Power distribution unit (PDU) monitoring · BACnet points list

Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller) BACnet points list

Updated 6 November 2026

Short answer

The Liebert FDC / FPC / PPC / RDC power distribution reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, output, panel and branch circuit electrical data, Binary Values carry events and Multi-state Values carry status, breaker states and resets. Panel and branch objects repeat per panel and branch, so the list is long.

This page lists 102 BACnet objects for the Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller) — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Equipment
Power distribution unit (PDU) monitoring
Equipment type
Other equipment
BACnet objects
102 (4 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 102 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 134717_1Acknowledge / reset eventsWrite
MV 124123_1Normal, warning or alarm stateRead
AV 1075187_1Panel 1 main voltage X-YRead
AV 1195199_1Panel 1 output power, kWRead
AV 1225202_1Panel 1 load, %Read
BV 655212_1Panel 1 summary alarmRead

Network setup

Watch out for

Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

102 of 102 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller) BACnet Points List
DescriptionStates
BVmin655212_1Panel Summary Alarm (Panel 1)ReadActive = alarm
BV665213_1Panel Overvoltage (Panel 1)ReadActive = alarm
BV675214_1Panel Undervoltage (Panel 1)ReadActive = alarm
BV685215_1Panel Phase Overcurrent (Panel 1)ReadActive = alarm
BV695216_1Panel Neutral Overcurrent (Panel 1)ReadActive = alarm
BV705217_1Panel Ground Overcurrent (Panel 1)ReadActive = alarm
BV10895212_2Panel Summary Alarm (Panel 2)ReadActive = alarm
BV10905213_2Panel Overvoltage (Panel 2)ReadActive = alarm
BV10915214_2Panel Undervoltage (Panel 2)ReadActive = alarm
BV10925215_2Panel Phase Overcurrent (Panel 2)ReadActive = alarm
BV10935216_2Panel Neutral Overcurrent (Panel 2)ReadActive = alarm
BV10945217_2Panel Ground Overcurrent (Panel 2)ReadActive = alarm
BV31375212_4Panel Summary Alarm (Panel 4)ReadActive = alarm
BV31385213_4Panel Overvoltage (Panel 4)ReadActive = alarm
BV31395214_4Panel Undervoltage (Panel 4)ReadActive = alarm
BV31405215_4Panel Phase Overcurrent (Panel 4)ReadActive = alarm
BV31415216_4Panel Neutral Overcurrent (Panel 4)ReadActive = alarm
BV31425217_4Panel Ground Overcurrent (Panel 4)ReadActive = alarm
AV1055515_1Columns of Breakers (Panel 1)Read
AV1065516_1Number of Breakers (Panel 1)Read
AVmin1075187_1Panel Main Voltage X-Y (Panel 1)VRead
AV1085188_1Panel Main Voltage Y-Z (Panel 1)VRead
AV1095189_1Panel Main Voltage Z-X (Panel 1)VRead
AV1105190_1Panel Main Voltage X-N (Panel 1)VRead
AV1115191_1Panel Main Voltage Y-N (Panel 1)VRead
AV1125192_1Panel Main Voltage Z-N (Panel 1)VRead
AV1135193_1Panel Main Current Ix (Panel 1)ARead
AV1145194_1Panel Main Current Iy (Panel 1)ARead
AV1155195_1Panel Main Current Iz (Panel 1)ARead
AV1165196_1Panel Main Neutral Current (Panel 1)ARead
AV1175197_1Panel Main Ground Current (Panel 1)ARead
AV1185198_1Panel Main Output Power (kVA) (Panel 1)kVARead
AVmin1195199_1Panel Main Output Power (kW) (Panel 1)kWRead
AV1205200_1Panel Main Output kW-Hrs (Panel 1)kWhWrite
AV1215201_1Panel Main Output Power Factor (Panel 1)Read
AVmin1225202_1Panel Main Output Percent Load (Panel 1)%Read
AV1235203_1Panel Main Voltage Vx THD (Panel 1)%Read
AV1245204_1Panel Main Voltage Vy THD (Panel 1)%Read
AV1255205_1Panel Main Voltage Vz THD (Panel 1)%Read
AV1265206_1Panel Main Current Ix THD (Panel 1)%Read
AV1275207_1Panel Main Current Iy THD (Panel 1)%Read
AV1285208_1Panel Main Current Iz THD (Panel 1)%Read
AV1295209_1Panel Main Current Ix Crest Factor (Panel 1)Read
AV1305210_1Panel Main Current Iy Crest Factor (Panel 1)Read
AV1315211_1Panel Main Current Iz Crest Factor (Panel 1)Read
AV16545515_2Columns of Breakers (Panel 2)Read
AV16555516_2Number of Breakers (Panel 2)Read
AV16565187_2Panel Main Voltage X-Y (Panel 2)VRead
AV16575188_2Panel Main Voltage Y-Z (Panel 2)VRead
AV16585189_2Panel Main Voltage Z-X (Panel 2)VRead
AV16595190_2Panel Main Voltage X-N (Panel 2)VRead
AV16605191_2Panel Main Voltage Y-N (Panel 2)VRead
AV16615192_2Panel Main Voltage Z-N (Panel 2)VRead
AV16625193_2Panel Main Current Ix (Panel 2)ARead
AV16635194_2Panel Main Current Iy (Panel 2)ARead
AV16645195_2Panel Main Current Iz (Panel 2)ARead
AV16655196_2Panel Main Neutral Current (Panel 2)ARead
AV16665197_2Panel Main Ground Current (Panel 2)ARead
AV16675198_2Panel Main Output Power (kVA) (Panel 2)kVARead
AV16685199_2Panel Main Output Power (kW) (Panel 2)kWRead
AV16695200_2Panel Main Output kW-Hrs (Panel 2)kWhWrite
AV16705201_2Panel Main Output Power Factor (Panel 2)Read
AV16715202_2Panel Main Output Percent Load (Panel 2)%Read
AV16725203_2Panel Main Voltage Vx THD (Panel 2)%Read
AV16735204_2Panel Main Voltage Vy THD (Panel 2)%Read
AV16745205_2Panel Main Voltage Vz THD (Panel 2)%Read
AV16755206_2Panel Main Current Ix THD (Panel 2)%Read
AV16765207_2Panel Main Current Iy THD (Panel 2)%Read
AV16775208_2Panel Main Current Iz THD (Panel 2)%Read
AV16785209_2Panel Main Current Ix Crest Factor (Panel 2)Read
AV16795210_2Panel Main Current Iy Crest Factor (Panel 2)Read
AV16805211_2Panel Main Current Iz Crest Factor (Panel 2)Read
AV47525515_4Columns of Breakers (Panel 4)Read
AV47535516_4Number of Breakers (Panel 4)Read
AV47545187_4Panel Main Voltage X-Y (Panel 4)VRead
AV47555188_4Panel Main Voltage Y-Z (Panel 4)VRead
AV47565189_4Panel Main Voltage Z-X (Panel 4)VRead
AV47575190_4Panel Main Voltage X-N (Panel 4)VRead
AV47585191_4Panel Main Voltage Y-N (Panel 4)VRead
AV47595192_4Panel Main Voltage Z-N (Panel 4)VRead
AV47605193_4Panel Main Current Ix (Panel 4)ARead
AV47615194_4Panel Main Current Iy (Panel 4)ARead
AV47625195_4Panel Main Current Iz (Panel 4)ARead
AV47635196_4Panel Main Neutral Current (Panel 4)ARead
AV47645197_4Panel Main Ground Current (Panel 4)ARead
AV47655198_4Panel Main Output Power (kVA) (Panel 4)kVARead
AV47665199_4Panel Main Output Power (kW) (Panel 4)kWRead
AV47675200_4Panel Main Output kW-Hrs (Panel 4)kWhWrite
AV47685201_4Panel Main Output Power Factor (Panel 4)Read
AV47695202_4Panel Main Output Percent Load (Panel 4)%Read
AV47705203_4Panel Main Voltage Vx THD (Panel 4)%Read
AV47715204_4Panel Main Voltage Vy THD (Panel 4)%Read
AV47725205_4Panel Main Voltage Vz THD (Panel 4)%Read
AV47735206_4Panel Main Current Ix THD (Panel 4)%Read
AV47745207_4Panel Main Current Iy THD (Panel 4)%Read
AV47755208_4Panel Main Current Iz THD (Panel 4)%Read
AV47765209_4Panel Main Current Ix Crest Factor (Panel 4)Read
AV47775210_4Panel Main Current Iy Crest Factor (Panel 4)Read
AV47785211_4Panel Main Current Iz Crest Factor (Panel 4)Read
MV14553_1Server ClassRead1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR
MVmin124123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MVmin134717_1System Event Acknowledge/ResetWrite1=Reset, 2=Acknowledge
Object ID lookup: Vertiv Liebert FDC / FPC / PPC / RDC power distribution point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert FDC / FPC / PPC / RDC power distribution (CPM controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)

How many BACnet points does the Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller) have?

This list has 102 BACnet objects: 81 analog values, 18 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller) BACnet points are writable?

4 of the 102 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller) BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)?

Start with MV 13 4717_1 (Acknowledge / reset events); MV 12 4123_1 (Normal, warning or alarm state); AV 107 5187_1 (Panel 1 main voltage X-Y); AV 119 5199_1 (Panel 1 output power, kW); AV 122 5202_1 (Panel 1 load, %); BV 65 5212_1 (Panel 1 summary alarm).

How do I check these points on the real Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.