- Home
- BACnet points lists
- Vertiv
- Liebert NXL 60 Hz UPS (UL, model 40)
UPS (uninterruptible power supply) · BACnet points list
Vertiv Liebert NXL 60 Hz UPS (UL, model 40) BACnet points list
Updated 6 November 2026
The Liebert NXL 60 Hz UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.
This page lists 363 BACnet objects for the Vertiv Liebert NXL 60 Hz UPS (UL, model 40) — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert NXL 60 Hz UPS (UL, model 40)
- Equipment
- UPS (uninterruptible power supply)
- Equipment type
- Other equipment
- BACnet objects
- 363 (4 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Liebert NXL, NXL model 40, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 91 | 4123_1 | Normal, warning or alarm state | Read |
| MV 92 | 4872_1 | Load on inverter, bypass or battery | Read |
| AV 55 | 4150_1 | Estimated battery runtime, min | Read |
| AV 94 | 4208_1 | Output power, kW | Read |
| AV 1 | 4097_1 | Input voltage, V | Read |
| AV 84 | 4201_1 | Output voltage, V | Read |
| AV 90 | 4204_1 | Output current, A | Read |
| BV 43 | 4168_1 | Load is on battery | Read |
| BV 178 | 4300_1 | Internal communication lost | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert NXL 60 Hz UPS (UL, model 40) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | 4122_1 | System Input Power Problem | Read | Active = alarm | |
| BV | 2 | 4146_1 | System Input Phs Rotation Error | Read | Active = alarm | |
| BV | 3 | 4147_1 | System Input Current Limit | Read | Active = alarm | |
| BV | 4 | 4382_1 | System Input Current Imbalance | Read | Active = alarm | |
| BV | 15 | 4135_1 | Bypass Not Available | Read | Active = alarm | |
| BV | 16 | 4132_1 | Bypass Overload Phase A | Read | Active = alarm | |
| BV | 17 | 4133_1 | Bypass Overload Phase B | Read | Active = alarm | |
| BV | 18 | 4134_1 | Bypass Overload Phase C | Read | Active = alarm | |
| BV | 19 | 4138_1 | Bypass Auto Retransfer Failed | Read | Active = alarm | |
| BV | 20 | 4139_1 | Bypass - Excess Auto Retransfers | Read | Active = alarm | |
| BV | 21 | 4142_1 | Bypass Static Switch Overload | Read | Active = alarm | |
| BV | 22 | 4143_1 | Bypass Static Switch Unavailable | Read | Active = alarm | |
| BV | 23 | 4144_1 | Bypass Excessive Pulse Parallel | Read | Active = alarm | |
| BV | 24 | 4145_1 | Bypass Auto Transfer Failed | Read | Active = alarm | |
| BV | 25 | 4175_1 | Bypass Frequency Error | Read | Active = alarm | |
| BV | 26 | 4218_1 | Bypass - Manual Rexfr Inhibited | Read | Active = alarm | |
| BV | 27 | 4217_1 | Bypass - Manual Xfr Inhibited | Read | Active = alarm | |
| BV | 28 | 4383_1 | Bypass Static Switch Off Extrnl | Read | Active = alarm | |
| BV | 39 | 4164_1 | Battery Charging Error | Read | Active = alarm | |
| BV | 40 | 4740_1 | Battery Test Inhibited | Read | Active = alarm | |
| BV | 41 | 4165_1 | Battery Charging Reduced-Extrnl | Read | Active = alarm | |
| BV | 42 | 4166_1 | Battery Capacity Low | Read | Active = alarm | |
| BVmin | 43 | 4168_1 | Battery Discharging | Read | Active = alarm | |
| BV | 44 | 4169_1 | Battery Temperature Imbalance | Read | Active = alarm | |
| BV | 45 | 4170_1 | Battery Equalize | Read | Active = alarm | |
| BV | 46 | 4741_1 | Battery Self Test | Read | Active = alarm | |
| BV | 47 | 4173_1 | Main Battery Disconnect Open | Read | Active = alarm | |
| BV | 48 | 4162_1 | Battery Low | Read | Active = alarm | |
| BV | 49 | 4174_1 | Battery Temperature Sensor Fault | Read | Active = alarm | |
| BV | 50 | 4200_1 | Battery Charging Inhibited | Read | Active = alarm | |
| BV | 51 | 4176_1 | Battery Circuit Breaker 1 Open | Read | Active = alarm | |
| BV | 52 | 4179_1 | Battery Circuit Breaker 2 Open | Read | Active = alarm | |
| BV | 53 | 4182_1 | Battery Circuit Breaker 3 Open | Read | Active = alarm | |
| BV | 54 | 4185_1 | Battery Circuit Breaker 4 Open | Read | Active = alarm | |
| BV | 55 | 4188_1 | Battery Circuit Breaker 5 Open | Read | Active = alarm | |
| BV | 56 | 4191_1 | Battery Circuit Breaker 6 Open | Read | Active = alarm | |
| BV | 57 | 4194_1 | Battery Circuit Breaker 7 Open | Read | Active = alarm | |
| BV | 58 | 4197_1 | Battery Circuit Breaker 8 Open | Read | Active = alarm | |
| BV | 59 | 4220_1 | Battery - External Monitor 1 | Read | Active = alarm | |
| BV | 60 | 4221_1 | Battery - External Monitor 2 | Read | Active = alarm | |
| BV | 61 | 4222_1 | Battery Ground Fault | Read | Active = alarm | |
| BV | 62 | 4742_1 | Battery Low Shutdown | Read | Active = alarm | |
| BV | 63 | 4219_1 | Battery Over Temperature | Read | Active = alarm | |
| BV | 64 | 4323_1 | Battery Test Failed | Read | Active = alarm | |
| BV | 65 | 6354_1 | Battery Charging | Read | Active = alarm | |
| BV | 75 | 4308_1 | DC Bus Ground Fault - Positive | Read | Active = alarm | |
| BV | 76 | 4309_1 | DC Bus Ground Fault - Negative | Read | Active = alarm | |
| BV | 87 | 4213_1 | System Shutdown - EPO | Read | Active = alarm | |
| BV | 88 | 4214_1 | System Shutdown - REPO | Read | Active = alarm | |
| BV | 89 | 4215_1 | System Output Off | Read | Active = alarm | |
| BV | 90 | 4230_1 | System Output Low Power Factor | Read | Active = alarm | |
| BV | 91 | 4286_1 | Output Amp Over User Limit-Phs A | Read | Active = alarm | |
| BV | 92 | 4287_1 | Output Amp Over User Limit-Phs B | Read | Active = alarm | |
| BV | 93 | 4288_1 | Output Amp Over User Limit-Phs C | Read | Active = alarm | |
| BV | 94 | 4389_1 | System Output Fault | Read | Active = alarm | |
| BV | 95 | 5144_1 | Output Of/Uf | Read | Active = alarm | |
| BV | 106 | 4233_1 | Inverter Failure | Read | Active = alarm | |
| BV | 107 | 4234_1 | Inverter Overload Phase A | Read | Active = alarm | |
| BV | 108 | 4235_1 | Inverter Overload Phase B | Read | Active = alarm | |
| BV | 109 | 4236_1 | Inverter Overload Phase C | Read | Active = alarm | |
| BV | 110 | 4237_1 | Inverter Inhibit - External | Read | Active = alarm | |
| BV | 111 | 4290_1 | Inverter Shutdown - Overload | Read | Active = alarm | |
| BV | 112 | 4390_1 | Inverter Off - External | Read | Active = alarm | |
| BV | 113 | 4391_1 | Inverter Static Switch SCR Short | Read | Active = alarm | |
| BV | 124 | 4294_1 | Inlet Air Over Temperature | Read | Active = alarm | |
| BV | 125 | 5768_1 | Outlet Air Overtemperature Limit | Read | Active = alarm | |
| BV | 126 | 4747_1 | Equipment Temperature Sensor Fail | Read | Active = alarm | |
| BV | 127 | 4310_1 | Equipment Over Temperature | Read | Active = alarm | |
| BV | 138 | 4270_1 | Input Contact 01 | Read | Active = alarm | |
| BV | 139 | 4271_1 | Input Contact 02 | Read | Active = alarm | |
| BV | 140 | 4272_1 | Input Contact 03 | Read | Active = alarm | |
| BV | 141 | 4273_1 | Input Contact 04 | Read | Active = alarm | |
| BV | 142 | 4274_1 | Input Contact 05 | Read | Active = alarm | |
| BV | 143 | 4275_1 | Input Contact 06 | Read | Active = alarm | |
| BV | 144 | 4276_1 | Input Contact 07 | Read | Active = alarm | |
| BV | 145 | 4277_1 | Input Contact 08 | Read | Active = alarm | |
| BV | 146 | 4278_1 | Input Contact 09 | Read | Active = alarm | |
| BV | 147 | 4279_1 | Input Contact 10 | Read | Active = alarm | |
| BV | 148 | 4280_1 | Input Contact 11 | Read | Active = alarm | |
| BV | 149 | 4281_1 | Input Contact 12 | Read | Active = alarm | |
| BV | 150 | 4282_1 | Input Contact 13 | Read | Active = alarm | |
| BV | 151 | 4283_1 | Input Contact 14 | Read | Active = alarm | |
| BV | 152 | 4284_1 | Input Contact 15 | Read | Active = alarm | |
| BV | 153 | 4285_1 | Input Contact 16 | Read | Active = alarm | |
| BV | 164 | 4295_1 | Rectifier Failure | Read | Active = alarm | |
| BV | 165 | 4296_1 | Rectifier Operation Inhibit-Ext | Read | Active = alarm | |
| BV | 176 | 4749_1 | System Fan Failure - Redundant | Read | Active = alarm | |
| BV | 177 | 4750_1 | Multiple Fan Failure | Read | Active = alarm | |
| BVmin | 178 | 4300_1 | Internal Communications Failure | Read | Active = alarm | |
| BV | 179 | 4298_1 | UPS Output on Bypass | Read | Active = alarm | |
| BV | 180 | 4299_1 | Output Load on Maint. Bypass | Read | Active = alarm | |
| BV | 181 | 4325_1 | Backfeed Breaker Open | Read | Active = alarm | |
| BV | 182 | 4316_1 | Auto Restart In Progress | Read | Active = alarm | |
| BV | 183 | 4314_1 | Power Supply Failure | Read | Active = alarm | |
| BV | 184 | 4315_1 | On Generator | Read | Active = alarm | |
| BV | 185 | 4317_1 | Auto Restart Inhibited - Ext | Read | Active = alarm | |
| BV | 186 | 4439_1 | Automatic Restart Failed | Read | Active = alarm | |
| BV | 187 | 4753_1 | Main Controller Fault | Read | Active = alarm | |
| BV | 188 | 4440_1 | Fuse Failure | Read | Active = alarm | |
| BV | 189 | 4441_1 | System Controller Error | Read | Active = alarm | |
| BV | 190 | 4442_1 | System Breaker(s) Open Failure | Read | Active = alarm | |
| BV | 191 | 4754_1 | System Breaker(s) Close Failure | Read | Active = alarm | |
| BV | 192 | 4755_1 | Input Filter Cycle Lock | Read | Active = alarm | |
| BV | 193 | 5769_1 | EMO Shutdown | Read | Active = alarm | |
| BV | 194 | 4756_1 | Service Code Active | Read | Active = alarm | |
| BV | 195 | 4757_1 | LBS Active | Read | Active = alarm | |
| BV | 196 | 4758_1 | LBS Inhibited | Read | Active = alarm | |
| BV | 197 | 4759_1 | Leading Power Factor | Read | Active = alarm | |
| BV | 198 | 4760_1 | Controls Reset Required | Read | Active = alarm | |
| BV | 199 | 5561_1 | LBS Active - Master | Read | Active = alarm | |
| BV | 200 | 5562_1 | LBS Active - Slave | Read | Active = alarm | |
| BV | 201 | 5788_1 | Cont Tie Active | Read | Active = alarm | |
| BV | 202 | 5792_1 | User kWh Reset | Read | Active = alarm | |
| BV | 203 | 5796_1 | Peak kW Reset | Read | Active = alarm | |
| BV | 214 | 4823_1 | Parallel Comm Warning | Read | Active = alarm | |
| BV | 215 | 4824_1 | System Comm Fail | Read | Active = alarm | |
| BV | 216 | 4825_1 | Loss of Redundancy | Read | Active = alarm | |
| BV | 217 | 4826_1 | BPSS Startup Inhibit | Read | Active = alarm | |
| BV | 218 | 4827_1 | MMS Transfer Inhibit | Read | Active = alarm | |
| BV | 219 | 4828_1 | MMS Retransfer Inhibit | Read | Active = alarm | |
| BV | 220 | 4830_1 | MMS Loss of Sync Pulse | Read | Active = alarm | |
| BV | 221 | 4831_1 | MMS Overload | Read | Active = alarm | |
| BV | 222 | 4834_1 | MMS On Battery | Read | Active = alarm | |
| BV | 223 | 4835_1 | MMS Low Battery Warning | Read | Active = alarm | |
| BV | 224 | 5145_1 | MMS Module Alarm Active | Read | Active = alarm | |
| BV | 225 | 5447_1 | MMS Sharing Calib Active | Read | Active = alarm | |
| BV | 236 | 5453_1 | Module In Standby - Intelligent Paralleling | Read | Active = alarm | |
| BV | 247 | 5456_1 | ECO Mode Active | Read | Active = alarm | |
| BV | 248 | 5457_1 | ECO Mode Suspended | Read | Active = alarm | |
| BV | 249 | 5458_1 | Excess ECO Suspends | Read | Active = alarm | |
| BV | 260 | 4726_1 | Service Required | Read | Active = alarm | |
| AVmin | 1 | 4097_1 | System Input RMS A-B | V | Read | |
| AV | 2 | 4099_1 | System Input RMS B-C | V | Read | |
| AV | 3 | 4101_1 | System Input RMS C-A | V | Read | |
| AV | 4 | 4113_1 | System Input RMS Current Phase A | A | Read | |
| AV | 5 | 4114_1 | System Input RMS Current Phase B | A | Read | |
| AV | 6 | 4115_1 | System Input RMS Current Phase C | A | Read | |
| AV | 7 | 4105_1 | System Input Frequency | Hz | Read | |
| AV | 18 | 4125_1 | Bypass Input Voltage RMS A-B | V | Read | |
| AV | 19 | 4126_1 | Bypass Input Voltage RMS B-C | V | Read | |
| AV | 20 | 4127_1 | Bypass Input Voltage RMS C-A | V | Read | |
| AV | 21 | 4131_1 | Bypass Input Frequency | Hz | Read | |
| AV | 22 | 4136_1 | Bypass Sync Phase Difference | deg | Read | |
| AV | 23 | 4157_1 | Bypass SS Overload Time Remain | s | Read | |
| AV | 24 | 4738_1 | Auto Retransfer Time Remaining | s | Read | |
| AV | 25 | 6456_1 | Total Bypass Operating Time | h | Read | |
| AV | 35 | 4152_1 | Battery Total Discharge Time | h | Read | |
| AV | 36 | 4153_1 | Battery Percentage Charge | Read | ||
| AV | 37 | 4154_1 | Battery Volts at Main Disconnect | VDC | Read | |
| AV | 38 | 4155_1_1 | Battery Volts for Cabinet 1 | VDC | Read | |
| AV | 39 | 4155_1_2 | Battery Volts for Cabinet 2 | VDC | Read | |
| AV | 40 | 4155_1_3 | Battery Volts for Cabinet 3 | VDC | Read | |
| AV | 41 | 4155_1_4 | Battery Volts for Cabinet 4 | VDC | Read | |
| AV | 42 | 4155_1_5 | Battery Volts for Cabinet 5 | VDC | Read | |
| AV | 43 | 4155_1_6 | Battery Volts for Cabinet 6 | VDC | Read | |
| AV | 44 | 4155_1_7 | Battery Volts for Cabinet 7 | VDC | Read | |
| AV | 45 | 4155_1_8 | Battery Volts for Cabinet 8 | VDC | Read | |
| AV | 46 | 4156_1_1 | Battery Temperature for Cabinet 1 | °C | Read | |
| AV | 10046 | 4156_1_1_deg_F | Battery Temperature for Cabinet 1 | °F | Read | |
| AV | 47 | 4156_1_2 | Battery Temperature for Cabinet 2 | °C | Read | |
| AV | 10047 | 4156_1_2_deg_F | Battery Temperature for Cabinet 2 | °F | Read | |
| AV | 48 | 4156_1_3 | Battery Temperature for Cabinet 3 | °C | Read | |
| AV | 10048 | 4156_1_3_deg_F | Battery Temperature for Cabinet 3 | °F | Read | |
| AV | 49 | 4156_1_4 | Battery Temperature for Cabinet 4 | °C | Read | |
| AV | 10049 | 4156_1_4_deg_F | Battery Temperature for Cabinet 4 | °F | Read | |
| AV | 50 | 4156_1_5 | Battery Temperature for Cabinet 5 | °C | Read | |
| AV | 10050 | 4156_1_5_deg_F | Battery Temperature for Cabinet 5 | °F | Read | |
| AV | 51 | 4156_1_6 | Battery Temperature for Cabinet 6 | °C | Read | |
| AV | 10051 | 4156_1_6_deg_F | Battery Temperature for Cabinet 6 | °F | Read | |
| AV | 52 | 4156_1_7 | Battery Temperature for Cabinet 7 | °C | Read | |
| AV | 10052 | 4156_1_7_deg_F | Battery Temperature for Cabinet 7 | °F | Read | |
| AV | 53 | 4156_1_8 | Battery Temperature for Cabinet 8 | °C | Read | |
| AV | 10053 | 4156_1_8_deg_F | Battery Temperature for Cabinet 8 | °F | Read | |
| AV | 54 | 4739_1 | Battery Amp-Hours Consumed This Discharge | AH | Read | |
| AVmin | 55 | 4150_1 | Battery Time Remaining | min | Read | |
| AV | 56 | 4151_1 | Battery Discharge Time | s | Read | |
| AV | 57 | 4159_1 | Battery Discharge Power | W | Read | |
| AV | 58 | 4161_1 | Battery Last Discharge Date | Read | ||
| AV | 59 | 4160_1 | Battery Commission Date | Read | ||
| AV | 60 | 4158_1 | Battery Amp-Hours Consumed | AH | Read | |
| AV | 61 | 5767_1 | Total Number of Battery Discharges | Read | ||
| AV | 72 | 4148_1 | DC Bus Voltage | VDC | Read | |
| AV | 73 | 4149_1 | DC Bus Current | A DC | Read | |
| AVmin | 84 | 4201_1 | System Output Voltage RMS A-B | V | Read | |
| AV | 85 | 4202_1 | System Output Voltage RMS B-C | V | Read | |
| AV | 86 | 4203_1 | System Output Voltage RMS C-A | V | Read | |
| AV | 87 | 4385_1 | System Output Voltage RMS A-N | V | Read | |
| AV | 88 | 4386_1 | System Output Voltage RMS B-N | V | Read | |
| AV | 89 | 4387_1 | System Output Voltage RMS C-N | V | Read | |
| AVmin | 90 | 4204_1 | System Output RMS Current Phs A | A | Read | |
| AV | 91 | 4205_1 | System Output RMS Current Phs B | A | Read | |
| AV | 92 | 4206_1 | System Output RMS Current Phs C | A | Read | |
| AV | 93 | 4207_1 | System Output Frequency | Hz | Read | |
| AVmin | 94 | 4208_1 | System Output Power | kW | Read | |
| AV | 95 | 4209_1 | System Output Apparent Power | kVA | Read | |
| AV | 96 | 4210_1 | System Output Power Factor Phs A | Read | ||
| AV | 97 | 4211_1 | System Output Power Factor Phs B | Read | ||
| AV | 98 | 4212_1 | System Output Power Factor Phs C | Read | ||
| AV | 99 | 4223_1 | System Output Pct Power Phase A | % | Read | |
| AV | 100 | 4224_1 | System Output Pct Power Phase B | % | Read | |
| AV | 101 | 4225_1 | System Output Pct Power Phase C | % | Read | |
| AV | 102 | 4226_1 | System Output Pct Pwr (VA) Phs A | % | Read | |
| AV | 103 | 4227_1 | System Output Pct Pwr (VA) Phs B | % | Read | |
| AV | 104 | 4228_1 | System Output Pct Pwr (VA) Phs C | % | Read | |
| AV | 115 | 4232_1 | Inverter Overload Time Remaining | s | Read | |
| AV | 126 | 4291_1 | Inlet Air Temperature | °C | Read | |
| AV | 10126 | 4291_1_deg_F | Inlet Air Temperature | °F | Read | |
| AV | 127 | 4292_1 | Total System Operating Time | h | Read | |
| AV | 128 | 4293_1 | System Date and Time | Write | ||
| AV | 129 | 5446_1 | Total kW Hours Saved | kWh | Read | |
| AV | 140 | 5789_1 | System Accumulated Energy | kWh | Write | |
| AV | 141 | 5790_1 | Module Accumulated Energy | kWh | Write | |
| AV | 142 | 5791_1 | Output kWh Reset Timestamp | Read | ||
| AV | 143 | 5793_1 | Output Peak kW Demand | kW | Read | |
| AV | 144 | 5794_1 | Output Peak kW Demand Hist | kW | Read | |
| AV | 145 | 5797_1 | Peak kW Demand Timestamp | Read | ||
| AV | 156 | 4259_1 | Bypass Nominal Voltage | V | Read | |
| AV | 157 | 4102_1 | System Input Nominal Voltage | V | Read | |
| AV | 158 | 4103_1 | System Input Nominal Frequency | Hz | Read | |
| AV | 159 | 4260_1 | System Output Nominal Voltage | V | Read | |
| AV | 160 | 4261_1 | System Output Nominal Frequency | Hz | Read | |
| AV | 161 | 4262_1 | Battery Cell Count - Lead Acid | Read | ||
| AV | 162 | 4263_1 | Battery Cell Count-Nickel Cadmium | Read | ||
| AV | 163 | 4264_1 | Output Apparent Power Rating | kVA | Read | |
| AV | 164 | 4265_1 | Output Real Power Rating | kW | Read | |
| AV | 165 | 4800_1 | System UPS Module Count | Read | ||
| AV | 166 | 4267_1 | System Output Maximum Amp Rating | A | Read | |
| AV | 177 | 4801_1 | Multi-module System Output Voltage RMS A-B | V | Read | |
| AV | 178 | 4802_1 | Multi-module System Output Voltage RMS B-C | V | Read | |
| AV | 179 | 4803_1 | Multi-module System Output Voltage RMS C-A | V | Read | |
| AV | 180 | 4804_1 | Multi-module System Output Voltage RMS A-N | V | Read | |
| AV | 181 | 4805_1 | Multi-module System Output Voltage RMS B-N | V | Read | |
| AV | 182 | 4806_1 | Multi-module System Output Voltage RMS C-N | V | Read | |
| AV | 183 | 4807_1 | Sum of MMS Output RMS Currents for Phase A | A | Read | |
| AV | 184 | 4808_1 | Sum of MMS Output RMS Currents for Phase B | A | Read | |
| AV | 185 | 4809_1 | Sum of MMS Output RMS Currents for Phase C | A | Read | |
| AV | 186 | 4810_1 | MMS Output Frequency | Hz | Read | |
| AV | 187 | 4811_1 | MMS Output Power | kW | Read | |
| AV | 188 | 4812_1 | MMS Output Apparent Power | kVA | Read | |
| AV | 189 | 4813_1 | MMS Output Power Factor Phase A | Read | ||
| AV | 190 | 4814_1 | MMS Output Power Factor Phase B | Read | ||
| AV | 191 | 4815_1 | MMS Output Power Factor Phase C | Read | ||
| AV | 192 | 4816_1 | MMS Output Pct Power Phase A | % | Read | |
| AV | 193 | 4817_1 | MMS Output Pct Power Phase B | % | Read | |
| AV | 194 | 4818_1 | MMS Output Pct Power Phase C | % | Read | |
| AV | 195 | 4819_1 | MMS Output Pct Apparent Pwr (kVA) Phase A | % | Read | |
| AV | 196 | 4820_1 | MMS Output Pct Apparent Pwr (kVA) Phase B | % | Read | |
| AV | 197 | 4821_1 | MMS Output Pct Apparent Pwr (kVA) Phase C | % | Read | |
| AV | 198 | 4822_1 | Number of Redundant Modules | Read | ||
| AV | 199 | 4829_1 | MMS Module Number | Read | ||
| AV | 200 | 4833_1 | Number of Modules in a MMS | Read | ||
| AV | 211 | 4861_2 | MMS Module Total kW Output (ModuleList 1) | kW | Read | |
| AV | 212 | 4862_2 | MMS Module Total kVA Output (ModuleList 1) | kVA | Read | |
| AV | 213 | 4863_2 | MMS Module DC Bus Voltage (ModuleList 1) | VDC | Read | |
| AV | 214 | 4864_2 | MMS Module Battery Current (ModuleList 1) | A DC | Read | |
| AV | 215 | 4865_2 | MMS Module Battery Time Remaining (ModuleList 1) | min | Read | |
| AV | 226 | 4861_2 | MMS Module Total kW Output (ModuleList 2) | kW | Read | |
| AV | 227 | 4862_2 | MMS Module Total kVA Output (ModuleList 2) | kVA | Read | |
| AV | 228 | 4863_2 | MMS Module DC Bus Voltage (ModuleList 2) | VDC | Read | |
| AV | 229 | 4864_2 | MMS Module Battery Current (ModuleList 2) | A DC | Read | |
| AV | 230 | 4865_2 | MMS Module Battery Time Remaining (ModuleList 2) | min | Read | |
| AV | 316 | 4861_8 | MMS Module Total kW Output (ModuleList 8) | kW | Read | |
| AV | 317 | 4862_8 | MMS Module Total kVA Output (ModuleList 8) | kVA | Read | |
| AV | 318 | 4863_8 | MMS Module DC Bus Voltage (ModuleList 8) | VDC | Read | |
| AV | 319 | 4864_8 | MMS Module Battery Current (ModuleList 8) | A DC | Read | |
| AV | 320 | 4865_8 | MMS Module Battery Time Remaining (ModuleList 8) | min | Read | |
| AV | 331 | 5450_1 | Intelligent Paralleling Shutdown Delay | min | Read | |
| AV | 332 | 5451_1 | Intelligent Parallel Minimum Redundancy | Read | ||
| AV | 333 | 5452_1 | Intelligent Parallel Maximum Time in Standby | day | Read | |
| AV | 344 | 5459_1 | Maximum Auto Suspensions - ECO Mode | Read | ||
| AV | 345 | 5460_1 | Restart Delay - ECO Mode | min | Read | |
| AV | 346 | 5466_1 | Time Remaining - ECO Mode | min | Read | |
| AV | 357 | 5464_1_1 | Schedule Hour - ECO Mode (EcoModeSchedule 1) | h | Read | |
| AV | 358 | 5465_1_1 | Schedule Minute - ECO Mode (EcoModeSchedule 1) | min | Read | |
| AV | 369 | 5464_1_2 | Schedule Hour - ECO Mode (EcoModeSchedule 2) | h | Read | |
| AV | 370 | 5465_1_2 | Schedule Minute - ECO Mode (EcoModeSchedule 2) | min | Read | |
| AV | 537 | 5464_1_16 | Schedule Hour - ECO Mode (EcoModeSchedule 16) | h | Read | |
| AV | 538 | 5465_1_16 | Schedule Minute - ECO Mode (EcoModeSchedule 16) | min | Read | |
| MV | 1 | 4735_1 | Input Qualification Status | Read | 1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High | |
| MV | 12 | 4736_1 | Static Bypass Switch | Read | 1=off | |
| MV | 13 | 4737_1 | Bypass Qualification Status | Read | 1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High | |
| MV | 24 | 4871_1 | UPS Battery Status | Read | 1=Unknown, 2=Normal, 3=Low, 4=Depleted | |
| MV | 35 | 4743_1 | DC Bus Qualification Status | Read | 1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High | |
| MV | 46 | 4744_1 | Output Qualification Status | Read | 1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High | |
| MV | 57 | 4745_1 | Inverter Output Qualification Status | Read | 1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High | |
| MV | 58 | 4746_1 | Inverter On/Off State | Read | 1=off, 2=on | |
| MV | 69 | 4257_1 | Rectifier Pulse Count | Read | 1=6 Pulse, 2=12 Pulse, 3=18 Pulse, 4=24 Pulse | |
| MV | 70 | 4258_1 | Rectifier Input Passive Filter | Read | 1=Not Installed, 2=Installed | |
| MV | 71 | 4301_1 | Rectifier Passive Filter Switch | Read | 1=Not Installed, 2=Installed | |
| MV | 72 | 4302_1 | Rectifier Active Filter | Read | 1=Not Installed, 2=Installed | |
| MV | 73 | 4748_1 | Rectifier Status | Read | 1=off, 2=on | |
| MV | 84 | 4303_1 | UPS Module Type | Read | 1=Single Module System, 2=Module (1 + 1), 3=Module (1 + N), 4=Module (N + 1), 5=System Control Cabinet, 6=Main Static Switch | |
| MV | 85 | 4304_1 | Bypass Input Wire Configuration | Read | 1=Two Wire (single phase + return), 2=Two Wire (2 phase, no neutral), 3=Three Wire (2 phase + neutral), 4=Three Wire (3 phase, no neutral), 5=Four Wire (3 phases + neutral) | |
| MV | 86 | 4305_1 | Output Wire Configuration | Read | 1=Two Wire (single phase + return), 2=Two Wire (2 phase, no neutral), 3=Three Wire (2 phase + neutral), 4=Three Wire (3 phase, no neutral), 5=Four Wire (3 phases + neutral) | |
| MV | 87 | 4306_1 | Static Switch Type | Read | 1=Not Applicable, 2=Continuous Duty, 3=Momentary Duty | |
| MV | 88 | 4751_1 | Configuration Description | Read | 1=Single Module System 33, 2=Single Module System 34, 3=Single Module System 44, 4=1+1 33, 5=1+1 34, 6=1+1 44, 7=1+N 33, 8=1+N 34, 9=1+N 44, 10=N+1 33, 11=N+1 34, 12=N+1 44, 13=SCC w/Continuous Duty SS 33, 14=SCC w/Continuous Duty SS 44, 15=SCC w/Momentary Duty SS, 16=Main Static Switch | |
| MV | 89 | 4752_1 | UPS System Output Source | Read | 1=off, 2=Normal, 3=Bypass, 4=Maintenance Bypass | |
| MV | 90 | 4318_1 | System Input Power Source | Read | 1=None, 2=Utility (mains), 3=Generator | |
| MVmin | 91 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=AbNormalOperation | |
| MVmin | 92 | 4872_1 | UPS Output Source | Read | 1=Other, 2=off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer | |
| MV | 93 | 5795_1 | Peak kW Demand Period | Read | 1=Hourly, 2=Daily, 3=Weekly, 4=Monthly, 5=Yearly | |
| MV | 104 | 4266_1 | Input Isolation Transformer | Read | 1=Not Installed, 2=Installed | |
| MV | 115 | 4764_1 | Backfeed Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 116 | 4765_1 | SBS Load Disconnect | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 117 | 4766_1 | Input Breaker (CB1/RIB) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 118 | 4767_1 | Trap Filter Disconnect | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 119 | 4768_1 | Output Breaker (CB2/IOB) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 120 | 4769_1 | Internal Bypass Breaker (CB3) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 121 | 4770_1 | Bypass Isolation Breaker (BIB) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 122 | 4771_1 | Rectifier Feed Breaker (RFB) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 123 | 4772_1 | Maintenance Bypass Breaker (MBB) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 124 | 4773_1 | Maintenance Isolation Breaker (MIB) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 125 | 4774_1 | Output Series Static Switch | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 126 | 4775_1 | Module Output Breaker (MOB) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 137 | 4836_1 | Module Output Breaker for Module 1 (MOB1) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 138 | 4837_1 | Module Output Breaker for Module 2 (MOB2) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 139 | 4838_1 | Module Output Breaker for Module 3 (MOB3) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 140 | 4839_1 | Module Output Breaker for Module 4 (MOB4) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 141 | 4840_1 | Module Output Breaker for Module 5 (MOB5) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 142 | 4841_1 | Module Output Breaker for Module 6 (MOB6) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 143 | 4842_1 | Module Output Breaker for Module 7 (MOB7) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 144 | 4843_1 | Module Output Breaker for Module 8 (MOB8) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 145 | 4844_1 | Bypass Isolation Breaker for Module 1 (BIB1) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 146 | 4845_1 | Bypass Isolation Breaker for Module 2 (BIB2) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 147 | 4846_1 | Bypass Isolation Breaker for Module 3 (BIB3) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 148 | 4847_1 | Bypass Isolation Breaker for Module 4 (BIB4) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 149 | 4848_1 | Bypass Isolation Breaker for Module 5 (BIB5) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 150 | 4849_1 | Bypass Isolation Breaker for Module 6 (BIB6) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 151 | 4850_1 | Bypass Isolation Breaker for Module 7 (BIB7) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 152 | 4851_1 | Bypass Isolation Breaker for Module 8 (BIB8) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 153 | 4852_1 | System Output Breaker (UOB) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 154 | 4853_1 | System Load Bank Breaker (LBB) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 155 | 4854_1 | System Isolation Output Breaker (IOB) | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 156 | 4855_1 | SCC Event Summary | Read | 1=None, 2=Alarm, 3=Fault | |
| MV | 157 | 4873_1 | MMS UPS Battery Status | Read | 1=Unknown, 2=Normal, 3=Low, 4=Depleted | |
| MV | 158 | 4874_1 | MMS UPS Output Source | Read | 1=Other, 2=off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer | |
| MV | 169 | 4856_1 | MMS Inter-Module Comm Status (ModuleList 1) | Read | 1=Failed, 2=Normal | |
| MV | 170 | 4857_1 | MMS Event Summary (ModuleList 1) | Read | 1=None, 2=Alarm, 3=Fault | |
| MV | 171 | 4858_1 | MMS Module Inverter Status (ModuleList 1) | Read | 1=off, 2=on | |
| MV | 172 | 4859_1 | MMS Module Output Voltage Status (ModuleList 1) | Read | 1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High | |
| MV | 173 | 4860_1 | MMS Module Output Source (ModuleList 1) | Read | 1=off, 2=Normal, 3=Bypass, 4=Maintenance Bypass | |
| MV | 184 | 4856_2 | MMS Inter-Module Comm Status (ModuleList 2) | Read | 1=Failed, 2=Normal | |
| MV | 185 | 4857_2 | MMS Event Summary (ModuleList 2) | Read | 1=None, 2=Alarm, 3=Fault | |
| MV | 186 | 4858_2 | MMS Module Inverter Status (ModuleList 2) | Read | 1=off, 2=on | |
| MV | 187 | 4859_2 | MMS Module Output Voltage Status (ModuleList 2) | Read | 1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High | |
| MV | 188 | 4860_2 | MMS Module Output Source (ModuleList 2) | Read | 1=off, 2=Normal, 3=Bypass, 4=Maintenance Bypass | |
| MV | 274 | 4856_8 | MMS Inter-Module Comm Status (ModuleList 8) | Read | 1=Failed, 2=Normal | |
| MV | 275 | 4857_8 | MMS Event Summary (ModuleList 8) | Read | 1=None, 2=Alarm, 3=Fault | |
| MV | 276 | 4858_8 | MMS Module Inverter Status (ModuleList 8) | Read | 1=off, 2=on | |
| MV | 277 | 4859_8 | MMS Module Output Voltage Status (ModuleList 8) | Read | 1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High | |
| MV | 278 | 4860_8 | MMS Module Output Source (ModuleList 8) | Read | 1=off, 2=Normal, 3=Bypass, 4=Maintenance Bypass | |
| MV | 289 | 5448_1 | Intelligent Parallel Operation State | Read | 1=disabled, 2=enabled | |
| MV | 290 | 5449_1 | Intelligent Parallel Mode | Read | 1=Idle (Fast Recovery), 2=Disconnect (More Efficient), 3=off (Most Efficient) | |
| MV | 301 | 5454_1 | ECO Mode Operation State | Write | 1=disabled, 2=enabled | |
| MV | 302 | 5455_1 | Continuous Operation - ECO Mode | Read | 1=disabled, 2=enabled | |
| MV | 313 | 5461_1_1 | Schedule Operation State - ECO Mode (EcoModeSchedule 1) | Read | 1=disabled, 2=enabled | |
| MV | 314 | 5462_1_1 | Schedule Action - ECO Mode (EcoModeSchedule 1) | Read | 1=stop, 2=start | |
| MV | 326 | 5461_1_2 | Schedule Operation State - ECO Mode (EcoModeSchedule 2) | Read | 1=disabled, 2=enabled | |
| MV | 327 | 5462_1_2 | Schedule Action - ECO Mode (EcoModeSchedule 2) | Read | 1=stop, 2=start | |
| MV | 328 | 5463_1_2 | Schedule Day of Week - ECO Mode (EcoModeSchedule 2) | Read | 1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday | |
| MV | 508 | 5461_1_16 | Schedule Operation State - ECO Mode (EcoModeSchedule 16) | Read | 1=disabled, 2=enabled | |
| MV | 509 | 5462_1_16 | Schedule Action - ECO Mode (EcoModeSchedule 16) | Read | 1=stop, 2=start | |
| MV | 510 | 5463_1_16 | Schedule Day of Week - ECO Mode (EcoModeSchedule 16) | Read | 1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday |
No points match these filters.
Object ID lookup: Vertiv Liebert NXL 60 Hz UPS point IDs by name
BV14122_1BV24146_1BV34147_1BV44382_1BV154135_1BV164132_1BV174133_1BV184134_1BV194138_1BV204139_1BV214142_1BV224143_1BV234144_1BV244145_1BV254175_1BV264218_1BV274217_1BV284383_1BV394164_1BV404740_1BV414165_1BV424166_1BV434168_1BV444169_1BV454170_1BV464741_1BV474173_1BV484162_1BV494174_1BV504200_1BV514176_1BV524179_1BV534182_1BV544185_1BV554188_1BV564191_1BV574194_1BV584197_1BV594220_1BV604221_1BV614222_1BV624742_1BV634219_1BV644323_1BV656354_1BV754308_1BV764309_1BV874213_1BV884214_1BV894215_1BV904230_1BV914286_1BV924287_1BV934288_1BV944389_1BV955144_1BV1064233_1BV1074234_1BV1084235_1BV1094236_1BV1104237_1BV1114290_1BV1124390_1BV1134391_1BV1244294_1BV1255768_1BV1264747_1BV1274310_1BV1384270_1BV1394271_1BV1404272_1BV1414273_1BV1424274_1BV1434275_1BV1444276_1BV1454277_1BV1464278_1BV1474279_1BV1484280_1BV1494281_1BV1504282_1BV1514283_1BV1524284_1BV1534285_1BV1644295_1BV1654296_1BV1764749_1BV1774750_1BV1784300_1BV1794298_1BV1804299_1BV1814325_1BV1824316_1BV1834314_1BV1844315_1BV1854317_1BV1864439_1BV1874753_1BV1884440_1BV1894441_1BV1904442_1BV1914754_1BV1924755_1BV1935769_1BV1944756_1BV1954757_1BV1964758_1BV1974759_1BV1984760_1BV1995561_1BV2005562_1BV2015788_1BV2025792_1BV2035796_1BV2144823_1BV2154824_1BV2164825_1BV2174826_1BV2184827_1BV2194828_1BV2204830_1BV2214831_1BV2224834_1BV2234835_1BV2245145_1BV2255447_1BV2365453_1BV2475456_1BV2485457_1BV2495458_1BV2604726_1AV14097_1AV24099_1AV34101_1AV44113_1AV54114_1AV64115_1AV74105_1AV184125_1AV194126_1AV204127_1AV214131_1AV224136_1AV234157_1AV244738_1AV256456_1AV354152_1AV364153_1AV374154_1AV384155_1_1AV394155_1_2AV404155_1_3AV414155_1_4AV424155_1_5AV434155_1_6AV444155_1_7AV454155_1_8AV464156_1_1AV100464156_1_1_deg_FAV474156_1_2AV100474156_1_2_deg_FAV484156_1_3AV100484156_1_3_deg_FAV494156_1_4AV100494156_1_4_deg_FAV504156_1_5AV100504156_1_5_deg_FAV514156_1_6AV100514156_1_6_deg_FAV524156_1_7AV100524156_1_7_deg_FAV534156_1_8AV100534156_1_8_deg_FAV544739_1AV554150_1AV564151_1AV574159_1AV584161_1AV594160_1AV604158_1AV615767_1AV724148_1AV734149_1AV844201_1AV854202_1AV864203_1AV874385_1AV884386_1AV894387_1AV904204_1AV914205_1AV924206_1AV934207_1AV944208_1AV954209_1AV964210_1AV974211_1AV984212_1AV994223_1AV1004224_1AV1014225_1AV1024226_1AV1034227_1AV1044228_1AV1154232_1AV1264291_1AV101264291_1_deg_FAV1274292_1AV1284293_1AV1295446_1AV1405789_1AV1415790_1AV1425791_1AV1435793_1AV1445794_1AV1455797_1AV1564259_1AV1574102_1AV1584103_1AV1594260_1AV1604261_1AV1614262_1AV1624263_1AV1634264_1AV1644265_1AV1654800_1AV1664267_1AV1774801_1AV1784802_1AV1794803_1AV1804804_1AV1814805_1AV1824806_1AV1834807_1AV1844808_1AV1854809_1AV1864810_1AV1874811_1AV1884812_1AV1894813_1AV1904814_1AV1914815_1AV1924816_1AV1934817_1AV1944818_1AV1954819_1AV1964820_1AV1974821_1AV1984822_1AV1994829_1AV2004833_1AV2114861_2AV2124862_2AV2134863_2AV2144864_2AV2154865_2AV2264861_2AV2274862_2AV2284863_2AV2294864_2AV2304865_2AV3164861_8AV3174862_8AV3184863_8AV3194864_8AV3204865_8AV3315450_1AV3325451_1AV3335452_1AV3445459_1AV3455460_1AV3465466_1AV3575464_1_1AV3585465_1_1AV3695464_1_2AV3705465_1_2AV5375464_1_16AV5385465_1_16MV14735_1MV124736_1MV134737_1MV244871_1MV354743_1MV464744_1MV574745_1MV584746_1MV694257_1MV704258_1MV714301_1MV724302_1MV734748_1MV844303_1MV854304_1MV864305_1MV874306_1MV884751_1MV894752_1MV904318_1MV914123_1MV924872_1MV935795_1MV1044266_1MV1154764_1MV1164765_1MV1174766_1MV1184767_1MV1194768_1MV1204769_1MV1214770_1MV1224771_1MV1234772_1MV1244773_1MV1254774_1MV1264775_1MV1374836_1MV1384837_1MV1394838_1MV1404839_1MV1414840_1MV1424841_1MV1434842_1MV1444843_1MV1454844_1MV1464845_1MV1474846_1MV1484847_1MV1494848_1MV1504849_1MV1514850_1MV1524851_1MV1534852_1MV1544853_1MV1554854_1MV1564855_1MV1574873_1MV1584874_1MV1694856_1MV1704857_1MV1714858_1MV1724859_1MV1734860_1MV1844856_2MV1854857_2MV1864858_2MV1874859_2MV1884860_2MV2744856_8MV2754857_8MV2764858_8MV2774859_8MV2784860_8MV2895448_1MV2905449_1MV3015454_1MV3025455_1MV3135461_1_1MV3145462_1_1MV3265461_1_2MV3275462_1_2MV3285463_1_2MV5085461_1_16MV5095462_1_16MV5105463_1_16
Integration notes
- Tables 5.178, 5.179, 5.180, pdf pages 2214-2232 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert NXL 60 Hz UPS (UL, model 40) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
How many BACnet points does the Vertiv Liebert NXL 60 Hz UPS (UL, model 40) have?
This list has 363 BACnet objects: 147 analog values, 131 binary values, 85 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert NXL 60 Hz UPS (UL, model 40) BACnet points are writable?
4 of the 363 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert NXL 60 Hz UPS (UL, model 40) BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert NXL 60 Hz UPS (UL, model 40)?
Start with MV 91 4123_1 (Normal, warning or alarm state); MV 92 4872_1 (Load on inverter, bypass or battery); AV 55 4150_1 (Estimated battery runtime, min); AV 94 4208_1 (Output power, kW); AV 1 4097_1 (Input voltage, V); AV 84 4201_1 (Output voltage, V); AV 90 4204_1 (Output current, A); BV 43 4168_1 (Load is on battery); BV 178 4300_1 (Internal communication lost).
How do I check these points on the real Liebert NXL 60 Hz UPS (UL, model 40)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.