- Liebert EXS / ITA2 UPS
UPS (uninterruptible power supply) · BACnet points list
Vertiv Liebert EXS / ITA2 UPS BACnet points list
Updated 6 November 2026
The Liebert EXS / ITA2 UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.
This page lists 271 BACnet objects for the Vertiv Liebert EXS / ITA2 UPS — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert EXS / ITA2 UPS
- Equipment
- UPS (uninterruptible power supply)
- Equipment type
- Other equipment
- BACnet objects
- 271 (16 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Liebert EXS, Liebert ITA2, ITA2, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert EXS / ITA2 UPS
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 63 | 4123_1 | Normal, warning or alarm state | Read |
| MV 29 | 4872_1 | Load on inverter, bypass or battery | Read |
| AV 53 | 4150_1 | Estimated battery runtime, min | Read |
| AV 86 | 4208_1 | Output power, W | Read |
| AV 1 | 4096_1 | Input voltage, V | Read |
| AV 76 | 4385_1 | Output voltage, V | Read |
| AV 82 | 4204_1 | Output current, A | Read |
| BV 39 | 4168_1 | Load is on battery | Read |
| BV 58 | 4300_1 | Internal communication lost | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert EXS / ITA2 UPS BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | 4135_1 | Bypass Not Available | Read | Active = alarm | |
| BV | 2 | 5957_1 | Bypass Input Voltage Fault | Read | Active = alarm | |
| BV | 3 | 4216_1 | Bypass Backfeed Detected | Read | Active = alarm | |
| BV | 4 | 8448_1 | Bypass Abnormal In ECO Mode | Read | Active = alarm | |
| BV | 5 | 8449_1 | Shutdown Due To Bypass Overcurrent Timeout | Read | Active = alarm | |
| BV | 6 | 8450_1 | Shutdown Due To Bypass Backfeed Fault | Read | Active = alarm | |
| BV | 7 | 8451_1 | ECO Bypass Mode | Read | Active = alarm | |
| BV | 8 | 8452_1 | Parallel Bypass Cable Connection Abnormal | Read | Active = alarm | |
| BV | 12 | 4741_1 | Battery Self Test | Read | Active = alarm | |
| BV | 13 | 4162_1 | Battery Low | Read | Active = alarm | |
| BV | 14 | 4323_1 | Battery Test Failed | Read | Active = alarm | |
| BV | 15 | 6182_1 | Replace Battery | Read | Active = alarm | |
| BV | 16 | 5149_1 | Battery Not Qualified | Read | Active = alarm | |
| BV | 17 | 5150_1 | Battery Terminals Reversed | Read | Active = alarm | |
| BV | 18 | 7164_1 | Battery Deep Discharge | Read | Active = alarm | |
| BV | 19 | 4219_1 | Battery Over Temperature | Read | Active = alarm | |
| BV | 20 | 4222_1 | Battery Ground Fault | Read | Active = alarm | |
| BV | 76 | 8344_1_1 | Battery Voltage Abnormal (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 77 | 8345_1_1 | Battery Temperature Abnormal (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 78 | 8346_1_1 | Battery Current Abnormal (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 79 | 8347_1_1 | Battery Cabinet Address Fault (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 80 | 8348_1_1 | Battery Cabinet Connect Fault (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 81 | 8438_1_1 | Battery Cabinet Parallel Failure (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 82 | 8349_1_1 | Battery Cabinet Communication Fail (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 83 | 8336_1_1 | Lithium Battery Cabinet Wait Charge (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 84 | 7464_1_1 | Lithium-Ion Battery System Abnormal (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 85 | 8439_1_1 | Battery Cabinet SOH Low (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 86 | 8474_1_1 | Incompatible Battery Management System version (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 87 | 8475_1_1 | Lithium Battery EOL (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 88 | 8476_1_1 | Lithium Battery Sampling Circuit Failure (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 89 | 8477_1_1 | Lithium Battery Hardware Circuit Protection Active (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 90 | 8478_1_1 | Lithium Battery Cell Capacity Low (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 96 | 8344_1_2 | Battery Voltage Abnormal (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 97 | 8345_1_2 | Battery Temperature Abnormal (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 98 | 8346_1_2 | Battery Current Abnormal (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 99 | 8347_1_2 | Battery Cabinet Address Fault (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 100 | 8348_1_2 | Battery Cabinet Connect Fault (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 101 | 8438_1_2 | Battery Cabinet Parallel Failure (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 102 | 8349_1_2 | Battery Cabinet Communication Fail (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 103 | 8336_1_2 | Lithium Battery Cabinet Wait Charge (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 104 | 7464_1_2 | Lithium-Ion Battery System Abnormal (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 105 | 8439_1_2 | Battery Cabinet SOH Low (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 106 | 8474_1_2 | Incompatible Battery Management System version (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 107 | 8475_1_2 | Lithium Battery EOL (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 108 | 8476_1_2 | Lithium Battery Sampling Circuit Failure (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 109 | 8477_1_2 | Lithium Battery Hardware Circuit Protection Active (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 110 | 8478_1_2 | Lithium Battery Cell Capacity Low (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 376 | 8344_1_16 | Battery Voltage Abnormal (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 377 | 8345_1_16 | Battery Temperature Abnormal (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 378 | 8346_1_16 | Battery Current Abnormal (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 379 | 8347_1_16 | Battery Cabinet Address Fault (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 380 | 8348_1_16 | Battery Cabinet Connect Fault (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 381 | 8438_1_16 | Battery Cabinet Parallel Failure (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 382 | 8349_1_16 | Battery Cabinet Communication Fail (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 383 | 8336_1_16 | Lithium Battery Cabinet Wait Charge (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 384 | 7464_1_16 | Lithium-Ion Battery System Abnormal (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 385 | 8439_1_16 | Battery Cabinet SOH Low (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 386 | 8474_1_16 | Incompatible Battery Management System version (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 387 | 8475_1_16 | Lithium Battery EOL (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 388 | 8476_1_16 | Lithium Battery Sampling Circuit Failure (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 389 | 8477_1_16 | Lithium Battery Hardware Circuit Protection Active (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 390 | 8478_1_16 | Lithium Battery Cell Capacity Low (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 396 | 8331_1_1 | Battery Cabinet Serial Number Illegal Error | Read | Active = alarm | |
| BV | 397 | 8332_1_1 | Lithium Battery Cabinet Online Number Error | Read | Active = alarm | |
| BV | 398 | 8333_1_1 | Lithium Battery Cabinet Communication Failure | Read | Active = alarm | |
| BV | 399 | 8334_1_1 | Lithium Battery Cabinet mismatch the unit | Read | Active = alarm | |
| BV | 400 | 8335_1_1 | Lithium Battery Cabinet Address Set Error | Read | Active = alarm | |
| BV | 401 | 8337_1_1 | Number of Lithium Battery Cabinets Over Limit | Read | Active = alarm | |
| BV | 402 | 8339_1_1 | Lithium Battery Manual Wake up Event | Read | Active = alarm | |
| BV | 403 | 8338_1_1 | Lithium Battery Cabinet Check | Read | Active = alarm | |
| BV | 404 | 8479_1_1 | Lithium Battery Cable Connection Issue | Read | Active = alarm | |
| BV | 405 | 8480_1_1 | Dischargeable Battery Count Less Than Configured Number | Read | Active = alarm | |
| BV | 406 | 8481_1_1 | Ambient temperature lower than recommended | Read | Active = alarm | |
| BV | 407 | 8482_1_1 | Ambient temperature higher than recommended | Read | Active = alarm | |
| BV | 408 | 8483_1_1 | Ambient temperature low pre-alarm | Read | Active = alarm | |
| BV | 409 | 8484_1_1 | Ambient temperature high pre-alarm | Read | Active = alarm | |
| BV | 26 | 5806_1 | Output Overload | Read | Active = alarm | |
| BV | 27 | 4215_1 | System Output Off | Read | Active = alarm | |
| BV | 28 | 4389_1 | System Output Fault | Read | Active = alarm | |
| BV | 29 | 5808_1 | System Shutdown - Output Short | Read | Active = alarm | |
| BV | 30 | 8368_1 | System output Inhibit - Ext | Read | Active = alarm | |
| BV | 38 | 4298_1 | UPS Output on Bypass | Read | Active = alarm | |
| BVmin | 39 | 4168_1 | Battery Discharging | Read | Active = alarm | |
| BV | 40 | 4122_1 | System Input Power Problem | Read | Active = alarm | |
| BV | 41 | 4310_1 | Equipment Over Temperature | Read | Active = alarm | |
| BV | 42 | 6186_1 | Input Frequency Deviation | Read | Active = alarm | |
| BV | 43 | 6187_1 | Shutdown Pending | Read | Active = alarm | |
| BV | 44 | 5588_1 | Unspecified General Event | Read | Active = alarm | |
| BV | 45 | 4823_1 | Parallel Comm Warning | Read | Active = alarm | |
| BV | 46 | 4825_1 | Loss of Redundancy | Read | Active = alarm | |
| BV | 47 | 6254_1 | Charger Failure | Read | Active = alarm | |
| BV | 48 | 4295_1 | Rectifier Failure | Read | Active = alarm | |
| BV | 49 | 4233_1 | Inverter Failure | Read | Active = alarm | |
| BV | 50 | 5976_1 | Maintenance Bypass Breaker Closed | Read | Active = alarm | |
| BV | 51 | 4311_1 | System Fan Failure | Read | Active = alarm | |
| BV | 52 | 4229_1 | Emergency Power Off - Latched | Read | Active = alarm | |
| BV | 53 | 6453_1 | Input Wiring Fault | Read | Active = alarm | |
| BV | 54 | 6454_1 | DC to DC Converter Fault | Read | Active = alarm | |
| BV | 55 | 5154_1 | DC Bus Abnormal | Read | Active = alarm | |
| BV | 56 | 5153_1 | Load Sharing Fault | Read | Active = alarm | |
| BV | 57 | 6059_1 | Inverter Relay Fault | Read | Active = alarm | |
| BVmin | 58 | 4300_1 | Internal Communications Failure | Read | Active = alarm | |
| BV | 59 | 4147_1 | System Input Current Limit | Read | Active = alarm | |
| BV | 500 | 8454_1 | Fan Replacement Required | Read | Active = alarm | |
| BV | 501 | 8455_1 | Load Off Due To Shutdown On Battery | Read | Active = alarm | |
| BV | 502 | 8456_1 | System Redundant Overload | Read | Active = alarm | |
| BV | 503 | 8457_1 | DSP Fault Condition | Read | Active = alarm | |
| BV | 504 | 8458_1 | On Intelligent Sleep Mode | Read | Active = alarm | |
| BV | 505 | 8459_1 | Fan Replaced | Read | Active = alarm | |
| BV | 506 | 5840_1 | Power Module Shutdown - Over Temperature | Read | Active = alarm | |
| BV | 507 | 4382_1 | System Input Current Imbalance | Read | Active = alarm | |
| BV | 508 | 4167_1 | Output Off | Read | Active = alarm | |
| BV | 509 | 4297_1 | UPS Output on Inverter | Read | Active = alarm | |
| BV | 510 | 8310_1 | Auxiliary power fault | Read | Active = alarm | |
| BV | 511 | 8307_1 | Battery cabinet connection abnormal | Read | Active = alarm | |
| BV | 512 | 6350_1 | General Fault | Read | Active = alarm | |
| BV | 513 | 6066_1 | Parallel Cable Failure | Read | Active = alarm | |
| BV | 514 | 8309_1 | Bypass disabled | Read | Active on Alarm | |
| BV | 515 | 8317_1 | Battery to utility transition | Read | Active = alarm | |
| BV | 516 | 8315_1 | Manual Power On | Read | Active = alarm | |
| BV | 517 | 8316_1 | Remote Power On | Read | Active = alarm | |
| BV | 518 | 5810_1 | System Shutdown - Remote Shutdown | Read | Active = alarm | |
| BV | 519 | 8318_1 | UPS was reset to factory defaults | Read | Active = alarm | |
| BV | 520 | 8319_1 | Device Faults were cleared, as requested | Read | Active = alarm | |
| BV | 521 | 8311_1 | Output off due to abnormal bypass | Read | Active = alarm | |
| BV | 522 | 8312_1 | Local output is disconnected | Read | Active = alarm | |
| BV | 523 | 8313_1 | Output off voltage is not zero | Read | Active = alarm | |
| BV | 524 | 6064_1 | LBS Cable Failure | Read | Active = alarm | |
| BV | 525 | 5809_1 | System Shutdown - Low Battery | Read | Active = alarm | |
| BV | 526 | 8314_1 | Parallel output frequency abnormal | Read | Active = alarm | |
| BV | 527 | 8284_1 | Output Breaker Open | Read | Active = alarm | |
| BV | 528 | 8617_1 | UPS is in Service Mode | Read | Active = alarm | |
| BV | 65 | 6061_1 | Input Source Backfeed | Read | Active = alarm | |
| BV | 66 | 8446_1 | Shutdown Due To System Input Backfeed Fault | Read | Active = alarm | |
| BV | 67 | 8447_1 | Input Neutral Ground Abnormal | Read | Active = alarm | |
| AVmin | 1 | 4096_1 | System Input RMS L1-N | V | Read | |
| AV | 2 | 4098_1 | System Input RMS L2-N | V | Read | |
| AV | 3 | 4100_1 | System Input RMS L3-N | V | Read | |
| AV | 4 | 4097_1 | System Input RMS L1-L2 | V | Read | |
| AV | 5 | 4099_1 | System Input RMS L2-L3 | V | Read | |
| AV | 6 | 4101_1 | System Input RMS L3-L1 | V | Read | |
| AV | 7 | 4113_1 | System Input RMS Current L1 | A | Read | |
| AV | 8 | 4114_1 | System Input RMS Current L2 | A | Read | |
| AV | 9 | 4115_1 | System Input RMS Current L3 | A | Read | |
| AV | 10 | 4105_1 | System Input Frequency | Hz | Read | |
| AV | 11 | 4116_1 | System Input Power Factor L1 | Read | ||
| AV | 12 | 4117_1 | System Input Power Factor L2 | Read | ||
| AV | 13 | 4118_1 | System Input Power Factor L3 | Read | ||
| AV | 14 | 4106_1 | System Input Max Voltage L1-N | V | Read | |
| AV | 15 | 4107_1 | System Input Min Voltage L1-N | V | Read | |
| AV | 16 | 4108_1 | System Input Max Voltage L2-N | V | Read | |
| AV | 17 | 4109_1 | System Input Min Voltage L2-N | V | Read | |
| AV | 18 | 4110_1 | System Input Max Voltage L3-N | V | Read | |
| AV | 19 | 4111_1 | System Input Min Voltage L3-N | V | Read | |
| AV | 20 | 4102_1 | System Input Nominal Voltage | V | Read | |
| AV | 21 | 4104_1 | System Input Nominal Current | A | Read | |
| AV | 22 | 4103_1 | System Input Nominal Frequency | Hz | Read | |
| AV | 23 | 4112_1 | System Input Phase Count | Read | ||
| AV | 24 | 5900_1 | Input Energy | kWh | Read | |
| AV | 25 | 6318_1 | System Input Power Phase A | kW | Read | |
| AV | 26 | 6319_1 | System Input Power Phase B | kW | Read | |
| AV | 27 | 6320_1 | System Input Power Phase C | kW | Read | |
| AV | 28 | 8281_1 | Positive DC Bus Voltage | VDC | Read | |
| AV | 29 | 8282_1 | Negative DC Bus Voltage | VDC | Read | |
| AV | 35 | 4128_1 | Bypass Input Voltage RMS L1-N | V | Read | |
| AV | 36 | 4129_1 | Bypass Input Voltage RMS L2-N | V | Read | |
| AV | 37 | 4130_1 | Bypass Input Voltage RMS L3-N | V | Read | |
| AV | 38 | 4125_1 | Bypass Input Voltage RMS L1-L2 | V | Read | |
| AV | 39 | 4126_1 | Bypass Input Voltage RMS L2-L3 | V | Read | |
| AV | 40 | 4127_1 | Bypass Input Voltage RMS L3-L1 | V | Read | |
| AV | 41 | 4131_1 | Bypass Input Frequency | Hz | Read | |
| AV | 42 | 4259_1 | Bypass Nominal Voltage | V | Read | |
| AVmin | 53 | 4150_1 | Battery Time Remaining | min | Read | |
| AV | 54 | 4153_1 | Battery Percentage Charge | % | Read | |
| AV | 55 | 4149_1 | Battery Current | A DC | Read | |
| AV | 56 | 4148_1 | DC Bus Voltage | VDC | Read | |
| AV | 57 | 6189_1 | DC Bus Nominal Voltage | VDC | Read | |
| AV | 58 | 4156_1 | Battery Temperature | °C | Read | |
| AV | 10058 | 4156_1_deg_F | Battery Temperature | °F | Read | |
| AV | 59 | 4898_1 | Battery Rating | AH | Read | |
| AV | 60 | 5802_1 | Low Battery Warning Time | min | Write | |
| AV | 61 | 5800_1 | Number of EBC Installed | Read | ||
| AV | 62 | 6195_1 | Nominal Battery Capacity | min | Read | |
| AV | 63 | 4151_1 | Battery Discharge Time | min | Read | |
| AV | 64 | 4152_1 | Battery Total Discharge Time | h | Read | |
| AV | 65 | 5767_1 | Total Number of Battery Discharges | Read | ||
| AV | 66 | 8453_1 | Battery Run Time | day | Read | |
| AV | 67 | 4587_1 | Relative Humidity | % | Read | |
| AV | 68 | 4160_1 | Battery Commission Date | Secs since Epoch(UTC) | Read | |
| AV | 69 | 7462_1 | Battery State of Health | % | Read | |
| AV | 153 | 8340_1_1 | Lithium Battery Cabinet State of Charge (Lithium Battery Group 1) | % | Read | |
| AV | 154 | 8341_1_1 | Battery State of Health (Lithium Battery Group 1) | % | Read | |
| AV | 165 | 8340_1_2 | Lithium Battery Cabinet State of Charge (Lithium Battery Group 2) | % | Read | |
| AV | 166 | 8341_1_2 | Battery State of Health (Lithium Battery Group 2) | % | Read | |
| AV | 333 | 8340_1_16 | Lithium Battery Cabinet State of Charge (Lithium Battery Group 16) | % | Read | |
| AV | 334 | 8341_1_16 | Battery State of Health (Lithium Battery Group 16) | % | Read | |
| AV | 356 | 8328_1_1 | Maximum Cell Voltage | mV DC | Read | |
| AV | 357 | 8329_1_1 | Minimum Cell Voltage | mV DC | Read | |
| AVmin | 76 | 4385_1 | System Output Voltage RMS L1-N | V | Read | |
| AV | 77 | 4386_1 | System Output Voltage RMS L2-N | V | Read | |
| AV | 78 | 4387_1 | System Output Voltage RMS L3-N | V | Read | |
| AV | 79 | 4201_1 | System Output Voltage RMS L1-L2 | V | Read | |
| AV | 80 | 4202_1 | System Output Voltage RMS L2-L3 | V | Read | |
| AV | 81 | 4203_1 | System Output Voltage RMS L3-L1 | V | Read | |
| AVmin | 82 | 4204_1 | System Output RMS Current L1 | A | Read | |
| AV | 83 | 4205_1 | System Output RMS Current L2 | A | Read | |
| AV | 84 | 4206_1 | System Output RMS Current L3 | A | Read | |
| AV | 85 | 4207_1 | System Output Frequency | Hz | Read | |
| AVmin | 86 | 4208_1 | System Output Power | W | Read | |
| AV | 87 | 5859_1 | System Output Power L1 | W | Read | |
| AV | 88 | 5860_1 | System Output Power L2 | W | Read | |
| AV | 89 | 5959_1 | System Output Power L3 | W | Read | |
| AV | 90 | 5861_1 | System Output Pct Power | % | Read | |
| AV | 91 | 4223_1 | System Output Pct Power L1 | % | Read | |
| AV | 92 | 4224_1 | System Output Pct Power L2 | % | Read | |
| AV | 93 | 4225_1 | System Output Pct Power L3 | % | Read | |
| AV | 94 | 4209_1 | System Output Apparent Power | VA | Read | |
| AV | 95 | 5868_1 | System Output Apparent Power L1 | VA | Read | |
| AV | 96 | 5869_1 | System Output Apparent Power L2 | VA | Read | |
| AV | 97 | 5870_1 | System Output Apparent Power L3 | VA | Read | |
| AV | 98 | 5159_1 | Output Current Crest Factor L1 | Read | ||
| AV | 99 | 5160_1 | Output Current Crest Factor L2 | Read | ||
| AV | 100 | 5161_1 | Output Current Crest Factor L3 | Read | ||
| AV | 101 | 4210_1 | System Output Power Factor L1 | Read | ||
| AV | 102 | 4211_1 | System Output Power Factor L2 | Read | ||
| AV | 103 | 4212_1 | System Output Power Factor L3 | Read | ||
| AV | 104 | 4260_1 | System Output Nominal Voltage | V | Read | |
| AV | 105 | 5166_1 | Output Energy | kWh | Write | |
| AV | 106 | 4264_1 | Output Apparent Power Rating | VA | Read | |
| AV | 107 | 4261_1 | System Output Nominal Frequency | Hz | Read | |
| AV | 108 | 5816_1 | Output On Delay | s | Write | |
| AV | 109 | 5815_1 | Reboot With Delay | s | Write | |
| AV | 110 | 5814_1 | Shutdown After Delay | s | Write | |
| AV | 111 | 5812_1 | Nominal Power Factor | Read | ||
| AV | 112 | 4811_1 | Parallel Output Power | W | Read | |
| AV | 113 | 4812_1 | Parallel Output Apparent Power | VA | Read | |
| AV | 114 | 4829_1 | Parallel ID | Read | ||
| AV | 115 | 4833_1 | Number of parallel units | Read | ||
| AV | 126 | 4510_1 | Outlet Group Identifier | Read | ||
| AV | 137 | 4120_1 | System Input Black Out Count | Read | ||
| AV | 138 | 4119_1 | System Input Brown Out Count | Read | ||
| AV | 139 | 4710_1 | Auto Restart Delay | s | Write | |
| AV | 140 | 4291_1 | Inlet Air Temperature | °C | Read | |
| AV | 10140 | 4291_1_deg_F | Inlet Air Temperature | °F | Read | |
| AV | 141 | 4292_1 | Total System Operating Time | h | Read | |
| AV | 142 | 5821_1 | System Capacity | kVA | Read | |
| MV | 1 | 4553_1 | Server Class | Read | 1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR | |
| MV | 12 | 4871_1 | UPS Battery Status | Read | 1=Unknown, 2=Normal, 3=Low, 4=Depleted | |
| MV | 13 | 5799_1 | Battery Charge Status | Read | 1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off) | |
| MV | 14 | 5803_1 | Automatic Battery Test | Write | 1=disabled, 2=enabled | |
| MV | 15 | 5805_1 | Auto Battery Test Interval | Write | 1=8 weeks, 2=12 weeks, 3=16 weeks, 4=20 weeks, 5=26 weeks | |
| MV | 16 | 5858_1 | Manual Battery Test | Write | 1=Start Test | |
| MV | 17 | 6181_1 | Battery Test Result | Read | 1=Unknown, 2=Passed, 3=Failed, 4=In Progress, 5=System Failure, 6=Inhibited | |
| MV | 18 | 6183_1 | Battery Cabinet Type | Read | 1=Internal, 2=External, 3=LRT | |
| MV | 19 | 8330_1 | Battery type | Read | 1=VRLA, 2=Lithium Battery | |
| MV | 81 | 8350_1_1 | Lithium Battery Status (Lithium Battery Group 1) | Read | 1=Idle, 2=charging, 3=discharging, 4=Balance | |
| MV | 92 | 8350_1_2 | Lithium Battery Status (Lithium Battery Group 2) | Read | 1=Idle, 2=charging, 3=discharging, 4=Balance | |
| MV | 246 | 8350_1_16 | Lithium Battery Status (Lithium Battery Group 16) | Read | 1=Idle, 2=charging, 3=discharging, 4=Balance | |
| MV | 270 | 8361_1_1 | Lithium Battery Manual Wake Up | Write | 1=Wake up the lithium battery manually | |
| MVmin | 29 | 4872_1 | UPS Output Source | Read | 1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer | |
| MV | 40 | 4365_1 | Outlet Group Power Control | Write | 1=Off, 2=On, 3=Cycle Power | |
| MV | 51 | 6198_1 | ECO Mode Status | Read | 1=off, 2=on | |
| MV | 52 | 5454_1 | ECO Mode Operation State | Write | 1=disabled, 2=enabled | |
| MVmin | 63 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation | |
| MV | 64 | 5831_1 | Auto Restart | Write | 1=disabled, 2=enabled | |
| MV | 65 | 4746_1 | Inverter On/Off State | Read | 1=off, 2=on | |
| MV | 66 | 6197_1 | Shutdown Reason | Read | 1=None, 2=Over Temperature, 3=Overload, 4=DC Bus Overload, 5=Output Short, 6=Line Swap, 7=Low Battery, 8=Remote Command, 9=Input Under Voltage, 10=Power Factor Correction Fail, 11=External Signal Command | |
| MV | 67 | 6199_1 | UPS Topology | Read | 1=unknown, 2=Offline, 3=Line Interactive, 4=Online | |
| MV | 68 | 6191_1 | Reset Power Statistics | Write | 1=Reset | |
| MV | 69 | 6188_1 | Audible Alarm Control | Write | 1=off, 2=on | |
| MV | 70 | 6257_1 | Silence Audible Alarm | Write | 1=Silence Alarm |
No points match these filters.
Object ID lookup: Vertiv Liebert EXS / ITA2 UPS point IDs by name
BV14135_1BV25957_1BV34216_1BV48448_1BV58449_1BV68450_1BV78451_1BV88452_1BV124741_1BV134162_1BV144323_1BV156182_1BV165149_1BV175150_1BV187164_1BV194219_1BV204222_1BV768344_1_1BV778345_1_1BV788346_1_1BV798347_1_1BV808348_1_1BV818438_1_1BV828349_1_1BV838336_1_1BV847464_1_1BV858439_1_1BV868474_1_1BV878475_1_1BV888476_1_1BV898477_1_1BV908478_1_1BV968344_1_2BV978345_1_2BV988346_1_2BV998347_1_2BV1008348_1_2BV1018438_1_2BV1028349_1_2BV1038336_1_2BV1047464_1_2BV1058439_1_2BV1068474_1_2BV1078475_1_2BV1088476_1_2BV1098477_1_2BV1108478_1_2BV3768344_1_16BV3778345_1_16BV3788346_1_16BV3798347_1_16BV3808348_1_16BV3818438_1_16BV3828349_1_16BV3838336_1_16BV3847464_1_16BV3858439_1_16BV3868474_1_16BV3878475_1_16BV3888476_1_16BV3898477_1_16BV3908478_1_16BV3968331_1_1BV3978332_1_1BV3988333_1_1BV3998334_1_1BV4008335_1_1BV4018337_1_1BV4028339_1_1BV4038338_1_1BV4048479_1_1BV4058480_1_1BV4068481_1_1BV4078482_1_1BV4088483_1_1BV4098484_1_1BV265806_1BV274215_1BV284389_1BV295808_1BV308368_1BV384298_1BV394168_1BV404122_1BV414310_1BV426186_1BV436187_1BV445588_1BV454823_1BV464825_1BV476254_1BV484295_1BV494233_1BV505976_1BV514311_1BV524229_1BV536453_1BV546454_1BV555154_1BV565153_1BV576059_1BV584300_1BV594147_1BV5008454_1BV5018455_1BV5028456_1BV5038457_1BV5048458_1BV5058459_1BV5065840_1BV5074382_1BV5084167_1BV5094297_1BV5108310_1BV5118307_1BV5126350_1BV5136066_1BV5148309_1BV5158317_1BV5168315_1BV5178316_1BV5185810_1BV5198318_1BV5208319_1BV5218311_1BV5228312_1BV5238313_1BV5246064_1BV5255809_1BV5268314_1BV5278284_1BV5288617_1BV656061_1BV668446_1BV678447_1AV14096_1AV24098_1AV34100_1AV44097_1AV54099_1AV64101_1AV74113_1AV84114_1AV94115_1AV104105_1AV114116_1AV124117_1AV134118_1AV144106_1AV154107_1AV164108_1AV174109_1AV184110_1AV194111_1AV204102_1AV214104_1AV224103_1AV234112_1AV245900_1AV256318_1AV266319_1AV276320_1AV288281_1AV298282_1AV354128_1AV364129_1AV374130_1AV384125_1AV394126_1AV404127_1AV414131_1AV424259_1AV534150_1AV544153_1AV554149_1AV564148_1AV576189_1AV584156_1AV100584156_1_deg_FAV594898_1AV605802_1AV615800_1AV626195_1AV634151_1AV644152_1AV655767_1AV668453_1AV674587_1AV684160_1AV697462_1AV1538340_1_1AV1548341_1_1AV1658340_1_2AV1668341_1_2AV3338340_1_16AV3348341_1_16AV3568328_1_1AV3578329_1_1AV764385_1AV774386_1AV784387_1AV794201_1AV804202_1AV814203_1AV824204_1AV834205_1AV844206_1AV854207_1AV864208_1AV875859_1AV885860_1AV895959_1AV905861_1AV914223_1AV924224_1AV934225_1AV944209_1AV955868_1AV965869_1AV975870_1AV985159_1AV995160_1AV1005161_1AV1014210_1AV1024211_1AV1034212_1AV1044260_1AV1055166_1AV1064264_1AV1074261_1AV1085816_1AV1095815_1AV1105814_1AV1115812_1AV1124811_1AV1134812_1AV1144829_1AV1154833_1AV1264510_1AV1374120_1AV1384119_1AV1394710_1AV1404291_1AV101404291_1_deg_FAV1414292_1AV1425821_1MV14553_1MV124871_1MV135799_1MV145803_1MV155805_1MV165858_1MV176181_1MV186183_1MV198330_1MV818350_1_1MV928350_1_2MV2468350_1_16MV2708361_1_1MV294872_1MV404365_1MV516198_1MV525454_1MV634123_1MV645831_1MV654746_1MV666197_1MV676199_1MV686191_1MV696188_1MV706257_1
Integration notes
- Tables 5.154, 5.155, 5.156, pdf pages 2130-2143 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
- The guide prints the same instance twice for: AV 60 (5802_1 and 5802_1_1); MV 14 (5803_1 and 5803_1_1); MV 15 (5805_1 and 5805_1_1); MV 16 (5858_1 and 5858_1_1); only the first is listed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert EXS / ITA2 UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert EXS / ITA2 UPS
How many BACnet points does the Vertiv Liebert EXS / ITA2 UPS have?
This list has 271 BACnet objects: 111 analog values, 135 binary values, 25 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert EXS / ITA2 UPS BACnet points are writable?
16 of the 271 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert EXS / ITA2 UPS BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert EXS / ITA2 UPS?
Start with MV 63 4123_1 (Normal, warning or alarm state); MV 29 4872_1 (Load on inverter, bypass or battery); AV 53 4150_1 (Estimated battery runtime, min); AV 86 4208_1 (Output power, W); AV 1 4096_1 (Input voltage, V); AV 76 4385_1 (Output voltage, V); AV 82 4204_1 (Output current, A); BV 39 4168_1 (Load is on battery); BV 58 4300_1 (Internal communication lost).
How do I check these points on the real Liebert EXS / ITA2 UPS?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.