Easy BACnet
  1. Home
  2. BACnet points lists
  3. Vertiv
  4. Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)

Ceiling-mounted precision split cooling unit · BACnet points list

Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card) BACnet points list

Updated 11 November 2026

Short answer

The Liebert Mini-Mate2 8 ton map is a short legacy list: unit status, temperature and humidity readings and setpoints, an on/off control word and alarm words where several alarms share one object as bits. Only use it with the card variant named in the title.

This page lists 18 BACnet objects for the Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Equipment
Ceiling-mounted precision split cooling unit
Equipment type
VRF & split air conditioners
BACnet objects
18 (3 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 18 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)

Integration in brief

Fit a Liebert IntelliSlot IS-WEBADPT card (BACnet IP only), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 4bc01_1Control word: unit on/off and lockouts (bit-coded)Write
AV 11bc02_1Temperature setpointWrite
AV 12bc03_1Humidity setpointWrite
AV 18bs18_1Unit on/off status (0 = off, 1 = on)Read
AV 5bs01_1Room temperatureRead
AV 6bs02_1Room humidityRead
AV 8bs09_1Cooling capacity, %Read
AV 1ba01_1Alarm word 1 (bit-coded)Read

Network setup

Watch out for

Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

18 of 18 shown
Type
Analog
Access
Show
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card) BACnet Points List
DescriptionStates
AVmin5bs01_1Temperature (Status Points (View))Read
AVmin6bs02_1Humidity (Status Points (View))Read
AV13bs03_1CoolingRead0=Off, 1=On
AV14bs04_1HeatingRead0=Off, 1=On
AV15bs05_1HumidificationRead0=Off, 1=On
AV16bs06_1DehumidificationRead0=Off, 1=On
AV17bs07_1Econ-O-CycleRead0=Off, 1=On
AV7bs08_1StagesRead
AVmin8bs09_1% CapacityRead
AVmin18bs18_1Unit Status (On/Off)Read0=Off, 1=On
AVmin1ba01_1Bit-packed: Alarm PointsReadBit 0 = Communications; Bit 1 = Local Off; Bit 2 = Remote Off; Bit 3 = High Head Pressure 1; Bit 4 = High Head Pressure 2; Bit 5 = Loss of Airflow; Bit 6 = Standby Glycol Unit On; Bit 8 = Change Filters; Bit 9 = High Temperature; Bit 10 = Low Temperature
AV2ba02_1Bit-packed: Alarm PointsReadBit 0 = High Humidity; Bit 1 = Low Humidity; Bit 2 = Humidifier Problem; Bit 8 = Smoke Detected; Bit 9 = Loss of Water Flow; Bit 10 = Standby Unit On
AV3ba03_1Bit-packed: Alarm PointsReadBit 1 = Short Cycle; Bit 2 = Loss of Power; Bit 6 = Local Alarm 1; Bit 7 = Local Alarm 2; Bit 8 = High Water; Bit 9 = Local Alarm 3
AV9bs10_1Temperature (Setpoints (View))Read
AV10bs12_1Humidity (Setpoints (View))Read
AVmin4bc01_1Bit-packed: Control PointsWriteUnit On/Off: Bit 0 - ON = Unit Off Bit 1 - ON = Unit On; Reheat Lockout: Bit 2 - ON = Reheat Lockout Off Bit 3 - ON = Reheat Lockout On*; Humidifier Lockout: Bit 4 - ON = Humidifier Lockout Off Bit 5 - ON = Humidifier Lockout On*
AVmin11bc02_1Temperature SetpointWrite
AVmin12bc03_1Humidity SetpointWrite
Object ID lookup: Vertiv Liebert Mini-Mate2 8 Ton IS-WEBADPT point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)

How many BACnet points does the Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card) have?

This list has 18 BACnet objects: 18 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card) BACnet points are writable?

3 of the 18 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card) BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)?

Start with AV 4 bc01_1 (Control word: unit on/off and lockouts (bit-coded)); AV 11 bc02_1 (Temperature setpoint); AV 12 bc03_1 (Humidity setpoint); AV 18 bs18_1 (Unit on/off status (0 = off, 1 = on)); AV 5 bs01_1 (Room temperature); AV 6 bs02_1 (Room humidity); AV 8 bs09_1 (Cooling capacity, %); AV 1 ba01_1 (Alarm word 1 (bit-coded)).

How do I check these points on the real Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.