Short answer

The Liebert APM2 UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.

This page lists 845 BACnet objects for the Vertiv Liebert APM2 UPS — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert APM2 UPS
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
845 (1 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
APM2, Liebert APM2, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 845 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert APM2 UPS

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 6434123_1Normal, warning or alarm stateRead
AV 2674150_1Estimated battery runtime, minRead
AV 774208_1Output power, kWRead
AV 14097_1Input voltage, VRead
AV 554201_1Output voltage, VRead
AV 614204_1Output current, ARead
BV 9394168_1Load is on batteryRead
BV 9094300_1Internal communication lostRead

Network setup

Watch out for

Vertiv Liebert APM2 UPS BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

845 of 845 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert APM2 UPS BACnet Points List
DescriptionStates
BV15155_1Mains Input Neutral LostReadActive = alarm
BV24146_1System Input Phs Rotation ErrorReadActive = alarm
BV34122_1System Input Power ProblemReadActive = alarm
BV46630_1Input Under VoltageReadActive = alarm
BV56061_1Input Source BackfeedReadActive = alarm
BV166333_1Bypass out of syncReadActive = alarm
BV175957_1Bypass Input Voltage FaultReadActive = alarm
BV184325_1Backfeed Breaker OpenReadActive = alarm
BV195976_1Maintenance Bypass Breaker ClosedReadActive = alarm
BV208489_1System Bypass Phase Rotation ErrorReadActive = alarm
BV315806_1Output OverloadReadActive = alarm
BV324389_1System Output FaultReadActive = alarm
BV336220_1Module Output Breaker OpenReadActive = alarm
BV448494_1System Control Card Not Ready (System Control Card 1)ReadActive = alarm
BV458495_1System Control Card Power Supply Failure (System Control Card 1)ReadActive = alarm
BV468496_1System Control Card Communication Fail (System Control Card 1)ReadActive = alarm
BV578494_2System Control Card Not Ready (System Control Card 2)ReadActive = alarm
BV588495_2System Control Card Power Supply Failure (System Control Card 2)ReadActive = alarm
BV598496_2System Control Card Communication Fail (System Control Card 2)ReadActive = alarm
BV708501_1Bypass Module Not ReadyReadActive = alarm
BV718502_1Bypass Module Power Supply FailureReadActive = alarm
BV728503_1Bypass Module Communication FaultReadActive = alarm
BV734143_1Bypass Static Switch UnavailableReadActive = alarm
BV744216_1Bypass Backfeed DetectedReadActive = alarm
BV758096_1Bypass controlling the SCR autonomouslyReadActive = alarm
BV764139_1Bypass - Excess Auto RetransfersReadActive = alarm
BV778504_1Bypass Module Over TemperatureReadActive = alarm
BV788505_1Bypass Module Fan FaultReadActive = alarm
BV898512_1Power Module Not Ready (Power Module 1)ReadActive = alarm
BV906441_1Power Module Power Supply Failure (Power Module 1)ReadActive = alarm
BV918098_1Power Module Communication status (Power Module 1)ReadActive = alarm
BV926440_1Power Module Fuse Failure (Power Module 1)ReadActive = alarm
BV935838_1Power Module Fan Fault (Power Module 1)ReadActive = alarm
BV945839_1Power Module Over Temperature (Power Module 1)ReadActive = alarm
BV1056438_1_1Power Module Input Current Abnormal (Power Module 1 Rectifier 1)ReadActive = alarm
BV1068285_1_1Power Module Input Current High (Power Module 1 Rectifier 1)ReadActive = alarm
BV1074295_1_1Rectifier Failure (Power Module 1 Rectifier 1)ReadActive = alarm
BV1185154_1_1DC Bus Abnormal (Power Module 1 DC Bus 1)ReadActive = alarm
BV1196439_1_1Power Module Balancer of DC Bus Failure (Power Module 1 DC Bus 1)ReadActive = alarm
BV1305153_1_1Load Sharing Fault (Power Module 1 Inverter 1)ReadActive = alarm
BV1316059_1_1Inverter Relay Fault (Power Module 1 Inverter 1)ReadActive = alarm
BV1324290_1_1Inverter Shutdown - Overload (Power Module 1 Inverter 1)ReadActive = alarm
BV1336062_1_1Loss of Synchronization (Power Module 1 Inverter 1)ReadActive = alarm
BV1344233_1_1Inverter Failure (Power Module 1 Inverter 1)ReadActive = alarm
BV1456254_1_1Charger Failure (Power Module 1 Charger 1)ReadActive = alarm
BV1568510_1_1Discharger Failure (Power Module 1 Discharger 1)ReadActive = alarm
BV1578274_1_1Discharger Shutdown (Power Module 1 Discharger 1)ReadActive = alarm
BV1586063_1_1Battery Converter Current Limit (Power Module 1 Discharger 1)ReadActive = alarm
BV1698512_2Power Module Not Ready (Power Module 2)ReadActive = alarm
BV1706441_2Power Module Power Supply Failure (Power Module 2)ReadActive = alarm
BV1718098_2Power Module Communication status (Power Module 2)ReadActive = alarm
BV1726440_2Power Module Fuse Failure (Power Module 2)ReadActive = alarm
BV1735838_2Power Module Fan Fault (Power Module 2)ReadActive = alarm
BV1745839_2Power Module Over Temperature (Power Module 2)ReadActive = alarm
BV1856438_2_1Power Module Input Current Abnormal (Power Module 2 Rectifier 1)ReadActive = alarm
BV1868285_2_1Power Module Input Current High (Power Module 2 Rectifier 1)ReadActive = alarm
BV1874295_2_1Rectifier Failure (Power Module 2 Rectifier 1)ReadActive = alarm
BV1985154_2_1DC Bus Abnormal (Power Module 2 DC Bus 1)ReadActive = alarm
BV1996439_2_1Power Module Balancer of DC Bus Failure (Power Module 2 DC Bus 1)ReadActive = alarm
BV2105153_2_1Load Sharing Fault (Power Module 2 Inverter 1)ReadActive = alarm
BV2116059_2_1Inverter Relay Fault (Power Module 2 Inverter 1)ReadActive = alarm
BV2124290_2_1Inverter Shutdown - Overload (Power Module 2 Inverter 1)ReadActive = alarm
BV2136062_2_1Loss of Synchronization (Power Module 2 Inverter 1)ReadActive = alarm
BV2144233_2_1Inverter Failure (Power Module 2 Inverter 1)ReadActive = alarm
BV2256254_2_1Charger Failure (Power Module 2 Charger 1)ReadActive = alarm
BV2368510_2_1Discharger Failure (Power Module 2 Discharger 1)ReadActive = alarm
BV2378274_2_1Discharger Shutdown (Power Module 2 Discharger 1)ReadActive = alarm
BV2386063_2_1Battery Converter Current Limit (Power Module 2 Discharger 1)ReadActive = alarm
BV8098512_10Power Module Not Ready (Power Module 10)ReadActive = alarm
BV8106441_10Power Module Power Supply Failure (Power Module 10)ReadActive = alarm
BV8118098_10Power Module Communication status (Power Module 10)ReadActive = alarm
BV8126440_10Power Module Fuse Failure (Power Module 10)ReadActive = alarm
BV8135838_10Power Module Fan Fault (Power Module 10)ReadActive = alarm
BV8145839_10Power Module Over Temperature (Power Module 10)ReadActive = alarm
BV8256438_10_1Power Module Input Current Abnormal (Power Module 10 Rectifier 1)ReadActive = alarm
BV8268285_10_1Power Module Input Current High (Power Module 10 Rectifier 1)ReadActive = alarm
BV8274295_10_1Rectifier Failure (Power Module 10 Rectifier 1)ReadActive = alarm
BV8385154_10_1DC Bus Abnormal (Power Module 10 DC Bus 1)ReadActive = alarm
BV8396439_10_1Power Module Balancer of DC Bus Failure (Power Module 10 DC Bus 1)ReadActive = alarm
BV8505153_10_1Load Sharing Fault (Power Module 10 Inverter 1)ReadActive = alarm
BV8516059_10_1Inverter Relay Fault (Power Module 10 Inverter 1)ReadActive = alarm
BV8524290_10_1Inverter Shutdown - Overload (Power Module 10 Inverter 1)ReadActive = alarm
BV8536062_10_1Loss of Synchronization (Power Module 10 Inverter 1)ReadActive = alarm
BV8544233_10_1Inverter Failure (Power Module 10 Inverter 1)ReadActive = alarm
BV8656254_10_1Charger Failure (Power Module 10 Charger 1)ReadActive = alarm
BV8768510_10_1Discharger Failure (Power Module 10 Discharger 1)ReadActive = alarm
BV8778274_10_1Discharger Shutdown (Power Module 10 Discharger 1)ReadActive = alarm
BV8786063_10_1Battery Converter Current Limit (Power Module 10 Discharger 1)ReadActive = alarm
BV8896066_1Parallel Cable FailureReadActive = alarm
BV8904823_1Parallel Comm WarningReadActive = alarm
BV8916536_1MMS Capacity ExceededReadActive = alarm
BV8925817_1Loss of RedundancyReadActive = alarm
BV9036529_1Hardware MismatchReadActive = alarm
BV9046064_1LBS Cable FailureReadActive = alarm
BV9056060_1Transfer to Bypass - System OverloadReadActive = alarm
BV9065458_1Excess ECO SuspendsReadActive = alarm
BV9075157_1User Operation InvalidReadActive = alarm
BV9085156_1Load Impact TransferReadActive = alarm
BVmin9094300_1Internal Communications FailureReadActive = alarm
BV9104310_1Equipment Over TemperatureReadActive = alarm
BV9114758_1LBS InhibitedReadActive = alarm
BV9124315_1On GeneratorReadActive = alarm
BV9134757_1LBS ActiveReadActive = alarm
BV9144213_1System Shutdown - EPOReadActive = alarm
BV9154440_1Fuse FailureReadActive = alarm
BV9165970_1Ground FaultReadActive = alarm
BV9174311_1System Fan FailureReadActive = alarm
BV9188286_1Parameter Configuration FailedReadActive = alarm
BV9194215_1System Output OffReadActive = alarm
BV9208287_1Output DisabledReadActive = alarm
BV9215770_1Top Outlet Fan FaultReadActive = alarm
BV9228100_1ECO mode InhibitedReadActive = alarm
BV9234289_1Inverter Transfer Inhibit - ExtReadActive = alarm
BV9244298_1UPS Output on BypassReadActive = alarm
BV9254299_1Output Load on Maint. BypassReadActive = alarm
BV9265185_1Transformer OvertemperatureReadActive = alarm
BV9374741_1Battery Self TestReadActive = alarm
BV9384200_1Battery Charging InhibitedReadActive = alarm
BVmin9394168_1Battery DischargingReadActive = alarm
BV9404171_1Battery Manual Test In ProgressReadActive = alarm
BV9414172_1Battery Auto Test In ProgressReadActive = alarm
BV9424323_1Battery Test FailedReadActive = alarm
BV9434162_1Battery LowReadActive = alarm
BV9444222_1Battery Ground FaultReadActive = alarm
BV9455149_1Battery Not QualifiedReadActive = alarm
BV9465150_1Battery Terminals ReversedReadActive = alarm
BV9476182_1Replace BatteryReadActive = alarm
BV9486065_1Battery Charge Equalization TimeoutReadActive = alarm
BV9496068_1Battery Room AlarmReadActive = alarm
BV9504170_1Battery EqualizeReadActive = alarm
BV9518288_1Battery Terminal AbnormalReadActive = alarm
BV9528429_1Battery System Communication AbnormalReadActive = alarm
BV9538430_1Battery System WarningReadActive = alarm
BV9548431_1Battery System FaultReadActive = alarm
BV9554176_1Battery Circuit Breaker 1 OpenReadActive = alarm
BV9564179_1Battery Circuit Breaker 2 OpenReadActive = alarm
BV9574182_1Battery Circuit Breaker 3 OpenReadActive = alarm
BV9584185_1Battery Circuit Breaker 4 OpenReadActive = alarm
BV9594188_1Battery Circuit Breaker 5 OpenReadActive = alarm
BV9604191_1Battery Circuit Breaker 6 OpenReadActive = alarm
BV9614194_1Battery Circuit Breaker 7 OpenReadActive = alarm
BV9624197_1Battery Circuit Breaker 8 OpenReadActive = alarm
BV9638517_1Battery Circuit Breaker 9 OpenReadActive = alarm
BV9648518_1Battery Circuit Breaker 10 OpenReadActive = alarm
BV9658519_1Battery Circuit Breaker 11 OpenReadActive = alarm
BV9668520_1Battery Circuit Breaker 12 OpenReadActive = alarm
BV9674178_1Battery Breaker 1 Open FailureReadActive = alarm
BV9684180_1Battery Breaker 2 Open FailureReadActive = alarm
BV9694183_1Battery Breaker 3 Open FailureReadActive = alarm
BV9704186_1Battery Breaker 4 Open FailureReadActive = alarm
BV9714190_1Battery Breaker 5 Open FailureReadActive = alarm
BV9724192_1Battery Breaker 6 Open FailureReadActive = alarm
BV9734195_1Battery Breaker 7 Open FailureReadActive = alarm
BV9744198_1Battery Breaker 8 Open FailureReadActive = alarm
BV9758521_1Battery Breaker 9 Open FailureReadActive = alarm
BV9768522_1Battery Breaker 10 Open FailureReadActive = alarm
BV9778523_1Battery Breaker 11 Open FailureReadActive = alarm
BV9788524_1Battery Breaker 12 Open FailureReadActive = alarm
BV9898537_1Battery Cabinet High Overall Voltage (Battery Cabinet 1)ReadActive = alarm
BV9908538_1Battery Cabinet Low Overall Voltage (Battery Cabinet 1)ReadActive = alarm
BV9918539_1Battery Cabinet High Cell Voltage (Battery Cabinet 1)ReadActive = alarm
BV9928540_1Battery Cabinet Low Cell Voltage (Battery Cabinet 1)ReadActive = alarm
BV9938541_1Battery Cabinet Over Overall Voltage (Battery Cabinet 1)ReadActive = alarm
BV9948542_1Battery Cabinet Under Overall Voltage (Battery Cabinet 1)ReadActive = alarm
BV9958543_1Battery Cabinet Over Cell Voltage (Battery Cabinet 1)ReadActive = alarm
BV9968544_1Battery Cabinet Under Cell Voltage (Battery Cabinet 1)ReadActive = alarm
BV9978545_1Battery Cabinet Charge Over Current (Battery Cabinet 1)ReadActive = alarm
BV9988546_1Battery Cabinet Discharge Over Current (Battery Cabinet 1)ReadActive = alarm
BV9998547_1Battery Cabinet Over Temperature (Battery Cabinet 1)ReadActive = alarm
BV10008548_1Battery Cabinet Under Temperature (Battery Cabinet 1)ReadActive = alarm
BV10014174_1Battery Temperature Sensor Fault (Battery Cabinet 1)ReadActive = alarm
BV10128587_1_1Battery Module Disconnected (Battery Cabinet 1 Battery Module 1)ReadActive = alarm
BV10138590_1_1Battery Module Over Temperature (Battery Cabinet 1 Battery Module 1)ReadActive = alarm
BV10248579_1_1_1Battery Module High Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10258580_1_1_1Battery Module Low Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10268581_1_1_1Battery Module High Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10278582_1_1_1Battery Module Low Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10288583_1_1_1Battery Module Over Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10298584_1_1_1Battery Module Under Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10308585_1_1_1Battery Module Over Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10318586_1_1_1Battery Module Under Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10328588_1_1_1Battery Module Charge Over Current (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10338589_1_1_1Battery Module Discharge Over Current (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10348591_1_1_1Battery Module Under Temperature (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10358592_1_1_1Battery Module Fault (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV10468587_1_2Battery Module Disconnected (Battery Cabinet 1 Battery Module 2)ReadActive = alarm
BV10478590_1_2Battery Module Over Temperature (Battery Cabinet 1 Battery Module 2)ReadActive = alarm
BV10588579_1_2_1Battery Module High Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10598580_1_2_1Battery Module Low Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10608581_1_2_1Battery Module High Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10618582_1_2_1Battery Module Low Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10628583_1_2_1Battery Module Over Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10638584_1_2_1Battery Module Under Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10648585_1_2_1Battery Module Over Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10658586_1_2_1Battery Module Under Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10668588_1_2_1Battery Module Charge Over Current (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10678589_1_2_1Battery Module Discharge Over Current (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10688591_1_2_1Battery Module Under Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV10698592_1_2_1Battery Module Fault (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20668587_1_32Battery Module Disconnected (Battery Cabinet 1 Battery Module 32)ReadActive = alarm
BV20678590_1_32Battery Module Over Temperature (Battery Cabinet 1 Battery Module 32)ReadActive = alarm
BV20788579_1_32_1Battery Module High Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20798580_1_32_1Battery Module Low Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20808581_1_32_1Battery Module High Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20818582_1_32_1Battery Module Low Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20828583_1_32_1Battery Module Over Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20838584_1_32_1Battery Module Under Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20848585_1_32_1Battery Module Over Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20858586_1_32_1Battery Module Under Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20868588_1_32_1Battery Module Charge Over Current (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20878589_1_32_1Battery Module Discharge Over Current (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20888591_1_32_1Battery Module Under Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV20898592_1_32_1Battery Module Fault (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV21008537_2Battery Cabinet High Overall Voltage (Battery Cabinet 2)ReadActive = alarm
BV21018538_2Battery Cabinet Low Overall Voltage (Battery Cabinet 2)ReadActive = alarm
BV21028539_2Battery Cabinet High Cell Voltage (Battery Cabinet 2)ReadActive = alarm
BV21038540_2Battery Cabinet Low Cell Voltage (Battery Cabinet 2)ReadActive = alarm
BV21048541_2Battery Cabinet Over Overall Voltage (Battery Cabinet 2)ReadActive = alarm
BV21058542_2Battery Cabinet Under Overall Voltage (Battery Cabinet 2)ReadActive = alarm
BV21068543_2Battery Cabinet Over Cell Voltage (Battery Cabinet 2)ReadActive = alarm
BV21078544_2Battery Cabinet Under Cell Voltage (Battery Cabinet 2)ReadActive = alarm
BV21088545_2Battery Cabinet Charge Over Current (Battery Cabinet 2)ReadActive = alarm
BV21098546_2Battery Cabinet Discharge Over Current (Battery Cabinet 2)ReadActive = alarm
BV21108547_2Battery Cabinet Over Temperature (Battery Cabinet 2)ReadActive = alarm
BV21118548_2Battery Cabinet Under Temperature (Battery Cabinet 2)ReadActive = alarm
BV21124174_2Battery Temperature Sensor Fault (Battery Cabinet 2)ReadActive = alarm
BV21238587_2_1Battery Module Disconnected (Battery Cabinet 2 Battery Module 1)ReadActive = alarm
BV21248590_2_1Battery Module Over Temperature (Battery Cabinet 2 Battery Module 1)ReadActive = alarm
BV21358579_2_1_1Battery Module High Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21368580_2_1_1Battery Module Low Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21378581_2_1_1Battery Module High Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21388582_2_1_1Battery Module Low Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21398583_2_1_1Battery Module Over Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21408584_2_1_1Battery Module Under Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21418585_2_1_1Battery Module Over Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21428586_2_1_1Battery Module Under Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21438588_2_1_1Battery Module Charge Over Current (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21448589_2_1_1Battery Module Discharge Over Current (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21458591_2_1_1Battery Module Under Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21468592_2_1_1Battery Module Fault (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)ReadActive = alarm
BV21578587_2_2Battery Module Disconnected (Battery Cabinet 2 Battery Module 2)ReadActive = alarm
BV21588590_2_2Battery Module Over Temperature (Battery Cabinet 2 Battery Module 2)ReadActive = alarm
BV21698579_2_2_1Battery Module High Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21708580_2_2_1Battery Module Low Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21718581_2_2_1Battery Module High Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21728582_2_2_1Battery Module Low Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21738583_2_2_1Battery Module Over Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21748584_2_2_1Battery Module Under Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21758585_2_2_1Battery Module Over Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21768586_2_2_1Battery Module Under Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21778588_2_2_1Battery Module Charge Over Current (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21788589_2_2_1Battery Module Discharge Over Current (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21798591_2_2_1Battery Module Under Temperature (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV21808592_2_2_1Battery Module Fault (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)ReadActive = alarm
BV31778587_2_32Battery Module Disconnected (Battery Cabinet 2 Battery Module 32)ReadActive = alarm
BV31788590_2_32Battery Module Over Temperature (Battery Cabinet 2 Battery Module 32)ReadActive = alarm
BV31898579_2_32_1Battery Module High Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV31908580_2_32_1Battery Module Low Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV31918581_2_32_1Battery Module High Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV31928582_2_32_1Battery Module Low Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV31938583_2_32_1Battery Module Over Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV31948584_2_32_1Battery Module Under Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV31958585_2_32_1Battery Module Over Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV31968586_2_32_1Battery Module Under Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV31978588_2_32_1Battery Module Charge Over Current (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV31988589_2_32_1Battery Module Discharge Over Current (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV31998591_2_32_1Battery Module Under Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV32008592_2_32_1Battery Module Fault (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV98778537_9Battery Cabinet High Overall Voltage (Battery Cabinet 9)ReadActive = alarm
BV98788538_9Battery Cabinet Low Overall Voltage (Battery Cabinet 9)ReadActive = alarm
BV98798539_9Battery Cabinet High Cell Voltage (Battery Cabinet 9)ReadActive = alarm
BV98808540_9Battery Cabinet Low Cell Voltage (Battery Cabinet 9)ReadActive = alarm
BV98818541_9Battery Cabinet Over Overall Voltage (Battery Cabinet 9)ReadActive = alarm
BV98828542_9Battery Cabinet Under Overall Voltage (Battery Cabinet 9)ReadActive = alarm
BV98838543_9Battery Cabinet Over Cell Voltage (Battery Cabinet 9)ReadActive = alarm
BV98848544_9Battery Cabinet Under Cell Voltage (Battery Cabinet 9)ReadActive = alarm
BV98858545_9Battery Cabinet Charge Over Current (Battery Cabinet 9)ReadActive = alarm
BV98868546_9Battery Cabinet Discharge Over Current (Battery Cabinet 9)ReadActive = alarm
BV98878547_9Battery Cabinet Over Temperature (Battery Cabinet 9)ReadActive = alarm
BV98888548_9Battery Cabinet Under Temperature (Battery Cabinet 9)ReadActive = alarm
BV98894174_9Battery Temperature Sensor Fault (Battery Cabinet 9)ReadActive = alarm
BV99008587_9_1Battery Module Disconnected (Battery Cabinet 9 Battery Module 1)ReadActive = alarm
BV99018590_9_1Battery Module Over Temperature (Battery Cabinet 9 Battery Module 1)ReadActive = alarm
BV99128579_9_1_1Battery Module High Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99138580_9_1_1Battery Module Low Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99148581_9_1_1Battery Module High Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99158582_9_1_1Battery Module Low Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99168583_9_1_1Battery Module Over Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99178584_9_1_1Battery Module Under Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99188585_9_1_1Battery Module Over Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99198586_9_1_1Battery Module Under Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99208588_9_1_1Battery Module Charge Over Current (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99218589_9_1_1Battery Module Discharge Over Current (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99228591_9_1_1Battery Module Under Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99238592_9_1_1Battery Module Fault (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99348587_9_2Battery Module Disconnected (Battery Cabinet 9 Battery Module 2)ReadActive = alarm
BV99358590_9_2Battery Module Over Temperature (Battery Cabinet 9 Battery Module 2)ReadActive = alarm
BV99468579_9_2_1Battery Module High Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99478580_9_2_1Battery Module Low Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99488581_9_2_1Battery Module High Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99498582_9_2_1Battery Module Low Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99508583_9_2_1Battery Module Over Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99518584_9_2_1Battery Module Under Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99528585_9_2_1Battery Module Over Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99538586_9_2_1Battery Module Under Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99548588_9_2_1Battery Module Charge Over Current (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99558589_9_2_1Battery Module Discharge Over Current (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99568591_9_2_1Battery Module Under Temperature (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV99578592_9_2_1Battery Module Fault (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109548587_9_32Battery Module Disconnected (Battery Cabinet 9 Battery Module 32)ReadActive = alarm
BV109558590_9_32Battery Module Over Temperature (Battery Cabinet 9 Battery Module 32)ReadActive = alarm
BV109668579_9_32_1Battery Module High Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109678580_9_32_1Battery Module Low Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109688581_9_32_1Battery Module High Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109698582_9_32_1Battery Module Low Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109708583_9_32_1Battery Module Over Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109718584_9_32_1Battery Module Under Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109728585_9_32_1Battery Module Over Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109738586_9_32_1Battery Module Under Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109748588_9_32_1Battery Module Charge Over Current (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109758589_9_32_1Battery Module Discharge Over Current (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109768591_9_32_1Battery Module Under Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109778592_9_32_1Battery Module Fault (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)ReadActive = alarm
BV109888605_1Battery String High Overall Voltage (Battery String 1)ReadActive = alarm
BV109898606_1Battery String Low Overall Voltage (Battery String 1)ReadActive = alarm
BV109908558_1Battery String High Cell Voltage (Battery String 1)ReadActive = alarm
BV109918559_1Battery String Low Cell Voltage (Battery String 1)ReadActive = alarm
BV109928560_1Battery String Over Overall Voltage (Battery String 1)ReadActive = alarm
BV109938561_1Battery String Under Overall Voltage (Battery String 1)ReadActive = alarm
BV109948562_1Battery String Over Cell Voltage (Battery String 1)ReadActive = alarm
BV109958563_1Battery String Under Cell Voltage (Battery String 1)ReadActive = alarm
BV109968564_1Battery String Charge Over Current (Battery String 1)ReadActive = alarm
BV109978565_1Battery String Discharge Over Current (Battery String 1)ReadActive = alarm
BV109988566_1Battery String Over Temperature (Battery String 1)ReadActive = alarm
BV109998567_1Battery String Under Temperature (Battery String 1)ReadActive = alarm
BV110108605_2Battery String High Overall Voltage (Battery String 2)ReadActive = alarm
BV110118606_2Battery String Low Overall Voltage (Battery String 2)ReadActive = alarm
BV110128558_2Battery String High Cell Voltage (Battery String 2)ReadActive = alarm
BV110138559_2Battery String Low Cell Voltage (Battery String 2)ReadActive = alarm
BV110148560_2Battery String Over Overall Voltage (Battery String 2)ReadActive = alarm
BV110158561_2Battery String Under Overall Voltage (Battery String 2)ReadActive = alarm
BV110168562_2Battery String Over Cell Voltage (Battery String 2)ReadActive = alarm
BV110178563_2Battery String Under Cell Voltage (Battery String 2)ReadActive = alarm
BV110188564_2Battery String Charge Over Current (Battery String 2)ReadActive = alarm
BV110198565_2Battery String Discharge Over Current (Battery String 2)ReadActive = alarm
BV110208566_2Battery String Over Temperature (Battery String 2)ReadActive = alarm
BV110218567_2Battery String Under Temperature (Battery String 2)ReadActive = alarm
BV111428605_8Battery String High Overall Voltage (Battery String 8)ReadActive = alarm
BV111438606_8Battery String Low Overall Voltage (Battery String 8)ReadActive = alarm
BV111448558_8Battery String High Cell Voltage (Battery String 8)ReadActive = alarm
BV111458559_8Battery String Low Cell Voltage (Battery String 8)ReadActive = alarm
BV111468560_8Battery String Over Overall Voltage (Battery String 8)ReadActive = alarm
BV111478561_8Battery String Under Overall Voltage (Battery String 8)ReadActive = alarm
BV111488562_8Battery String Over Cell Voltage (Battery String 8)ReadActive = alarm
BV111498563_8Battery String Under Cell Voltage (Battery String 8)ReadActive = alarm
BV111508564_8Battery String Charge Over Current (Battery String 8)ReadActive = alarm
BV111518565_8Battery String Discharge Over Current (Battery String 8)ReadActive = alarm
BV111528566_8Battery String Over Temperature (Battery String 8)ReadActive = alarm
BV111538567_8Battery String Under Temperature (Battery String 8)ReadActive = alarm
AVmin14097_1System Input RMS A-BVRead
AV24099_1System Input RMS B-CVRead
AV34101_1System Input RMS C-AVRead
AV44096_1System Input RMS A-NVRead
AV54098_1System Input RMS B-NVRead
AV64100_1System Input RMS C-NVRead
AV74113_1System Input RMS Current Phase AARead
AV84114_1System Input RMS Current Phase BARead
AV94115_1System Input RMS Current Phase CARead
AV104105_1System Input FrequencyHzRead
AV114116_1System Input Power Factor Phs ARead
AV124117_1System Input Power Factor Phs BRead
AV134118_1System Input Power Factor Phs CRead
AV146318_1System Input Power Phase AkWRead
AV156319_1System Input Power Phase BkWRead
AV166320_1System Input Power Phase CkWRead
AV178093_1System Input Apparent Power Phs AkVARead
AV188094_1System Input Apparent Power Phs BkVARead
AV198095_1System Input Apparent Power Phs CkVARead
AV204119_1System Input Brown Out CountRead
AV214120_1System Input Black Out CountRead
AV324125_1Bypass Input Voltage RMS A-BVRead
AV334126_1Bypass Input Voltage RMS B-CVRead
AV344127_1Bypass Input Voltage RMS C-AVRead
AV354128_1Bypass Input Voltage RMS A-NVRead
AV364129_1Bypass Input Voltage RMS B-NVRead
AV374130_1Bypass Input Voltage RMS C-NVRead
AV384131_1Bypass Input FrequencyHzRead
AV396325_1Bypass Power Phase AkWRead
AV406326_1Bypass Power Phase BkWRead
AV416327_1Bypass Power Phase CkWRead
AV426328_1Bypass Apparent Power Phase AkVARead
AV436329_1Bypass Apparent Power Phase BkVARead
AV446330_1Bypass Apparent Power Phase CkVARead
AVmin554201_1System Output Voltage RMS A-BVRead
AV564202_1System Output Voltage RMS B-CVRead
AV574203_1System Output Voltage RMS C-AVRead
AV584385_1System Output Voltage RMS A-NVRead
AV594386_1System Output Voltage RMS B-NVRead
AV604387_1System Output Voltage RMS C-NVRead
AVmin614204_1System Output RMS Current Phs AARead
AV624205_1System Output RMS Current Phs BARead
AV634206_1System Output RMS Current Phs CARead
AV645159_1Output Current Crest Factor Phs ARead
AV655160_1Output Current Crest Factor Phs BRead
AV665161_1Output Current Crest Factor Phs CRead
AV674207_1System Output FrequencyHzRead
AV684210_1System Output Power Factor Phs ARead
AV694211_1System Output Power Factor Phs BRead
AV704212_1System Output Power Factor Phs CRead
AV715859_1System Output Power Phase AkWRead
AV725860_1System Output Power Phase BkWRead
AV735959_1System Output Power Phase CkWRead
AV745868_1System Output Apparent Power Phs AkVARead
AV755869_1System Output Apparent Power Phs BkVARead
AV765870_1System Output Apparent Power Phs CkVARead
AVmin774208_1System Output PowerkWRead
AV784209_1System Output Apparent PowerkVARead
AV794226_1System Output Pct Pwr (VA) Phs A%Read
AV804227_1System Output Pct Pwr (VA) Phs B%Read
AV814228_1System Output Pct Pwr (VA) Phs C%Read
AV824223_1System Output Pct Power Phase A%Read
AV834224_1System Output Pct Power Phase B%Read
AV844225_1System Output Pct Power Phase C%Read
AV958281_1_1Positive DC Bus Voltage (Power Module 1 DC Bus 1)VDCRead
AV968282_1_1Negative DC Bus Voltage (Power Module 1 DC Bus 1)VDCRead
AV1078281_2_1Positive DC Bus Voltage (Power Module 2 DC Bus 1)VDCRead
AV1088282_2_1Negative DC Bus Voltage (Power Module 2 DC Bus 1)VDCRead
AV2038281_10_1Positive DC Bus Voltage (Power Module 10 DC Bus 1)VDCRead
AV2048282_10_1Negative DC Bus Voltage (Power Module 10 DC Bus 1)VDCRead
AV2154811_1MMS Output PowerkWRead
AV2164812_1MMS Output Apparent PowerkVARead
AV2275824_1Number Of Active Power ModulesRead
AV2285823_1Number of Installed Power ModulesRead
AV2298513_1Redundant Count of Power ModuleRead
AV2304291_1Inlet Air Temperature°CRead
AV5002304291_1_deg_FInlet Air Temperature°FRead
AV2316069_1Average system efficiency%Read
AV2328097_1ECO Suspended Time RemainingsRead
AV2334292_1Total System Operating TimehRead
AV2444293_1System Date and TimeSecs since Epoch(UTC)Write
AV2455821_1System CapacitykVARead
AV2464102_1System Input Nominal VoltageVRead
AV2474104_1System Input Nominal CurrentARead
AV2484259_1Bypass Nominal VoltageVRead
AV2494260_1System Output Nominal VoltageVRead
AV2504261_1System Output Nominal FrequencyHzRead
AV2618514_1External Battery Cabinet CountRead
AV2628515_1Battery String CountRead
AV2634148_1DC Bus VoltageVDCRead
AV2644149_1DC Bus CurrentA DCRead
AV2658516_1Battery Temperature°CRead
AV5002658516_1_deg_FBattery Temperature°FRead
AV2664153_1Battery Percentage Charge%Read
AVmin2674150_1Battery Time RemainingminRead
AV2685845_1Number of Discharge CyclesRead
AV2695846_1Accumulated Discharge TimehRead
AV2705991_1Battery Self Test Cycle TimedayRead
AV2715804_1Time Until Next Auto Battery TestminRead
AV2725802_1Low Battery Warning TimeminRead
AV2834155_1Battery Volts for Cabinet (Battery Cabinet 1)VDCRead
AV2848527_1Battery Current for Cabinet (Battery Cabinet 1)A DCRead
AV2854156_1Battery Temperature for Cabinet (Battery Cabinet 1)°CRead
AV5002854156_1_deg_FBattery Temperature for Cabinet (Battery Cabinet 1)°FRead
AV2868528_1Battery Cabinet Capacity (Battery Cabinet 1)%Read
AV2878529_1Battery Cabinet Max Cell Voltage (Battery Cabinet 1)VDCRead
AV2888530_1Battery Cabinet Min Cell Voltage (Battery Cabinet 1)VDCRead
AV2898531_1Battery Cabinet Highest Cell Temperature (Battery Cabinet 1)°CRead
AV5002898531_1_deg_FBattery Cabinet Highest Cell Temperature (Battery Cabinet 1)°FRead
AV2908532_1Battery Cabinet Lowest Cell Temperature (Battery Cabinet 1)°CRead
AV5002908532_1_deg_FBattery Cabinet Lowest Cell Temperature (Battery Cabinet 1)°FRead
AV3014962_1_1Cell Voltage (Battery Cabinet 1 Battery Cell In Cabinet 1)VDCRead
AV3024963_1_1Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 1)°CRead
AV5003024963_1_1_deg_FCell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 1)°FRead
AV3035443_1_1Internal Resistance Value (Battery Cabinet 1 Battery Cell In Cabinet 1)milliOhmRead
AV3144962_1_2Cell Voltage (Battery Cabinet 1 Battery Cell In Cabinet 2)VDCRead
AV3154963_1_2Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 2)°CRead
AV5003154963_1_2_deg_FCell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 2)°FRead
AV3165443_1_2Internal Resistance Value (Battery Cabinet 1 Battery Cell In Cabinet 2)milliOhmRead
AV28884962_1_200Cell Voltage (Battery Cabinet 1 Battery Cell In Cabinet 200)VDCRead
AV28894963_1_200Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 200)°CRead
AV5028894963_1_200_deg_FCell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 200)°FRead
AV28905443_1_200Internal Resistance Value (Battery Cabinet 1 Battery Cell In Cabinet 200)milliOhmRead
AV29015844_1_1Battery Module Temperature (Battery Cabinet 1 Battery Module 1)°CRead
AV5029015844_1_1_deg_FBattery Module Temperature (Battery Cabinet 1 Battery Module 1)°FRead
AV29128571_1_1_1Battery Module Voltage (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)VDCRead
AV29138572_1_1_1Battery Module Current (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)A DCRead
AV29148573_1_1_1Battery Module State Of Charge (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)%Read
AV29158574_1_1_1Battery Module Max Cell Voltage (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)VDCRead
AV29168575_1_1_1Battery Module Min Cell Voltage (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)VDCRead
AV29178576_1_1_1Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)°CRead
AV5029178576_1_1_1_deg_FBattery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)°FRead
AV29188577_1_1_1Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)°CRead
AV5029188577_1_1_1_deg_FBattery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)°FRead
AV29308593_1_1_1Battery Cell Voltage (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 1)VDCRead
AV29318570_1_1_1Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 1)°CRead
AV5029318570_1_1_1_deg_FBattery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 1)°FRead
AV29428593_1_1_2Battery Cell Voltage (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 2)VDCRead
AV29438570_1_1_2Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 2)°CRead
AV5029438570_1_1_2_deg_FBattery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 2)°FRead
AV41188593_1_1_100Battery Cell Voltage (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 100)VDCRead
AV41198570_1_1_100Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 100)°CRead
AV5041198570_1_1_100_deg_FBattery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 100)°FRead
AV41295844_1_2Battery Module Temperature (Battery Cabinet 1 Battery Module 2)°CRead
AV5041295844_1_2_deg_FBattery Module Temperature (Battery Cabinet 1 Battery Module 2)°FRead
AV41408571_1_2_1Battery Module Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)VDCRead
AV41418572_1_2_1Battery Module Current (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)A DCRead
AV41428573_1_2_1Battery Module State Of Charge (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)%Read
AV41438574_1_2_1Battery Module Max Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)VDCRead
AV41448575_1_2_1Battery Module Min Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)VDCRead
AV41458576_1_2_1Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)°CRead
AV5041458576_1_2_1_deg_FBattery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)°FRead
AV41468577_1_2_1Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)°CRead
AV5041468577_1_2_1_deg_FBattery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)°FRead
AV41588593_1_2_1Battery Cell Voltage (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 1)VDCRead
AV41598570_1_2_1Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 1)°CRead
AV5041598570_1_2_1_deg_FBattery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 1)°FRead
AV41708593_1_2_2Battery Cell Voltage (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 2)VDCRead
AV41718570_1_2_2Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 2)°CRead
AV5041718570_1_2_2_deg_FBattery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 2)°FRead
AV53468593_1_2_100Battery Cell Voltage (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 100)VDCRead
AV53478570_1_2_100Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 100)°CRead
AV5053478570_1_2_100_deg_FBattery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 100)°FRead
AV409695844_1_32Battery Module Temperature (Battery Cabinet 1 Battery Module 32)°CRead
AV5409695844_1_32_deg_FBattery Module Temperature (Battery Cabinet 1 Battery Module 32)°FRead
AV409808571_1_32_1Battery Module Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)VDCRead
AV409818572_1_32_1Battery Module Current (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)A DCRead
AV409828573_1_32_1Battery Module State Of Charge (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)%Read
AV409838574_1_32_1Battery Module Max Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)VDCRead
AV409848575_1_32_1Battery Module Min Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)VDCRead
AV409858576_1_32_1Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)°CRead
AV5409858576_1_32_1_deg_FBattery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)°FRead
AV409868577_1_32_1Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)°CRead
AV5409868577_1_32_1_deg_FBattery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)°FRead
AV409988593_1_32_1Battery Cell Voltage (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 1)VDCRead
AV409998570_1_32_1Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 1)°CRead
AV5409998570_1_32_1_deg_FBattery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 1)°FRead
AV410108593_1_32_2Battery Cell Voltage (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 2)VDCRead
AV410118570_1_32_2Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 2)°CRead
AV5410118570_1_32_2_deg_FBattery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 2)°FRead
AV421868593_1_32_100Battery Cell Voltage (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 100)VDCRead
AV421878570_1_32_100Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 100)°CRead
AV5421878570_1_32_100_deg_FBattery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 100)°FRead
AV421974155_2Battery Volts for Cabinet (Battery Cabinet 2)VDCRead
AV421988527_2Battery Current for Cabinet (Battery Cabinet 2)A DCRead
AV421994156_2Battery Temperature for Cabinet (Battery Cabinet 2)°CRead
AV5421994156_2_deg_FBattery Temperature for Cabinet (Battery Cabinet 2)°FRead
AV422008528_2Battery Cabinet Capacity (Battery Cabinet 2)%Read
AV422018529_2Battery Cabinet Max Cell Voltage (Battery Cabinet 2)VDCRead
AV422028530_2Battery Cabinet Min Cell Voltage (Battery Cabinet 2)VDCRead
AV422038531_2Battery Cabinet Highest Cell Temperature (Battery Cabinet 2)°CRead
AV5422038531_2_deg_FBattery Cabinet Highest Cell Temperature (Battery Cabinet 2)°FRead
AV422048532_2Battery Cabinet Lowest Cell Temperature (Battery Cabinet 2)°CRead
AV5422048532_2_deg_FBattery Cabinet Lowest Cell Temperature (Battery Cabinet 2)°FRead
AV422154962_2_1Cell Voltage (Battery Cabinet 2 Battery Cell In Cabinet 1)VDCRead
AV422164963_2_1Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 1)°CRead
AV5422164963_2_1_deg_FCell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 1)°FRead
AV422175443_2_1Internal Resistance Value (Battery Cabinet 2 Battery Cell In Cabinet 1)milliOhmRead
AV422284962_2_2Cell Voltage (Battery Cabinet 2 Battery Cell In Cabinet 2)VDCRead
AV422294963_2_2Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 2)°CRead
AV5422294963_2_2_deg_FCell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 2)°FRead
AV422305443_2_2Internal Resistance Value (Battery Cabinet 2 Battery Cell In Cabinet 2)milliOhmRead
AV448024962_2_200Cell Voltage (Battery Cabinet 2 Battery Cell In Cabinet 200)VDCRead
AV448034963_2_200Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 200)°CRead
AV5448034963_2_200_deg_FCell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 200)°FRead
AV448045443_2_200Internal Resistance Value (Battery Cabinet 2 Battery Cell In Cabinet 200)milliOhmRead
AV448155844_2_1Battery Module Temperature (Battery Cabinet 2 Battery Module 1)°CRead
AV5448155844_2_1_deg_FBattery Module Temperature (Battery Cabinet 2 Battery Module 1)°FRead
AV448268571_2_1_1Battery Module Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)VDCRead
AV448278572_2_1_1Battery Module Current (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)A DCRead
AV448288573_2_1_1Battery Module State Of Charge (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)%Read
AV448298574_2_1_1Battery Module Max Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)VDCRead
AV448308575_2_1_1Battery Module Min Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)VDCRead
AV448318576_2_1_1Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)°CRead
AV5448318576_2_1_1_deg_FBattery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)°FRead
AV448328577_2_1_1Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)°CRead
AV5448328577_2_1_1_deg_FBattery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)°FRead
AV448448593_2_1_1Battery Cell Voltage (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 1)VDCRead
AV448458570_2_1_1Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 1)°CRead
AV5448458570_2_1_1_deg_FBattery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 1)°FRead
AV448568593_2_1_2Battery Cell Voltage (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 2)VDCRead
AV448578570_2_1_2Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 2)°CRead
AV5448578570_2_1_2_deg_FBattery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 2)°FRead
AV460328593_2_1_100Battery Cell Voltage (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 100)VDCRead
AV460338570_2_1_100Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 100)°CRead
AV5460338570_2_1_100_deg_FBattery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 100)°FRead
AV460435844_2_2Battery Module Temperature (Battery Cabinet 2 Battery Module 2)°CRead
AV5460435844_2_2_deg_FBattery Module Temperature (Battery Cabinet 2 Battery Module 2)°FRead
AV460548571_2_2_1Battery Module Voltage (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)VDCRead
AV460558572_2_2_1Battery Module Current (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)A DCRead
AV460568573_2_2_1Battery Module State Of Charge (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)%Read
AV460578574_2_2_1Battery Module Max Cell Voltage (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)VDCRead
AV460588575_2_2_1Battery Module Min Cell Voltage (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)VDCRead
AV460598576_2_2_1Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)°CRead
AV5460598576_2_2_1_deg_FBattery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)°FRead
AV460608577_2_2_1Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)°CRead
AV5460608577_2_2_1_deg_FBattery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)°FRead
AV460728593_2_2_1Battery Cell Voltage (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 1)VDCRead
AV460738570_2_2_1Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 1)°CRead
AV5460738570_2_2_1_deg_FBattery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 1)°FRead
AV460848593_2_2_2Battery Cell Voltage (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 2)VDCRead
AV460858570_2_2_2Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 2)°CRead
AV5460858570_2_2_2_deg_FBattery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 2)°FRead
AV472608593_2_2_100Battery Cell Voltage (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 100)VDCRead
AV472618570_2_2_100Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 100)°CRead
AV5472618570_2_2_100_deg_FBattery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 100)°FRead
AV828835844_2_32Battery Module Temperature (Battery Cabinet 2 Battery Module 32)°CRead
AV5828835844_2_32_deg_FBattery Module Temperature (Battery Cabinet 2 Battery Module 32)°FRead
AV828948571_2_32_1Battery Module Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)VDCRead
AV828958572_2_32_1Battery Module Current (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)A DCRead
AV828968573_2_32_1Battery Module State Of Charge (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)%Read
AV828978574_2_32_1Battery Module Max Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)VDCRead
AV828988575_2_32_1Battery Module Min Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)VDCRead
AV828998576_2_32_1Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)°CRead
AV5828998576_2_32_1_deg_FBattery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)°FRead
AV829008577_2_32_1Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)°CRead
AV5829008577_2_32_1_deg_FBattery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)°FRead
AV829128593_2_32_1Battery Cell Voltage (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 1)VDCRead
AV829138570_2_32_1Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 1)°CRead
AV5829138570_2_32_1_deg_FBattery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 1)°FRead
AV829248593_2_32_2Battery Cell Voltage (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 2)VDCRead
AV829258570_2_32_2Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 2)°CRead
AV5829258570_2_32_2_deg_FBattery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 2)°FRead
AV841008593_2_32_100Battery Cell Voltage (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 100)VDCRead
AV841018570_2_32_100Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 100)°CRead
AV5841018570_2_32_100_deg_FBattery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 100)°FRead
AV3355954155_9Battery Volts for Cabinet (Battery Cabinet 9)VDCRead
AV3355968527_9Battery Current for Cabinet (Battery Cabinet 9)A DCRead
AV3355974156_9Battery Temperature for Cabinet (Battery Cabinet 9)°CRead
AV8355974156_9_deg_FBattery Temperature for Cabinet (Battery Cabinet 9)°FRead
AV3355988528_9Battery Cabinet Capacity (Battery Cabinet 9)%Read
AV3355998529_9Battery Cabinet Max Cell Voltage (Battery Cabinet 9)VDCRead
AV3356008530_9Battery Cabinet Min Cell Voltage (Battery Cabinet 9)VDCRead
AV3356018531_9Battery Cabinet Highest Cell Temperature (Battery Cabinet 9)°CRead
AV8356018531_9_deg_FBattery Cabinet Highest Cell Temperature (Battery Cabinet 9)°FRead
AV3356028532_9Battery Cabinet Lowest Cell Temperature (Battery Cabinet 9)°CRead
AV8356028532_9_deg_FBattery Cabinet Lowest Cell Temperature (Battery Cabinet 9)°FRead
AV3356134962_9_1Cell Voltage (Battery Cabinet 9 Battery Cell In Cabinet 1)VDCRead
AV3356144963_9_1Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 1)°CRead
AV8356144963_9_1_deg_FCell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 1)°FRead
AV3356155443_9_1Internal Resistance Value (Battery Cabinet 9 Battery Cell In Cabinet 1)milliOhmRead
AV3356264962_9_2Cell Voltage (Battery Cabinet 9 Battery Cell In Cabinet 2)VDCRead
AV3356274963_9_2Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 2)°CRead
AV8356274963_9_2_deg_FCell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 2)°FRead
AV3356285443_9_2Internal Resistance Value (Battery Cabinet 9 Battery Cell In Cabinet 2)milliOhmRead
AV3382004962_9_200Cell Voltage (Battery Cabinet 9 Battery Cell In Cabinet 200)VDCRead
AV3382014963_9_200Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 200)°CRead
AV8382014963_9_200_deg_FCell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 200)°FRead
AV3382025443_9_200Internal Resistance Value (Battery Cabinet 9 Battery Cell In Cabinet 200)milliOhmRead
AV3382135844_9_1Battery Module Temperature (Battery Cabinet 9 Battery Module 1)°CRead
AV8382135844_9_1_deg_FBattery Module Temperature (Battery Cabinet 9 Battery Module 1)°FRead
AV3382248571_9_1_1Battery Module Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)VDCRead
AV3382258572_9_1_1Battery Module Current (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)A DCRead
AV3382268573_9_1_1Battery Module State Of Charge (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)%Read
AV3382278574_9_1_1Battery Module Max Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)VDCRead
AV3382288575_9_1_1Battery Module Min Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)VDCRead
AV3382298576_9_1_1Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)°CRead
AV8382298576_9_1_1_deg_FBattery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)°FRead
AV3382308577_9_1_1Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)°CRead
AV8382308577_9_1_1_deg_FBattery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)°FRead
AV3382428593_9_1_1Battery Cell Voltage (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 1)VDCRead
AV3382438570_9_1_1Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 1)°CRead
AV8382438570_9_1_1_deg_FBattery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 1)°FRead
AV3382548593_9_1_2Battery Cell Voltage (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 2)VDCRead
AV3382558570_9_1_2Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 2)°CRead
AV8382558570_9_1_2_deg_FBattery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 2)°FRead
AV3394308593_9_1_100Battery Cell Voltage (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 100)VDCRead
AV3394318570_9_1_100Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 100)°CRead
AV8394318570_9_1_100_deg_FBattery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 100)°FRead
AV3394415844_9_2Battery Module Temperature (Battery Cabinet 9 Battery Module 2)°CRead
AV8394415844_9_2_deg_FBattery Module Temperature (Battery Cabinet 9 Battery Module 2)°FRead
AV3394528571_9_2_1Battery Module Voltage (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)VDCRead
AV3394538572_9_2_1Battery Module Current (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)A DCRead
AV3394548573_9_2_1Battery Module State Of Charge (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)%Read
AV3394558574_9_2_1Battery Module Max Cell Voltage (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)VDCRead
AV3394568575_9_2_1Battery Module Min Cell Voltage (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)VDCRead
AV3394578576_9_2_1Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)°CRead
AV8394578576_9_2_1_deg_FBattery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)°FRead
AV3394588577_9_2_1Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)°CRead
AV8394588577_9_2_1_deg_FBattery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)°FRead
AV3394708593_9_2_1Battery Cell Voltage (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 1)VDCRead
AV3394718570_9_2_1Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 1)°CRead
AV8394718570_9_2_1_deg_FBattery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 1)°FRead
AV3394828593_9_2_2Battery Cell Voltage (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 2)VDCRead
AV3394838570_9_2_2Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 2)°CRead
AV8394838570_9_2_2_deg_FBattery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 2)°FRead
AV3406588593_9_2_100Battery Cell Voltage (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 100)VDCRead
AV3406598570_9_2_100Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 100)°CRead
AV8406598570_9_2_100_deg_FBattery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 100)°FRead
AV3762815844_9_32Battery Module Temperature (Battery Cabinet 9 Battery Module 32)°CRead
AV8762815844_9_32_deg_FBattery Module Temperature (Battery Cabinet 9 Battery Module 32)°FRead
AV3762928571_9_32_1Battery Module Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)VDCRead
AV3762938572_9_32_1Battery Module Current (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)A DCRead
AV3762948573_9_32_1Battery Module State Of Charge (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)%Read
AV3762958574_9_32_1Battery Module Max Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)VDCRead
AV3762968575_9_32_1Battery Module Min Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)VDCRead
AV3762978576_9_32_1Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)°CRead
AV8762978576_9_32_1_deg_FBattery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)°FRead
AV3762988577_9_32_1Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)°CRead
AV8762988577_9_32_1_deg_FBattery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)°FRead
AV3763108593_9_32_1Battery Cell Voltage (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 1)VDCRead
AV3763118570_9_32_1Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 1)°CRead
AV8763118570_9_32_1_deg_FBattery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 1)°FRead
AV3763228593_9_32_2Battery Cell Voltage (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 2)VDCRead
AV3763238570_9_32_2Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 2)°CRead
AV8763238570_9_32_2_deg_FBattery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 2)°FRead
AV3774988593_9_32_100Battery Cell Voltage (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 100)VDCRead
AV3774998570_9_32_100Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 100)°CRead
AV8774998570_9_32_100_deg_FBattery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 100)°FRead
AV3775094900_1String Overall Voltage (Battery String 1)VDCRead
AV3775104901_1String Current (Battery String 1)A DCRead
AV3775118549_1Battery String Temperature (Battery String 1)°CRead
AV8775118549_1_deg_FBattery String Temperature (Battery String 1)°FRead
AV3775128550_1Battery String State Of Charge (Battery String 1)%Read
AV3775138551_1Battery String Max Cell Voltage (Battery String 1)VDCRead
AV3775148552_1Battery String Min Cell Voltage (Battery String 1)VDCRead
AV3775158553_1Battery String Highest Cell Temperature (Battery String 1)°CRead
AV8775158553_1_deg_FBattery String Highest Cell Temperature (Battery String 1)°FRead
AV3775168554_1Battery String Lowest Cell Temperature (Battery String 1)°CRead
AV8775168554_1_deg_FBattery String Lowest Cell Temperature (Battery String 1)°FRead
AV3775278568_1_1Battery Cell Voltage (Battery String 1 Battery Cell In String 1)VDCRead
AV3775288569_1_1Battery Cell Temperature (Battery String 1 Battery Cell In String 1)°CRead
AV8775288569_1_1_deg_FBattery Cell Temperature (Battery String 1 Battery Cell In String 1)°FRead
AV3775398568_1_2Battery Cell Voltage (Battery String 1 Battery Cell In String 2)VDCRead
AV3775408569_1_2Battery Cell Temperature (Battery String 1 Battery Cell In String 2)°CRead
AV8775408569_1_2_deg_FBattery Cell Temperature (Battery String 1 Battery Cell In String 2)°FRead
AV3787158568_1_100Battery Cell Voltage (Battery String 1 Battery Cell In String 100)VDCRead
AV3787168569_1_100Battery Cell Temperature (Battery String 1 Battery Cell In String 100)°CRead
AV8787168569_1_100_deg_FBattery Cell Temperature (Battery String 1 Battery Cell In String 100)°FRead
AV3787274900_2String Overall Voltage (Battery String 2)VDCRead
AV3787284901_2String Current (Battery String 2)A DCRead
AV3787298549_2Battery String Temperature (Battery String 2)°CRead
AV8787298549_2_deg_FBattery String Temperature (Battery String 2)°FRead
AV3787308550_2Battery String State Of Charge (Battery String 2)%Read
AV3787318551_2Battery String Max Cell Voltage (Battery String 2)VDCRead
AV3787328552_2Battery String Min Cell Voltage (Battery String 2)VDCRead
AV3787338553_2Battery String Highest Cell Temperature (Battery String 2)°CRead
AV8787338553_2_deg_FBattery String Highest Cell Temperature (Battery String 2)°FRead
AV3787348554_2Battery String Lowest Cell Temperature (Battery String 2)°CRead
AV8787348554_2_deg_FBattery String Lowest Cell Temperature (Battery String 2)°FRead
AV3787458568_2_1Battery Cell Voltage (Battery String 2 Battery Cell In String 1)VDCRead
AV3787468569_2_1Battery Cell Temperature (Battery String 2 Battery Cell In String 1)°CRead
AV8787468569_2_1_deg_FBattery Cell Temperature (Battery String 2 Battery Cell In String 1)°FRead
AV3787578568_2_2Battery Cell Voltage (Battery String 2 Battery Cell In String 2)VDCRead
AV3787588569_2_2Battery Cell Temperature (Battery String 2 Battery Cell In String 2)°CRead
AV8787588569_2_2_deg_FBattery Cell Temperature (Battery String 2 Battery Cell In String 2)°FRead
AV3799338568_2_100Battery Cell Voltage (Battery String 2 Battery Cell In String 100)VDCRead
AV3799348569_2_100Battery Cell Temperature (Battery String 2 Battery Cell In String 100)°CRead
AV8799348569_2_100_deg_FBattery Cell Temperature (Battery String 2 Battery Cell In String 100)°FRead
AV3860354900_8String Overall Voltage (Battery String 8)VDCRead
AV3860364901_8String Current (Battery String 8)A DCRead
AV3860378549_8Battery String Temperature (Battery String 8)°CRead
AV8860378549_8_deg_FBattery String Temperature (Battery String 8)°FRead
AV3860388550_8Battery String State Of Charge (Battery String 8)%Read
AV3860398551_8Battery String Max Cell Voltage (Battery String 8)VDCRead
AV3860408552_8Battery String Min Cell Voltage (Battery String 8)VDCRead
AV3860418553_8Battery String Highest Cell Temperature (Battery String 8)°CRead
AV8860418553_8_deg_FBattery String Highest Cell Temperature (Battery String 8)°FRead
AV3860428554_8Battery String Lowest Cell Temperature (Battery String 8)°CRead
AV8860428554_8_deg_FBattery String Lowest Cell Temperature (Battery String 8)°FRead
AV3860538568_8_1Battery Cell Voltage (Battery String 8 Battery Cell In String 1)VDCRead
AV3860548569_8_1Battery Cell Temperature (Battery String 8 Battery Cell In String 1)°CRead
AV8860548569_8_1_deg_FBattery Cell Temperature (Battery String 8 Battery Cell In String 1)°FRead
AV3860658568_8_2Battery Cell Voltage (Battery String 8 Battery Cell In String 2)VDCRead
AV3860668569_8_2Battery Cell Temperature (Battery String 8 Battery Cell In String 2)°CRead
AV8860668569_8_2_deg_FBattery Cell Temperature (Battery String 8 Battery Cell In String 2)°FRead
AV3872418568_8_100Battery Cell Voltage (Battery String 8 Battery Cell In String 100)VDCRead
AV3872428569_8_100Battery Cell Temperature (Battery String 8 Battery Cell In String 100)°CRead
AV8872428569_8_100_deg_FBattery Cell Temperature (Battery String 8 Battery Cell In String 100)°FRead
MV14771_1Rectifier Isolation BreakerRead1=Open, 2=Close, 3=Not Installed
MV124770_1Bypass Isolation BreakerRead1=Open, 2=Close, 3=Not Installed
MV134772_1Maintenance Bypass BreakerRead1=Open, 2=Close, 3=Not Installed
MV244775_1Module Output BreakerRead1=Open, 2=Close, 3=Not Installed
MV254773_1Maintenance Isolation BreakerRead1=Open, 2=Close, 3=Not Installed
MV368493_1System Control Card Operating Status (System Control Card 1)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV478493_2System Control Card Operating Status (System Control Card 2)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV588500_1Bypass Module Operating StatusRead1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV594736_1Static Bypass SwitchRead1=off, 2=on
MV705833_1Module Operating Status (Power Module 1)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV716437_1Power Module Sleep Status (Power Module 1)Read1=Sleeping, 2=Not Sleeping
MV824748_1_1Rectifier Status (Power Module 1 Rectifier 1)Read1=off, 2=on
MV935864_1_1Inverter Status (Power Module 1 Inverter 1)Read1=Inverter Inactive, 2=Inverter Active
MV1046256_1_1Charger On/Off State (Power Module 1 Charger 1)Read1=off, 2=on
MV1158509_1_1Discharger On/Off Status (Power Module 1 Discharger 1)Read1=off, 2=on
MV1265833_2Module Operating Status (Power Module 2)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV1276437_2Power Module Sleep Status (Power Module 2)Read1=Sleeping, 2=Not Sleeping
MV1384748_2_1Rectifier Status (Power Module 2 Rectifier 1)Read1=off, 2=on
MV1495864_2_1Inverter Status (Power Module 2 Inverter 1)Read1=Inverter Inactive, 2=Inverter Active
MV1606256_2_1Charger On/Off State (Power Module 2 Charger 1)Read1=off, 2=on
MV1718509_2_1Discharger On/Off Status (Power Module 2 Discharger 1)Read1=off, 2=on
MV5745833_10Module Operating Status (Power Module 10)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV5756437_10Power Module Sleep Status (Power Module 10)Read1=Sleeping, 2=Not Sleeping
MV5864748_10_1Rectifier Status (Power Module 10 Rectifier 1)Read1=off, 2=on
MV5975864_10_1Inverter Status (Power Module 10 Inverter 1)Read1=Inverter Inactive, 2=Inverter Active
MV6086256_10_1Charger On/Off State (Power Module 10 Charger 1)Read1=off, 2=on
MV6198509_10_1Discharger On/Off Status (Power Module 10 Discharger 1)Read1=off, 2=on
MV6308594_1MMS UPS Loading StatusRead1=Load on Other Module, 2=Load Off, 3=Load on Inverter, 4=Load on Bypass, 5=Load on Maintenance Bypass, 6=Load on Battery, 7=Load on Shared Source
MV6418275_1Application Mode For UPSRead1=UPS Mode, 2=Frequency Converter Mode, 3=Intelligent Paralleling Mode, 4=Intelligent Paralleling Mode Demo, 5=ECO Mode, 6=Intelligent ECO Mode, 7=Intelligent ECO Mode Demo, 8=Testing Mode, 9=Regen Mode, 10=Power Conditioner Mode, 11=Frequency Converter Mode without Battery, 12=Dynamic Online Mode, 13=Dynamic Online Mode Demo
MV6428595_1UPS Loading StatusRead1=Load on Other Module, 2=Load Off, 3=Load on Inverter, 4=Load on Bypass, 5=Load on Maintenance Bypass, 6=Load on Battery, 7=Load on Shared Source
MVmin6434123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MV6548330_1Battery typeRead1=VRLA, 2=Lithium Battery
MV6554871_1UPS Battery StatusRead1=Unknown, 2=Normal, 3=Low, 4=Depleted
MV6565799_1Battery isRead1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off)
MV6575803_1Automatic Battery TestRead1=disabled, 2=enabled
MV6688607_1Battery Cabinet Type (Battery Cabinet 1)Read1=Internal, 2=External
MV6698533_1Battery Cabinet Operating Status (Battery Cabinet 1)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV6708534_1Battery Cabinet Circuit Breaker Status (Battery Cabinet 1)Read1=Open, 2=Close, 3=Not Installed
MV6718535_1Battery Cabinet Charge Disconnect Status (Battery Cabinet 1)Read1=Open, 2=Close, 3=Not Installed
MV6728536_1Battery Cabinet Discharge Disconnect Status (Battery Cabinet 1)Read1=Open, 2=Close, 3=Not Installed
MV6835834_1_1Module Operating Status (Battery Cabinet 1 Battery Module 1)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV6848578_1_1Battery Module Disconnect Status (Battery Cabinet 1 Battery Module 1)Read1=Open, 2=Close, 3=Not Installed
MV6955834_1_2Module Operating Status (Battery Cabinet 1 Battery Module 2)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV6968578_1_2Battery Module Disconnect Status (Battery Cabinet 1 Battery Module 2)Read1=Open, 2=Close, 3=Not Installed
MV10555834_1_32Module Operating Status (Battery Cabinet 1 Battery Module 32)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV10568578_1_32Battery Module Disconnect Status (Battery Cabinet 1 Battery Module 32)Read1=Open, 2=Close, 3=Not Installed
MV10678607_2Battery Cabinet Type (Battery Cabinet 2)Read1=Internal, 2=External
MV10688533_2Battery Cabinet Operating Status (Battery Cabinet 2)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV10698534_2Battery Cabinet Circuit Breaker Status (Battery Cabinet 2)Read1=Open, 2=Close, 3=Not Installed
MV10708535_2Battery Cabinet Charge Disconnect Status (Battery Cabinet 2)Read1=Open, 2=Close, 3=Not Installed
MV10718536_2Battery Cabinet Discharge Disconnect Status (Battery Cabinet 2)Read1=Open, 2=Close, 3=Not Installed
MV10825834_2_1Module Operating Status (Battery Cabinet 2 Battery Module 1)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV10838578_2_1Battery Module Disconnect Status (Battery Cabinet 2 Battery Module 1)Read1=Open, 2=Close, 3=Not Installed
MV10945834_2_2Module Operating Status (Battery Cabinet 2 Battery Module 2)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV10958578_2_2Battery Module Disconnect Status (Battery Cabinet 2 Battery Module 2)Read1=Open, 2=Close, 3=Not Installed
MV14545834_2_32Module Operating Status (Battery Cabinet 2 Battery Module 32)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV14558578_2_32Battery Module Disconnect Status (Battery Cabinet 2 Battery Module 32)Read1=Open, 2=Close, 3=Not Installed
MV38608607_9Battery Cabinet Type (Battery Cabinet 9)Read1=Internal, 2=External
MV38618533_9Battery Cabinet Operating Status (Battery Cabinet 9)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV38628534_9Battery Cabinet Circuit Breaker Status (Battery Cabinet 9)Read1=Open, 2=Close, 3=Not Installed
MV38638535_9Battery Cabinet Charge Disconnect Status (Battery Cabinet 9)Read1=Open, 2=Close, 3=Not Installed
MV38648536_9Battery Cabinet Discharge Disconnect Status (Battery Cabinet 9)Read1=Open, 2=Close, 3=Not Installed
MV38755834_9_1Module Operating Status (Battery Cabinet 9 Battery Module 1)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV38768578_9_1Battery Module Disconnect Status (Battery Cabinet 9 Battery Module 1)Read1=Open, 2=Close, 3=Not Installed
MV38875834_9_2Module Operating Status (Battery Cabinet 9 Battery Module 2)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV38888578_9_2Battery Module Disconnect Status (Battery Cabinet 9 Battery Module 2)Read1=Open, 2=Close, 3=Not Installed
MV42475834_9_32Module Operating Status (Battery Cabinet 9 Battery Module 32)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV42488578_9_32Battery Module Disconnect Status (Battery Cabinet 9 Battery Module 32)Read1=Open, 2=Close, 3=Not Installed
MV42598555_1Battery String Operating Status (Battery String 1)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV42608556_1Battery String Charge Disconnect Status (Battery String 1)Read1=Open, 2=Close, 3=Not Installed
MV42618557_1Battery String Discharge Disconnect Status (Battery String 1)Read1=Open, 2=Close, 3=Not Installed
MV42728555_2Battery String Operating Status (Battery String 2)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV42738556_2Battery String Charge Disconnect Status (Battery String 2)Read1=Open, 2=Close, 3=Not Installed
MV42748557_2Battery String Discharge Disconnect Status (Battery String 2)Read1=Open, 2=Close, 3=Not Installed
MV43508555_8Battery String Operating Status (Battery String 8)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV43518556_8Battery String Charge Disconnect Status (Battery String 8)Read1=Open, 2=Close, 3=Not Installed
MV43528557_8Battery String Discharge Disconnect Status (Battery String 8)Read1=Open, 2=Close, 3=Not Installed
Object ID lookup: Vertiv Liebert APM2 UPS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert APM2 UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert APM2 UPS

How many BACnet points does the Vertiv Liebert APM2 UPS have?

This list has 845 BACnet objects: 409 analog values, 359 binary values, 77 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert APM2 UPS BACnet points are writable?

1 of the 845 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert APM2 UPS BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert APM2 UPS?

Start with MV 643 4123_1 (Normal, warning or alarm state); AV 267 4150_1 (Estimated battery runtime, min); AV 77 4208_1 (Output power, kW); AV 1 4097_1 (Input voltage, V); AV 55 4201_1 (Output voltage, V); AV 61 4204_1 (Output current, A); BV 939 4168_1 (Load is on battery); BV 909 4300_1 (Internal communication lost).

How do I check these points on the real Liebert APM2 UPS?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.