Free-cooling chiller · BACnet points list
Vertiv Liebert HPC chiller BACnet points list
Updated 6 November 2026
The Liebert HPC chiller reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Binary Values carry events, Analog Values carry fluid temperatures, setpoints, compressor, pump and power data, and Multi-state Values carry states and controls. Objects are created when the card discovers the chiller, so only fitted options appear.
This page lists 188 BACnet objects for the Vertiv Liebert HPC chiller — 46 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert HPC chiller
- Equipment
- Free-cooling chiller
- Equipment type
- Chillers
- BACnet objects
- 188 (46 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Liebert HPC, HPC chiller, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert HPC chiller
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 62 | 5143_1 | On/off command (1=off, 2=on) | Write |
| AV 72 | 5283_1_1 | Supply fluid temperature setpoint, °C | Write |
| MV 47 | 4717_1 | Acknowledge / reset events | Write |
| MV 59 | 4706_1 | Run / standby / off state | Read |
| MV 58 | 4123_1 | Normal, warning or alarm state | Read |
| AV 164 | 4643_1 | Supply fluid temperature, °C | Read |
| AV 263 | 4097_1 | Input voltage, V | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert HPC chiller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | 5263_1 | Compressor Not Stopping | Read | Active = alarm | |
| BV | 2 | 5604_1 | Compressor Superheat Over Threshold | Read | Active = alarm | |
| BV | 12 | 5269_1_1 | Compressor Hours Exceeded (Compressor 1) | Read | Active = alarm | |
| BV | 13 | 5270_1_1 | Compressor High Head Pressure (Compressor 1) | Read | Active = alarm | |
| BV | 14 | 5271_1_1 | Compressor Low Suction Pressure (Compressor 1) | Read | Active = alarm | |
| BV | 15 | 5272_1_1 | Compressor Thermal Overload (Compressor 1) | Read | Active = alarm | |
| BV | 16 | 5273_1_1 | Compressor Low Oil Pressure (Compressor 1) | Read | Active = alarm | |
| BV | 17 | 5275_1_1 | Compressor Loss of Differential Pressure (Compressor 1) | Read | Active = alarm | |
| BV | 18 | 5513_1_1 | Compressor Capacity Reduced (Compressor 1) | Read | Active = alarm | |
| BV | 19 | 5773_1_1 | Compressor Capacity Normal (Compressor 1) | Read | Active = alarm | |
| BV | 20 | 5774_1_1 | Compressor Contactor Issue (Compressor 1) | Read | Active = alarm | |
| BV | 29 | 5269_1_2 | Compressor Hours Exceeded (Compressor 2) | Read | Active = alarm | |
| BV | 30 | 5270_1_2 | Compressor High Head Pressure (Compressor 2) | Read | Active = alarm | |
| BV | 31 | 5271_1_2 | Compressor Low Suction Pressure (Compressor 2) | Read | Active = alarm | |
| BV | 32 | 5272_1_2 | Compressor Thermal Overload (Compressor 2) | Read | Active = alarm | |
| BV | 33 | 5273_1_2 | Compressor Low Oil Pressure (Compressor 2) | Read | Active = alarm | |
| BV | 34 | 5275_1_2 | Compressor Loss of Differential Pressure (Compressor 2) | Read | Active = alarm | |
| BV | 35 | 5513_1_2 | Compressor Capacity Reduced (Compressor 2) | Read | Active = alarm | |
| BV | 36 | 5773_1_2 | Compressor Capacity Normal (Compressor 2) | Read | Active = alarm | |
| BV | 37 | 5774_1_2 | Compressor Contactor Issue (Compressor 2) | Read | Active = alarm | |
| BV | 263 | 5269_1_4 | Compressor Hours Exceeded (Compressor 4) | Read | Active = alarm | |
| BV | 264 | 5270_1_4 | Compressor High Head Pressure (Compressor 4) | Read | Active = alarm | |
| BV | 265 | 5271_1_4 | Compressor Low Suction Pressure (Compressor 4) | Read | Active = alarm | |
| BV | 266 | 5272_1_4 | Compressor Thermal Overload (Compressor 4) | Read | Active = alarm | |
| BV | 267 | 5273_1_4 | Compressor Low Oil Pressure (Compressor 4) | Read | Active = alarm | |
| BV | 268 | 5275_1_4 | Compressor Loss of Differential Pressure (Compressor 4) | Read | Active = alarm | |
| BV | 269 | 5513_1_4 | Compressor Capacity Reduced (Compressor 4) | Read | Active = alarm | |
| BV | 270 | 5773_1_4 | Compressor Capacity Normal (Compressor 4) | Read | Active = alarm | |
| BV | 271 | 5774_1_4 | Compressor Contactor Issue (Compressor 4) | Read | Active = alarm | |
| BV | 46 | 5277_1 | Condenser Fan Issue (Condenser 1) | Read | Active = alarm | |
| BV | 47 | 5278_1 | Low Condenser Refrigerant Pressure (Condenser 1) | Read | Active = alarm | |
| BV | 48 | 5545_1 | Condenser Max Fan Speed Override (Condenser 1) | Read | Active = alarm | |
| BV | 59 | 5277_2 | Condenser Fan Issue (Condenser 2) | Read | Active = alarm | |
| BV | 60 | 5278_2 | Low Condenser Refrigerant Pressure (Condenser 2) | Read | Active = alarm | |
| BV | 61 | 5545_2 | Condenser Max Fan Speed Override (Condenser 2) | Read | Active = alarm | |
| BV | 67 | 5277_4 | Condenser Fan Issue (Condenser 4) | Read | Active = alarm | |
| BV | 68 | 5278_4 | Low Condenser Refrigerant Pressure (Condenser 4) | Read | Active = alarm | |
| BV | 69 | 5545_4 | Condenser Max Fan Speed Override (Condenser 4) | Read | Active = alarm | |
| BV | 72 | 5280_1 | Low Fluid Pressure | Read | Active = alarm | |
| BV | 73 | 5295_1 | Return Fluid Temp Sensor Issue | Read | Active = alarm | |
| BV | 84 | 4645_1_1 | Supply Fluid Over Temp | Read | Active = alarm | |
| BV | 85 | 4648_1_1 | Supply Fluid Under Temp | Read | Active = alarm | |
| BV | 86 | 4651_1_1 | Supply Fluid Temp Sensor Issue | Read | Active = alarm | |
| BV | 97 | 5297_1 | All Pumps Loss of Flow | Read | Active = alarm | |
| BV | 98 | 4656_1 | Pump 1 Loss of Flow | Read | Active = alarm | |
| BV | 99 | 4659_1 | Pump 2 Loss of Flow | Read | Active = alarm | |
| BV | 110 | 5300_1_1 | Pump Hours Exceeded (Pump 1) | Read | Active = alarm | |
| BV | 121 | 5300_1_2 | Pump Hours Exceeded (Pump 2) | Read | Active = alarm | |
| BV | 132 | 5306_1 | Free Cooling Valve Hours Exceeded | Read | Active = alarm | |
| BV | 133 | 4618_1 | Ambient Air Temperature Sensor Issue | Read | Active = alarm | |
| BV | 144 | 5308_1 | Evaporator Inlet Temp Sensor Issue | Read | Active = alarm | |
| BV | 145 | 5559_1 | Evaporator Return Fluid Over Temp | Read | Active = alarm | |
| BV | 146 | 5560_1 | Evaporator Return Fluid Under Temp | Read | Active = alarm | |
| BV | 157 | 5310_1_1 | Evaporator Fluid Freeze - Auto Reset (Evaporator 1) | Read | Active = alarm | |
| BV | 158 | 5311_1_1 | Evaporator Fluid Freeze - Manual Reset Required (Evaporator 1) | Read | Active = alarm | |
| BV | 159 | 4640_1_1 | Supply Refrigerant Temp Sensor Issue (Evaporator 1) | Read | Active = alarm | |
| BV | 170 | 5310_1_2 | Evaporator Fluid Freeze - Auto Reset (Evaporator 2) | Read | Active = alarm | |
| BV | 171 | 5311_1_2 | Evaporator Fluid Freeze - Manual Reset Required (Evaporator 2) | Read | Active = alarm | |
| BV | 172 | 4640_1_2 | Supply Refrigerant Temp Sensor Issue (Evaporator 2) | Read | Active = alarm | |
| BV | 183 | 4270_1 | Customer Input 1 | Read | Active = alarm | |
| BV | 184 | 4271_1 | Customer Input 2 | Read | Active = alarm | |
| BV | 194 | 4272_1 | Customer Input 3 | Read | Active = alarm | |
| BV | 195 | 4273_1 | Customer Input 4 | Read | Active = alarm | |
| BV | 185 | 5109_1 | Unit On | Read | Active = alarm | |
| BV | 186 | 5110_1 | Unit Off | Read | Active = alarm | |
| BV | 187 | 5120_1 | Master Unit Communication Lost | Read | Active = alarm | |
| BV | 188 | 5315_1 | Subgroup Event Occurred During Communication Loss | Read | Active = alarm | |
| BV | 189 | 5045_1 | Humidifier Control Board Not Detected | Read | Active = alarm | |
| BV | 190 | 5119_1 | RAM Battery Issue | Read | Active = alarm | |
| BV | 191 | 5418_1 | Unit Code Missing | Read | Active = alarm | |
| BV | 192 | 5588_1 | Unspecified General Event | Read | Active = alarm | |
| BV | 193 | 5775_1 | Unit Shutdown Unspecified General Event | Read | Active = alarm | |
| BV | 200 | 5625_1 | EEV Unspecified General Event (EEV 1) | Read | Active = alarm | |
| BV | 210 | 5625_2 | EEV Unspecified General Event (EEV 2) | Read | Active = alarm | |
| BV | 230 | 5625_4 | EEV Unspecified General Event (EEV 4) | Read | Active = alarm | |
| BV | 282 | 5967_1 | Modbus Power Meter Communication Lost (Power Measurement 1) | Read | Active = alarm | |
| BV | 293 | 5967_2 | Modbus Power Meter Communication Lost (Power Measurement 2) | Read | Active = alarm | |
| AV | 1 | 5262_1 | Compressor Shut Down - Ambient Air Low Temp Limit | °C | Write | |
| AV | 10001 | 5262_1_deg_F | Compressor Shut Down - Ambient Air Low Temp Limit | °F | Write | |
| AV | 12 | 5266_1_1 | Compressor Head Pressure (Compressor 1) | bar | Read | |
| AV | 13 | 5267_1_1 | Compressor Hours (Compressor 1) | h | Write | |
| AV | 14 | 5268_1_1 | Compressor Hours Threshold (Compressor 1) | h | Write | |
| AV | 25 | 5266_1_2 | Compressor Head Pressure (Compressor 2) | bar | Read | |
| AV | 26 | 5267_1_2 | Compressor Hours (Compressor 2) | h | Write | |
| AV | 27 | 5268_1_2 | Compressor Hours Threshold (Compressor 2) | h | Write | |
| AV | 215 | 5266_1_4 | Compressor Head Pressure (Compressor 4) | bar | Read | |
| AV | 216 | 5267_1_4 | Compressor Hours (Compressor 4) | h | Write | |
| AV | 217 | 5268_1_4 | Compressor Hours Threshold (Compressor 4) | h | Write | |
| AV | 38 | 5276_1 | Condenser Fan Speed (Condenser 1) | % | Read | |
| AV | 49 | 5276_2 | Condenser Fan Speed (Condenser 2) | % | Read | |
| AV | 55 | 5276_4 | Condenser Fan Speed (Condenser 4) | % | Read | |
| AV | 60 | 5279_1 | Fluid Pressure | bar | Read | |
| AV | 61 | 5281_1 | Fluid Cooling Proportional Band | °C | Write | |
| AV | 10061 | 5281_1_deg_F | Fluid Cooling Proportional Band | °F | Write | |
| AVmin | 72 | 5283_1_1 | Supply Fluid Temp Set Point 1 | °C | Write | |
| AV | 10072 | 5283_1_1_deg_F | Supply Fluid Temp Set Point 1 | °F | Write | |
| AV | 73 | 5284_1_1 | Supply Fluid Temp Set Point 2 | °C | Write | |
| AV | 10073 | 5284_1_1_deg_F | Supply Fluid Temp Set Point 2 | °F | Write | |
| AV | 74 | 5285_1_1 | Supply Fluid Over Temp Alarm Threshold | °C | Write | |
| AV | 10074 | 5285_1_1_deg_F | Supply Fluid Over Temp Alarm Threshold | °F | Write | |
| AV | 75 | 4644_1_1 | Supply Fluid Over Temp Warning Threshold | °C | Write | |
| AV | 10075 | 4644_1_1_deg_F | Supply Fluid Over Temp Warning Threshold | °F | Write | |
| AV | 76 | 5286_1_1 | Supply Fluid Under Temp Warning Threshold | °C | Write | |
| AV | 10076 | 5286_1_1_deg_F | Supply Fluid Under Temp Warning Threshold | °F | Write | |
| AV | 77 | 5287_1_1 | Supply Fluid Under Temp Alarm Threshold | °C | Write | |
| AV | 10077 | 5287_1_1_deg_F | Supply Fluid Under Temp Alarm Threshold | °F | Write | |
| AV | 88 | 5298_1_1 | Pump Hours (Pump 1) | h | Write | |
| AV | 89 | 5299_1_1 | Pump Hours Threshold (Pump 1) | h | Write | |
| AV | 100 | 5298_1_2 | Pump Hours (Pump 2) | h | Write | |
| AV | 101 | 5299_1_2 | Pump Hours Threshold (Pump 2) | h | Write | |
| AV | 112 | 5301_1 | Free Cooling External Temperature Delta | °C | Write | |
| AV | 10112 | 5301_1_deg_F | Free Cooling External Temperature Delta | °F | Write | |
| AV | 113 | 5303_1 | Free Cooling Valve Open Position | % | Read | |
| AV | 114 | 5304_1 | Free Cooling Valve Hours | h | Write | |
| AV | 115 | 5305_1 | Free Cooling Valve Hours Threshold | h | Write | |
| AV | 126 | 5307_1 | Evaporator Return Fluid Temperature | °C | Read | |
| AV | 10126 | 5307_1_deg_F | Evaporator Return Fluid Temperature | °F | Read | |
| AV | 127 | 5555_1 | Evaporator Return Fluid Over Temp Alarm Threshold | °C | Write | |
| AV | 10127 | 5555_1_deg_F | Evaporator Return Fluid Over Temp Alarm Threshold | °F | Write | |
| AV | 128 | 5556_1 | Evaporator Return Fluid Over Temp Warning Threshold | °C | Write | |
| AV | 10128 | 5556_1_deg_F | Evaporator Return Fluid Over Temp Warning Threshold | °F | Write | |
| AV | 129 | 5557_1 | Evaporator Return Fluid Under Temp Warning Threshold | °C | Write | |
| AV | 10129 | 5557_1_deg_F | Evaporator Return Fluid Under Temp Warning Threshold | °F | Write | |
| AV | 130 | 5558_1 | Evaporator Return Fluid Under Temp Alarm Threshold | °C | Write | |
| AV | 10130 | 5558_1_deg_F | Evaporator Return Fluid Under Temp Alarm Threshold | °F | Write | |
| AV | 141 | 5312_1 | Supply Brine Temp Set Point | °C | Write | |
| AV | 10141 | 5312_1_deg_F | Supply Brine Temp Set Point | °F | Write | |
| AV | 152 | 5314_1 | Standby Units | Write | ||
| AV | 163 | 5288_1 | Return Fluid Temperature | °C | Read | |
| AV | 10163 | 5288_1_deg_F | Return Fluid Temperature | °F | Read | |
| AVmin | 164 | 4643_1 | Supply Fluid Temperature | °C | Read | |
| AV | 10164 | 4643_1_deg_F | Supply Fluid Temperature | °F | Read | |
| AV | 165 | 5282_1 | Actual Supply Fluid Temp Set Point | °C | Read | |
| AV | 10165 | 5282_1_deg_F | Actual Supply Fluid Temp Set Point | °F | Read | |
| AV | 166 | 5517_1 | Condenser Inlet Water Temperature | °C | Read | |
| AV | 10166 | 5517_1_deg_F | Condenser Inlet Water Temperature | °F | Read | |
| AV | 167 | 5518_1 | Condenser Outlet Water Temperature | °C | Read | |
| AV | 10167 | 5518_1_deg_F | Condenser Outlet Water Temperature | °F | Read | |
| AV | 168 | 5313_1 | Supply Heated Water Temp Set Point | °C | Write | |
| AV | 10168 | 5313_1_deg_F | Supply Heated Water Temp Set Point | °F | Write | |
| AV | 169 | 5519_1 | Free Cooling Utilization | % | Read | |
| AV | 170 | 5080_1 | Reheat Utilization | % | Read | |
| AV | 171 | 5078_1 | Compressor Utilization | % | Read | |
| AV | 172 | 4594_1 | Ambient Air Temperature | °C | Read | |
| AV | 10172 | 4594_1_deg_F | Ambient Air Temperature | °F | Read | |
| AV | 173 | 5520_1 | Compressor Economizer Utilization | % | Read | |
| AV | 174 | 5521_1 | Condenser Adiabatic Cooling Utilization | % | Read | |
| AV | 185 | 4293_1 | System Date and Time | Write | ||
| AVmin | 263 | 4097_1 | System Input RMS A-B (Power Measurement 1) | V | Read | |
| AV | 264 | 4096_1 | System Input RMS A-N (Power Measurement 1) | V | Read | |
| AV | 265 | 4113_1 | System Input RMS Current Phase A (Power Measurement 1) | A | Read | |
| AV | 266 | 4099_1 | System Input RMS B-C (Power Measurement 1) | V | Read | |
| AV | 267 | 4098_1 | System Input RMS B-N (Power Measurement 1) | V | Read | |
| AV | 268 | 4114_1 | System Input RMS Current Phase B (Power Measurement 1) | A | Read | |
| AV | 269 | 4101_1 | System Input RMS C-A (Power Measurement 1) | V | Read | |
| AV | 270 | 4100_1 | System Input RMS C-N (Power Measurement 1) | V | Read | |
| AV | 271 | 4115_1 | System Input RMS Current Phase C (Power Measurement 1) | A | Read | |
| AV | 272 | 5900_1 | Energy Consumption (Power Measurement 1) | kWh | Read | |
| AV | 273 | 5901_1 | Instantaneous Power (Power Measurement 1) | W | Read | |
| AV | 274 | 5167_1 | Output Power Factor (Power Measurement 1) | Read | ||
| AV | 285 | 4097_2 | System Input RMS A-B (Power Measurement 2) | V | Read | |
| AV | 286 | 4096_2 | System Input RMS A-N (Power Measurement 2) | V | Read | |
| AV | 287 | 4113_2 | System Input RMS Current Phase A (Power Measurement 2) | A | Read | |
| AV | 288 | 4099_2 | System Input RMS B-C (Power Measurement 2) | V | Read | |
| AV | 289 | 4098_2 | System Input RMS B-N (Power Measurement 2) | V | Read | |
| AV | 290 | 4114_2 | System Input RMS Current Phase B (Power Measurement 2) | A | Read | |
| AV | 291 | 4101_2 | System Input RMS C-A (Power Measurement 2) | V | Read | |
| AV | 292 | 4100_2 | System Input RMS C-N (Power Measurement 2) | V | Read | |
| AV | 293 | 4115_2 | System Input RMS Current Phase C (Power Measurement 2) | A | Read | |
| AV | 294 | 5900_2 | Energy Consumption (Power Measurement 2) | kWh | Read | |
| AV | 295 | 5901_2 | Instantaneous Power (Power Measurement 2) | W | Read | |
| AV | 296 | 5167_2 | Output Power Factor (Power Measurement 2) | Read | ||
| MV | 1 | 4553_1 | Server Class | Read | 1=UPS, 2=AIR, 3=PMP, 4=PDU | |
| MV | 12 | 5264_1_1 | Compressor State (Compressor 1) | Read | 1=off, 2=on | |
| MV | 13 | 5265_1_1 | Compressor Capacity Control State (Compressor 1) | Read | 1=off, 2=on | |
| MV | 24 | 5264_1_2 | Compressor State (Compressor 2) | Read | 1=off, 2=on | |
| MV | 25 | 5265_1_2 | Compressor Capacity Control State (Compressor 2) | Read | 1=off, 2=on | |
| MV | 246 | 5264_1_4 | Compressor State (Compressor 4) | Read | 1=off, 2=on | |
| MV | 247 | 5265_1_4 | Compressor Capacity Control State (Compressor 4) | Read | 1=off, 2=on | |
| MV | 36 | 5302_1 | Free Cooling Status | Read | 1=off, 2=on, 3=No Support | |
| MVmin | 47 | 4717_1 | System Event Acknowledge/Reset | Write | 1=Reset, 2=Acknowledge | |
| MVmin | 58 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation | |
| MVmin | 59 | 4706_1 | System Operating State | Read | 1=off, 2=on, 3=standby | |
| MV | 60 | 4707_1 | System Control Mode | Read | 1=Internal (Auto), 2=External (Manual) | |
| MV | 61 | 5074_1 | System Operating State Reason | Read | 1=Reason Unknown, 2=Network Display, 3=Alarm, 4=Schedule, 5=Remote System, 6=External Input, 7=Local Display | |
| MVmin | 62 | 5143_1 | System On/Off Control | Write | 1=off, 2=on | |
| MV | 73 | 4654_1 | Pump 1 State | Read | 1=off, 2=on | |
| MV | 74 | 4655_1 | Pump 2 State | Read | 1=off, 2=on |
No points match these filters.
Object ID lookup: Vertiv Liebert HPC chiller point IDs by name
BV15263_1BV25604_1BV125269_1_1BV135270_1_1BV145271_1_1BV155272_1_1BV165273_1_1BV175275_1_1BV185513_1_1BV195773_1_1BV205774_1_1BV295269_1_2BV305270_1_2BV315271_1_2BV325272_1_2BV335273_1_2BV345275_1_2BV355513_1_2BV365773_1_2BV375774_1_2BV2635269_1_4BV2645270_1_4BV2655271_1_4BV2665272_1_4BV2675273_1_4BV2685275_1_4BV2695513_1_4BV2705773_1_4BV2715774_1_4BV465277_1BV475278_1BV485545_1BV595277_2BV605278_2BV615545_2BV675277_4BV685278_4BV695545_4BV725280_1BV735295_1BV844645_1_1BV854648_1_1BV864651_1_1BV975297_1BV984656_1BV994659_1BV1105300_1_1BV1215300_1_2BV1325306_1BV1334618_1BV1445308_1BV1455559_1BV1465560_1BV1575310_1_1BV1585311_1_1BV1594640_1_1BV1705310_1_2BV1715311_1_2BV1724640_1_2BV1834270_1BV1844271_1BV1944272_1BV1954273_1BV1855109_1BV1865110_1BV1875120_1BV1885315_1BV1895045_1BV1905119_1BV1915418_1BV1925588_1BV1935775_1BV2005625_1BV2105625_2BV2305625_4BV2825967_1BV2935967_2AV15262_1AV100015262_1_deg_FAV125266_1_1AV135267_1_1AV145268_1_1AV255266_1_2AV265267_1_2AV275268_1_2AV2155266_1_4AV2165267_1_4AV2175268_1_4AV385276_1AV495276_2AV555276_4AV605279_1AV615281_1AV100615281_1_deg_FAV725283_1_1AV100725283_1_1_deg_FAV735284_1_1AV100735284_1_1_deg_FAV745285_1_1AV100745285_1_1_deg_FAV754644_1_1AV100754644_1_1_deg_FAV765286_1_1AV100765286_1_1_deg_FAV775287_1_1AV100775287_1_1_deg_FAV885298_1_1AV895299_1_1AV1005298_1_2AV1015299_1_2AV1125301_1AV101125301_1_deg_FAV1135303_1AV1145304_1AV1155305_1AV1265307_1AV101265307_1_deg_FAV1275555_1AV101275555_1_deg_FAV1285556_1AV101285556_1_deg_FAV1295557_1AV101295557_1_deg_FAV1305558_1AV101305558_1_deg_FAV1415312_1AV101415312_1_deg_FAV1525314_1AV1635288_1AV101635288_1_deg_FAV1644643_1AV101644643_1_deg_FAV1655282_1AV101655282_1_deg_FAV1665517_1AV101665517_1_deg_FAV1675518_1AV101675518_1_deg_FAV1685313_1AV101685313_1_deg_FAV1695519_1AV1705080_1AV1715078_1AV1724594_1AV101724594_1_deg_FAV1735520_1AV1745521_1AV1854293_1AV2634097_1AV2644096_1AV2654113_1AV2664099_1AV2674098_1AV2684114_1AV2694101_1AV2704100_1AV2714115_1AV2725900_1AV2735901_1AV2745167_1AV2854097_2AV2864096_2AV2874113_2AV2884099_2AV2894098_2AV2904114_2AV2914101_2AV2924100_2AV2934115_2AV2945900_2AV2955901_2AV2965167_2MV14553_1MV125264_1_1MV135265_1_1MV245264_1_2MV255265_1_2MV2465264_1_4MV2475265_1_4MV365302_1MV474717_1MV584123_1MV594706_1MV604707_1MV615074_1MV625143_1MV734654_1MV744655_1
Integration notes
- Tables 5.48, 5.49, 5.50, pdf pages 1517-1525 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert HPC chiller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert HPC chiller
How many BACnet points does the Vertiv Liebert HPC chiller have?
This list has 188 BACnet objects: 95 analog values, 77 binary values, 16 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert HPC chiller BACnet points are writable?
46 of the 188 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert HPC chiller BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert HPC chiller?
Start with MV 62 5143_1 (On/off command (1=off, 2=on)); AV 72 5283_1_1 (Supply fluid temperature setpoint, °C); MV 47 4717_1 (Acknowledge / reset events); MV 59 4706_1 (Run / standby / off state); MV 58 4123_1 (Normal, warning or alarm state); AV 164 4643_1 (Supply fluid temperature, °C); AV 263 4097_1 (Input voltage, V).
How do I check these points on the real Liebert HPC chiller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.