UPS (uninterruptible power supply) · BACnet points list

Vertiv Liebert EXL S1 UPS BACnet points list

Updated 6 November 2026

Short answer

The Liebert EXL S1 UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.

This page lists 254 BACnet objects for the Vertiv Liebert EXL S1 UPS — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert EXL S1 UPS
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
254 (1 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
EXL S1, Liebert EXL S1, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 254 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert EXL S1 UPS

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 144123_1Normal, warning or alarm stateRead
MV 165971_1UPS operating stateRead
MV 134872_1Load on inverter, bypass or batteryRead
AV 1454150_1Estimated battery runtime, minRead
AV 504096_1Input voltage, VRead
AV 2474385_1Output voltage, VRead
AV 2534204_1Output current, ARead
BV 404168_1Load is on batteryRead
BV 524300_1Internal communication lostRead

Network setup

Watch out for

Vertiv Liebert EXL S1 UPS BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

254 of 254 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert EXL S1 UPS BACnet Points List
DescriptionStates
BV14325_1Backfeed Breaker OpenReadActive = alarm
BV25973_1Input Breaker OpenReadActive = alarm
BV35975_1Output Breaker OpenReadActive = alarm
BV45977_1Battery Breaker OpenReadActive = alarm
BV55976_1Maintenance Bypass Breaker ClosedReadActive = alarm
BV64176_1Battery Circuit Breaker 1 OpenReadActive = alarm
BV74179_1Battery Circuit Breaker 2 OpenReadActive = alarm
BV84182_1Battery Circuit Breaker 3 OpenReadActive = alarm
BV94185_1Battery Circuit Breaker 4 OpenReadActive = alarm
BV104188_1Battery Circuit Breaker 5 OpenReadActive = alarm
BV114191_1Battery Circuit Breaker 6 OpenReadActive = alarm
BV124194_1Battery Circuit Breaker 7 OpenReadActive = alarm
BV134197_1Battery Circuit Breaker 8 OpenReadActive = alarm
BV144141_1Bypass Breaker ClosedReadActive = alarm
BV155982_1Bypass Breaker (SBB) OpenReadActive = alarm
BV166350_1General FaultReadActive = alarm
BV176353_1General WarningReadActive = alarm
BV184215_1System Output OffReadActive = alarm
BV194298_1UPS Output on BypassReadActive = alarm
BV205807_1Output Off PendingReadActive = alarm
BV216357_1System Restart PendingReadActive = alarm
BV226333_1Bypass out of syncReadActive = alarm
BV234389_1System Output FaultReadActive = alarm
BV244213_1System Shutdown - EPOReadActive = alarm
BV255808_1System Shutdown - Output ShortReadActive = alarm
BV265970_1Ground FaultReadActive = alarm
BV274122_1System Input Power ProblemReadActive = alarm
BV285957_1Bypass Input Voltage FaultReadActive = alarm
BV295798_1Bypass OverloadReadActive = alarm
BV305960_1Inverter OverloadReadActive = alarm
BV314147_1System Input Current LimitReadActive = alarm
BV324135_1Bypass Not AvailableReadActive = alarm
BV334143_1Bypass Static Switch UnavailableReadActive = alarm
BV344295_1Rectifier FailureReadActive = alarm
BV354233_1Inverter FailureReadActive = alarm
BV366254_1Charger FailureReadActive = alarm
BV376253_1Booster FailureReadActive = alarm
BV385154_1DC Bus AbnormalReadActive = alarm
BV394222_1Battery Ground FaultReadActive = alarm
BVmin404168_1Battery DischargingReadActive = alarm
BV416354_1Battery ChargingReadActive = alarm
BV424162_1Battery LowReadActive = alarm
BV434322_1Battery Test PassedReadActive = alarm
BV444323_1Battery Test FailedReadActive = alarm
BV454172_1Battery Auto Test In ProgressReadActive = alarm
BV464171_1Battery Manual Test In ProgressReadActive = alarm
BV474311_1System Fan FailureReadActive = alarm
BV484440_1Fuse FailureReadActive = alarm
BV494310_1Equipment Over TemperatureReadActive = alarm
BV506180_1Battery Under VoltageReadActive = alarm
BV515806_1Output OverloadReadActive = alarm
BVmin524300_1Internal Communications FailureReadActive = alarm
BV536356_1Battery Circuit OpenReadActive = alarm
BV548166_1BIB Battery Breaker Power Supply FailureReadActive = alarm
BV558179_1Battery Management System Power Supply FailureReadActive = alarm
BV568194_1Battery Management System Rack is Offline WarningReadActive = alarm
BV578195_1Battery Management System General WarningReadActive = alarm
BV588196_1Battery Management System FaultReadActive = alarm
BV598197_1Battery Management System End-Of-Discharge WarningReadActive = alarm
BV608290_1MOB Aux Sensing FaultReadActive = alarm
BV618294_1SMPS Input Power Supply FailureReadActive = alarm
BV628295_1Rectifier off due to fan power not availableReadActive = alarm
BV638470_1SMS Stop Inverter InhibitReadActive = alarm
BV648471_1Unit In Special Capacity ModeReadActive = alarm
BV658472_1Rectifier Overcurrent WarningReadActive = alarm
AV14293_1System Date and TimeSecs since Epoch (UTC)Write
AV114264_1_1Output Apparent Power RatingkVARead
AV124103_1_1System Input Nominal FrequencyHzRead
AV134102_1_1System Input Nominal VoltageVRead
AV144261_1_1System Output Nominal FrequencyHzRead
AV154260_1_1System Output Nominal VoltageVRead
AV164104_1_1System Input Nominal CurrentARead
AV266317_1_1Firmware version (DSP FW Version 1)Read
AV376317_1_2Firmware version (DSP FW Version 2)Read
AV416317_1_3Firmware version (DSP FW Version 3)Read
AV484120_1System Input Black Out CountRead
AV494105_1System Input FrequencyHzRead
AVmin504096_1System Input RMS A-NVRead
AV514098_1System Input RMS B-NVRead
AV524100_1System Input RMS C-NVRead
AV534097_1System Input RMS A-BVRead
AV544099_1System Input RMS B-CVRead
AV554101_1System Input RMS C-AVRead
AV564113_1System Input RMS Current Phase AARead
AV574114_1System Input RMS Current Phase BARead
AV584115_1System Input RMS Current Phase CARead
AV596318_1System Input Power Phase AkWRead
AV606319_1System Input Power Phase BkWRead
AV616320_1System Input Power Phase CkWRead
AV626321_1UPS DC input voltageVDCRead
AV638093_1System Input Apparent Power Phs AkVARead
AV648094_1System Input Apparent Power Phs BkVARead
AV658095_1System Input Apparent Power Phs CkVARead
AV736245_1_1Rectifier Phase A Temperature sensor (Rectifier Module Temperature 1)°CRead
AV100736245_1_1_deg_FRectifier Phase A Temperature sensor (Rectifier Module Temperature 1)°FRead
AV746246_1_1Rectifier Phase B Temperature sensor (Rectifier Module Temperature 1)°CRead
AV100746246_1_1_deg_FRectifier Phase B Temperature sensor (Rectifier Module Temperature 1)°FRead
AV756247_1_1Rectifier Phase C Temperature sensor (Rectifier Module Temperature 1)°CRead
AV100756247_1_1_deg_FRectifier Phase C Temperature sensor (Rectifier Module Temperature 1)°FRead
AV866245_1_2Rectifier Phase A Temperature sensor (Rectifier Module Temperature 2)°CRead
AV100866245_1_2_deg_FRectifier Phase A Temperature sensor (Rectifier Module Temperature 2)°FRead
AV876246_1_2Rectifier Phase B Temperature sensor (Rectifier Module Temperature 2)°CRead
AV100876246_1_2_deg_FRectifier Phase B Temperature sensor (Rectifier Module Temperature 2)°FRead
AV886247_1_2Rectifier Phase C Temperature sensor (Rectifier Module Temperature 2)°CRead
AV100886247_1_2_deg_FRectifier Phase C Temperature sensor (Rectifier Module Temperature 2)°FRead
AV1126245_1_4Rectifier Phase A Temperature sensor (Rectifier Module Temperature 4)°CRead
AV101126245_1_4_deg_FRectifier Phase A Temperature sensor (Rectifier Module Temperature 4)°FRead
AV1136246_1_4Rectifier Phase B Temperature sensor (Rectifier Module Temperature 4)°CRead
AV101136246_1_4_deg_FRectifier Phase B Temperature sensor (Rectifier Module Temperature 4)°FRead
AV1146247_1_4Rectifier Phase C Temperature sensor (Rectifier Module Temperature 4)°CRead
AV101146247_1_4_deg_FRectifier Phase C Temperature sensor (Rectifier Module Temperature 4)°FRead
AV1254131_1Bypass Input FrequencyHzRead
AV1264128_1Bypass Input Voltage RMS A-NVRead
AV1274129_1Bypass Input Voltage RMS B-NVRead
AV1284130_1Bypass Input Voltage RMS C-NVRead
AV1294125_1Bypass Input Voltage RMS A-BVRead
AV1304126_1Bypass Input Voltage RMS B-CVRead
AV1314127_1Bypass Input Voltage RMS C-AVRead
AV1325570_1Bypass Input RMS Current Phase AARead
AV1335571_1Bypass Input RMS Current Phase BARead
AV1345572_1Bypass Input RMS Current Phase CARead
AV1488048_1Bypass Input Power Factor Phase ARead
AV1498049_1Bypass Input Power Factor Phase BRead
AV1508050_1Bypass Input Power Factor Phase CRead
AV1516325_1Bypass Power Phase AkWRead
AV1526326_1Bypass Power Phase BkWRead
AV1536327_1Bypass Power Phase CkWRead
AV1424155_1Battery Volts for CabinetVDCRead
AV1434149_1DC Bus CurrentA DCRead
AV1444151_1Battery Discharge TimesRead
AVmin1454150_1Battery Time RemainingminRead
AV1464153_1Battery Percentage Charge%Read
AV1474156_1Battery Temperature for Cabinet°CRead
AV101474156_1_deg_FBattery Temperature for Cabinet°FRead
AV1585963_1Booster-Charger Temperature (Booster Charger Module Temperature 1)°CRead
AV101585963_1_deg_FBooster-Charger Temperature (Booster Charger Module Temperature 1)°FRead
AV1695963_2Booster-Charger Temperature (Booster Charger Module Temperature 2)°CRead
AV101695963_2_deg_FBooster-Charger Temperature (Booster Charger Module Temperature 2)°FRead
AV2355963_8Booster-Charger Temperature (Booster Charger Module Temperature 8)°CRead
AV102355963_8_deg_FBooster-Charger Temperature (Booster Charger Module Temperature 8)°FRead
AV2464207_1System Output FrequencyHzRead
AVmin2474385_1System Output Voltage RMS A-NVRead
AV2484386_1System Output Voltage RMS B-NVRead
AV2494387_1System Output Voltage RMS C-NVRead
AV2504201_1System Output Voltage RMS A-BVRead
AV2514202_1System Output Voltage RMS B-CVRead
AV2524203_1System Output Voltage RMS C-AVRead
AVmin2534204_1System Output RMS Current Phs AARead
AV2544205_1System Output RMS Current Phs BARead
AV2554206_1System Output RMS Current Phs CARead
AV2565859_1System Output Power Phase AkWRead
AV2575860_1System Output Power Phase BkWRead
AV2585959_1System Output Power Phase CkWRead
AV2594223_1System Output Pct Power Phase A%Read
AV2604224_1System Output Pct Power Phase B%Read
AV2614225_1System Output Pct Power Phase C%Read
AV2625868_1System Output Apparent Power Phs AkVARead
AV2635869_1System Output Apparent Power Phs BkVARead
AV2645870_1System Output Apparent Power Phs CkVARead
AV2655574_1Outside Air Temperature°CRead
AV102655574_1_deg_FOutside Air Temperature°FRead
AV2664265_1Output Real Power RatingkWRead
AV2674210_1System Output Power Factor Phs ARead
AV2684211_1System Output Power Factor Phs BRead
AV2694212_1System Output Power Factor Phs CRead
AV2776249_1_1Inverter Phase A Temperature sensor (Inverter Module Temperature 1)°CRead
AV102776249_1_1_deg_FInverter Phase A Temperature sensor (Inverter Module Temperature 1)°FRead
AV2786250_1_1Inverter Phase B Temperature sensor (Inverter Module Temperature 1)°CRead
AV102786250_1_1_deg_FInverter Phase B Temperature sensor (Inverter Module Temperature 1)°FRead
AV2796251_1_1Inverter Phase C temperature sensor (Inverter Module Temperature 1)°CRead
AV102796251_1_1_deg_FInverter Phase C temperature sensor (Inverter Module Temperature 1)°FRead
AV2906249_1_2Inverter Phase A Temperature sensor (Inverter Module Temperature 2)°CRead
AV102906249_1_2_deg_FInverter Phase A Temperature sensor (Inverter Module Temperature 2)°FRead
AV2916250_1_2Inverter Phase B Temperature sensor (Inverter Module Temperature 2)°CRead
AV102916250_1_2_deg_FInverter Phase B Temperature sensor (Inverter Module Temperature 2)°FRead
AV2926251_1_2Inverter Phase C temperature sensor (Inverter Module Temperature 2)°CRead
AV102926251_1_2_deg_FInverter Phase C temperature sensor (Inverter Module Temperature 2)°FRead
AV3166249_1_4Inverter Phase A Temperature sensor (Inverter Module Temperature 4)°CRead
AV103166249_1_4_deg_FInverter Phase A Temperature sensor (Inverter Module Temperature 4)°FRead
AV3176250_1_4Inverter Phase B Temperature sensor (Inverter Module Temperature 4)°CRead
AV103176250_1_4_deg_FInverter Phase B Temperature sensor (Inverter Module Temperature 4)°FRead
AV3186251_1_4Inverter Phase C temperature sensor (Inverter Module Temperature 4)°CRead
AV103186251_1_4_deg_FInverter Phase C temperature sensor (Inverter Module Temperature 4)°FRead
AV3294292_1Total System Operating TimehRead
AV3508291_1Critical Load GS Battery Energy AvailablekWhRead
AV3518292_1Under Freq GS Battery Energy AvailablekWhRead
AV3528293_1Over Freq GS Battery Energy AvailablekWhRead
AV3818432_1_1Static Switch Fan Speed (Static Switch Fans 1)RPMRead
AV3928432_1_2Static Switch Fan Speed (Static Switch Fans 2)RPMRead
AV4038432_1_3Static Switch Fan Speed (Static Switch Fans 3)RPMRead
AV4148433_1_1_1Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 1 Inverter/Rectifier Phase 1 Inverter/Rectifier Fans 1)RPMRead
AV4258433_1_1_2Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 1 Inverter/Rectifier Phase 1 Inverter/Rectifier Fans 2)RPMRead
AV4588433_1_1_5Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 1 Inverter/Rectifier Phase 1 Inverter/Rectifier Fans 5)RPMRead
AV4698433_1_2_1Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 1 Inverter/Rectifier Phase 2 Inverter/Rectifier Fans 1)RPMRead
AV4808433_1_2_2Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 1 Inverter/Rectifier Phase 2 Inverter/Rectifier Fans 2)RPMRead
AV5138433_1_2_5Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 1 Inverter/Rectifier Phase 2 Inverter/Rectifier Fans 5)RPMRead
AV5248433_1_3_1Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 1 Inverter/Rectifier Phase 3 Inverter/Rectifier Fans 1)RPMRead
AV5358433_1_3_2Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 1 Inverter/Rectifier Phase 3 Inverter/Rectifier Fans 2)RPMRead
AV5688433_1_3_5Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 1 Inverter/Rectifier Phase 3 Inverter/Rectifier Fans 5)RPMRead
AV5798433_2_1_1Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 2 Inverter/Rectifier Phase 1 Inverter/Rectifier Fans 1)RPMRead
AV5908433_2_1_2Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 2 Inverter/Rectifier Phase 1 Inverter/Rectifier Fans 2)RPMRead
AV6238433_2_1_5Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 2 Inverter/Rectifier Phase 1 Inverter/Rectifier Fans 5)RPMRead
AV6348433_2_2_1Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 2 Inverter/Rectifier Phase 2 Inverter/Rectifier Fans 1)RPMRead
AV6458433_2_2_2Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 2 Inverter/Rectifier Phase 2 Inverter/Rectifier Fans 2)RPMRead
AV6788433_2_2_5Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 2 Inverter/Rectifier Phase 2 Inverter/Rectifier Fans 5)RPMRead
AV6898433_2_3_1Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 2 Inverter/Rectifier Phase 3 Inverter/Rectifier Fans 1)RPMRead
AV7008433_2_3_2Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 2 Inverter/Rectifier Phase 3 Inverter/Rectifier Fans 2)RPMRead
AV7338433_2_3_5Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 2 Inverter/Rectifier Phase 3 Inverter/Rectifier Fans 5)RPMRead
AV7448433_3_1_1Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 3 Inverter/Rectifier Phase 1 Inverter/Rectifier Fans 1)RPMRead
AV7558433_3_1_2Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 3 Inverter/Rectifier Phase 1 Inverter/Rectifier Fans 2)RPMRead
AV7888433_3_1_5Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 3 Inverter/Rectifier Phase 1 Inverter/Rectifier Fans 5)RPMRead
AV7998433_3_2_1Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 3 Inverter/Rectifier Phase 2 Inverter/Rectifier Fans 1)RPMRead
AV8108433_3_2_2Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 3 Inverter/Rectifier Phase 2 Inverter/Rectifier Fans 2)RPMRead
AV8438433_3_2_5Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 3 Inverter/Rectifier Phase 2 Inverter/Rectifier Fans 5)RPMRead
AV8548433_3_3_1Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 3 Inverter/Rectifier Phase 3 Inverter/Rectifier Fans 1)RPMRead
AV8658433_3_3_2Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 3 Inverter/Rectifier Phase 3 Inverter/Rectifier Fans 2)RPMRead
AV8988433_3_3_5Inverter/Rectifier Fan Speed (Inverter/Rectifier Module 3 Inverter/Rectifier Phase 3 Inverter/Rectifier Fans 5)RPMRead
AV9098434_1_1Booster Fan Speed (Booster Module 1 Booster Fans 1)RPMRead
AV9208434_1_2Booster Fan Speed (Booster Module 1 Booster Fans 2)RPMRead
AV9538434_1_5Booster Fan Speed (Booster Module 1 Booster Fans 5)RPMRead
AV9648434_2_1Booster Fan Speed (Booster Module 2 Booster Fans 1)RPMRead
AV9758434_2_2Booster Fan Speed (Booster Module 2 Booster Fans 2)RPMRead
AV10088434_2_5Booster Fan Speed (Booster Module 2 Booster Fans 5)RPMRead
AV10198434_3_1Booster Fan Speed (Booster Module 3 Booster Fans 1)RPMRead
AV10308434_3_2Booster Fan Speed (Booster Module 3 Booster Fans 2)RPMRead
AV10638434_3_5Booster Fan Speed (Booster Module 3 Booster Fans 5)RPMRead
MV16316_1UPS manufacturerRead1=Chloride, 2=Masterguard, 3=Oneac, 4=Vertiv, 5=Other
MV24303_1UPS Module TypeRead1=Single Module System, 2=Module (1 + 1), 3=Module (1 + N), 4=Module (N + 1), 5=System Control Cabinet, 6=Main Static Switch
MVmin134872_1UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MVmin144123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MV155961_1Inverter Synchronization SourceRead1=External, 2=Self clock (internal), 3=Output, 4=Bypass
MVmin165971_1UPS Operating ModeRead1=Idle, 2=Double Conversion Mode (VFI), 3=Interactive Mode (VI), 4=Stand-By Mode (VFD), 5=CR Mode (CR), 6=ECO Mode (DIM)
MV175454_1ECO Mode Operation StateRead1=disabled, 2=enabled
MV185972_1Circular Redundancy StatusRead1=Idle, 2=Core Running, 3=Core Sleeping
MV194736_1Static Bypass SwitchRead1=off, 2=on
MV204737_1Bypass Qualification StatusRead1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High
MV216256_1Charger On/Off StateRead1=off, 2=on
MV226255_1Booster On/Off StateRead1=off, 2=on
MV234871_1UPS battery1 statusRead1=Unknown, 2=Normal, 3=Low, 4=Depleted
MV246337_1Bypass StatusRead1=Bypass not present, 2=Bypass on, 3=Bypass off, 4=Bypass fault, 5=Bypass not ready
MV256336_1Inverter StatusRead1=Inverter off, 2=Inverter turning on, 3=Inverter on, 4=Inverter stopped due to Fault, 5=Inverter in Stand By, 6=Inverter Ready and Sync, 7=Inverter Not Ready
MV266338_1Charger StatusRead1=Charger in standby, 2=Charger on, 3=Charger switched off, 4=Charger forced on, 5=Charger stopped due to a fault
MV276335_1Rectifier StatusRead1=Rectifier off, 2=Rectifier turning on, 3=Rectifier on, 4=Rectifier fault
MV384773_1Maintenance Isolation BreakerRead1=Open, 2=Close, 3=Not Installed
MV394853_1System Load Bank BreakerRead1=Open, 2=Close, 3=Not Installed
MV508296_1GS EnabledRead1=Disabled, 2=Enabled
MV518297_1GS PausedRead1=Disabled, 2=Enabled
MV528298_1GS StoppedRead1=Disabled, 2=Enabled
MV538299_1GS Run from Battery for a defined timeRead1=Disabled, 2=Enabled
MV548300_1GS Stop Charging for a defined timeRead1=Disabled, 2=Enabled
MV558301_1GS Stop Charging foreverRead1=Disabled, 2=Enabled
MV568302_1GS Grid SupportRead1=Disabled, 2=Enabled
MV578303_1GS Grid Support ChargingRead1=Disabled, 2=Enabled
MV588304_1GS Grid Support DischargingRead1=Disabled, 2=Enabled
Object ID lookup: Vertiv Liebert EXL S1 UPS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert EXL S1 UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert EXL S1 UPS

How many BACnet points does the Vertiv Liebert EXL S1 UPS have?

This list has 254 BACnet objects: 161 analog values, 65 binary values, 28 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert EXL S1 UPS BACnet points are writable?

1 of the 254 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert EXL S1 UPS BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert EXL S1 UPS?

Start with MV 14 4123_1 (Normal, warning or alarm state); MV 16 5971_1 (UPS operating state); MV 13 4872_1 (Load on inverter, bypass or battery); AV 145 4150_1 (Estimated battery runtime, min); AV 50 4096_1 (Input voltage, V); AV 247 4385_1 (Output voltage, V); AV 253 4204_1 (Output current, A); BV 40 4168_1 (Load is on battery); BV 52 4300_1 (Internal communication lost).

How do I check these points on the real Liebert EXL S1 UPS?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.