1_2_deg_FAV1556250_1_2AV101556250_1_2_deg_FAV1566251_1_2AV101566251_1_2_deg_FAV1806249_1_4AV101806249_1_4_deg_FAV1816250_1_4AV101816250_1_4_deg_FAV1826251_1_4AV101826251_1_4_deg_FAV1935987_1AV1946252_1AV2055963_1_1AV102055963_1_1_deg_FAV2165963_1_2AV102165963_1_2_deg_FAV2385963_1_4AV102385963_1_4_deg_FAV2494264_1AV2504102_1AV2514103_1MV14748_1MV124736_1MV134737_1MV244743_1MV254871_1MV364872_1MV374319_1MV484746_1MV495961_1MV606255_1MV616256_1MV724123_1MV735971_1MV745454_1
Integration notes
- Tables 5.174, 5.175, 5.176, pdf pages 2204-2210 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
- Applies only with the optional MUND control board; without it the NX uses a Modbus-only card.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert NX 225-600 kVA UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert NX 225-600 kVA UPS
How many BACnet points does the Vertiv Liebert NX 225-600 kVA UPS have?
This list has 147 BACnet objects: 87 analog values, 46 binary values, 14 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert NX 225-600 kVA UPS BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Vertiv Liebert NX 225-600 kVA UPS BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert NX 225-600 kVA UPS?
Start with MV 72 4123_1 (Normal, warning or alarm state); MV 73 5971_1 (UPS operating state); MV 36 4872_1 (Load on inverter, bypass or battery); AV 87 4150_1 (Estimated battery runtime, min); AV 118 5168_1 (Output load, %); AV 108 4208_1 (Output power, kW); AV 1 4097_1 (Input voltage, V); AV 100 4201_1 (Output voltage, V); AV 103 4204_1 (Output current, A); BV 97 5113_1 (Unit shut down by an event).
How do I check these points on the real Liebert NX 225-600 kVA UPS?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.