XD refrigerant cooling system unit · BACnet points list
Vertiv Liebert DCP (Liebert XD system unit) BACnet points list
Updated 6 November 2026
The Liebert DCP is part of a Liebert XD pumped-refrigerant cooling system and reports through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Binary Values carry events, Analog Values carry temperatures, capacities and settings, and Multi-state Values carry states, event control and event type settings. Objects are created when the card discovers the unit.
This page lists 273 BACnet objects for the Vertiv Liebert DCP (Liebert XD system unit) — 126 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert DCP (Liebert XD system unit)
- Equipment
- XD refrigerant cooling system unit
- Equipment type
- Other equipment
- BACnet objects
- 273 (126 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Liebert DCP, DCP, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert DCP (Liebert XD system unit)
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 841 | 5143_1 | On/off command (1=off, 2=on) | Write |
| MV 876 | 4717_1 | Acknowledge / reset events | Write |
| MV 838 | 4706_1 | Run / standby / off state | Read |
| MV 837 | 4123_1 | Normal, warning or alarm state | Read |
| AV 22 | 4624_1 | Supply fluid temperature, °C | Read |
| AV 94 | 5490_1 | Cooling output, % | Read |
| BV 458 | 5113_1_1 | Unit shut down by an event | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert DCP (Liebert XD system unit) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | 4601_1 | Ext Air Sensor A Over Temperature | Read | Active = alarm | |
| BV | 2 | 4604_1 | Ext Air Sensor B Over Temperature | Read | Active = alarm | |
| BV | 3 | 4608_1 | Ext Air Sensor A Under Temperature | Read | Active = alarm | |
| BV | 4 | 4611_1 | Ext Air Sensor B Under Temperature | Read | Active = alarm | |
| BV | 5 | 4615_1 | Ext Dew Point Over Temperature | Read | Active = alarm | |
| BV | 6 | 4618_1 | Ext Air Sensor A Issue | Read | Active = alarm | |
| BV | 7 | 4621_1 | Ext Air Sensor B Issue | Read | Active = alarm | |
| BV | 18 | 4626_1 | Supply Chilled Water Over Temp | Read | Active = alarm | |
| BV | 19 | 4629_1 | Supply Chilled Water Temp Sensor Issue | Read | Active = alarm | |
| BV | 20 | 4703_1 | Chilled Water Control Valve Failure | Read | Active = alarm | |
| BV | 44 | 4645_1 | Supply Fluid Over Temp | Read | Active = alarm | |
| BV | 45 | 4648_1 | Supply Fluid Under Temp | Read | Active = alarm | |
| BV | 46 | 4651_1 | Supply Fluid Temp Sensor Issue | Read | Active = alarm | |
| BV | 57 | 4656_1 | Pump 1 Loss of Flow | Read | Active = alarm | |
| BV | 58 | 4659_1 | Pump 2 Loss of Flow | Read | Active = alarm | |
| BV | 59 | 4662_1 | Pump Short Cycle | Read | Active = alarm | |
| BV | 70 | 5300_1_1 | Pump Hours Exceeded (PumpHours) | Read | Active = alarm | |
| BV | 81 | 5300_1_2 | Pump Hours Exceeded (PumpHours) | Read | Active = alarm | |
| BV | 112 | 5492_1 | Ext System Condensation Detected (XDSystem) | Read | Active = alarm | |
| BV | 113 | 5495_1 | Ext Fan Issue (XDSystem) | Read | Active = alarm | |
| BV | 114 | 5060_1 | Sensor Issue (XDSystem) | Read | Active = alarm | |
| BV | 115 | 5500_1 | Ext Remote Shutdown (XDSystem) | Read | Active = alarm | |
| BV | 116 | 5505_1 | Hot Aisle Temp Out of Range (XDSystem) | Read | Active = alarm | |
| BV | 117 | 5508_1 | Cold Aisle Temp Out of Range (XDSystem) | Read | Active = alarm | |
| BV | 118 | 6535_1 | XD Module Communication Lost (XDSystem) | Read | Active = alarm | |
| BV | 128 | 5492_2 | Ext System Condensation Detected (XDSystem 2) | Read | Active = alarm | |
| BV | 129 | 5495_2 | Ext Fan Issue (XDSystem 2) | Read | Active = alarm | |
| BV | 130 | 5060_2 | Sensor Issue (XDSystem 2) | Read | Active = alarm | |
| BV | 131 | 5500_2 | Ext Remote Shutdown (XDSystem 2) | Read | Active = alarm | |
| BV | 132 | 5505_2 | Hot Aisle Temp Out of Range (XDSystem 2) | Read | Active = alarm | |
| BV | 133 | 5508_2 | Cold Aisle Temp Out of Range (XDSystem 2) | Read | Active = alarm | |
| BV | 134 | 6535_2 | XD Module Communication Lost (XDSystem 2) | Read | Active = alarm | |
| BV | 432 | 4270_1 | Customer Input 1 | Read | Active = alarm | |
| BV | 433 | 4711_1 | System Condensation Detected | Read | Active = alarm | |
| BV | 434 | 4714_1 | Shutdown - Loss Of Power | Read | Active = alarm | |
| BV | 435 | 4720_1 | Smoke Detected | Read | Active = alarm | |
| BV | 436 | 4723_1 | Water Under Floor | Read | Active = alarm | |
| BV | 437 | 4726_1 | Service Required | Read | Active = alarm | |
| BV | 438 | 4729_1 | Fan Issue | Read | Active = alarm | |
| BV | 439 | 5419_1 | Unit Communication Lost | Read | Active = alarm | |
| BV | 440 | 5119_1 | RAM Battery Issue | Read | Active = alarm | |
| BV | 441 | 5120_1 | Master Unit Communication Lost | Read | Active = alarm | |
| BV | 442 | 5512_1 | Remote Shutdown | Read | Active = alarm | |
| BV | 443 | 5418_1 | Unit Code Missing | Read | Active = alarm | |
| BV | 454 | 5109_1_1 | Unit On | Read | Active = alarm | |
| BV | 455 | 5110_1_1 | Unit Off | Read | Active = alarm | |
| BV | 456 | 5111_1_1 | Unit Standby | Read | Active = alarm | |
| BV | 457 | 5112_1_1 | Unit Partial Shutdown | Read | Active = alarm | |
| BVmin | 458 | 5113_1_1 | Unit Shutdown | Read | Active = alarm | |
| BV | 459 | 5116_1_1 | Maintenance Due | Read | Active = alarm | |
| BV | 460 | 5117_1_1 | Maintenance Completed | Read | Active = alarm | |
| BV | 18000 | 5642_1 | SFA Reserved Event 1 | Read | Active = alarm | |
| BV | 18001 | 5643_1 | SFA Reserved Event 2 | Read | Active = alarm | |
| BV | 18002 | 5644_1 | SFA Reserved Event 3 | Read | Active = alarm | |
| BV | 18003 | 5645_1 | SFA Reserved Event 4 | Read | Active = alarm | |
| BV | 18004 | 5646_1 | SFA Reserved Event 5 | Read | Active = alarm | |
| BV | 18005 | 5647_1 | SFA Reserved Event 6 | Read | Active = alarm | |
| BV | 18006 | 5648_1 | SFA Reserved Event 7 | Read | Active = alarm | |
| BV | 18007 | 5649_1 | SFA Reserved Event 8 | Read | Active = alarm | |
| BV | 18008 | 5650_1 | SFA Reserved Event 9 | Read | Active = alarm | |
| BV | 18009 | 5651_1 | SFA Reserved Event 10 | Read | Active = alarm | |
| BV | 18010 | 5652_1 | SFA Reserved Event 11 | Read | Active = alarm | |
| BV | 18011 | 5653_1 | SFA Reserved Event 12 | Read | Active = alarm | |
| BV | 18012 | 5654_1 | SFA Reserved Event 13 | Read | Active = alarm | |
| BV | 18013 | 5655_1 | SFA Reserved Event 14 | Read | Active = alarm | |
| BV | 18014 | 5656_1 | SFA Reserved Event 15 | Read | Active = alarm | |
| BV | 18015 | 5657_1 | SFA Reserved Event 16 | Read | Active = alarm | |
| BV | 18016 | 5658_1 | SFA Reserved Event 17 | Read | Active = alarm | |
| BV | 18017 | 5659_1 | SFA Reserved Event 18 | Read | Active = alarm | |
| BV | 18018 | 5660_1 | SFA Reserved Event 19 | Read | Active = alarm | |
| BV | 18019 | 5661_1 | SFA Reserved Event 20 | Read | Active = alarm | |
| BV | 18020 | 5662_1 | SFA Reserved Event 21 | Read | Active = alarm | |
| BV | 18021 | 5663_1 | SFA Reserved Event 22 | Read | Active = alarm | |
| BV | 18022 | 5664_1 | SFA Reserved Event 23 | Read | Active = alarm | |
| BV | 18023 | 5665_1 | SFA Reserved Event 24 | Read | Active = alarm | |
| BV | 18024 | 5666_1 | SFA Reserved Event 25 | Read | Active = alarm | |
| BV | 71 | 6534_1_1 | Pump Thermal Overload (Pumps – Pump 1) | Read | Active = alarm | |
| BV | 82 | 6534_1_2 | Pump Thermal Overload (Pumps – Pump 2) | Read | Active = alarm | |
| AV | 1 | 4867_1 | Dew Point Temperature | °C | Read | |
| AV | 10001 | 4867_1_deg_F | Dew Point Temperature | °F | Read | |
| AV | 2 | 4709_1 | Minimum Room Temperature Set Point | °C | Write | |
| AV | 10002 | 4709_1_deg_F | Minimum Room Temperature Set Point | °F | Write | |
| AV | 3 | 4594_1 | Ext Air Sensor A Temperature | °C | Read | |
| AV | 10003 | 4594_1_deg_F | Ext Air Sensor A Temperature | °F | Read | |
| AV | 4 | 4595_1 | Ext Air Sensor A Humidity | %RH | Read | |
| AV | 5 | 4596_1 | Ext Air Sensor A Dew Point Temp | °C | Read | |
| AV | 10005 | 4596_1_deg_F | Ext Air Sensor A Dew Point Temp | °F | Read | |
| AV | 6 | 4597_1 | Ext Air Sensor B Temperature | °C | Read | |
| AV | 10006 | 4597_1_deg_F | Ext Air Sensor B Temperature | °F | Read | |
| AV | 7 | 4598_1 | Ext Air Sensor B Humidity | %RH | Read | |
| AV | 8 | 4599_1 | Ext Air Sensor B Dew Point Temp | °C | Read | |
| AV | 10008 | 4599_1_deg_F | Ext Air Sensor B Dew Point Temp | °F | Read | |
| AV | 9 | 4600_1 | Ext Air Over Temp Threshold | °C | Write | |
| AV | 10009 | 4600_1_deg_F | Ext Air Over Temp Threshold | °F | Write | |
| AV | 10 | 4607_1 | Ext Air Under Temp Threshold | °C | Write | |
| AV | 10010 | 4607_1_deg_F | Ext Air Under Temp Threshold | °F | Write | |
| AV | 11 | 4614_1 | Ext Dew Point Over Temp Threshold | °C | Write | |
| AV | 10011 | 4614_1_deg_F | Ext Dew Point Over Temp Threshold | °F | Write | |
| AVmin | 22 | 4624_1 | Supply Fluid Temperature (Chilled Water) | °C | Read | |
| AV | 10022 | 4624_1_deg_F | Supply Fluid Temperature (Chilled Water) | °F | Read | |
| AV | 23 | 4625_1 | High Supply Fluid Temperature Threshold | °C | Write | |
| AV | 10023 | 4625_1_deg_F | High Supply Fluid Temperature Threshold | °F | Write | |
| AV | 24 | 5640_1 | Chilled Water Valve Open Position | Read | ||
| AV | 46 | 4643_1 | Supply Fluid Temperature | °C | Read | |
| AV | 10046 | 4643_1_deg_F | Supply Fluid Temperature | °F | Read | |
| AV | 47 | 4644_1 | Supply Fluid Over Temp Threshold | °C | Write | |
| AV | 10047 | 4644_1_deg_F | Supply Fluid Over Temp Threshold | °F | Write | |
| AV | 58 | 5298_1_1 | Pump Hours (PumpHours) | h | Write | |
| AV | 59 | 5299_1_1 | Pump Hours Threshold (PumpHours) | h | Write | |
| AV | 70 | 5298_1_2 | Pump Hours (PumpHours) | h | Write | |
| AV | 71 | 5299_1_2 | Pump Hours Threshold (PumpHours) | h | Write | |
| AVmin | 94 | 5490_1 | Cooling Capacity (XDSystem) | % | Read | |
| AV | 95 | 5491_1 | Cooling Capacity (XDSystem) | kW | Read | |
| AV | 96 | 5503_1 | Hot Aisle Over Temp Threshold (XDSystem) | °C | Write | |
| AV | 10096 | 5503_1_deg_F | Hot Aisle Over Temp Threshold (XDSystem) | °F | Write | |
| AV | 97 | 5504_1 | Hot Aisle Under Temp Threshold (XDSystem) | °C | Write | |
| AV | 10097 | 5504_1_deg_F | Hot Aisle Under Temp Threshold (XDSystem) | °F | Write | |
| AV | 98 | 5506_1 | Cold Aisle Over Temp Threshold (XDSystem) | °C | Write | |
| AV | 10098 | 5506_1_deg_F | Cold Aisle Over Temp Threshold (XDSystem) | °F | Write | |
| AV | 99 | 5507_1 | Cold Aisle Under Temp Threshold (XDSystem) | °C | Write | |
| AV | 10099 | 5507_1_deg_F | Cold Aisle Under Temp Threshold (XDSystem) | °F | Write | |
| AV | 110 | 5059_1_1 | Sensor Temperature (Temperature Sensor 1) | °C | Read | |
| AV | 10110 | 5059_1_1_deg_F | Sensor Temperature (Temperature Sensor 1) | °F | Read | |
| AV | 121 | 5059_1_2 | Sensor Temperature (Temperature Sensor 2) | °C | Read | |
| AV | 10121 | 5059_1_2_deg_F | Sensor Temperature (Temperature Sensor 2) | °F | Read | |
| AV | 143 | 5059_1_4 | Sensor Temperature (Temperature Sensor 4) | °C | Read | |
| AV | 10143 | 5059_1_4_deg_F | Sensor Temperature (Temperature Sensor 4) | °F | Read | |
| AV | 154 | 5490_2 | Cooling Capacity (XDSystem 2) | % | Read | |
| AV | 155 | 5491_2 | Cooling Capacity (XDSystem 2) | kW | Read | |
| AV | 156 | 5503_2 | Hot Aisle Over Temp Threshold (XDSystem 2) | °C | Write | |
| AV | 10156 | 5503_2_deg_F | Hot Aisle Over Temp Threshold (XDSystem 2) | °F | Write | |
| AV | 157 | 5504_2 | Hot Aisle Under Temp Threshold (XDSystem 2) | °C | Write | |
| AV | 10157 | 5504_2_deg_F | Hot Aisle Under Temp Threshold (XDSystem 2) | °F | Write | |
| AV | 158 | 5506_2 | Cold Aisle Over Temp Threshold (XDSystem 2) | °C | Write | |
| AV | 10158 | 5506_2_deg_F | Cold Aisle Over Temp Threshold (XDSystem 2) | °F | Write | |
| AV | 159 | 5507_2 | Cold Aisle Under Temp Threshold (XDSystem 2) | °C | Write | |
| AV | 10159 | 5507_2_deg_F | Cold Aisle Under Temp Threshold (XDSystem 2) | °F | Write | |
| AV | 170 | 5059_2_1 | Sensor Temperature (Temperature Sensor 1) | °C | Read | |
| AV | 10170 | 5059_2_1_deg_F | Sensor Temperature (Temperature Sensor 1) | °F | Read | |
| AV | 181 | 5059_2_2 | Sensor Temperature (Temperature Sensor 2) | °C | Read | |
| AV | 10181 | 5059_2_2_deg_F | Sensor Temperature (Temperature Sensor 2) | °F | Read | |
| AV | 203 | 5059_2_4 | Sensor Temperature (Temperature Sensor 4) | °C | Read | |
| AV | 10203 | 5059_2_4_deg_F | Sensor Temperature (Temperature Sensor 4) | °F | Read | |
| AV | 1294 | 4710_1 | Auto Restart Delay | s | Write | |
| AV | 1295 | 4870_1 | Maintenance Ramp | % | Read | |
| AV | 1296 | 4868_1 | Calculated Next Maintenance Month | Read | ||
| AV | 1297 | 4869_1 | Calculated Next Maintenance Year | Read | ||
| AV | 1308 | 4293_1 | System Date and Time | Secs since Epoch(UTC) | Write | |
| AV | 18000 | 5641_1 | SFA ID Number | Generic | Read | |
| AV | 18001 | 5667_1 | SFA 16bit Read Only Value 1 | Generic | Read | |
| AV | 18002 | 5668_1 | SFA 16bit Read Only Value 2 | Generic | Read | |
| AV | 18003 | 5669_1 | SFA 16bit Read Only Value 3 | Generic | Read | |
| AV | 18004 | 5670_1 | SFA 16bit Read Only Value 4 | Generic | Read | |
| AV | 18005 | 5671_1 | SFA 16bit Read Only Value 5 | Generic | Read | |
| AV | 18006 | 5672_1 | SFA 16bit Read Only Value 6 | Generic | Read | |
| AV | 18007 | 5673_1 | SFA 16bit Read Only Value 7 | Generic | Read | |
| AV | 18008 | 5674_1 | SFA 16bit Read Only Value 8 | Generic | Read | |
| AV | 18009 | 5675_1 | SFA 16bit Read Only Value 9 | Generic | Read | |
| AV | 18010 | 5676_1 | SFA 16bit Read Only Value 10 | Generic | Read | |
| AV | 18011 | 5692_1 | SFA 32bit Read Only Value 1 | Generic | Read | |
| AV | 18012 | 5693_1 | SFA 32bit Read Only Value 2 | Generic | Read | |
| AV | 18013 | 5694_1 | SFA 32bit Read Only Value 3 | Generic | Read | |
| AV | 18014 | 5695_1 | SFA 32bit Read Only Value 4 | Generic | Read | |
| AV | 18015 | 5696_1 | SFA 32bit Read Only Value 5 | Generic | Read | |
| AV | 18016 | 5697_1 | SFA 32bit Read Only Value 6 | Generic | Read | |
| AV | 18017 | 5698_1 | SFA 32bit Read Only Value 7 | Generic | Read | |
| AV | 18018 | 5699_1 | SFA 32bit Read Only Value 8 | Generic | Read | |
| AV | 18019 | 5700_1 | SFA 32bit Read Only Value 9 | Generic | Read | |
| AV | 18020 | 5701_1 | SFA 32bit Read Only Value 10 | Generic | Read | |
| AV | 18021 | 5717_1 | SFA 16bit Writable Value 1 | Generic | Write | |
| AV | 18022 | 5718_1 | SFA 16bit Writable Value 2 | Generic | Write | |
| AV | 18023 | 5719_1 | SFA 16bit Writable Value 3 | Generic | Write | |
| AV | 18024 | 5720_1 | SFA 16bit Writable Value 4 | Generic | Write | |
| AV | 18025 | 5721_1 | SFA 16bit Writable Value 5 | Generic | Write | |
| AV | 18026 | 5722_1 | SFA 16bit Writable Value 6 | Generic | Write | |
| AV | 18027 | 5723_1 | SFA 16bit Writable Value 7 | Generic | Write | |
| AV | 18028 | 5724_1 | SFA 16bit Writable Value 8 | Generic | Write | |
| AV | 18029 | 5725_1 | SFA 16bit Writable Value 9 | Generic | Write | |
| AV | 18030 | 5726_1 | SFA 16bit Writable Value 10 | Generic | Write | |
| AV | 18031 | 5742_1 | SFA 32bit Writable Value 1 | Generic | Write | |
| AV | 18032 | 5743_1 | SFA 32bit Writable Value 2 | Generic | Write | |
| AV | 18033 | 5744_1 | SFA 32bit Writable Value 3 | Generic | Write | |
| AV | 18034 | 5745_1 | SFA 32bit Writable Value 4 | Generic | Write | |
| AV | 18035 | 5746_1 | SFA 32bit Writable Value 5 | Generic | Write | |
| AV | 18036 | 5747_1 | SFA 32bit Writable Value 6 | Generic | Write | |
| AV | 18037 | 5748_1 | SFA 32bit Writable Value 7 | Generic | Write | |
| AV | 18038 | 5749_1 | SFA 32bit Writable Value 8 | Generic | Write | |
| AV | 18039 | 5750_1 | SFA 32bit Writable Value 9 | Generic | Write | |
| AV | 18040 | 5751_1 | SFA 32bit Writable Value 10 | Generic | Write | |
| MV | 1 | 4602_1 | Ext Air Sensor A Over Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 2 | 4603_1 | Ext Air Sensor A Over Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 3 | 4605_1 | Ext Air Sensor B Over Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 4 | 4606_1 | Ext Air Sensor B Over Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 5 | 4609_1 | Ext Air Sensor A Under Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 6 | 4610_1 | Ext Air Sensor A Under Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 7 | 4612_1 | Ext Air Sensor B Under Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 8 | 4613_1 | Ext Air Sensor B Under Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 9 | 4616_1 | Ext Dew Point Over Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 10 | 4617_1 | Ext Dew Point Over Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 11 | 4619_1 | Ext Air Sensor A Issue - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 12 | 4620_1 | Ext Air Sensor A Issue - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 13 | 4622_1 | Ext Air Sensor B Issue - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 14 | 4623_1 | Ext Air Sensor B Issue - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 25 | 4627_1 | Supply CW Over Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 26 | 4628_1 | Supply CW Over Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 27 | 4630_1 | Supply CW Temp Sensor Issue - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 28 | 4631_1 | Supply CW Temp Sensor Issue - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 29 | 4704_1 | Chilled Water Cntrl Valve Pos - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 30 | 4705_1 | Chilled Water Cntrl Valve Pos - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 57 | 4646_1 | Supply Fluid Over Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 58 | 4647_1 | Supply Fluid Over Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 59 | 4649_1 | Supply Fluid Under Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 60 | 4650_1 | Supply Fluid Under Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 61 | 4652_1 | Supply Fluid Temp Sensor Issue - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 62 | 4653_1 | Supply Fluid Temp Sensor Issue - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 73 | 4654_1 | Pump 1 State | Read | 1=off, 2=on | |
| MV | 74 | 4655_1 | Pump 2 State | Read | 1=off, 2=on | |
| MV | 75 | 4657_1 | Pump 1 Loss of Flow - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 76 | 4658_1 | Pump 1 Loss of Flow - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 77 | 4660_1 | Pump 2 Loss of Flow - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 78 | 4661_1 | Pump 2 Loss of Flow - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 79 | 4663_1 | Pump Short Cycle - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 80 | 4664_1 | Pump Short Cycle - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 137 | 5486_1 | Communication Status (XDSystem) | Read | 1=Connected, 2=Not Connected | |
| MV | 138 | 5487_1 | Fan On/Off Control (XDSystem) | Write | 1=off, 2=on | |
| MV | 139 | 5509_1 | Master Fan Group State (XDSystem) | Read | 1=off, 2=on, 3=economy | |
| MV | 140 | 5488_1 | Fan Button Control (XDSystem) | Write | 1=enabled, 2=disabled | |
| MV | 141 | 5489_1 | Visual ID Control (XDSystem) | Write | 1=disabled, 2=enabled | |
| MV | 142 | 5493_1 | Ext System Condensation Detected - Event Control (XDSystem) | Write | 1=disabled, 2=enabled | |
| MV | 143 | 5494_1 | Ext System Condensation Detected - Event Type (XDSystem) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 144 | 5496_1 | Ext Fan Issue - Event Control (XDSystem) | Write | 1=disabled, 2=enabled | |
| MV | 145 | 5497_1 | Ext Fan Issue - Event Type (XDSystem) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 146 | 5498_1 | Sensor Issue - Event Control (XDSystem) | Write | 1=disabled, 2=enabled | |
| MV | 147 | 5499_1 | Sensor Issue - Event Type (XDSystem) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 148 | 5501_1 | Ext Remote Shutdown - Event Control (XDSystem) | Write | 1=disabled, 2=enabled | |
| MV | 149 | 5502_1 | Ext Remote Shutdown - Event Type (XDSystem) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 160 | 5510_1_1 | Fan State (XSsyst;em – Slave Fans 1) | Read | 1=off, 2=on, 3=economy | |
| MV | 161 | 5511_1_1 | Fan Economy Mode (XSsyst;em – Slave Fans 1) | Write | 1=disabled, 2=automatic, 3=manual | |
| MV | 172 | 5486_2 | Communication Status (XDSystem 2) | Read | 1=Connected, 2=Not Connected | |
| MV | 173 | 5487_2 | Fan On/Off Control (XDSystem 2) | Write | 1=off, 2=on | |
| MV | 174 | 5509_2 | Master Fan Group State (XDSystem 2) | Read | 1=off, 2=on, 3=economy | |
| MV | 175 | 5488_2 | Fan Button Control (XDSystem 2) | Write | 1=enabled, 2=disabled | |
| MV | 176 | 5489_2 | Visual ID Control (XDSystem 2) | Write | 1=disabled, 2=enabled | |
| MV | 177 | 5493_2 | Ext System Condensation Detected - Event Control (XDSystem 2) | Write | 1=disabled, 2=enabled | |
| MV | 178 | 5494_2 | Ext System Condensation Detected - Event Type (XDSystem 2) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 179 | 5496_2 | Ext Fan Issue - Event Control (XDSystem 2) | Write | 1=disabled, 2=enabled | |
| MV | 180 | 5497_2 | Ext Fan Issue - Event Type (XDSystem 2) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 181 | 5498_2 | Sensor Issue - Event Control (XDSystem 2) | Write | 1=disabled, 2=enabled | |
| MV | 182 | 5499_2 | Sensor Issue - Event Type (XDSystem 2) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 183 | 5501_2 | Ext Remote Shutdown - Event Control (XDSystem 2) | Write | 1=disabled, 2=enabled | |
| MV | 184 | 5502_2 | Ext Remote Shutdown - Event Type (XDSystem 2) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 195 | 5510_2_1 | Fan State (XDSystem – Slave Fans 1) | Read | 1=off, 2=on, 3=economy | |
| MV | 196 | 5511_2_1 | Fan Economy Mode (XDSystem – Slave Fans 1) | Write | 1=disabled, 2=automatic, 3=manual | |
| MVmin | 837 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation | |
| MVmin | 838 | 4706_1 | Unit Operating State | Read | 1=off, 2=on, 3=standby | |
| MV | 839 | 4707_1 | Unit Control Mode | Read | 1=Internal (Auto), 2=External (Manual) | |
| MV | 840 | 5074_1 | Unit Off Reason | Read | 1=None, 2=User, 3=Alarm, 4=Timer, 5=Monitoring, 6=Remote Off, 7=HCS12 Off | |
| MVmin | 841 | 5143_1 | System On/Off Control | Write | 1=off, 2=on | |
| MV | 852 | 4718_1 | Customer Input 1 - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 853 | 4719_1 | Customer Input 1 - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 854 | 4712_1 | System Condensation Detected - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 855 | 4713_1 | System Condensation Detected - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 856 | 4715_1 | Shutdown - Loss Of Power - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 857 | 4716_1 | Shutdown - Loss Of Power - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 858 | 4721_1 | Smoke Detected - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 859 | 4722_1 | Smoke Detected - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 860 | 4724_1 | Water Under Floor - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 861 | 4725_1 | Water Under Floor - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 862 | 4727_1 | Service Required - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 863 | 4728_1 | Service Required - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 864 | 4730_1 | Fan Issue - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 865 | 4731_1 | Fan Issue - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MVmin | 876 | 4717_1 | System Event Acknowledge/Reset | Write | 1=Reset, 2=Acknowledge |
No points match these filters.
Object ID lookup: Vertiv Liebert DCP point IDs by name
BV14601_1BV24604_1BV34608_1BV44611_1BV54615_1BV64618_1BV74621_1BV184626_1BV194629_1BV204703_1BV444645_1BV454648_1BV464651_1BV574656_1BV584659_1BV594662_1BV705300_1_1BV815300_1_2BV1125492_1BV1135495_1BV1145060_1BV1155500_1BV1165505_1BV1175508_1BV1186535_1BV1285492_2BV1295495_2BV1305060_2BV1315500_2BV1325505_2BV1335508_2BV1346535_2BV4324270_1BV4334711_1BV4344714_1BV4354720_1BV4364723_1BV4374726_1BV4384729_1BV4395419_1BV4405119_1BV4415120_1BV4425512_1BV4435418_1BV4545109_1_1BV4555110_1_1BV4565111_1_1BV4575112_1_1BV4585113_1_1BV4595116_1_1BV4605117_1_1BV180005642_1BV180015643_1BV180025644_1BV180035645_1BV180045646_1BV180055647_1BV180065648_1BV180075649_1BV180085650_1BV180095651_1BV180105652_1BV180115653_1BV180125654_1BV180135655_1BV180145656_1BV180155657_1BV180165658_1BV180175659_1BV180185660_1BV180195661_1BV180205662_1BV180215663_1BV180225664_1BV180235665_1BV180245666_1BV716534_1_1BV826534_1_2AV14867_1AV100014867_1_deg_FAV24709_1AV100024709_1_deg_FAV34594_1AV100034594_1_deg_FAV44595_1AV54596_1AV100054596_1_deg_FAV64597_1AV100064597_1_deg_FAV74598_1AV84599_1AV100084599_1_deg_FAV94600_1AV100094600_1_deg_FAV104607_1AV100104607_1_deg_FAV114614_1AV100114614_1_deg_FAV224624_1AV100224624_1_deg_FAV234625_1AV100234625_1_deg_FAV245640_1AV464643_1AV100464643_1_deg_FAV474644_1AV100474644_1_deg_FAV585298_1_1AV595299_1_1AV705298_1_2AV715299_1_2AV945490_1AV955491_1AV965503_1AV100965503_1_deg_FAV975504_1AV100975504_1_deg_FAV985506_1AV100985506_1_deg_FAV995507_1AV100995507_1_deg_FAV1105059_1_1AV101105059_1_1_deg_FAV1215059_1_2AV101215059_1_2_deg_FAV1435059_1_4AV101435059_1_4_deg_FAV1545490_2AV1555491_2AV1565503_2AV101565503_2_deg_FAV1575504_2AV101575504_2_deg_FAV1585506_2AV101585506_2_deg_FAV1595507_2AV101595507_2_deg_FAV1705059_2_1AV101705059_2_1_deg_FAV1815059_2_2AV101815059_2_2_deg_FAV2035059_2_4AV102035059_2_4_deg_FAV12944710_1AV12954870_1AV12964868_1AV12974869_1AV13084293_1AV180005641_1AV180015667_1AV180025668_1AV180035669_1AV180045670_1AV180055671_1AV180065672_1AV180075673_1AV180085674_1AV180095675_1AV180105676_1AV180115692_1AV180125693_1AV180135694_1AV180145695_1AV180155696_1AV180165697_1AV180175698_1AV180185699_1AV180195700_1AV180205701_1AV180215717_1AV180225718_1AV180235719_1AV180245720_1AV180255721_1AV180265722_1AV180275723_1AV180285724_1AV180295725_1AV180305726_1AV180315742_1AV180325743_1AV180335744_1AV180345745_1AV180355746_1AV180365747_1AV180375748_1AV180385749_1AV180395750_1AV180405751_1MV14602_1MV24603_1MV34605_1MV44606_1MV54609_1MV64610_1MV74612_1MV84613_1MV94616_1MV104617_1MV114619_1MV124620_1MV134622_1MV144623_1MV254627_1MV264628_1MV274630_1MV284631_1MV294704_1MV304705_1MV574646_1MV584647_1MV594649_1MV604650_1MV614652_1MV624653_1MV734654_1MV744655_1MV754657_1MV764658_1MV774660_1MV784661_1MV794663_1MV804664_1MV1375486_1MV1385487_1MV1395509_1MV1405488_1MV1415489_1MV1425493_1MV1435494_1MV1445496_1MV1455497_1MV1465498_1MV1475499_1MV1485501_1MV1495502_1MV1605510_1_1MV1615511_1_1MV1725486_2MV1735487_2MV1745509_2MV1755488_2MV1765489_2MV1775493_2MV1785494_2MV1795496_2MV1805497_2MV1815498_2MV1825499_2MV1835501_2MV1845502_2MV1955510_2_1MV1965511_2_1MV8374123_1MV8384706_1MV8394707_1MV8405074_1MV8415143_1MV8524718_1MV8534719_1MV8544712_1MV8554713_1MV8564715_1MV8574716_1MV8584721_1MV8594722_1MV8604724_1MV8614725_1MV8624727_1MV8634728_1MV8644730_1MV8654731_1MV8764717_1
Integration notes
- Tables 5.40, 5.41, 5.42, pdf pages 1487-1500 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert DCP (Liebert XD system unit) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert DCP (Liebert XD system unit)
How many BACnet points does the Vertiv Liebert DCP (Liebert XD system unit) have?
This list has 273 BACnet objects: 111 analog values, 78 binary values, 84 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert DCP (Liebert XD system unit) BACnet points are writable?
126 of the 273 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert DCP (Liebert XD system unit) BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert DCP (Liebert XD system unit)?
Start with MV 841 5143_1 (On/off command (1=off, 2=on)); MV 876 4717_1 (Acknowledge / reset events); MV 838 4706_1 (Run / standby / off state); MV 837 4123_1 (Normal, warning or alarm state); AV 22 4624_1 (Supply fluid temperature, °C); AV 94 5490_1 (Cooling output, %); BV 458 5113_1_1 (Unit shut down by an event).
How do I check these points on the real Liebert DCP (Liebert XD system unit)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.