In-row precision cooling unit (computer room air handler) · BACnet points list

Vertiv Liebert CRV CRD10 in-row cooling BACnet points list

Updated 6 November 2026

Short answer

The Liebert CRV CRD10 in-row cooling reports to a BMS through a Liebert IntelliSlot card (IS-UNITY-DP, for BACnet IP or BACnet MS/TP). The object list has Binary Values for events, Analog Values for temperatures, humidity, setpoints and run hours, and Multi-state Values for states and control modes. Objects are created on the card when it discovers the unit, so only options fitted to the unit appear.

This page lists 231 BACnet objects for the Vertiv Liebert CRV CRD10 in-row cooling — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert CRV CRD10 in-row cooling
Equipment
In-row precision cooling unit (computer room air handler)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
231 (23 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
CRD10, Liebert CRV CRD10, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 231 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert CRV CRD10 in-row cooling

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 607536_1Monitoring on/off (1=off, 2=on)Write
AV 85331_1Supply air temperature setpoint, °CWrite
AV 95333_1Return air temperature setpoint, °CWrite
MV 717528_1Run / standby / off stateRead
MV 724123_1Normal, warning or alarm stateRead
AV 15002_1Supply air temperature, °CRead
AV 24291_1Return air temperature, °CRead
AV 65028_1Return air humidity, %RHRead
AV 4875078_1Cooling output, %Read
AV 4235077_1Fan speed, %Read

Network setup

Watch out for

Vertiv Liebert CRV CRD10 in-row cooling BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

231 of 231 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert CRV CRD10 in-row cooling BACnet Points List
DescriptionStates
BV15598_1Remote Sensor Under TemperatureReadActive = alarm
BV25015_1Supply Air Over TemperatureReadActive = alarm
BV37559_1Loss of Airflow Sensor FailureReadActive = alarm
BV45034_1High Return HumidityReadActive = alarm
BV55597_1Remote Sensor Over TemperatureReadActive = alarm
BV65036_1Low Return HumidityReadActive = alarm
BV75335_1Return Air Under TemperatureReadActive = alarm
BV85118_1Clogged Air FilterReadActive = alarm
BV97537_1Filter Maintenance DueReadActive = alarm
BV107526_1Air Damper FailureReadActive = alarm
BV117522_1Loss of AirflowReadActive = alarm
BV127489_1Low Supply Air HumidityReadActive = alarm
BV137490_1High Supply Air HumidityReadActive = alarm
BV147491_1Low Remote Air HumidityReadActive = alarm
BV157492_1High Remote Air HumidityReadActive = alarm
BV165019_1Supply Air Under TemperatureReadActive = alarm
BV175023_1Return Air Over TemperatureReadActive = alarm
BV285026_1_1Supply Air Sensor Issue (Supply Air Temp Sensor 1)ReadActive = alarm
BV395026_1_2Supply Air Sensor Issue (Supply Air Temp Sensor 2)ReadActive = alarm
BV505026_1_3Supply Air Sensor Issue (Supply Air Temp Sensor 3)ReadActive = alarm
BV615147_1_1Return Air Sensor Issue (Return Air Temp Sensor 1)ReadActive = alarm
BV725147_1_2Return Air Sensor Issue (Return Air Temp Sensor 2)ReadActive = alarm
BV835147_1_3Return Air Sensor Issue (Return Air Temp Sensor 3)ReadActive = alarm
BV947495_1_1External Air Sensor Issue (Remote Temp Sensor 1)ReadActive = alarm
BV1057495_1_2External Air Sensor Issue (Remote Temp Sensor 2)ReadActive = alarm
BV1937495_1_10External Air Sensor Issue (Remote Temp Sensor 10)ReadActive = alarm
BV2047493_1_1Supply Humidity Sensor Issue (Supply Air Humidity Sensor 1)ReadActive = alarm
BV2157493_1_2Supply Humidity Sensor Issue (Supply Air Humidity Sensor 2)ReadActive = alarm
BV2267493_1_3Supply Humidity Sensor Issue (Supply Air Humidity Sensor 3)ReadActive = alarm
BV2375902_1_1Return Humidity Sensor Issue (Return Air Humidity Sensor 1)ReadActive = alarm
BV2485902_1_2Return Humidity Sensor Issue (Return Air Humidity Sensor 2)ReadActive = alarm
BV2595902_1_3Return Humidity Sensor Issue (Return Air Humidity Sensor 3)ReadActive = alarm
BV2707494_1_1External Humidity Sensor Issue (Remote Humidity Sensor 1)ReadActive = alarm
BV2817494_1_2External Humidity Sensor Issue (Remote Humidity Sensor 2)ReadActive = alarm
BV3697494_1_10External Humidity Sensor Issue (Remote Humidity Sensor 10)ReadActive = alarm
BV3807562_1Water Pressure Sensor FailureReadActive = alarm
BV3816239_1Fluid Valve Hours ExceededReadActive = alarm
BV3826313_1Chilled Water Inlet Temperature Sensor FailureReadActive = alarm
BV3836314_1Chilled Water Outlet Temperature Sensor FailureReadActive = alarm
BV3847507_1Inlet Fluid Low PressureReadActive = alarm
BV3857508_1Inlet Fluid High PressureReadActive = alarm
BV3867509_1Outlet Fluid Under TempReadActive = alarm
BV3877510_1Outlet Fluid Over TempReadActive = alarm
BV3887512_1Inlet Fluid Under TempReadActive = alarm
BV3897511_1Inlet Fluid Over TempReadActive = alarm
BV3907506_1Supply Fluid Low FlowReadActive = alarm
BV3914980_1Supply Chilled Water Loss of FlowReadActive = alarm
BV3927558_1Water Flow Sensor FailureReadActive = alarm
BV4037504_1_1Water Valve FailureReadActive = alarm
BV4147557_1Compressor Suction Temperature Sensor FailureReadActive = alarm
BV4157556_1Compressor Discharge Temperature Sensor FailureReadActive = alarm
BV4167555_1Low Compressor Pressure Sensor Failure LockoutReadActive = alarm
BV4177554_1Low Compressor Pressure Sensor FailureReadActive = alarm
BV4187553_1High Compressor Pressure Sensor FailureReadActive = alarm
BV4197548_1Low Compressor Discharge Superheat LockoutReadActive = alarm
BV4207547_1Low Compressor Discharge SuperheatReadActive = alarm
BV4217550_1Low Compressor Pressure AbnormalReadActive = alarm
BV4227549_1High Compressor Pressure AbnormalReadActive = alarm
BV4237546_1Low Compressor Discharge Temperature LockoutReadActive = alarm
BV4247541_1Low Compressor PressureReadActive = alarm
BV4257545_1Low Compressor Discharge TemperatureReadActive = alarm
BV4267544_1High Compressor Discharge Temperature LockoutReadActive = alarm
BV4277543_1High Compressor Discharge TemperatureReadActive = alarm
BV4287542_1Low Compressor Pressure LockoutReadActive = alarm
BV4297540_1High Compressor Presssure LockoutReadActive = alarm
BV4307539_1High Compressor PressureReadActive = alarm
BV4317496_1Compressor Driver Failure LockoutReadActive = alarm
BV4327497_1Compressor Driver FailureReadActive = alarm
BV4337498_1Compressor Driver Communication Failure LockoutReadActive = alarm
BV4347499_1Compressor Pressure Difference LockoutReadActive = alarm
BV4357500_1Compressor Driver Communication FailureReadActive = alarm
BV4367501_1Compressor Pressure DifferenceReadActive = alarm
BV4378051_1Compressor Drive Failure U00ReadActive = alarm
BV4388052_1Compressor Drive Failure U01ReadActive = alarm
BV4398053_1Compressor Drive Failure U02ReadActive = alarm
BV4408054_1Compressor Drive Failure U03ReadActive = alarm
BV4418055_1Compressor Drive Failure U04ReadActive = alarm
BV4428056_1Compressor Drive Failure U05ReadActive = alarm
BV4438057_1Compressor Drive Failure U06ReadActive = alarm
BV4448058_1Compressor Drive Failure U07ReadActive = alarm
BV4458059_1Compressor Drive Failure U08ReadActive = alarm
BV4468060_1Compressor Drive Failure U09ReadActive = alarm
BV4478061_1Compressor Drive Failure U10ReadActive = alarm
BV4488062_1Compressor Drive Failure U11ReadActive = alarm
BV4498063_1Compressor Drive Failure U12ReadActive = alarm
BV4508064_1Compressor Drive Failure U13ReadActive = alarm
BV4518065_1Compressor Drive Failure U14ReadActive = alarm
BV4528066_1Compressor Drive Failure U15ReadActive = alarm
BV4538067_1EEV Driver Unselect RefrigerantReadActive = alarm
BV4548068_1Compressor Drive Heatsink High TemperatureReadActive = alarm
BV4558069_1Compressor Drive Over CurrentReadActive = alarm
BV4568070_1Compressor Drive Phase LossReadActive = alarm
BV4578071_1Compressor Drive DC Power AbnormalReadActive = alarm
BV4685054_1Fan Hours ExceededReadActive = alarm
BV4697515_1Fan Detection Board Communication FailureReadActive = alarm
BV4804729_1_1Fan Issue (Fan Issue 1)ReadActive = alarm
BV4914729_1_2Fan Issue (Fan Issue 2)ReadActive = alarm
BV5794729_1_10Fan Issue (Fan Issue 10)ReadActive = alarm
BV5907563_1_1Fan Static Pressure Sensor Failure (Static Pressure 1)ReadActive = alarm
BV6017563_1_2Fan Static Pressure Sensor Failure (Static Pressure 2)ReadActive = alarm
BV6125568_1Input UndervoltageReadActive = alarm
BV6135569_1Input OvervoltageReadActive = alarm
BV6146615_1DC Power Supply FailReadActive = alarm
BV6156186_1Input Frequency DeviationReadActive = alarm
BV6167518_1Surge Protection Device AlarmReadActive = alarm
BV6176614_1AC Power Supply FailReadActive = alarm
BV6187519_1Power Opposite PhaseReadActive = alarm
BV6197520_1Power Loss Of PhaseReadActive = alarm
BV6307503_1Electrical Heater FailureReadActive = alarm
BV6417538_1Heater Maintenance DueReadActive = alarm
BV6427525_1Repeated Teamwork AddressReadActive = alarm
BV6437524_1Loss of Teamwork SlaveReadActive = alarm
BV6447523_1Teamwork Master is offline or not connected to the networkReadActive = alarm
BV6454720_1Smoke DetectedReadActive = alarm
BV6464723_1Water Under FloorReadActive = alarm
BV6475108_1External Fire DetectedReadActive = alarm
BV6485043_1Humidifier IssueReadActive = alarm
BV6495037_1Humidifier Hours ExceededReadActive = alarm
BV6507551_1EEV Driver Communication FailureReadActive = alarm
BV6517552_1EEV Driver FailureReadActive = alarm
BV6527560_1Filter Pressure Difference Sensor FailureReadActive = alarm
BV6534300_1Internal Communications FailureReadActive = alarm
BV6548072_110DI Sensor Communication FailReadActive = alarm
BV6558073_1System Lack Of RefrigerantReadActive = alarm
BV6565106_1Ext Condenser Pump High WaterReadActive = alarm
BV6575500_1Ext Remote ShutdownReadActive = alarm
BV6584714_1Shutdown - Loss Of PowerReadActive = alarm
BV6698083_1_1Condensate Pump Failure (Condensate Pump Fail 1)ReadActive = alarm
BV6808083_1_2Condensate Pump Failure (Condensate Pump Fail 2)ReadActive = alarm
BV6917561_1_1Custom Alarm (Custom Alarm 1)ReadActive = alarm
BV7027561_1_2Custom Alarm (Custom Alarm 2)ReadActive = alarm
BV7467561_1_6Custom Alarm (Custom Alarm 6)ReadActive = alarm
AVmin15002_1Supply Air Temperature°CRead
AV100015002_1_deg_FSupply Air Temperature°FRead
AVmin24291_1Return Air Temperature°CRead
AV100024291_1_deg_FReturn Air Temperature°FRead
AV35007_1Remote Sensor Average Temperature°CRead
AV100035007_1_deg_FRemote Sensor Average Temperature°FRead
AV58090_1%RHRead
AVmin65028_1Return Humidity%RHRead
AV78081_1Average Relative HumidityRead
AVmin85331_1Supply Air Temperature Set Point°CWrite
AV100085331_1_deg_FSupply Air Temperature Set Point°FWrite
AVmin95333_1Return Air Temperature Set Point°CWrite
AV100095333_1_deg_FReturn Air Temperature Set Point°FWrite
AV108082_1Remote Sensor Air Temperature Set Point°CWrite
AV100108082_1_deg_FRemote Sensor Air Temperature Set Point°FWrite
AV115029_1Humidity Set Point%RHWrite
AV125009_1Cooling Proportional Band°CWrite
AV100125009_1_deg_FCooling Proportional Band°FWrite
AV135030_1Humidification Proportional Band%RHWrite
AV147521_1Air Filter HourshWrite
AV258077_1_1Supply Air Sensor Temperature (Supply Air Temp Sensor 1)°CRead
AV100258077_1_1_deg_FSupply Air Sensor Temperature (Supply Air Temp Sensor 1)°FRead
AV368077_1_2Supply Air Sensor Temperature (Supply Air Temp Sensor 2)°CRead
AV100368077_1_2_deg_FSupply Air Sensor Temperature (Supply Air Temp Sensor 2)°FRead
AV478077_1_3Supply Air Sensor Temperature (Supply Air Temp Sensor 3)°CRead
AV100478077_1_3_deg_FSupply Air Sensor Temperature (Supply Air Temp Sensor 3)°FRead
AV588078_1_1Return Air Sensor Temperature (Return Air Temp Sensor 1)°CRead
AV100588078_1_1_deg_FReturn Air Sensor Temperature (Return Air Temp Sensor 1)°FRead
AV698078_1_2Return Air Sensor Temperature (Return Air Temp Sensor 2)°CRead
AV100698078_1_2_deg_FReturn Air Sensor Temperature (Return Air Temp Sensor 2)°FRead
AV808078_1_3Return Air Sensor Temperature (Return Air Temp Sensor 3)°CRead
AV100808078_1_3_deg_FReturn Air Sensor Temperature (Return Air Temp Sensor 3)°FRead
AV915059_1_1Remote Sensor Temperature (Remote Temp Sensor 1)°CRead
AV100915059_1_1_deg_FRemote Sensor Temperature (Remote Temp Sensor 1)°FRead
AV1025059_1_2Remote Sensor Temperature (Remote Temp Sensor 2)°CRead
AV101025059_1_2_deg_FRemote Sensor Temperature (Remote Temp Sensor 2)°FRead
AV1905059_1_10Remote Sensor Temperature (Remote Temp Sensor 10)°CRead
AV101905059_1_10_deg_FRemote Sensor Temperature (Remote Temp Sensor 10)°FRead
AV2018079_1_1Supply Sensor Humidity (Supply Air Humidity Sensor 1)%RHRead
AV2128079_1_2Supply Sensor Humidity (Supply Air Humidity Sensor 2)%RHRead
AV2238079_1_3Supply Sensor Humidity (Supply Air Humidity Sensor 3)%RHRead
AV2348080_1_1Return Sensor Humidity (Return Air Humidity Sensor 1)%RHRead
AV2458080_1_2Return Sensor Humidity (Return Air Humidity Sensor 2)%RHRead
AV2568080_1_3Return Sensor Humidity (Return Air Humidity Sensor 3)%RHRead
AV2674587_1_1Relative Humidity (Remote Humidity Sensor 1)%RHRead
AV2784587_1_2Relative Humidity (Remote Humidity Sensor 2)%RHRead
AV3664587_1_10Relative Humidity (Remote Humidity Sensor 10)%RHRead
AV3776311_1Chilled Water Inlet Temperature°CRead
AV103776311_1_deg_FChilled Water Inlet Temperature°FRead
AV3786312_1Chilled Water Outlet Temperature°CRead
AV103786312_1_deg_FChilled Water Outlet Temperature°FRead
AV3795899_1Fluid Flow Ratem3/hRead
AV3807514_1Inlet Fluid PressurePaRead
AV3817513_1Outlet Fluid PressurePaRead
AV3925640_1_1Chilled Water Valve Open Position%Read
AV3935614_1_1Chilled Water Valve HourshWrite
AV4047532_1Compressor Discharge Temperature°CRead
AV104047532_1_deg_FCompressor Discharge Temperature°FRead
AV4057533_1Compressor Suction Temperature°CRead
AV104057533_1_deg_FCompressor Suction Temperature°FRead
AV4067534_1Compressor Suction Superheat°CRead
AV104067534_1_deg_FCompressor Suction Superheat°FRead
AV4077535_1Compressor Discharge Superheat°CRead
AV104077535_1_deg_FCompressor Discharge Superheat°FRead
AV4087531_1Compressor Low PressurebarRead
AV4097530_1Compressor High PressurebarRead
AV4105267_1Compressor HourshWrite
AV4217517_1Fan Temperature Difference Setpoint°CWrite
AV104217517_1_deg_FFan Temperature Difference Setpoint°FWrite
AV4225374_1Fan HourshWrite
AVmin4235077_1Fan Speed%Read
AV4245276_1Condenser Fan Speed%Read
AV4357527_1_1Fan Static Pressure (Static Pressure 1)PaRead
AV4467527_1_2Fan Static Pressure (Static Pressure 2)PaRead
AV4574096_1System Input RMS A-NVRead
AV4584113_1System Input RMS Current Phase AARead
AV4594098_1System Input RMS B-NVRead
AV4604114_1System Input RMS Current Phase BARead
AV4614100_1System Input RMS C-NVRead
AV4624115_1System Input RMS Current Phase CARead
AV4635900_1Energy ConsumptionkWhWrite
AV4645901_1Instantaneous PowerWRead
AV4654105_1System Input FrequencyHzRead
AV4765366_1Electric Reheater HourshWrite
AVmin4875078_1Cooling Capacity (Master)%Read
AV4885369_1Humidifier HourshWrite
AV4895371_1Dehumidifier HourshWrite
MV14553_1Server ClassRead1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR
MV127505_1_1Water Valve Control ModeRead1=ReturnAirAverageTemp, 2=ReturnAirMaxTemp, 3=ReturnAirMinTemp, 4=SupplyAirAverageTemp, 5=SupplyAirMaxTemp, 6=SupplyAirMinTemp, 7=RemoteAverageTemp, 8=RemoteMaxTemp, 9=RemoteMinTemp
MV237502_1Compressor Control ModeWrite1=ReturnAirAverageTemp, 2=ReturnAirMaxTemp, 3=ReturnAirMinTemp, 4=SupplyAirAverageTemp, 5=SupplyAirMaxTemp, 6=SupplyAirMinTemp, 7=RemoteAverageTemp, 8=RemoteMaxTemp, 9=RemoteMinTemp
MV347516_1Fan Control ModeWrite1=ReturnAirAverageTemp, 2=ReturnAirMaxTemp, 3=ReturnAirMinTemp, 4=SupplyAirAverageTemp, 5=SupplyAirMaxTemp, 6=SupplyAirMinTemp, 7=RemoteAverageTemp, 8=RemoteMaxTemp, 9=RemoteMinTemp, 10=TemperatureDiff, 11=StaticPressure
MV455386_1Electric Reheat StateRead1=off, 2=on
MV565388_1Humidifier StateRead1=off, 2=on
MV575387_1Dehumidifier StateRead1=off, 2=on
MV585382_1Cooling StateRead1=off, 2=on
MV597529_1Teamwork StatusRead1=NoTeamwork, 2=TeamworkMode0, 3=TeamworkMode1
MVmin607536_1Monitoring ON/OFFWrite1=off, 2=on
MVmin717528_1System Operating StateRead1=Run, 2=Standby, 3=Display Off, 4=Remote Off, 5=Monitoring Off, 6=Lockout
MVmin724123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
Object ID lookup: Vertiv Liebert CRV CRD10 in-row cooling point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert CRV CRD10 in-row cooling and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert CRV CRD10 in-row cooling

How many BACnet points does the Vertiv Liebert CRV CRD10 in-row cooling have?

This list has 231 BACnet objects: 87 analog values, 132 binary values, 12 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert CRV CRD10 in-row cooling BACnet points are writable?

23 of the 231 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert CRV CRD10 in-row cooling BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert CRV CRD10 in-row cooling?

Start with MV 60 7536_1 (Monitoring on/off (1=off, 2=on)); AV 8 5331_1 (Supply air temperature setpoint, °C); AV 9 5333_1 (Return air temperature setpoint, °C); MV 71 7528_1 (Run / standby / off state); MV 72 4123_1 (Normal, warning or alarm state); AV 1 5002_1 (Supply air temperature, °C); AV 2 4291_1 (Return air temperature, °C); AV 6 5028_1 (Return air humidity, %RH); AV 487 5078_1 (Cooling output, %); AV 423 5077_1 (Fan speed, %).

How do I check these points on the real Liebert CRV CRD10 in-row cooling?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.