UPS (uninterruptible power supply) · BACnet points list

Vertiv Liebert PSI5 / Vertiv Edge UPS BACnet points list

Updated 6 November 2026

Short answer

The Liebert PSI5 / Vertiv Edge UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.

This page lists 82 BACnet objects for the Vertiv Liebert PSI5 / Vertiv Edge UPS — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert PSI5 / Vertiv Edge UPS
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
82 (22 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
PSI5, Liebert PSI5, Vertiv Edge, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 82 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert PSI5 / Vertiv Edge UPS

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 604123_1Normal, warning or alarm stateRead
MV 274872_1Load on inverter, bypass or batteryRead
AV 174150_1Estimated battery runtime, minRead
AV 374208_1Output power, WRead
AV 14096_1Input voltage, VRead
AV 344385_1Output voltage, VRead
AV 354204_1Output current, ARead
BV 434168_1Load is on batteryRead

Network setup

Watch out for

Vertiv Liebert PSI5 / Vertiv Edge UPS BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

82 of 82 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert PSI5 / Vertiv Edge UPS BACnet Points List
DescriptionStates
BV15568_1Input UndervoltageReadActive = alarm
BV25569_1Input OvervoltageReadActive = alarm
BV134741_1Battery Self TestReadActive = alarm
BV144162_1Battery LowReadActive = alarm
BV156180_1Battery Under VoltageReadActive = alarm
BV165874_1Battery Over VoltageReadActive = alarm
BV174323_1Battery Test FailedReadActive = alarm
BV186182_1Replace BatteryReadActive = alarm
BV295806_1Output OverloadReadActive = alarm
BV305179_1Output UndervoltageReadActive = alarm
BV315178_1Output OvervoltageReadActive = alarm
BV324215_1System Output OffReadActive = alarm
BVmin434168_1Battery DischargingReadActive = alarm
BV444122_1System Input Power ProblemReadActive = alarm
BV454310_1Equipment Over TemperatureReadActive = alarm
BV466186_1Input Frequency DeviationReadActive = alarm
BV476187_1Shutdown PendingReadActive = alarm
BV485588_1Unspecified General EventReadActive = alarm
BV494823_1Parallel Comm WarningReadActive = alarm
BV506254_1Charger FailureReadActive = alarm
BV514295_1Rectifier FailureReadActive = alarm
BV524233_1Inverter FailureReadActive = alarm
BV534311_1System Fan FailureReadActive = alarm
BV544229_1Emergency Power Off - LatchedReadActive = alarm
BV556453_1Input Wiring FaultReadActive = alarm
BV566454_1DC to DC Converter FaultReadActive = alarm
AVmin14096_1System Input RMS L1-NVRead
AV24113_1System Input RMS Current L1ARead
AV34105_1System Input FrequencyHzRead
AV44102_1System Input Nominal VoltageVRead
AV54104_1System Input Nominal CurrentARead
AV64103_1System Input Nominal FrequencyHzRead
AVmin174150_1Battery Time RemainingminRead
AV184153_1Battery Percentage Charge%Read
AV194148_1DC Bus VoltageVDCRead
AV206189_1DC Bus Nominal VoltageVDCRead
AV215802_1Low Battery Warning TimeminWrite
AV225800_1Number of EBC InstalledWrite
AV234151_1Battery Discharge TimeminRead
AVmin344385_1System Output Voltage RMS L1-NVRead
AVmin354204_1System Output RMS Current L1ARead
AV364207_1System Output FrequencyHzRead
AVmin374208_1System Output PowerWRead
AV385861_1System Output Pct Power%Read
AV394209_1System Output Apparent PowerVARead
AV404260_1System Output Nominal VoltageVRead
AV414264_1Output Apparent Power RatingVARead
AV424261_1System Output Nominal FrequencyHzRead
AV435816_1Output On DelaysWrite
AV445815_1Reboot With DelaysWrite
AV455814_1Shutdown After DelaysWrite
AV465812_1Nominal Power FactorRead
AV574510_1Outlet Group Identifier (Outlet Group 1)Read
AV684510_2Outlet Group Identifier (Outlet Group 2)Read
AV794710_1Auto Restart DelaysWrite
AV804291_1Inlet Air Temperature°CRead
AV100804291_1_deg_FInlet Air Temperature°FRead
AV816721_1Programmable outlet time limitminWrite
AV826723_1Non-Programmable outlet time limitminWrite
MV14553_1Server ClassRead1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR
MV124871_1UPS Battery StatusRead1=Unknown, 2=Normal, 3=Low, 4=Depleted
MV135799_1Battery Charge StatusRead1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off)
MV146181_1Battery Test ResultRead1=Unknown, 2=Passed, 3=Failed, 4=In Progress, 5=System Failure, 6=Inhibited
MV155858_1Manual Battery TestWrite1=Start Test
MV165803_1Automatic Battery TestRead1=disabled, 2=enabled
MVmin274872_1UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MV386730_1Outlet Group Power Control (Outlet Group 1)Write1=off, 2=on
MV496730_2Outlet Group Power Control (Outlet Group 2)Write1=off, 2=on
MVmin604123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MV615831_1Auto RestartWrite1=disabled, 2=enabled
MV626200_1Abort CommandWrite1=Issue Command
MV636003_1DC Converter StatusRead1=off, 2=on
MV646199_1UPS TopologyRead1=unknown, 2=Offline, 3=Line Interactive, 4=Online
MV656191_1Reset Power StatisticsWrite1=Reset
MV666188_1Audible Alarm ControlWrite1=off, 2=on
MV676257_1Silence Audible AlarmWrite1=Silence Alarm
MV686720_1Enable/Disable programmable outletsWrite1=enabled, 2=disabled
MV696722_1Enable/Disable non-programmable outletsWrite1=enabled, 2=disabled
MV706724_1Enable/Disable site fault detectionWrite1=enabled, 2=disabled
MV716725_1Enable/Disable neutral grounding in battery modeWrite1=enabled, 2=disabled
MV726726_1Emergency Power Off (EPO) LogicWrite1=Active Open, 2=Active Close
MV736727_1Input Waveform SensitivityWrite1=High Sensitivity, 2=Middle Sensitivity, 3=Low Sensitivity
Object ID lookup: Vertiv Liebert PSI5 / Vertiv Edge UPS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert PSI5 / Vertiv Edge UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert PSI5 / Vertiv Edge UPS

How many BACnet points does the Vertiv Liebert PSI5 / Vertiv Edge UPS have?

This list has 82 BACnet objects: 33 analog values, 26 binary values, 23 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert PSI5 / Vertiv Edge UPS BACnet points are writable?

22 of the 82 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert PSI5 / Vertiv Edge UPS BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert PSI5 / Vertiv Edge UPS?

Start with MV 60 4123_1 (Normal, warning or alarm state); MV 27 4872_1 (Load on inverter, bypass or battery); AV 17 4150_1 (Estimated battery runtime, min); AV 37 4208_1 (Output power, W); AV 1 4096_1 (Input voltage, V); AV 34 4385_1 (Output voltage, V); AV 35 4204_1 (Output current, A); BV 43 4168_1 (Load is on battery).

How do I check these points on the real Liebert PSI5 / Vertiv Edge UPS?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.