UPS (uninterruptible power supply) · BACnet points list

Vertiv Liebert Trinergy Cube UPS BACnet points list

Updated 6 November 2026

Short answer

The Liebert Trinergy Cube UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.

This page lists 141 BACnet objects for the Vertiv Liebert Trinergy Cube UPS — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert Trinergy Cube UPS
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
141 (1 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Trinergy Cube, Liebert Trinergy, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 141 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert Trinergy Cube UPS

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 144123_1Normal, warning or alarm stateRead
MV 165971_1UPS operating stateRead
MV 134872_1Load on inverter, bypass or batteryRead
AV 1454150_1Estimated battery runtime, minRead
AV 504096_1Input voltage, VRead
AV 2474385_1Output voltage, VRead
AV 2534204_1Output current, ARead
BV 404168_1Load is on batteryRead

Network setup

Watch out for

Vertiv Liebert Trinergy Cube UPS BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

141 of 141 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert Trinergy Cube UPS BACnet Points List
DescriptionStates
AV14293_1System Date and TimesWrite
BV14325_1Backfeed Breaker OpenReadActive = alarm
BV25973_1Input Breaker OpenReadActive = alarm
BV35975_1Output Breaker OpenReadActive = alarm
BV45977_1Battery Breaker OpenReadActive = alarm
BV55976_1Maintenance Bypass Breaker ClosedReadActive = alarm
BV144141_1Bypass Breaker ClosedReadActive = alarm
BV155982_1Bypass Breaker (SBB) OpenReadActive = alarm
BV166350_1General FaultReadActive = alarm
BV176353_1General WarningReadActive = alarm
BV184215_1System Output OffReadActive = alarm
BV194298_1UPS Output on BypassReadActive = alarm
BV205807_1Output Off PendingReadActive = alarm
BV216357_1System Restart PendingReadActive = alarm
BV226333_1Bypass out of syncReadActive = alarm
BV234389_1System Output FaultReadActive = alarm
BV244213_1System Shutdown - EPOReadActive = alarm
BV265970_1Ground FaultReadActive = alarm
BV274122_1System Input Power ProblemReadActive = alarm
BV285957_1Bypass Input Voltage FaultReadActive = alarm
BV295798_1Bypass OverloadReadActive = alarm
BV305960_1Inverter OverloadReadActive = alarm
BV324135_1Bypass Not AvailableReadActive = alarm
BV334143_1Bypass Static Switch UnavailableReadActive = alarm
BV344295_1Rectifier FailureReadActive = alarm
BV354233_1Inverter FailureReadActive = alarm
BV366254_1Charger FailureReadActive = alarm
BV376253_1Booster FailureReadActive = alarm
BV385154_1DC Bus AbnormalReadActive = alarm
BV394222_1Battery Ground FaultReadActive = alarm
BVmin404168_1Battery DischargingReadActive = alarm
BV416354_1Battery ChargingReadActive = alarm
BV424162_1Battery LowReadActive = alarm
BV434322_1Battery Test PassedReadActive = alarm
BV444323_1Battery Test FailedReadActive = alarm
BV454172_1Battery Auto Test In ProgressReadActive = alarm
BV464171_1Battery Manual Test In ProgressReadActive = alarm
BV474311_1System Fan FailureReadActive = alarm
BV484440_1Fuse FailureReadActive = alarm
BV494310_1Equipment Over TemperatureReadActive = alarm
BV506180_1Battery Under VoltageReadActive = alarm
BV536356_1Battery Circuit OpenReadActive = alarm
BV544315_1On GeneratorReadActive = alarm
AV114264_1_1Output Apparent Power RatingkVARead
AV124103_1_1System Input Nominal FrequencyHzRead
AV134102_1_1System Input Nominal VoltageVRead
AV144261_1_1System Output Nominal FrequencyHzRead
AV154260_1_1System Output Nominal VoltageVRead
AV164104_1_1System Input Nominal CurrentARead
AV266317_1_1Firmware version (DSP FW Version 1)Read
AV376317_1_2Firmware version (DSP FW Version 2)Read
AV416317_1_3Firmware version (DSP FW Version 3)Read
AV494105_1System Input FrequencyHzRead
AVmin504096_1System Input RMS A-NVRead
AV514098_1System Input RMS B-NVRead
AV524100_1System Input RMS C-NVRead
AV534097_1System Input RMS A-BVRead
AV544099_1System Input RMS B-CVRead
AV554101_1System Input RMS C-AVRead
AV564113_1System Input RMS Current Phase AARead
AV574114_1System Input RMS Current Phase BARead
AV584115_1System Input RMS Current Phase CARead
AV596318_1System Input Power Phase AkWRead
AV606319_1System Input Power Phase BkWRead
AV616320_1System Input Power Phase CkWRead
AV626321_1UPS DC input voltageVDCRead
AV636322_1UPS input real powerkWRead
AV646323_1UPS input apparent powerkVARead
AV1254131_1Bypass Input FrequencyHzRead
AV1264128_1Bypass Input Voltage RMS A-NVRead
AV1274129_1Bypass Input Voltage RMS B-NVRead
AV1284130_1Bypass Input Voltage RMS C-NVRead
AV1294125_1Bypass Input Voltage RMS A-BVRead
AV1304126_1Bypass Input Voltage RMS B-CVRead
AV1314127_1Bypass Input Voltage RMS C-AVRead
AV1325570_1Bypass Input RMS Current Phase AARead
AV1335571_1Bypass Input RMS Current Phase BARead
AV1345572_1Bypass Input RMS Current Phase CARead
AV1488048_1Bypass Input Power Factor Phase ARead
AV1498049_1Bypass Input Power Factor Phase BRead
AV1508050_1Bypass Input Power Factor Phase CRead
AV1516325_1Bypass Power Phase AkWRead
AV1526326_1Bypass Power Phase BkWRead
AV1536327_1Bypass Power Phase CkWRead
AV1424155_1Battery Volts for CabinetVDCRead
AV1434149_1DC Bus CurrentA DCRead
AV1444151_1Battery Discharge TimesRead
AVmin1454150_1Battery Time RemainingminRead
AV1464153_1Battery Percentage Charge%Read
AV1474156_1Battery Temperature for Cabinet°CRead
AV101474156_1_deg_FBattery Temperature for Cabinet°FRead
AV2464207_1System Output FrequencyHzRead
AVmin2474385_1System Output Voltage RMS A-NVRead
AV2484386_1System Output Voltage RMS B-NVRead
AV2494387_1System Output Voltage RMS C-NVRead
AV2504201_1System Output Voltage RMS A-BVRead
AV2514202_1System Output Voltage RMS B-CVRead
AV2524203_1System Output Voltage RMS C-AVRead
AVmin2534204_1System Output RMS Current Phs AARead
AV2544205_1System Output RMS Current Phs BARead
AV2554206_1System Output RMS Current Phs CARead
AV2565859_1System Output Power Phase AkWRead
AV2575860_1System Output Power Phase BkWRead
AV2585959_1System Output Power Phase CkWRead
AV2594223_1System Output Pct Power Phase A%Read
AV2604224_1System Output Pct Power Phase B%Read
AV2614225_1System Output Pct Power Phase C%Read
AV2625868_1System Output Apparent Power Phs AkVARead
AV2635869_1System Output Apparent Power Phs BkVARead
AV2645870_1System Output Apparent Power Phs CkVARead
AV2655574_1Outside Air Temperature°CRead
AV102655574_1_deg_FOutside Air Temperature°FRead
AV2674210_1System Output Power Factor Phs ARead
AV2684211_1System Output Power Factor Phs BRead
AV2694212_1System Output Power Factor Phs CRead
MV16316_1UPS manufacturerRead1=Chloride, 2=Masterguard, 3=Oneac, 4=Vertiv, 5=Other
MV24303_1UPS Module TypeRead1=Single Module System, 2=Module (1 + 1), 3=Module (1 + N), 4=Module (N + 1), 5=System Control Cabinet, 6=Main Static Switch
MVmin134872_1UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MVmin144123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MVmin165971_1UPS Operating ModeRead1=Idle, 2=Double Conversion Mode (VFI), 3=Interactive Mode (VI), 4=Stand-By Mode (VFD), 5=CR Mode (CR), 6=ECO Mode (DIM)
MV175454_1ECO Mode Operation StateRead1=disabled, 2=enabled
MV194736_1Static Bypass SwitchRead1=off, 2=on
MV204737_1Bypass Qualification StatusRead1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High
MV216256_1Charger On/Off StateRead1=off, 2=on
MV226255_1Booster On/Off StateRead1=off, 2=on
MV246337_1Bypass StatusRead1=Bypass not present, 2=Bypass on, 3=Bypass off, 4=Bypass fault, 5=Bypass not ready
MV256336_1Inverter StatusRead1=Inverter off, 2=Inverter turning on, 3=Inverter on, 4=Inverter stopped due to Fault, 5=Inverter in Stand By, 6=Inverter Ready and Sync, 7=Inverter Not Ready
MV266338_1Charger StatusRead1=Charger in standby, 2=Charger on, 3=Charger switched off, 4=Charger forced on, 5=Charger stopped due to a fault
MV276335_1Rectifier StatusRead1=Rectifier off, 2=Rectifier turning on, 3=Rectifier on, 4=Rectifier fault
MV384773_1Maintenance Isolation BreakerRead1=Open, 2=Close, 3=Not Installed
MV394853_1System Load Bank BreakerRead1=Open, 2=Close, 3=Not Installed
MV408128_1Static Switch Input BreakerRead1=Open, 2=Close, 3=Not Installed
MV488129_1_1QS1 Breaker (Core Information 1 Core Breakers 1)Read1=Open, 2=Close, 3=Not Installed
MV498130_1_1QS4 Breaker (Core Information 1 Core Breakers 1)Read1=Open, 2=Close, 3=Not Installed
MV508131_1_1Battery Circuit Breaker (Core Information 1 Core Breakers 1)Read1=Open, 2=Close, 3=Not Installed
MV618129_2_1QS1 Breaker (Core Information 2 Core Breakers 1)Read1=Open, 2=Close, 3=Not Installed
MV628130_2_1QS4 Breaker (Core Information 2 Core Breakers 1)Read1=Open, 2=Close, 3=Not Installed
MV638131_2_1Battery Circuit Breaker (Core Information 2 Core Breakers 1)Read1=Open, 2=Close, 3=Not Installed
MV1008129_5_1QS1 Breaker (Core Information 5 Core Breakers 1)Read1=Open, 2=Close, 3=Not Installed
MV1018130_5_1QS4 Breaker (Core Information 5 Core Breakers 1)Read1=Open, 2=Close, 3=Not Installed
MV1028131_5_1Battery Circuit Breaker (Core Information 5 Core Breakers 1)Read1=Open, 2=Close, 3=Not Installed
Object ID lookup: Vertiv Liebert Trinergy Cube UPS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert Trinergy Cube UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert Trinergy Cube UPS

How many BACnet points does the Vertiv Liebert Trinergy Cube UPS have?

This list has 141 BACnet objects: 73 analog values, 42 binary values, 26 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert Trinergy Cube UPS BACnet points are writable?

1 of the 141 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert Trinergy Cube UPS BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert Trinergy Cube UPS?

Start with MV 14 4123_1 (Normal, warning or alarm state); MV 16 5971_1 (UPS operating state); MV 13 4872_1 (Load on inverter, bypass or battery); AV 145 4150_1 (Estimated battery runtime, min); AV 50 4096_1 (Input voltage, V); AV 247 4385_1 (Output voltage, V); AV 253 4204_1 (Output current, A); BV 40 4168_1 (Load is on battery).

How do I check these points on the real Liebert Trinergy Cube UPS?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.