- Home
- BACnet points lists
- Vertiv
- Liebert APM2 UPS
UPS (uninterruptible power supply) · BACnet points list
Vertiv Liebert APM2 UPS BACnet points list
Updated 6 November 2026
The Liebert APM2 UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.
This page lists 845 BACnet objects for the Vertiv Liebert APM2 UPS — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert APM2 UPS
- Equipment
- UPS (uninterruptible power supply)
- Equipment type
- Other equipment
- BACnet objects
- 845 (1 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- APM2, Liebert APM2, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert APM2 UPS
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 643 | 4123_1 | Normal, warning or alarm state | Read |
| AV 267 | 4150_1 | Estimated battery runtime, min | Read |
| AV 77 | 4208_1 | Output power, kW | Read |
| AV 1 | 4097_1 | Input voltage, V | Read |
| AV 55 | 4201_1 | Output voltage, V | Read |
| AV 61 | 4204_1 | Output current, A | Read |
| BV 939 | 4168_1 | Load is on battery | Read |
| BV 909 | 4300_1 | Internal communication lost | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert APM2 UPS BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | 5155_1 | Mains Input Neutral Lost | Read | Active = alarm | |
| BV | 2 | 4146_1 | System Input Phs Rotation Error | Read | Active = alarm | |
| BV | 3 | 4122_1 | System Input Power Problem | Read | Active = alarm | |
| BV | 4 | 6630_1 | Input Under Voltage | Read | Active = alarm | |
| BV | 5 | 6061_1 | Input Source Backfeed | Read | Active = alarm | |
| BV | 16 | 6333_1 | Bypass out of sync | Read | Active = alarm | |
| BV | 17 | 5957_1 | Bypass Input Voltage Fault | Read | Active = alarm | |
| BV | 18 | 4325_1 | Backfeed Breaker Open | Read | Active = alarm | |
| BV | 19 | 5976_1 | Maintenance Bypass Breaker Closed | Read | Active = alarm | |
| BV | 20 | 8489_1 | System Bypass Phase Rotation Error | Read | Active = alarm | |
| BV | 31 | 5806_1 | Output Overload | Read | Active = alarm | |
| BV | 32 | 4389_1 | System Output Fault | Read | Active = alarm | |
| BV | 33 | 6220_1 | Module Output Breaker Open | Read | Active = alarm | |
| BV | 44 | 8494_1 | System Control Card Not Ready (System Control Card 1) | Read | Active = alarm | |
| BV | 45 | 8495_1 | System Control Card Power Supply Failure (System Control Card 1) | Read | Active = alarm | |
| BV | 46 | 8496_1 | System Control Card Communication Fail (System Control Card 1) | Read | Active = alarm | |
| BV | 57 | 8494_2 | System Control Card Not Ready (System Control Card 2) | Read | Active = alarm | |
| BV | 58 | 8495_2 | System Control Card Power Supply Failure (System Control Card 2) | Read | Active = alarm | |
| BV | 59 | 8496_2 | System Control Card Communication Fail (System Control Card 2) | Read | Active = alarm | |
| BV | 70 | 8501_1 | Bypass Module Not Ready | Read | Active = alarm | |
| BV | 71 | 8502_1 | Bypass Module Power Supply Failure | Read | Active = alarm | |
| BV | 72 | 8503_1 | Bypass Module Communication Fault | Read | Active = alarm | |
| BV | 73 | 4143_1 | Bypass Static Switch Unavailable | Read | Active = alarm | |
| BV | 74 | 4216_1 | Bypass Backfeed Detected | Read | Active = alarm | |
| BV | 75 | 8096_1 | Bypass controlling the SCR autonomously | Read | Active = alarm | |
| BV | 76 | 4139_1 | Bypass - Excess Auto Retransfers | Read | Active = alarm | |
| BV | 77 | 8504_1 | Bypass Module Over Temperature | Read | Active = alarm | |
| BV | 78 | 8505_1 | Bypass Module Fan Fault | Read | Active = alarm | |
| BV | 89 | 8512_1 | Power Module Not Ready (Power Module 1) | Read | Active = alarm | |
| BV | 90 | 6441_1 | Power Module Power Supply Failure (Power Module 1) | Read | Active = alarm | |
| BV | 91 | 8098_1 | Power Module Communication status (Power Module 1) | Read | Active = alarm | |
| BV | 92 | 6440_1 | Power Module Fuse Failure (Power Module 1) | Read | Active = alarm | |
| BV | 93 | 5838_1 | Power Module Fan Fault (Power Module 1) | Read | Active = alarm | |
| BV | 94 | 5839_1 | Power Module Over Temperature (Power Module 1) | Read | Active = alarm | |
| BV | 105 | 6438_1_1 | Power Module Input Current Abnormal (Power Module 1 Rectifier 1) | Read | Active = alarm | |
| BV | 106 | 8285_1_1 | Power Module Input Current High (Power Module 1 Rectifier 1) | Read | Active = alarm | |
| BV | 107 | 4295_1_1 | Rectifier Failure (Power Module 1 Rectifier 1) | Read | Active = alarm | |
| BV | 118 | 5154_1_1 | DC Bus Abnormal (Power Module 1 DC Bus 1) | Read | Active = alarm | |
| BV | 119 | 6439_1_1 | Power Module Balancer of DC Bus Failure (Power Module 1 DC Bus 1) | Read | Active = alarm | |
| BV | 130 | 5153_1_1 | Load Sharing Fault (Power Module 1 Inverter 1) | Read | Active = alarm | |
| BV | 131 | 6059_1_1 | Inverter Relay Fault (Power Module 1 Inverter 1) | Read | Active = alarm | |
| BV | 132 | 4290_1_1 | Inverter Shutdown - Overload (Power Module 1 Inverter 1) | Read | Active = alarm | |
| BV | 133 | 6062_1_1 | Loss of Synchronization (Power Module 1 Inverter 1) | Read | Active = alarm | |
| BV | 134 | 4233_1_1 | Inverter Failure (Power Module 1 Inverter 1) | Read | Active = alarm | |
| BV | 145 | 6254_1_1 | Charger Failure (Power Module 1 Charger 1) | Read | Active = alarm | |
| BV | 156 | 8510_1_1 | Discharger Failure (Power Module 1 Discharger 1) | Read | Active = alarm | |
| BV | 157 | 8274_1_1 | Discharger Shutdown (Power Module 1 Discharger 1) | Read | Active = alarm | |
| BV | 158 | 6063_1_1 | Battery Converter Current Limit (Power Module 1 Discharger 1) | Read | Active = alarm | |
| BV | 169 | 8512_2 | Power Module Not Ready (Power Module 2) | Read | Active = alarm | |
| BV | 170 | 6441_2 | Power Module Power Supply Failure (Power Module 2) | Read | Active = alarm | |
| BV | 171 | 8098_2 | Power Module Communication status (Power Module 2) | Read | Active = alarm | |
| BV | 172 | 6440_2 | Power Module Fuse Failure (Power Module 2) | Read | Active = alarm | |
| BV | 173 | 5838_2 | Power Module Fan Fault (Power Module 2) | Read | Active = alarm | |
| BV | 174 | 5839_2 | Power Module Over Temperature (Power Module 2) | Read | Active = alarm | |
| BV | 185 | 6438_2_1 | Power Module Input Current Abnormal (Power Module 2 Rectifier 1) | Read | Active = alarm | |
| BV | 186 | 8285_2_1 | Power Module Input Current High (Power Module 2 Rectifier 1) | Read | Active = alarm | |
| BV | 187 | 4295_2_1 | Rectifier Failure (Power Module 2 Rectifier 1) | Read | Active = alarm | |
| BV | 198 | 5154_2_1 | DC Bus Abnormal (Power Module 2 DC Bus 1) | Read | Active = alarm | |
| BV | 199 | 6439_2_1 | Power Module Balancer of DC Bus Failure (Power Module 2 DC Bus 1) | Read | Active = alarm | |
| BV | 210 | 5153_2_1 | Load Sharing Fault (Power Module 2 Inverter 1) | Read | Active = alarm | |
| BV | 211 | 6059_2_1 | Inverter Relay Fault (Power Module 2 Inverter 1) | Read | Active = alarm | |
| BV | 212 | 4290_2_1 | Inverter Shutdown - Overload (Power Module 2 Inverter 1) | Read | Active = alarm | |
| BV | 213 | 6062_2_1 | Loss of Synchronization (Power Module 2 Inverter 1) | Read | Active = alarm | |
| BV | 214 | 4233_2_1 | Inverter Failure (Power Module 2 Inverter 1) | Read | Active = alarm | |
| BV | 225 | 6254_2_1 | Charger Failure (Power Module 2 Charger 1) | Read | Active = alarm | |
| BV | 236 | 8510_2_1 | Discharger Failure (Power Module 2 Discharger 1) | Read | Active = alarm | |
| BV | 237 | 8274_2_1 | Discharger Shutdown (Power Module 2 Discharger 1) | Read | Active = alarm | |
| BV | 238 | 6063_2_1 | Battery Converter Current Limit (Power Module 2 Discharger 1) | Read | Active = alarm | |
| BV | 809 | 8512_10 | Power Module Not Ready (Power Module 10) | Read | Active = alarm | |
| BV | 810 | 6441_10 | Power Module Power Supply Failure (Power Module 10) | Read | Active = alarm | |
| BV | 811 | 8098_10 | Power Module Communication status (Power Module 10) | Read | Active = alarm | |
| BV | 812 | 6440_10 | Power Module Fuse Failure (Power Module 10) | Read | Active = alarm | |
| BV | 813 | 5838_10 | Power Module Fan Fault (Power Module 10) | Read | Active = alarm | |
| BV | 814 | 5839_10 | Power Module Over Temperature (Power Module 10) | Read | Active = alarm | |
| BV | 825 | 6438_10_1 | Power Module Input Current Abnormal (Power Module 10 Rectifier 1) | Read | Active = alarm | |
| BV | 826 | 8285_10_1 | Power Module Input Current High (Power Module 10 Rectifier 1) | Read | Active = alarm | |
| BV | 827 | 4295_10_1 | Rectifier Failure (Power Module 10 Rectifier 1) | Read | Active = alarm | |
| BV | 838 | 5154_10_1 | DC Bus Abnormal (Power Module 10 DC Bus 1) | Read | Active = alarm | |
| BV | 839 | 6439_10_1 | Power Module Balancer of DC Bus Failure (Power Module 10 DC Bus 1) | Read | Active = alarm | |
| BV | 850 | 5153_10_1 | Load Sharing Fault (Power Module 10 Inverter 1) | Read | Active = alarm | |
| BV | 851 | 6059_10_1 | Inverter Relay Fault (Power Module 10 Inverter 1) | Read | Active = alarm | |
| BV | 852 | 4290_10_1 | Inverter Shutdown - Overload (Power Module 10 Inverter 1) | Read | Active = alarm | |
| BV | 853 | 6062_10_1 | Loss of Synchronization (Power Module 10 Inverter 1) | Read | Active = alarm | |
| BV | 854 | 4233_10_1 | Inverter Failure (Power Module 10 Inverter 1) | Read | Active = alarm | |
| BV | 865 | 6254_10_1 | Charger Failure (Power Module 10 Charger 1) | Read | Active = alarm | |
| BV | 876 | 8510_10_1 | Discharger Failure (Power Module 10 Discharger 1) | Read | Active = alarm | |
| BV | 877 | 8274_10_1 | Discharger Shutdown (Power Module 10 Discharger 1) | Read | Active = alarm | |
| BV | 878 | 6063_10_1 | Battery Converter Current Limit (Power Module 10 Discharger 1) | Read | Active = alarm | |
| BV | 889 | 6066_1 | Parallel Cable Failure | Read | Active = alarm | |
| BV | 890 | 4823_1 | Parallel Comm Warning | Read | Active = alarm | |
| BV | 891 | 6536_1 | MMS Capacity Exceeded | Read | Active = alarm | |
| BV | 892 | 5817_1 | Loss of Redundancy | Read | Active = alarm | |
| BV | 903 | 6529_1 | Hardware Mismatch | Read | Active = alarm | |
| BV | 904 | 6064_1 | LBS Cable Failure | Read | Active = alarm | |
| BV | 905 | 6060_1 | Transfer to Bypass - System Overload | Read | Active = alarm | |
| BV | 906 | 5458_1 | Excess ECO Suspends | Read | Active = alarm | |
| BV | 907 | 5157_1 | User Operation Invalid | Read | Active = alarm | |
| BV | 908 | 5156_1 | Load Impact Transfer | Read | Active = alarm | |
| BVmin | 909 | 4300_1 | Internal Communications Failure | Read | Active = alarm | |
| BV | 910 | 4310_1 | Equipment Over Temperature | Read | Active = alarm | |
| BV | 911 | 4758_1 | LBS Inhibited | Read | Active = alarm | |
| BV | 912 | 4315_1 | On Generator | Read | Active = alarm | |
| BV | 913 | 4757_1 | LBS Active | Read | Active = alarm | |
| BV | 914 | 4213_1 | System Shutdown - EPO | Read | Active = alarm | |
| BV | 915 | 4440_1 | Fuse Failure | Read | Active = alarm | |
| BV | 916 | 5970_1 | Ground Fault | Read | Active = alarm | |
| BV | 917 | 4311_1 | System Fan Failure | Read | Active = alarm | |
| BV | 918 | 8286_1 | Parameter Configuration Failed | Read | Active = alarm | |
| BV | 919 | 4215_1 | System Output Off | Read | Active = alarm | |
| BV | 920 | 8287_1 | Output Disabled | Read | Active = alarm | |
| BV | 921 | 5770_1 | Top Outlet Fan Fault | Read | Active = alarm | |
| BV | 922 | 8100_1 | ECO mode Inhibited | Read | Active = alarm | |
| BV | 923 | 4289_1 | Inverter Transfer Inhibit - Ext | Read | Active = alarm | |
| BV | 924 | 4298_1 | UPS Output on Bypass | Read | Active = alarm | |
| BV | 925 | 4299_1 | Output Load on Maint. Bypass | Read | Active = alarm | |
| BV | 926 | 5185_1 | Transformer Overtemperature | Read | Active = alarm | |
| BV | 937 | 4741_1 | Battery Self Test | Read | Active = alarm | |
| BV | 938 | 4200_1 | Battery Charging Inhibited | Read | Active = alarm | |
| BVmin | 939 | 4168_1 | Battery Discharging | Read | Active = alarm | |
| BV | 940 | 4171_1 | Battery Manual Test In Progress | Read | Active = alarm | |
| BV | 941 | 4172_1 | Battery Auto Test In Progress | Read | Active = alarm | |
| BV | 942 | 4323_1 | Battery Test Failed | Read | Active = alarm | |
| BV | 943 | 4162_1 | Battery Low | Read | Active = alarm | |
| BV | 944 | 4222_1 | Battery Ground Fault | Read | Active = alarm | |
| BV | 945 | 5149_1 | Battery Not Qualified | Read | Active = alarm | |
| BV | 946 | 5150_1 | Battery Terminals Reversed | Read | Active = alarm | |
| BV | 947 | 6182_1 | Replace Battery | Read | Active = alarm | |
| BV | 948 | 6065_1 | Battery Charge Equalization Timeout | Read | Active = alarm | |
| BV | 949 | 6068_1 | Battery Room Alarm | Read | Active = alarm | |
| BV | 950 | 4170_1 | Battery Equalize | Read | Active = alarm | |
| BV | 951 | 8288_1 | Battery Terminal Abnormal | Read | Active = alarm | |
| BV | 952 | 8429_1 | Battery System Communication Abnormal | Read | Active = alarm | |
| BV | 953 | 8430_1 | Battery System Warning | Read | Active = alarm | |
| BV | 954 | 8431_1 | Battery System Fault | Read | Active = alarm | |
| BV | 955 | 4176_1 | Battery Circuit Breaker 1 Open | Read | Active = alarm | |
| BV | 956 | 4179_1 | Battery Circuit Breaker 2 Open | Read | Active = alarm | |
| BV | 957 | 4182_1 | Battery Circuit Breaker 3 Open | Read | Active = alarm | |
| BV | 958 | 4185_1 | Battery Circuit Breaker 4 Open | Read | Active = alarm | |
| BV | 959 | 4188_1 | Battery Circuit Breaker 5 Open | Read | Active = alarm | |
| BV | 960 | 4191_1 | Battery Circuit Breaker 6 Open | Read | Active = alarm | |
| BV | 961 | 4194_1 | Battery Circuit Breaker 7 Open | Read | Active = alarm | |
| BV | 962 | 4197_1 | Battery Circuit Breaker 8 Open | Read | Active = alarm | |
| BV | 963 | 8517_1 | Battery Circuit Breaker 9 Open | Read | Active = alarm | |
| BV | 964 | 8518_1 | Battery Circuit Breaker 10 Open | Read | Active = alarm | |
| BV | 965 | 8519_1 | Battery Circuit Breaker 11 Open | Read | Active = alarm | |
| BV | 966 | 8520_1 | Battery Circuit Breaker 12 Open | Read | Active = alarm | |
| BV | 967 | 4178_1 | Battery Breaker 1 Open Failure | Read | Active = alarm | |
| BV | 968 | 4180_1 | Battery Breaker 2 Open Failure | Read | Active = alarm | |
| BV | 969 | 4183_1 | Battery Breaker 3 Open Failure | Read | Active = alarm | |
| BV | 970 | 4186_1 | Battery Breaker 4 Open Failure | Read | Active = alarm | |
| BV | 971 | 4190_1 | Battery Breaker 5 Open Failure | Read | Active = alarm | |
| BV | 972 | 4192_1 | Battery Breaker 6 Open Failure | Read | Active = alarm | |
| BV | 973 | 4195_1 | Battery Breaker 7 Open Failure | Read | Active = alarm | |
| BV | 974 | 4198_1 | Battery Breaker 8 Open Failure | Read | Active = alarm | |
| BV | 975 | 8521_1 | Battery Breaker 9 Open Failure | Read | Active = alarm | |
| BV | 976 | 8522_1 | Battery Breaker 10 Open Failure | Read | Active = alarm | |
| BV | 977 | 8523_1 | Battery Breaker 11 Open Failure | Read | Active = alarm | |
| BV | 978 | 8524_1 | Battery Breaker 12 Open Failure | Read | Active = alarm | |
| BV | 989 | 8537_1 | Battery Cabinet High Overall Voltage (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 990 | 8538_1 | Battery Cabinet Low Overall Voltage (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 991 | 8539_1 | Battery Cabinet High Cell Voltage (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 992 | 8540_1 | Battery Cabinet Low Cell Voltage (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 993 | 8541_1 | Battery Cabinet Over Overall Voltage (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 994 | 8542_1 | Battery Cabinet Under Overall Voltage (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 995 | 8543_1 | Battery Cabinet Over Cell Voltage (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 996 | 8544_1 | Battery Cabinet Under Cell Voltage (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 997 | 8545_1 | Battery Cabinet Charge Over Current (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 998 | 8546_1 | Battery Cabinet Discharge Over Current (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 999 | 8547_1 | Battery Cabinet Over Temperature (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 1000 | 8548_1 | Battery Cabinet Under Temperature (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 1001 | 4174_1 | Battery Temperature Sensor Fault (Battery Cabinet 1) | Read | Active = alarm | |
| BV | 1012 | 8587_1_1 | Battery Module Disconnected (Battery Cabinet 1 Battery Module 1) | Read | Active = alarm | |
| BV | 1013 | 8590_1_1 | Battery Module Over Temperature (Battery Cabinet 1 Battery Module 1) | Read | Active = alarm | |
| BV | 1024 | 8579_1_1_1 | Battery Module High Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1025 | 8580_1_1_1 | Battery Module Low Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1026 | 8581_1_1_1 | Battery Module High Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1027 | 8582_1_1_1 | Battery Module Low Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1028 | 8583_1_1_1 | Battery Module Over Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1029 | 8584_1_1_1 | Battery Module Under Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1030 | 8585_1_1_1 | Battery Module Over Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1031 | 8586_1_1_1 | Battery Module Under Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1032 | 8588_1_1_1 | Battery Module Charge Over Current (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1033 | 8589_1_1_1 | Battery Module Discharge Over Current (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1034 | 8591_1_1_1 | Battery Module Under Temperature (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1035 | 8592_1_1_1 | Battery Module Fault (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 1046 | 8587_1_2 | Battery Module Disconnected (Battery Cabinet 1 Battery Module 2) | Read | Active = alarm | |
| BV | 1047 | 8590_1_2 | Battery Module Over Temperature (Battery Cabinet 1 Battery Module 2) | Read | Active = alarm | |
| BV | 1058 | 8579_1_2_1 | Battery Module High Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1059 | 8580_1_2_1 | Battery Module Low Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1060 | 8581_1_2_1 | Battery Module High Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1061 | 8582_1_2_1 | Battery Module Low Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1062 | 8583_1_2_1 | Battery Module Over Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1063 | 8584_1_2_1 | Battery Module Under Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1064 | 8585_1_2_1 | Battery Module Over Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1065 | 8586_1_2_1 | Battery Module Under Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1066 | 8588_1_2_1 | Battery Module Charge Over Current (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1067 | 8589_1_2_1 | Battery Module Discharge Over Current (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1068 | 8591_1_2_1 | Battery Module Under Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 1069 | 8592_1_2_1 | Battery Module Fault (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2066 | 8587_1_32 | Battery Module Disconnected (Battery Cabinet 1 Battery Module 32) | Read | Active = alarm | |
| BV | 2067 | 8590_1_32 | Battery Module Over Temperature (Battery Cabinet 1 Battery Module 32) | Read | Active = alarm | |
| BV | 2078 | 8579_1_32_1 | Battery Module High Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2079 | 8580_1_32_1 | Battery Module Low Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2080 | 8581_1_32_1 | Battery Module High Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2081 | 8582_1_32_1 | Battery Module Low Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2082 | 8583_1_32_1 | Battery Module Over Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2083 | 8584_1_32_1 | Battery Module Under Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2084 | 8585_1_32_1 | Battery Module Over Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2085 | 8586_1_32_1 | Battery Module Under Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2086 | 8588_1_32_1 | Battery Module Charge Over Current (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2087 | 8589_1_32_1 | Battery Module Discharge Over Current (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2088 | 8591_1_32_1 | Battery Module Under Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2089 | 8592_1_32_1 | Battery Module Fault (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 2100 | 8537_2 | Battery Cabinet High Overall Voltage (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2101 | 8538_2 | Battery Cabinet Low Overall Voltage (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2102 | 8539_2 | Battery Cabinet High Cell Voltage (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2103 | 8540_2 | Battery Cabinet Low Cell Voltage (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2104 | 8541_2 | Battery Cabinet Over Overall Voltage (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2105 | 8542_2 | Battery Cabinet Under Overall Voltage (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2106 | 8543_2 | Battery Cabinet Over Cell Voltage (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2107 | 8544_2 | Battery Cabinet Under Cell Voltage (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2108 | 8545_2 | Battery Cabinet Charge Over Current (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2109 | 8546_2 | Battery Cabinet Discharge Over Current (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2110 | 8547_2 | Battery Cabinet Over Temperature (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2111 | 8548_2 | Battery Cabinet Under Temperature (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2112 | 4174_2 | Battery Temperature Sensor Fault (Battery Cabinet 2) | Read | Active = alarm | |
| BV | 2123 | 8587_2_1 | Battery Module Disconnected (Battery Cabinet 2 Battery Module 1) | Read | Active = alarm | |
| BV | 2124 | 8590_2_1 | Battery Module Over Temperature (Battery Cabinet 2 Battery Module 1) | Read | Active = alarm | |
| BV | 2135 | 8579_2_1_1 | Battery Module High Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2136 | 8580_2_1_1 | Battery Module Low Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2137 | 8581_2_1_1 | Battery Module High Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2138 | 8582_2_1_1 | Battery Module Low Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2139 | 8583_2_1_1 | Battery Module Over Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2140 | 8584_2_1_1 | Battery Module Under Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2141 | 8585_2_1_1 | Battery Module Over Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2142 | 8586_2_1_1 | Battery Module Under Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2143 | 8588_2_1_1 | Battery Module Charge Over Current (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2144 | 8589_2_1_1 | Battery Module Discharge Over Current (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2145 | 8591_2_1_1 | Battery Module Under Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2146 | 8592_2_1_1 | Battery Module Fault (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2157 | 8587_2_2 | Battery Module Disconnected (Battery Cabinet 2 Battery Module 2) | Read | Active = alarm | |
| BV | 2158 | 8590_2_2 | Battery Module Over Temperature (Battery Cabinet 2 Battery Module 2) | Read | Active = alarm | |
| BV | 2169 | 8579_2_2_1 | Battery Module High Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2170 | 8580_2_2_1 | Battery Module Low Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2171 | 8581_2_2_1 | Battery Module High Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2172 | 8582_2_2_1 | Battery Module Low Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2173 | 8583_2_2_1 | Battery Module Over Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2174 | 8584_2_2_1 | Battery Module Under Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2175 | 8585_2_2_1 | Battery Module Over Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2176 | 8586_2_2_1 | Battery Module Under Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2177 | 8588_2_2_1 | Battery Module Charge Over Current (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2178 | 8589_2_2_1 | Battery Module Discharge Over Current (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2179 | 8591_2_2_1 | Battery Module Under Temperature (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 2180 | 8592_2_2_1 | Battery Module Fault (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1) | Read | Active = alarm | |
| BV | 3177 | 8587_2_32 | Battery Module Disconnected (Battery Cabinet 2 Battery Module 32) | Read | Active = alarm | |
| BV | 3178 | 8590_2_32 | Battery Module Over Temperature (Battery Cabinet 2 Battery Module 32) | Read | Active = alarm | |
| BV | 3189 | 8579_2_32_1 | Battery Module High Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3190 | 8580_2_32_1 | Battery Module Low Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3191 | 8581_2_32_1 | Battery Module High Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3192 | 8582_2_32_1 | Battery Module Low Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3193 | 8583_2_32_1 | Battery Module Over Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3194 | 8584_2_32_1 | Battery Module Under Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3195 | 8585_2_32_1 | Battery Module Over Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3196 | 8586_2_32_1 | Battery Module Under Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3197 | 8588_2_32_1 | Battery Module Charge Over Current (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3198 | 8589_2_32_1 | Battery Module Discharge Over Current (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3199 | 8591_2_32_1 | Battery Module Under Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 3200 | 8592_2_32_1 | Battery Module Fault (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9877 | 8537_9 | Battery Cabinet High Overall Voltage (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9878 | 8538_9 | Battery Cabinet Low Overall Voltage (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9879 | 8539_9 | Battery Cabinet High Cell Voltage (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9880 | 8540_9 | Battery Cabinet Low Cell Voltage (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9881 | 8541_9 | Battery Cabinet Over Overall Voltage (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9882 | 8542_9 | Battery Cabinet Under Overall Voltage (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9883 | 8543_9 | Battery Cabinet Over Cell Voltage (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9884 | 8544_9 | Battery Cabinet Under Cell Voltage (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9885 | 8545_9 | Battery Cabinet Charge Over Current (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9886 | 8546_9 | Battery Cabinet Discharge Over Current (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9887 | 8547_9 | Battery Cabinet Over Temperature (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9888 | 8548_9 | Battery Cabinet Under Temperature (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9889 | 4174_9 | Battery Temperature Sensor Fault (Battery Cabinet 9) | Read | Active = alarm | |
| BV | 9900 | 8587_9_1 | Battery Module Disconnected (Battery Cabinet 9 Battery Module 1) | Read | Active = alarm | |
| BV | 9901 | 8590_9_1 | Battery Module Over Temperature (Battery Cabinet 9 Battery Module 1) | Read | Active = alarm | |
| BV | 9912 | 8579_9_1_1 | Battery Module High Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9913 | 8580_9_1_1 | Battery Module Low Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9914 | 8581_9_1_1 | Battery Module High Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9915 | 8582_9_1_1 | Battery Module Low Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9916 | 8583_9_1_1 | Battery Module Over Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9917 | 8584_9_1_1 | Battery Module Under Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9918 | 8585_9_1_1 | Battery Module Over Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9919 | 8586_9_1_1 | Battery Module Under Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9920 | 8588_9_1_1 | Battery Module Charge Over Current (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9921 | 8589_9_1_1 | Battery Module Discharge Over Current (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9922 | 8591_9_1_1 | Battery Module Under Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9923 | 8592_9_1_1 | Battery Module Fault (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9934 | 8587_9_2 | Battery Module Disconnected (Battery Cabinet 9 Battery Module 2) | Read | Active = alarm | |
| BV | 9935 | 8590_9_2 | Battery Module Over Temperature (Battery Cabinet 9 Battery Module 2) | Read | Active = alarm | |
| BV | 9946 | 8579_9_2_1 | Battery Module High Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9947 | 8580_9_2_1 | Battery Module Low Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9948 | 8581_9_2_1 | Battery Module High Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9949 | 8582_9_2_1 | Battery Module Low Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9950 | 8583_9_2_1 | Battery Module Over Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9951 | 8584_9_2_1 | Battery Module Under Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9952 | 8585_9_2_1 | Battery Module Over Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9953 | 8586_9_2_1 | Battery Module Under Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9954 | 8588_9_2_1 | Battery Module Charge Over Current (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9955 | 8589_9_2_1 | Battery Module Discharge Over Current (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9956 | 8591_9_2_1 | Battery Module Under Temperature (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 9957 | 8592_9_2_1 | Battery Module Fault (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10954 | 8587_9_32 | Battery Module Disconnected (Battery Cabinet 9 Battery Module 32) | Read | Active = alarm | |
| BV | 10955 | 8590_9_32 | Battery Module Over Temperature (Battery Cabinet 9 Battery Module 32) | Read | Active = alarm | |
| BV | 10966 | 8579_9_32_1 | Battery Module High Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10967 | 8580_9_32_1 | Battery Module Low Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10968 | 8581_9_32_1 | Battery Module High Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10969 | 8582_9_32_1 | Battery Module Low Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10970 | 8583_9_32_1 | Battery Module Over Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10971 | 8584_9_32_1 | Battery Module Under Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10972 | 8585_9_32_1 | Battery Module Over Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10973 | 8586_9_32_1 | Battery Module Under Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10974 | 8588_9_32_1 | Battery Module Charge Over Current (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10975 | 8589_9_32_1 | Battery Module Discharge Over Current (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10976 | 8591_9_32_1 | Battery Module Under Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10977 | 8592_9_32_1 | Battery Module Fault (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | Read | Active = alarm | |
| BV | 10988 | 8605_1 | Battery String High Overall Voltage (Battery String 1) | Read | Active = alarm | |
| BV | 10989 | 8606_1 | Battery String Low Overall Voltage (Battery String 1) | Read | Active = alarm | |
| BV | 10990 | 8558_1 | Battery String High Cell Voltage (Battery String 1) | Read | Active = alarm | |
| BV | 10991 | 8559_1 | Battery String Low Cell Voltage (Battery String 1) | Read | Active = alarm | |
| BV | 10992 | 8560_1 | Battery String Over Overall Voltage (Battery String 1) | Read | Active = alarm | |
| BV | 10993 | 8561_1 | Battery String Under Overall Voltage (Battery String 1) | Read | Active = alarm | |
| BV | 10994 | 8562_1 | Battery String Over Cell Voltage (Battery String 1) | Read | Active = alarm | |
| BV | 10995 | 8563_1 | Battery String Under Cell Voltage (Battery String 1) | Read | Active = alarm | |
| BV | 10996 | 8564_1 | Battery String Charge Over Current (Battery String 1) | Read | Active = alarm | |
| BV | 10997 | 8565_1 | Battery String Discharge Over Current (Battery String 1) | Read | Active = alarm | |
| BV | 10998 | 8566_1 | Battery String Over Temperature (Battery String 1) | Read | Active = alarm | |
| BV | 10999 | 8567_1 | Battery String Under Temperature (Battery String 1) | Read | Active = alarm | |
| BV | 11010 | 8605_2 | Battery String High Overall Voltage (Battery String 2) | Read | Active = alarm | |
| BV | 11011 | 8606_2 | Battery String Low Overall Voltage (Battery String 2) | Read | Active = alarm | |
| BV | 11012 | 8558_2 | Battery String High Cell Voltage (Battery String 2) | Read | Active = alarm | |
| BV | 11013 | 8559_2 | Battery String Low Cell Voltage (Battery String 2) | Read | Active = alarm | |
| BV | 11014 | 8560_2 | Battery String Over Overall Voltage (Battery String 2) | Read | Active = alarm | |
| BV | 11015 | 8561_2 | Battery String Under Overall Voltage (Battery String 2) | Read | Active = alarm | |
| BV | 11016 | 8562_2 | Battery String Over Cell Voltage (Battery String 2) | Read | Active = alarm | |
| BV | 11017 | 8563_2 | Battery String Under Cell Voltage (Battery String 2) | Read | Active = alarm | |
| BV | 11018 | 8564_2 | Battery String Charge Over Current (Battery String 2) | Read | Active = alarm | |
| BV | 11019 | 8565_2 | Battery String Discharge Over Current (Battery String 2) | Read | Active = alarm | |
| BV | 11020 | 8566_2 | Battery String Over Temperature (Battery String 2) | Read | Active = alarm | |
| BV | 11021 | 8567_2 | Battery String Under Temperature (Battery String 2) | Read | Active = alarm | |
| BV | 11142 | 8605_8 | Battery String High Overall Voltage (Battery String 8) | Read | Active = alarm | |
| BV | 11143 | 8606_8 | Battery String Low Overall Voltage (Battery String 8) | Read | Active = alarm | |
| BV | 11144 | 8558_8 | Battery String High Cell Voltage (Battery String 8) | Read | Active = alarm | |
| BV | 11145 | 8559_8 | Battery String Low Cell Voltage (Battery String 8) | Read | Active = alarm | |
| BV | 11146 | 8560_8 | Battery String Over Overall Voltage (Battery String 8) | Read | Active = alarm | |
| BV | 11147 | 8561_8 | Battery String Under Overall Voltage (Battery String 8) | Read | Active = alarm | |
| BV | 11148 | 8562_8 | Battery String Over Cell Voltage (Battery String 8) | Read | Active = alarm | |
| BV | 11149 | 8563_8 | Battery String Under Cell Voltage (Battery String 8) | Read | Active = alarm | |
| BV | 11150 | 8564_8 | Battery String Charge Over Current (Battery String 8) | Read | Active = alarm | |
| BV | 11151 | 8565_8 | Battery String Discharge Over Current (Battery String 8) | Read | Active = alarm | |
| BV | 11152 | 8566_8 | Battery String Over Temperature (Battery String 8) | Read | Active = alarm | |
| BV | 11153 | 8567_8 | Battery String Under Temperature (Battery String 8) | Read | Active = alarm | |
| AVmin | 1 | 4097_1 | System Input RMS A-B | V | Read | |
| AV | 2 | 4099_1 | System Input RMS B-C | V | Read | |
| AV | 3 | 4101_1 | System Input RMS C-A | V | Read | |
| AV | 4 | 4096_1 | System Input RMS A-N | V | Read | |
| AV | 5 | 4098_1 | System Input RMS B-N | V | Read | |
| AV | 6 | 4100_1 | System Input RMS C-N | V | Read | |
| AV | 7 | 4113_1 | System Input RMS Current Phase A | A | Read | |
| AV | 8 | 4114_1 | System Input RMS Current Phase B | A | Read | |
| AV | 9 | 4115_1 | System Input RMS Current Phase C | A | Read | |
| AV | 10 | 4105_1 | System Input Frequency | Hz | Read | |
| AV | 11 | 4116_1 | System Input Power Factor Phs A | Read | ||
| AV | 12 | 4117_1 | System Input Power Factor Phs B | Read | ||
| AV | 13 | 4118_1 | System Input Power Factor Phs C | Read | ||
| AV | 14 | 6318_1 | System Input Power Phase A | kW | Read | |
| AV | 15 | 6319_1 | System Input Power Phase B | kW | Read | |
| AV | 16 | 6320_1 | System Input Power Phase C | kW | Read | |
| AV | 17 | 8093_1 | System Input Apparent Power Phs A | kVA | Read | |
| AV | 18 | 8094_1 | System Input Apparent Power Phs B | kVA | Read | |
| AV | 19 | 8095_1 | System Input Apparent Power Phs C | kVA | Read | |
| AV | 20 | 4119_1 | System Input Brown Out Count | Read | ||
| AV | 21 | 4120_1 | System Input Black Out Count | Read | ||
| AV | 32 | 4125_1 | Bypass Input Voltage RMS A-B | V | Read | |
| AV | 33 | 4126_1 | Bypass Input Voltage RMS B-C | V | Read | |
| AV | 34 | 4127_1 | Bypass Input Voltage RMS C-A | V | Read | |
| AV | 35 | 4128_1 | Bypass Input Voltage RMS A-N | V | Read | |
| AV | 36 | 4129_1 | Bypass Input Voltage RMS B-N | V | Read | |
| AV | 37 | 4130_1 | Bypass Input Voltage RMS C-N | V | Read | |
| AV | 38 | 4131_1 | Bypass Input Frequency | Hz | Read | |
| AV | 39 | 6325_1 | Bypass Power Phase A | kW | Read | |
| AV | 40 | 6326_1 | Bypass Power Phase B | kW | Read | |
| AV | 41 | 6327_1 | Bypass Power Phase C | kW | Read | |
| AV | 42 | 6328_1 | Bypass Apparent Power Phase A | kVA | Read | |
| AV | 43 | 6329_1 | Bypass Apparent Power Phase B | kVA | Read | |
| AV | 44 | 6330_1 | Bypass Apparent Power Phase C | kVA | Read | |
| AVmin | 55 | 4201_1 | System Output Voltage RMS A-B | V | Read | |
| AV | 56 | 4202_1 | System Output Voltage RMS B-C | V | Read | |
| AV | 57 | 4203_1 | System Output Voltage RMS C-A | V | Read | |
| AV | 58 | 4385_1 | System Output Voltage RMS A-N | V | Read | |
| AV | 59 | 4386_1 | System Output Voltage RMS B-N | V | Read | |
| AV | 60 | 4387_1 | System Output Voltage RMS C-N | V | Read | |
| AVmin | 61 | 4204_1 | System Output RMS Current Phs A | A | Read | |
| AV | 62 | 4205_1 | System Output RMS Current Phs B | A | Read | |
| AV | 63 | 4206_1 | System Output RMS Current Phs C | A | Read | |
| AV | 64 | 5159_1 | Output Current Crest Factor Phs A | Read | ||
| AV | 65 | 5160_1 | Output Current Crest Factor Phs B | Read | ||
| AV | 66 | 5161_1 | Output Current Crest Factor Phs C | Read | ||
| AV | 67 | 4207_1 | System Output Frequency | Hz | Read | |
| AV | 68 | 4210_1 | System Output Power Factor Phs A | Read | ||
| AV | 69 | 4211_1 | System Output Power Factor Phs B | Read | ||
| AV | 70 | 4212_1 | System Output Power Factor Phs C | Read | ||
| AV | 71 | 5859_1 | System Output Power Phase A | kW | Read | |
| AV | 72 | 5860_1 | System Output Power Phase B | kW | Read | |
| AV | 73 | 5959_1 | System Output Power Phase C | kW | Read | |
| AV | 74 | 5868_1 | System Output Apparent Power Phs A | kVA | Read | |
| AV | 75 | 5869_1 | System Output Apparent Power Phs B | kVA | Read | |
| AV | 76 | 5870_1 | System Output Apparent Power Phs C | kVA | Read | |
| AVmin | 77 | 4208_1 | System Output Power | kW | Read | |
| AV | 78 | 4209_1 | System Output Apparent Power | kVA | Read | |
| AV | 79 | 4226_1 | System Output Pct Pwr (VA) Phs A | % | Read | |
| AV | 80 | 4227_1 | System Output Pct Pwr (VA) Phs B | % | Read | |
| AV | 81 | 4228_1 | System Output Pct Pwr (VA) Phs C | % | Read | |
| AV | 82 | 4223_1 | System Output Pct Power Phase A | % | Read | |
| AV | 83 | 4224_1 | System Output Pct Power Phase B | % | Read | |
| AV | 84 | 4225_1 | System Output Pct Power Phase C | % | Read | |
| AV | 95 | 8281_1_1 | Positive DC Bus Voltage (Power Module 1 DC Bus 1) | VDC | Read | |
| AV | 96 | 8282_1_1 | Negative DC Bus Voltage (Power Module 1 DC Bus 1) | VDC | Read | |
| AV | 107 | 8281_2_1 | Positive DC Bus Voltage (Power Module 2 DC Bus 1) | VDC | Read | |
| AV | 108 | 8282_2_1 | Negative DC Bus Voltage (Power Module 2 DC Bus 1) | VDC | Read | |
| AV | 203 | 8281_10_1 | Positive DC Bus Voltage (Power Module 10 DC Bus 1) | VDC | Read | |
| AV | 204 | 8282_10_1 | Negative DC Bus Voltage (Power Module 10 DC Bus 1) | VDC | Read | |
| AV | 215 | 4811_1 | MMS Output Power | kW | Read | |
| AV | 216 | 4812_1 | MMS Output Apparent Power | kVA | Read | |
| AV | 227 | 5824_1 | Number Of Active Power Modules | Read | ||
| AV | 228 | 5823_1 | Number of Installed Power Modules | Read | ||
| AV | 229 | 8513_1 | Redundant Count of Power Module | Read | ||
| AV | 230 | 4291_1 | Inlet Air Temperature | °C | Read | |
| AV | 500230 | 4291_1_deg_F | Inlet Air Temperature | °F | Read | |
| AV | 231 | 6069_1 | Average system efficiency | % | Read | |
| AV | 232 | 8097_1 | ECO Suspended Time Remaining | s | Read | |
| AV | 233 | 4292_1 | Total System Operating Time | h | Read | |
| AV | 244 | 4293_1 | System Date and Time | Secs since Epoch(UTC) | Write | |
| AV | 245 | 5821_1 | System Capacity | kVA | Read | |
| AV | 246 | 4102_1 | System Input Nominal Voltage | V | Read | |
| AV | 247 | 4104_1 | System Input Nominal Current | A | Read | |
| AV | 248 | 4259_1 | Bypass Nominal Voltage | V | Read | |
| AV | 249 | 4260_1 | System Output Nominal Voltage | V | Read | |
| AV | 250 | 4261_1 | System Output Nominal Frequency | Hz | Read | |
| AV | 261 | 8514_1 | External Battery Cabinet Count | Read | ||
| AV | 262 | 8515_1 | Battery String Count | Read | ||
| AV | 263 | 4148_1 | DC Bus Voltage | VDC | Read | |
| AV | 264 | 4149_1 | DC Bus Current | A DC | Read | |
| AV | 265 | 8516_1 | Battery Temperature | °C | Read | |
| AV | 500265 | 8516_1_deg_F | Battery Temperature | °F | Read | |
| AV | 266 | 4153_1 | Battery Percentage Charge | % | Read | |
| AVmin | 267 | 4150_1 | Battery Time Remaining | min | Read | |
| AV | 268 | 5845_1 | Number of Discharge Cycles | Read | ||
| AV | 269 | 5846_1 | Accumulated Discharge Time | h | Read | |
| AV | 270 | 5991_1 | Battery Self Test Cycle Time | day | Read | |
| AV | 271 | 5804_1 | Time Until Next Auto Battery Test | min | Read | |
| AV | 272 | 5802_1 | Low Battery Warning Time | min | Read | |
| AV | 283 | 4155_1 | Battery Volts for Cabinet (Battery Cabinet 1) | VDC | Read | |
| AV | 284 | 8527_1 | Battery Current for Cabinet (Battery Cabinet 1) | A DC | Read | |
| AV | 285 | 4156_1 | Battery Temperature for Cabinet (Battery Cabinet 1) | °C | Read | |
| AV | 500285 | 4156_1_deg_F | Battery Temperature for Cabinet (Battery Cabinet 1) | °F | Read | |
| AV | 286 | 8528_1 | Battery Cabinet Capacity (Battery Cabinet 1) | % | Read | |
| AV | 287 | 8529_1 | Battery Cabinet Max Cell Voltage (Battery Cabinet 1) | VDC | Read | |
| AV | 288 | 8530_1 | Battery Cabinet Min Cell Voltage (Battery Cabinet 1) | VDC | Read | |
| AV | 289 | 8531_1 | Battery Cabinet Highest Cell Temperature (Battery Cabinet 1) | °C | Read | |
| AV | 500289 | 8531_1_deg_F | Battery Cabinet Highest Cell Temperature (Battery Cabinet 1) | °F | Read | |
| AV | 290 | 8532_1 | Battery Cabinet Lowest Cell Temperature (Battery Cabinet 1) | °C | Read | |
| AV | 500290 | 8532_1_deg_F | Battery Cabinet Lowest Cell Temperature (Battery Cabinet 1) | °F | Read | |
| AV | 301 | 4962_1_1 | Cell Voltage (Battery Cabinet 1 Battery Cell In Cabinet 1) | VDC | Read | |
| AV | 302 | 4963_1_1 | Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 1) | °C | Read | |
| AV | 500302 | 4963_1_1_deg_F | Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 1) | °F | Read | |
| AV | 303 | 5443_1_1 | Internal Resistance Value (Battery Cabinet 1 Battery Cell In Cabinet 1) | milliOhm | Read | |
| AV | 314 | 4962_1_2 | Cell Voltage (Battery Cabinet 1 Battery Cell In Cabinet 2) | VDC | Read | |
| AV | 315 | 4963_1_2 | Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 2) | °C | Read | |
| AV | 500315 | 4963_1_2_deg_F | Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 2) | °F | Read | |
| AV | 316 | 5443_1_2 | Internal Resistance Value (Battery Cabinet 1 Battery Cell In Cabinet 2) | milliOhm | Read | |
| AV | 2888 | 4962_1_200 | Cell Voltage (Battery Cabinet 1 Battery Cell In Cabinet 200) | VDC | Read | |
| AV | 2889 | 4963_1_200 | Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 200) | °C | Read | |
| AV | 502889 | 4963_1_200_deg_F | Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 200) | °F | Read | |
| AV | 2890 | 5443_1_200 | Internal Resistance Value (Battery Cabinet 1 Battery Cell In Cabinet 200) | milliOhm | Read | |
| AV | 2901 | 5844_1_1 | Battery Module Temperature (Battery Cabinet 1 Battery Module 1) | °C | Read | |
| AV | 502901 | 5844_1_1_deg_F | Battery Module Temperature (Battery Cabinet 1 Battery Module 1) | °F | Read | |
| AV | 2912 | 8571_1_1_1 | Battery Module Voltage (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 2913 | 8572_1_1_1 | Battery Module Current (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1) | A DC | Read | |
| AV | 2914 | 8573_1_1_1 | Battery Module State Of Charge (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1) | % | Read | |
| AV | 2915 | 8574_1_1_1 | Battery Module Max Cell Voltage (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 2916 | 8575_1_1_1 | Battery Module Min Cell Voltage (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 2917 | 8576_1_1_1 | Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 502917 | 8576_1_1_1_deg_F | Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 2918 | 8577_1_1_1 | Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 502918 | 8577_1_1_1_deg_F | Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 2930 | 8593_1_1_1 | Battery Cell Voltage (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 1) | VDC | Read | |
| AV | 2931 | 8570_1_1_1 | Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 1) | °C | Read | |
| AV | 502931 | 8570_1_1_1_deg_F | Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 1) | °F | Read | |
| AV | 2942 | 8593_1_1_2 | Battery Cell Voltage (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 2) | VDC | Read | |
| AV | 2943 | 8570_1_1_2 | Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 2) | °C | Read | |
| AV | 502943 | 8570_1_1_2_deg_F | Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 2) | °F | Read | |
| AV | 4118 | 8593_1_1_100 | Battery Cell Voltage (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 100) | VDC | Read | |
| AV | 4119 | 8570_1_1_100 | Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 100) | °C | Read | |
| AV | 504119 | 8570_1_1_100_deg_F | Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 100) | °F | Read | |
| AV | 4129 | 5844_1_2 | Battery Module Temperature (Battery Cabinet 1 Battery Module 2) | °C | Read | |
| AV | 504129 | 5844_1_2_deg_F | Battery Module Temperature (Battery Cabinet 1 Battery Module 2) | °F | Read | |
| AV | 4140 | 8571_1_2_1 | Battery Module Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 4141 | 8572_1_2_1 | Battery Module Current (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | A DC | Read | |
| AV | 4142 | 8573_1_2_1 | Battery Module State Of Charge (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | % | Read | |
| AV | 4143 | 8574_1_2_1 | Battery Module Max Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 4144 | 8575_1_2_1 | Battery Module Min Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 4145 | 8576_1_2_1 | Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 504145 | 8576_1_2_1_deg_F | Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 4146 | 8577_1_2_1 | Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 504146 | 8577_1_2_1_deg_F | Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 4158 | 8593_1_2_1 | Battery Cell Voltage (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 1) | VDC | Read | |
| AV | 4159 | 8570_1_2_1 | Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 1) | °C | Read | |
| AV | 504159 | 8570_1_2_1_deg_F | Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 1) | °F | Read | |
| AV | 4170 | 8593_1_2_2 | Battery Cell Voltage (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 2) | VDC | Read | |
| AV | 4171 | 8570_1_2_2 | Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 2) | °C | Read | |
| AV | 504171 | 8570_1_2_2_deg_F | Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 2) | °F | Read | |
| AV | 5346 | 8593_1_2_100 | Battery Cell Voltage (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 100) | VDC | Read | |
| AV | 5347 | 8570_1_2_100 | Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 100) | °C | Read | |
| AV | 505347 | 8570_1_2_100_deg_F | Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 100) | °F | Read | |
| AV | 40969 | 5844_1_32 | Battery Module Temperature (Battery Cabinet 1 Battery Module 32) | °C | Read | |
| AV | 540969 | 5844_1_32_deg_F | Battery Module Temperature (Battery Cabinet 1 Battery Module 32) | °F | Read | |
| AV | 40980 | 8571_1_32_1 | Battery Module Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 40981 | 8572_1_32_1 | Battery Module Current (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | A DC | Read | |
| AV | 40982 | 8573_1_32_1 | Battery Module State Of Charge (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | % | Read | |
| AV | 40983 | 8574_1_32_1 | Battery Module Max Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 40984 | 8575_1_32_1 | Battery Module Min Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 40985 | 8576_1_32_1 | Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 540985 | 8576_1_32_1_deg_F | Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 40986 | 8577_1_32_1 | Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 540986 | 8577_1_32_1_deg_F | Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 40998 | 8593_1_32_1 | Battery Cell Voltage (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 1) | VDC | Read | |
| AV | 40999 | 8570_1_32_1 | Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 1) | °C | Read | |
| AV | 540999 | 8570_1_32_1_deg_F | Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 1) | °F | Read | |
| AV | 41010 | 8593_1_32_2 | Battery Cell Voltage (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 2) | VDC | Read | |
| AV | 41011 | 8570_1_32_2 | Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 2) | °C | Read | |
| AV | 541011 | 8570_1_32_2_deg_F | Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 2) | °F | Read | |
| AV | 42186 | 8593_1_32_100 | Battery Cell Voltage (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 100) | VDC | Read | |
| AV | 42187 | 8570_1_32_100 | Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 100) | °C | Read | |
| AV | 542187 | 8570_1_32_100_deg_F | Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 100) | °F | Read | |
| AV | 42197 | 4155_2 | Battery Volts for Cabinet (Battery Cabinet 2) | VDC | Read | |
| AV | 42198 | 8527_2 | Battery Current for Cabinet (Battery Cabinet 2) | A DC | Read | |
| AV | 42199 | 4156_2 | Battery Temperature for Cabinet (Battery Cabinet 2) | °C | Read | |
| AV | 542199 | 4156_2_deg_F | Battery Temperature for Cabinet (Battery Cabinet 2) | °F | Read | |
| AV | 42200 | 8528_2 | Battery Cabinet Capacity (Battery Cabinet 2) | % | Read | |
| AV | 42201 | 8529_2 | Battery Cabinet Max Cell Voltage (Battery Cabinet 2) | VDC | Read | |
| AV | 42202 | 8530_2 | Battery Cabinet Min Cell Voltage (Battery Cabinet 2) | VDC | Read | |
| AV | 42203 | 8531_2 | Battery Cabinet Highest Cell Temperature (Battery Cabinet 2) | °C | Read | |
| AV | 542203 | 8531_2_deg_F | Battery Cabinet Highest Cell Temperature (Battery Cabinet 2) | °F | Read | |
| AV | 42204 | 8532_2 | Battery Cabinet Lowest Cell Temperature (Battery Cabinet 2) | °C | Read | |
| AV | 542204 | 8532_2_deg_F | Battery Cabinet Lowest Cell Temperature (Battery Cabinet 2) | °F | Read | |
| AV | 42215 | 4962_2_1 | Cell Voltage (Battery Cabinet 2 Battery Cell In Cabinet 1) | VDC | Read | |
| AV | 42216 | 4963_2_1 | Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 1) | °C | Read | |
| AV | 542216 | 4963_2_1_deg_F | Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 1) | °F | Read | |
| AV | 42217 | 5443_2_1 | Internal Resistance Value (Battery Cabinet 2 Battery Cell In Cabinet 1) | milliOhm | Read | |
| AV | 42228 | 4962_2_2 | Cell Voltage (Battery Cabinet 2 Battery Cell In Cabinet 2) | VDC | Read | |
| AV | 42229 | 4963_2_2 | Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 2) | °C | Read | |
| AV | 542229 | 4963_2_2_deg_F | Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 2) | °F | Read | |
| AV | 42230 | 5443_2_2 | Internal Resistance Value (Battery Cabinet 2 Battery Cell In Cabinet 2) | milliOhm | Read | |
| AV | 44802 | 4962_2_200 | Cell Voltage (Battery Cabinet 2 Battery Cell In Cabinet 200) | VDC | Read | |
| AV | 44803 | 4963_2_200 | Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 200) | °C | Read | |
| AV | 544803 | 4963_2_200_deg_F | Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 200) | °F | Read | |
| AV | 44804 | 5443_2_200 | Internal Resistance Value (Battery Cabinet 2 Battery Cell In Cabinet 200) | milliOhm | Read | |
| AV | 44815 | 5844_2_1 | Battery Module Temperature (Battery Cabinet 2 Battery Module 1) | °C | Read | |
| AV | 544815 | 5844_2_1_deg_F | Battery Module Temperature (Battery Cabinet 2 Battery Module 1) | °F | Read | |
| AV | 44826 | 8571_2_1_1 | Battery Module Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | VDC | Read | |
| AV | 44827 | 8572_2_1_1 | Battery Module Current (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | A DC | Read | |
| AV | 44828 | 8573_2_1_1 | Battery Module State Of Charge (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | % | Read | |
| AV | 44829 | 8574_2_1_1 | Battery Module Max Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | VDC | Read | |
| AV | 44830 | 8575_2_1_1 | Battery Module Min Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | VDC | Read | |
| AV | 44831 | 8576_2_1_1 | Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | °C | Read | |
| AV | 544831 | 8576_2_1_1_deg_F | Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | °F | Read | |
| AV | 44832 | 8577_2_1_1 | Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | °C | Read | |
| AV | 544832 | 8577_2_1_1_deg_F | Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1) | °F | Read | |
| AV | 44844 | 8593_2_1_1 | Battery Cell Voltage (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 1) | VDC | Read | |
| AV | 44845 | 8570_2_1_1 | Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 1) | °C | Read | |
| AV | 544845 | 8570_2_1_1_deg_F | Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 1) | °F | Read | |
| AV | 44856 | 8593_2_1_2 | Battery Cell Voltage (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 2) | VDC | Read | |
| AV | 44857 | 8570_2_1_2 | Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 2) | °C | Read | |
| AV | 544857 | 8570_2_1_2_deg_F | Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 2) | °F | Read | |
| AV | 46032 | 8593_2_1_100 | Battery Cell Voltage (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 100) | VDC | Read | |
| AV | 46033 | 8570_2_1_100 | Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 100) | °C | Read | |
| AV | 546033 | 8570_2_1_100_deg_F | Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 100) | °F | Read | |
| AV | 46043 | 5844_2_2 | Battery Module Temperature (Battery Cabinet 2 Battery Module 2) | °C | Read | |
| AV | 546043 | 5844_2_2_deg_F | Battery Module Temperature (Battery Cabinet 2 Battery Module 2) | °F | Read | |
| AV | 46054 | 8571_2_2_1 | Battery Module Voltage (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 46055 | 8572_2_2_1 | Battery Module Current (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1) | A DC | Read | |
| AV | 46056 | 8573_2_2_1 | Battery Module State Of Charge (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1) | % | Read | |
| AV | 46057 | 8574_2_2_1 | Battery Module Max Cell Voltage (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 46058 | 8575_2_2_1 | Battery Module Min Cell Voltage (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 46059 | 8576_2_2_1 | Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 546059 | 8576_2_2_1_deg_F | Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 46060 | 8577_2_2_1 | Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 546060 | 8577_2_2_1_deg_F | Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 46072 | 8593_2_2_1 | Battery Cell Voltage (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 1) | VDC | Read | |
| AV | 46073 | 8570_2_2_1 | Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 1) | °C | Read | |
| AV | 546073 | 8570_2_2_1_deg_F | Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 1) | °F | Read | |
| AV | 46084 | 8593_2_2_2 | Battery Cell Voltage (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 2) | VDC | Read | |
| AV | 46085 | 8570_2_2_2 | Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 2) | °C | Read | |
| AV | 546085 | 8570_2_2_2_deg_F | Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 2) | °F | Read | |
| AV | 47260 | 8593_2_2_100 | Battery Cell Voltage (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 100) | VDC | Read | |
| AV | 47261 | 8570_2_2_100 | Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 100) | °C | Read | |
| AV | 547261 | 8570_2_2_100_deg_F | Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 100) | °F | Read | |
| AV | 82883 | 5844_2_32 | Battery Module Temperature (Battery Cabinet 2 Battery Module 32) | °C | Read | |
| AV | 582883 | 5844_2_32_deg_F | Battery Module Temperature (Battery Cabinet 2 Battery Module 32) | °F | Read | |
| AV | 82894 | 8571_2_32_1 | Battery Module Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 82895 | 8572_2_32_1 | Battery Module Current (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | A DC | Read | |
| AV | 82896 | 8573_2_32_1 | Battery Module State Of Charge (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | % | Read | |
| AV | 82897 | 8574_2_32_1 | Battery Module Max Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 82898 | 8575_2_32_1 | Battery Module Min Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 82899 | 8576_2_32_1 | Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 582899 | 8576_2_32_1_deg_F | Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 82900 | 8577_2_32_1 | Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 582900 | 8577_2_32_1_deg_F | Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 82912 | 8593_2_32_1 | Battery Cell Voltage (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 1) | VDC | Read | |
| AV | 82913 | 8570_2_32_1 | Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 1) | °C | Read | |
| AV | 582913 | 8570_2_32_1_deg_F | Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 1) | °F | Read | |
| AV | 82924 | 8593_2_32_2 | Battery Cell Voltage (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 2) | VDC | Read | |
| AV | 82925 | 8570_2_32_2 | Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 2) | °C | Read | |
| AV | 582925 | 8570_2_32_2_deg_F | Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 2) | °F | Read | |
| AV | 84100 | 8593_2_32_100 | Battery Cell Voltage (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 100) | VDC | Read | |
| AV | 84101 | 8570_2_32_100 | Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 100) | °C | Read | |
| AV | 584101 | 8570_2_32_100_deg_F | Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 100) | °F | Read | |
| AV | 335595 | 4155_9 | Battery Volts for Cabinet (Battery Cabinet 9) | VDC | Read | |
| AV | 335596 | 8527_9 | Battery Current for Cabinet (Battery Cabinet 9) | A DC | Read | |
| AV | 335597 | 4156_9 | Battery Temperature for Cabinet (Battery Cabinet 9) | °C | Read | |
| AV | 835597 | 4156_9_deg_F | Battery Temperature for Cabinet (Battery Cabinet 9) | °F | Read | |
| AV | 335598 | 8528_9 | Battery Cabinet Capacity (Battery Cabinet 9) | % | Read | |
| AV | 335599 | 8529_9 | Battery Cabinet Max Cell Voltage (Battery Cabinet 9) | VDC | Read | |
| AV | 335600 | 8530_9 | Battery Cabinet Min Cell Voltage (Battery Cabinet 9) | VDC | Read | |
| AV | 335601 | 8531_9 | Battery Cabinet Highest Cell Temperature (Battery Cabinet 9) | °C | Read | |
| AV | 835601 | 8531_9_deg_F | Battery Cabinet Highest Cell Temperature (Battery Cabinet 9) | °F | Read | |
| AV | 335602 | 8532_9 | Battery Cabinet Lowest Cell Temperature (Battery Cabinet 9) | °C | Read | |
| AV | 835602 | 8532_9_deg_F | Battery Cabinet Lowest Cell Temperature (Battery Cabinet 9) | °F | Read | |
| AV | 335613 | 4962_9_1 | Cell Voltage (Battery Cabinet 9 Battery Cell In Cabinet 1) | VDC | Read | |
| AV | 335614 | 4963_9_1 | Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 1) | °C | Read | |
| AV | 835614 | 4963_9_1_deg_F | Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 1) | °F | Read | |
| AV | 335615 | 5443_9_1 | Internal Resistance Value (Battery Cabinet 9 Battery Cell In Cabinet 1) | milliOhm | Read | |
| AV | 335626 | 4962_9_2 | Cell Voltage (Battery Cabinet 9 Battery Cell In Cabinet 2) | VDC | Read | |
| AV | 335627 | 4963_9_2 | Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 2) | °C | Read | |
| AV | 835627 | 4963_9_2_deg_F | Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 2) | °F | Read | |
| AV | 335628 | 5443_9_2 | Internal Resistance Value (Battery Cabinet 9 Battery Cell In Cabinet 2) | milliOhm | Read | |
| AV | 338200 | 4962_9_200 | Cell Voltage (Battery Cabinet 9 Battery Cell In Cabinet 200) | VDC | Read | |
| AV | 338201 | 4963_9_200 | Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 200) | °C | Read | |
| AV | 838201 | 4963_9_200_deg_F | Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 200) | °F | Read | |
| AV | 338202 | 5443_9_200 | Internal Resistance Value (Battery Cabinet 9 Battery Cell In Cabinet 200) | milliOhm | Read | |
| AV | 338213 | 5844_9_1 | Battery Module Temperature (Battery Cabinet 9 Battery Module 1) | °C | Read | |
| AV | 838213 | 5844_9_1_deg_F | Battery Module Temperature (Battery Cabinet 9 Battery Module 1) | °F | Read | |
| AV | 338224 | 8571_9_1_1 | Battery Module Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 338225 | 8572_9_1_1 | Battery Module Current (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | A DC | Read | |
| AV | 338226 | 8573_9_1_1 | Battery Module State Of Charge (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | % | Read | |
| AV | 338227 | 8574_9_1_1 | Battery Module Max Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 338228 | 8575_9_1_1 | Battery Module Min Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 338229 | 8576_9_1_1 | Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 838229 | 8576_9_1_1_deg_F | Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 338230 | 8577_9_1_1 | Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 838230 | 8577_9_1_1_deg_F | Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 338242 | 8593_9_1_1 | Battery Cell Voltage (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 1) | VDC | Read | |
| AV | 338243 | 8570_9_1_1 | Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 1) | °C | Read | |
| AV | 838243 | 8570_9_1_1_deg_F | Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 1) | °F | Read | |
| AV | 338254 | 8593_9_1_2 | Battery Cell Voltage (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 2) | VDC | Read | |
| AV | 338255 | 8570_9_1_2 | Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 2) | °C | Read | |
| AV | 838255 | 8570_9_1_2_deg_F | Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 2) | °F | Read | |
| AV | 339430 | 8593_9_1_100 | Battery Cell Voltage (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 100) | VDC | Read | |
| AV | 339431 | 8570_9_1_100 | Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 100) | °C | Read | |
| AV | 839431 | 8570_9_1_100_deg_F | Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 100) | °F | Read | |
| AV | 339441 | 5844_9_2 | Battery Module Temperature (Battery Cabinet 9 Battery Module 2) | °C | Read | |
| AV | 839441 | 5844_9_2_deg_F | Battery Module Temperature (Battery Cabinet 9 Battery Module 2) | °F | Read | |
| AV | 339452 | 8571_9_2_1 | Battery Module Voltage (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1) | VDC | Read | |
| AV | 339453 | 8572_9_2_1 | Battery Module Current (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1) | A DC | Read | |
| AV | 339454 | 8573_9_2_1 | Battery Module State Of Charge (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1) | % | Read | |
| AV | 339455 | 8574_9_2_1 | Battery Module Max Cell Voltage (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1) | VDC | Read | |
| AV | 339456 | 8575_9_2_1 | Battery Module Min Cell Voltage (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1) | VDC | Read | |
| AV | 339457 | 8576_9_2_1 | Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1) | °C | Read | |
| AV | 839457 | 8576_9_2_1_deg_F | Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1) | °F | Read | |
| AV | 339458 | 8577_9_2_1 | Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1) | °C | Read | |
| AV | 839458 | 8577_9_2_1_deg_F | Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1) | °F | Read | |
| AV | 339470 | 8593_9_2_1 | Battery Cell Voltage (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 1) | VDC | Read | |
| AV | 339471 | 8570_9_2_1 | Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 1) | °C | Read | |
| AV | 839471 | 8570_9_2_1_deg_F | Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 1) | °F | Read | |
| AV | 339482 | 8593_9_2_2 | Battery Cell Voltage (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 2) | VDC | Read | |
| AV | 339483 | 8570_9_2_2 | Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 2) | °C | Read | |
| AV | 839483 | 8570_9_2_2_deg_F | Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 2) | °F | Read | |
| AV | 340658 | 8593_9_2_100 | Battery Cell Voltage (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 100) | VDC | Read | |
| AV | 340659 | 8570_9_2_100 | Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 100) | °C | Read | |
| AV | 840659 | 8570_9_2_100_deg_F | Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 100) | °F | Read | |
| AV | 376281 | 5844_9_32 | Battery Module Temperature (Battery Cabinet 9 Battery Module 32) | °C | Read | |
| AV | 876281 | 5844_9_32_deg_F | Battery Module Temperature (Battery Cabinet 9 Battery Module 32) | °F | Read | |
| AV | 376292 | 8571_9_32_1 | Battery Module Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 376293 | 8572_9_32_1 | Battery Module Current (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | A DC | Read | |
| AV | 376294 | 8573_9_32_1 | Battery Module State Of Charge (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | % | Read | |
| AV | 376295 | 8574_9_32_1 | Battery Module Max Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 376296 | 8575_9_32_1 | Battery Module Min Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | VDC | Read | |
| AV | 376297 | 8576_9_32_1 | Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 876297 | 8576_9_32_1_deg_F | Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 376298 | 8577_9_32_1 | Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | °C | Read | |
| AV | 876298 | 8577_9_32_1_deg_F | Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1) | °F | Read | |
| AV | 376310 | 8593_9_32_1 | Battery Cell Voltage (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 1) | VDC | Read | |
| AV | 376311 | 8570_9_32_1 | Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 1) | °C | Read | |
| AV | 876311 | 8570_9_32_1_deg_F | Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 1) | °F | Read | |
| AV | 376322 | 8593_9_32_2 | Battery Cell Voltage (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 2) | VDC | Read | |
| AV | 376323 | 8570_9_32_2 | Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 2) | °C | Read | |
| AV | 876323 | 8570_9_32_2_deg_F | Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 2) | °F | Read | |
| AV | 377498 | 8593_9_32_100 | Battery Cell Voltage (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 100) | VDC | Read | |
| AV | 377499 | 8570_9_32_100 | Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 100) | °C | Read | |
| AV | 877499 | 8570_9_32_100_deg_F | Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 100) | °F | Read | |
| AV | 377509 | 4900_1 | String Overall Voltage (Battery String 1) | VDC | Read | |
| AV | 377510 | 4901_1 | String Current (Battery String 1) | A DC | Read | |
| AV | 377511 | 8549_1 | Battery String Temperature (Battery String 1) | °C | Read | |
| AV | 877511 | 8549_1_deg_F | Battery String Temperature (Battery String 1) | °F | Read | |
| AV | 377512 | 8550_1 | Battery String State Of Charge (Battery String 1) | % | Read | |
| AV | 377513 | 8551_1 | Battery String Max Cell Voltage (Battery String 1) | VDC | Read | |
| AV | 377514 | 8552_1 | Battery String Min Cell Voltage (Battery String 1) | VDC | Read | |
| AV | 377515 | 8553_1 | Battery String Highest Cell Temperature (Battery String 1) | °C | Read | |
| AV | 877515 | 8553_1_deg_F | Battery String Highest Cell Temperature (Battery String 1) | °F | Read | |
| AV | 377516 | 8554_1 | Battery String Lowest Cell Temperature (Battery String 1) | °C | Read | |
| AV | 877516 | 8554_1_deg_F | Battery String Lowest Cell Temperature (Battery String 1) | °F | Read | |
| AV | 377527 | 8568_1_1 | Battery Cell Voltage (Battery String 1 Battery Cell In String 1) | VDC | Read | |
| AV | 377528 | 8569_1_1 | Battery Cell Temperature (Battery String 1 Battery Cell In String 1) | °C | Read | |
| AV | 877528 | 8569_1_1_deg_F | Battery Cell Temperature (Battery String 1 Battery Cell In String 1) | °F | Read | |
| AV | 377539 | 8568_1_2 | Battery Cell Voltage (Battery String 1 Battery Cell In String 2) | VDC | Read | |
| AV | 377540 | 8569_1_2 | Battery Cell Temperature (Battery String 1 Battery Cell In String 2) | °C | Read | |
| AV | 877540 | 8569_1_2_deg_F | Battery Cell Temperature (Battery String 1 Battery Cell In String 2) | °F | Read | |
| AV | 378715 | 8568_1_100 | Battery Cell Voltage (Battery String 1 Battery Cell In String 100) | VDC | Read | |
| AV | 378716 | 8569_1_100 | Battery Cell Temperature (Battery String 1 Battery Cell In String 100) | °C | Read | |
| AV | 878716 | 8569_1_100_deg_F | Battery Cell Temperature (Battery String 1 Battery Cell In String 100) | °F | Read | |
| AV | 378727 | 4900_2 | String Overall Voltage (Battery String 2) | VDC | Read | |
| AV | 378728 | 4901_2 | String Current (Battery String 2) | A DC | Read | |
| AV | 378729 | 8549_2 | Battery String Temperature (Battery String 2) | °C | Read | |
| AV | 878729 | 8549_2_deg_F | Battery String Temperature (Battery String 2) | °F | Read | |
| AV | 378730 | 8550_2 | Battery String State Of Charge (Battery String 2) | % | Read | |
| AV | 378731 | 8551_2 | Battery String Max Cell Voltage (Battery String 2) | VDC | Read | |
| AV | 378732 | 8552_2 | Battery String Min Cell Voltage (Battery String 2) | VDC | Read | |
| AV | 378733 | 8553_2 | Battery String Highest Cell Temperature (Battery String 2) | °C | Read | |
| AV | 878733 | 8553_2_deg_F | Battery String Highest Cell Temperature (Battery String 2) | °F | Read | |
| AV | 378734 | 8554_2 | Battery String Lowest Cell Temperature (Battery String 2) | °C | Read | |
| AV | 878734 | 8554_2_deg_F | Battery String Lowest Cell Temperature (Battery String 2) | °F | Read | |
| AV | 378745 | 8568_2_1 | Battery Cell Voltage (Battery String 2 Battery Cell In String 1) | VDC | Read | |
| AV | 378746 | 8569_2_1 | Battery Cell Temperature (Battery String 2 Battery Cell In String 1) | °C | Read | |
| AV | 878746 | 8569_2_1_deg_F | Battery Cell Temperature (Battery String 2 Battery Cell In String 1) | °F | Read | |
| AV | 378757 | 8568_2_2 | Battery Cell Voltage (Battery String 2 Battery Cell In String 2) | VDC | Read | |
| AV | 378758 | 8569_2_2 | Battery Cell Temperature (Battery String 2 Battery Cell In String 2) | °C | Read | |
| AV | 878758 | 8569_2_2_deg_F | Battery Cell Temperature (Battery String 2 Battery Cell In String 2) | °F | Read | |
| AV | 379933 | 8568_2_100 | Battery Cell Voltage (Battery String 2 Battery Cell In String 100) | VDC | Read | |
| AV | 379934 | 8569_2_100 | Battery Cell Temperature (Battery String 2 Battery Cell In String 100) | °C | Read | |
| AV | 879934 | 8569_2_100_deg_F | Battery Cell Temperature (Battery String 2 Battery Cell In String 100) | °F | Read | |
| AV | 386035 | 4900_8 | String Overall Voltage (Battery String 8) | VDC | Read | |
| AV | 386036 | 4901_8 | String Current (Battery String 8) | A DC | Read | |
| AV | 386037 | 8549_8 | Battery String Temperature (Battery String 8) | °C | Read | |
| AV | 886037 | 8549_8_deg_F | Battery String Temperature (Battery String 8) | °F | Read | |
| AV | 386038 | 8550_8 | Battery String State Of Charge (Battery String 8) | % | Read | |
| AV | 386039 | 8551_8 | Battery String Max Cell Voltage (Battery String 8) | VDC | Read | |
| AV | 386040 | 8552_8 | Battery String Min Cell Voltage (Battery String 8) | VDC | Read | |
| AV | 386041 | 8553_8 | Battery String Highest Cell Temperature (Battery String 8) | °C | Read | |
| AV | 886041 | 8553_8_deg_F | Battery String Highest Cell Temperature (Battery String 8) | °F | Read | |
| AV | 386042 | 8554_8 | Battery String Lowest Cell Temperature (Battery String 8) | °C | Read | |
| AV | 886042 | 8554_8_deg_F | Battery String Lowest Cell Temperature (Battery String 8) | °F | Read | |
| AV | 386053 | 8568_8_1 | Battery Cell Voltage (Battery String 8 Battery Cell In String 1) | VDC | Read | |
| AV | 386054 | 8569_8_1 | Battery Cell Temperature (Battery String 8 Battery Cell In String 1) | °C | Read | |
| AV | 886054 | 8569_8_1_deg_F | Battery Cell Temperature (Battery String 8 Battery Cell In String 1) | °F | Read | |
| AV | 386065 | 8568_8_2 | Battery Cell Voltage (Battery String 8 Battery Cell In String 2) | VDC | Read | |
| AV | 386066 | 8569_8_2 | Battery Cell Temperature (Battery String 8 Battery Cell In String 2) | °C | Read | |
| AV | 886066 | 8569_8_2_deg_F | Battery Cell Temperature (Battery String 8 Battery Cell In String 2) | °F | Read | |
| AV | 387241 | 8568_8_100 | Battery Cell Voltage (Battery String 8 Battery Cell In String 100) | VDC | Read | |
| AV | 387242 | 8569_8_100 | Battery Cell Temperature (Battery String 8 Battery Cell In String 100) | °C | Read | |
| AV | 887242 | 8569_8_100_deg_F | Battery Cell Temperature (Battery String 8 Battery Cell In String 100) | °F | Read | |
| MV | 1 | 4771_1 | Rectifier Isolation Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 12 | 4770_1 | Bypass Isolation Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 13 | 4772_1 | Maintenance Bypass Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 24 | 4775_1 | Module Output Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 25 | 4773_1 | Maintenance Isolation Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 36 | 8493_1 | System Control Card Operating Status (System Control Card 1) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 47 | 8493_2 | System Control Card Operating Status (System Control Card 2) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 58 | 8500_1 | Bypass Module Operating Status | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 59 | 4736_1 | Static Bypass Switch | Read | 1=off, 2=on | |
| MV | 70 | 5833_1 | Module Operating Status (Power Module 1) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 71 | 6437_1 | Power Module Sleep Status (Power Module 1) | Read | 1=Sleeping, 2=Not Sleeping | |
| MV | 82 | 4748_1_1 | Rectifier Status (Power Module 1 Rectifier 1) | Read | 1=off, 2=on | |
| MV | 93 | 5864_1_1 | Inverter Status (Power Module 1 Inverter 1) | Read | 1=Inverter Inactive, 2=Inverter Active | |
| MV | 104 | 6256_1_1 | Charger On/Off State (Power Module 1 Charger 1) | Read | 1=off, 2=on | |
| MV | 115 | 8509_1_1 | Discharger On/Off Status (Power Module 1 Discharger 1) | Read | 1=off, 2=on | |
| MV | 126 | 5833_2 | Module Operating Status (Power Module 2) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 127 | 6437_2 | Power Module Sleep Status (Power Module 2) | Read | 1=Sleeping, 2=Not Sleeping | |
| MV | 138 | 4748_2_1 | Rectifier Status (Power Module 2 Rectifier 1) | Read | 1=off, 2=on | |
| MV | 149 | 5864_2_1 | Inverter Status (Power Module 2 Inverter 1) | Read | 1=Inverter Inactive, 2=Inverter Active | |
| MV | 160 | 6256_2_1 | Charger On/Off State (Power Module 2 Charger 1) | Read | 1=off, 2=on | |
| MV | 171 | 8509_2_1 | Discharger On/Off Status (Power Module 2 Discharger 1) | Read | 1=off, 2=on | |
| MV | 574 | 5833_10 | Module Operating Status (Power Module 10) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 575 | 6437_10 | Power Module Sleep Status (Power Module 10) | Read | 1=Sleeping, 2=Not Sleeping | |
| MV | 586 | 4748_10_1 | Rectifier Status (Power Module 10 Rectifier 1) | Read | 1=off, 2=on | |
| MV | 597 | 5864_10_1 | Inverter Status (Power Module 10 Inverter 1) | Read | 1=Inverter Inactive, 2=Inverter Active | |
| MV | 608 | 6256_10_1 | Charger On/Off State (Power Module 10 Charger 1) | Read | 1=off, 2=on | |
| MV | 619 | 8509_10_1 | Discharger On/Off Status (Power Module 10 Discharger 1) | Read | 1=off, 2=on | |
| MV | 630 | 8594_1 | MMS UPS Loading Status | Read | 1=Load on Other Module, 2=Load Off, 3=Load on Inverter, 4=Load on Bypass, 5=Load on Maintenance Bypass, 6=Load on Battery, 7=Load on Shared Source | |
| MV | 641 | 8275_1 | Application Mode For UPS | Read | 1=UPS Mode, 2=Frequency Converter Mode, 3=Intelligent Paralleling Mode, 4=Intelligent Paralleling Mode Demo, 5=ECO Mode, 6=Intelligent ECO Mode, 7=Intelligent ECO Mode Demo, 8=Testing Mode, 9=Regen Mode, 10=Power Conditioner Mode, 11=Frequency Converter Mode without Battery, 12=Dynamic Online Mode, 13=Dynamic Online Mode Demo | |
| MV | 642 | 8595_1 | UPS Loading Status | Read | 1=Load on Other Module, 2=Load Off, 3=Load on Inverter, 4=Load on Bypass, 5=Load on Maintenance Bypass, 6=Load on Battery, 7=Load on Shared Source | |
| MVmin | 643 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation | |
| MV | 654 | 8330_1 | Battery type | Read | 1=VRLA, 2=Lithium Battery | |
| MV | 655 | 4871_1 | UPS Battery Status | Read | 1=Unknown, 2=Normal, 3=Low, 4=Depleted | |
| MV | 656 | 5799_1 | Battery is | Read | 1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off) | |
| MV | 657 | 5803_1 | Automatic Battery Test | Read | 1=disabled, 2=enabled | |
| MV | 668 | 8607_1 | Battery Cabinet Type (Battery Cabinet 1) | Read | 1=Internal, 2=External | |
| MV | 669 | 8533_1 | Battery Cabinet Operating Status (Battery Cabinet 1) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 670 | 8534_1 | Battery Cabinet Circuit Breaker Status (Battery Cabinet 1) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 671 | 8535_1 | Battery Cabinet Charge Disconnect Status (Battery Cabinet 1) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 672 | 8536_1 | Battery Cabinet Discharge Disconnect Status (Battery Cabinet 1) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 683 | 5834_1_1 | Module Operating Status (Battery Cabinet 1 Battery Module 1) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 684 | 8578_1_1 | Battery Module Disconnect Status (Battery Cabinet 1 Battery Module 1) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 695 | 5834_1_2 | Module Operating Status (Battery Cabinet 1 Battery Module 2) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 696 | 8578_1_2 | Battery Module Disconnect Status (Battery Cabinet 1 Battery Module 2) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 1055 | 5834_1_32 | Module Operating Status (Battery Cabinet 1 Battery Module 32) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 1056 | 8578_1_32 | Battery Module Disconnect Status (Battery Cabinet 1 Battery Module 32) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 1067 | 8607_2 | Battery Cabinet Type (Battery Cabinet 2) | Read | 1=Internal, 2=External | |
| MV | 1068 | 8533_2 | Battery Cabinet Operating Status (Battery Cabinet 2) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 1069 | 8534_2 | Battery Cabinet Circuit Breaker Status (Battery Cabinet 2) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 1070 | 8535_2 | Battery Cabinet Charge Disconnect Status (Battery Cabinet 2) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 1071 | 8536_2 | Battery Cabinet Discharge Disconnect Status (Battery Cabinet 2) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 1082 | 5834_2_1 | Module Operating Status (Battery Cabinet 2 Battery Module 1) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 1083 | 8578_2_1 | Battery Module Disconnect Status (Battery Cabinet 2 Battery Module 1) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 1094 | 5834_2_2 | Module Operating Status (Battery Cabinet 2 Battery Module 2) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 1095 | 8578_2_2 | Battery Module Disconnect Status (Battery Cabinet 2 Battery Module 2) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 1454 | 5834_2_32 | Module Operating Status (Battery Cabinet 2 Battery Module 32) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 1455 | 8578_2_32 | Battery Module Disconnect Status (Battery Cabinet 2 Battery Module 32) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 3860 | 8607_9 | Battery Cabinet Type (Battery Cabinet 9) | Read | 1=Internal, 2=External | |
| MV | 3861 | 8533_9 | Battery Cabinet Operating Status (Battery Cabinet 9) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 3862 | 8534_9 | Battery Cabinet Circuit Breaker Status (Battery Cabinet 9) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 3863 | 8535_9 | Battery Cabinet Charge Disconnect Status (Battery Cabinet 9) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 3864 | 8536_9 | Battery Cabinet Discharge Disconnect Status (Battery Cabinet 9) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 3875 | 5834_9_1 | Module Operating Status (Battery Cabinet 9 Battery Module 1) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 3876 | 8578_9_1 | Battery Module Disconnect Status (Battery Cabinet 9 Battery Module 1) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 3887 | 5834_9_2 | Module Operating Status (Battery Cabinet 9 Battery Module 2) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 3888 | 8578_9_2 | Battery Module Disconnect Status (Battery Cabinet 9 Battery Module 2) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 4247 | 5834_9_32 | Module Operating Status (Battery Cabinet 9 Battery Module 32) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 4248 | 8578_9_32 | Battery Module Disconnect Status (Battery Cabinet 9 Battery Module 32) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 4259 | 8555_1 | Battery String Operating Status (Battery String 1) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 4260 | 8556_1 | Battery String Charge Disconnect Status (Battery String 1) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 4261 | 8557_1 | Battery String Discharge Disconnect Status (Battery String 1) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 4272 | 8555_2 | Battery String Operating Status (Battery String 2) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 4273 | 8556_2 | Battery String Charge Disconnect Status (Battery String 2) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 4274 | 8557_2 | Battery String Discharge Disconnect Status (Battery String 2) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 4350 | 8555_8 | Battery String Operating Status (Battery String 8) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 4351 | 8556_8 | Battery String Charge Disconnect Status (Battery String 8) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 4352 | 8557_8 | Battery String Discharge Disconnect Status (Battery String 8) | Read | 1=Open, 2=Close, 3=Not Installed |
No points match these filters.
Object ID lookup: Vertiv Liebert APM2 UPS point IDs by name
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
Integration notes
- Tables 5.118, 5.119, 5.120, pdf pages 1933-1970 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert APM2 UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert APM2 UPS
How many BACnet points does the Vertiv Liebert APM2 UPS have?
This list has 845 BACnet objects: 409 analog values, 359 binary values, 77 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert APM2 UPS BACnet points are writable?
1 of the 845 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert APM2 UPS BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert APM2 UPS?
Start with MV 643 4123_1 (Normal, warning or alarm state); AV 267 4150_1 (Estimated battery runtime, min); AV 77 4208_1 (Output power, kW); AV 1 4097_1 (Input voltage, V); AV 55 4201_1 (Output voltage, V); AV 61 4204_1 (Output current, A); BV 939 4168_1 (Load is on battery); BV 909 4300_1 (Internal communication lost).
How do I check these points on the real Liebert APM2 UPS?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.