Precision cooling unit (computer room air handler) · BACnet points list
Vertiv Liebert iCOM XDM precision cooling BACnet points list
Updated 6 November 2026
The Liebert iCOM XDM precision cooling reports to a BMS through a Liebert IntelliSlot card (IS-UNITY-DP for BACnet IP or BACnet MS/TP; some units also IS-IPBML). The object list has Binary Values for events, Analog Values for temperatures, humidity, setpoints and run hours, and Multi-state Values for states and control modes. Objects are created on the card when it discovers the unit, so only options fitted to the unit appear.
This page lists 680 BACnet objects for the Vertiv Liebert iCOM XDM precision cooling — 211 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert iCOM XDM precision cooling
- Equipment
- Precision cooling unit (computer room air handler)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 680 (211 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Liebert XDM, iCOM XDM, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert iCOM XDM precision cooling
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 115 | 5143_1 | On/off command (1=off, 2=on) | Write |
| AV 2844 | 8143_1_1 | Fluid temperature setpoint, °C | Write |
| AV 61 | 5029_1 | Humidity setpoint, %RH | Write |
| MV 292 | 4717_1 | Acknowledge / reset events | Write |
| MV 94 | 4706_1 | Run / standby / off state | Read |
| MV 93 | 4123_1 | Normal, warning or alarm state | Read |
| AV 19 | 5002_1_1 | Supply air temperature, °C | Read |
| AV 31 | 4291_1 | Return air temperature, °C | Read |
| AV 2584 | 4643_1 | Supply fluid temperature, °C | Read |
| AV 60 | 5028_1 | Return air humidity, %RH | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert iCOM XDM precision cooling BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 14 | 5023_1_1 | Return Air Over Temperature | Read | Active = alarm | |
| BV | 15 | 5335_1_1 | Return Air Under Temperature | Read | Active = alarm | |
| BV | 16 | 5147_1_1 | Return Air Sensor Issue | Read | Active = alarm | |
| BV | 27 | 4601_1_1 | Ext Air Sensor A Over Temperature | Read | Active = alarm | |
| BV | 28 | 4608_1_1 | Ext Air Sensor A Under Temperature | Read | Active = alarm | |
| BV | 29 | 4618_1_1 | Ext Air Sensor A Issue | Read | Active = alarm | |
| BV | 30 | 5573_1_1 | Ambient Air Sensor Issue | Read | Active = alarm | |
| BV | 31 | 4621_1_1 | External Air Sensor B Issue | Read | Active = alarm | |
| BV | 32 | 6531_1_1 | External Air Sensor C Issue | Read | Active = alarm | |
| BV | 33 | 6532_1_1 | External Air Sensor D Issue | Read | Active = alarm | |
| BV | 34 | 6533_1_1 | External Air Sensor E Issue | Read | Active = alarm | |
| BV | 1050 | 5966_1_1 | Aux Air Temp Device Communication Lost | Read | Active = alarm | |
| BV | 41 | 5034_1 | High Return Humidity | Read | Active = alarm | |
| BV | 42 | 5036_1 | Low Return Humidity | Read | Active = alarm | |
| BV | 43 | 5578_1 | Dew Point Over Temperature | Read | Active = alarm | |
| BV | 44 | 5579_1 | Dew Point Under Temperature | Read | Active = alarm | |
| BV | 45 | 5902_1 | Return Humidity Sensor Issue | Read | Active = alarm | |
| BV | 53 | 5349_1_1 | Ext Air Sensor A High Humidity | Read | Active = alarm | |
| BV | 54 | 5351_1_1 | Ext Air Sensor A Low Humidity | Read | Active = alarm | |
| BV | 55 | 4615_1_1 | Ext Dew Point Over Temperature | Read | Active = alarm | |
| BV | 56 | 5577_1_1 | Ext Dew Point Under Temperature | Read | Active = alarm | |
| BV | 65 | 5067_1 | Ext Compressor Lockout | Read | Active = alarm | |
| BV | 66 | 5513_1 | Compressor Capacity Reduced | Read | Active = alarm | |
| BV | 77 | 5269_1_1 | Compressor Hours Exceeded (Compressor 1) | Read | Active = alarm | |
| BV | 78 | 5270_1_1 | Compressor High Head Pressure (Compressor 1) | Read | Active = alarm | |
| BV | 79 | 5271_1_1 | Compressor Low Suction Pressure (Compressor 1) | Read | Active = alarm | |
| BV | 80 | 5352_1_1 | Compressor Short Cycle (Compressor 1) | Read | Active = alarm | |
| BV | 81 | 5146_1_1 | Compressor Pump Down Issue (Compressor 1) | Read | Active = alarm | |
| BV | 82 | 5272_1_1 | Compressor Thermal Overload (Compressor 1) | Read | Active = alarm | |
| BV | 83 | 5354_1_1 | Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 1) | Read | Active = alarm | |
| BV | 84 | 5355_1_1 | Dig Scroll Comp Over Temp (Compressor 1) | Read | Active = alarm | |
| BV | 85 | 5514_1_1 | Compressor Low Pressure Transducer Issue (Compressor 1) | Read | Active = alarm | |
| BV | 86 | 5148_1_1 | Compressor High Pressure Transducer Issue (Compressor 1) | Read | Active = alarm | |
| BV | 87 | 5604_1_1 | Compressor Superheat Over Threshold (Compressor 1) | Read | Active = alarm | |
| BV | 88 | 5903_1_1 | Compressor Low Differential Pressure Lockout (Compressor 1) | Read | Active = alarm | |
| BV | 89 | 6758_1_1 | Compressor Freeze Protection (Compressor 1) | Read | Active = alarm | |
| BV | 97 | 5269_1_2 | Compressor Hours Exceeded (Compressor 2) | Read | Active = alarm | |
| BV | 98 | 5270_1_2 | Compressor High Head Pressure (Compressor 2) | Read | Active = alarm | |
| BV | 99 | 5271_1_2 | Compressor Low Suction Pressure (Compressor 2) | Read | Active = alarm | |
| BV | 100 | 5352_1_2 | Compressor Short Cycle (Compressor 2) | Read | Active = alarm | |
| BV | 101 | 5146_1_2 | Compressor Pump Down Issue (Compressor 2) | Read | Active = alarm | |
| BV | 102 | 5272_1_2 | Compressor Thermal Overload (Compressor 2) | Read | Active = alarm | |
| BV | 103 | 5354_1_2 | Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 2) | Read | Active = alarm | |
| BV | 104 | 5355_1_2 | Dig Scroll Comp Over Temp (Compressor 2) | Read | Active = alarm | |
| BV | 105 | 5514_1_2 | Compressor Low Pressure Transducer Issue (Compressor 2) | Read | Active = alarm | |
| BV | 106 | 5148_1_2 | Compressor High Pressure Transducer Issue (Compressor 2) | Read | Active = alarm | |
| BV | 107 | 5604_1_2 | Compressor Superheat Over Threshold (Compressor 2) | Read | Active = alarm | |
| BV | 108 | 5903_1_2 | Compressor Low Differential Pressure Lockout (Compressor 2) | Read | Active = alarm | |
| BV | 109 | 6758_1_2 | Compressor Freeze Protection (Compressor 2) | Read | Active = alarm | |
| BV | 1287 | 5269_1_4 | Compressor Hours Exceeded (Compressor 4) | Read | Active = alarm | |
| BV | 1288 | 5270_1_4 | Compressor High Head Pressure (Compressor 4) | Read | Active = alarm | |
| BV | 1289 | 5271_1_4 | Compressor Low Suction Pressure (Compressor 4) | Read | Active = alarm | |
| BV | 1290 | 5352_1_4 | Compressor Short Cycle (Compressor 4) | Read | Active = alarm | |
| BV | 1291 | 5146_1_4 | Compressor Pump Down Issue (Compressor 4) | Read | Active = alarm | |
| BV | 1292 | 5272_1_4 | Compressor Thermal Overload (Compressor 4) | Read | Active = alarm | |
| BV | 1293 | 5354_1_4 | Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 4) | Read | Active = alarm | |
| BV | 1294 | 5355_1_4 | Dig Scroll Comp Over Temp (Compressor 4) | Read | Active = alarm | |
| BV | 1295 | 5514_1_4 | Compressor Low Pressure Transducer Issue (Compressor 4) | Read | Active = alarm | |
| BV | 1296 | 5148_1_4 | Compressor High Pressure Transducer Issue (Compressor 4) | Read | Active = alarm | |
| BV | 1297 | 5604_1_4 | Compressor Superheat Over Threshold (Compressor 4) | Read | Active = alarm | |
| BV | 1298 | 5903_1_4 | Compressor Low Differential Pressure Lockout (Compressor 4) | Read | Active = alarm | |
| BV | 1299 | 6758_1_4 | Compressor Freeze Protection (Compressor 4) | Read | Active = alarm | |
| BV | 253 | 4270_1 | Customer Input 1 | Read | Active = alarm | |
| BV | 254 | 4271_1 | Customer Input 2 | Read | Active = alarm | |
| BV | 255 | 4272_1 | Customer Input 3 | Read | Active = alarm | |
| BV | 256 | 4273_1 | Customer Input 4 | Read | Active = alarm | |
| BV | 257 | 5415_1 | Ext Loss of Air Blower | Read | Active = alarm | |
| BV | 258 | 5105_1 | Ext Loss of Flow | Read | Active = alarm | |
| BV | 259 | 5107_1 | Ext Standby Glycol Pump On | Read | Active = alarm | |
| BV | 260 | 5115_1 | BMS Communications Timeout | Read | Active = alarm | |
| BV | 261 | 5416_1 | Ext Standby Unit On | Read | Active = alarm | |
| BV | 262 | 5118_1 | Clogged Air Filter | Read | Active = alarm | |
| BV | 263 | 5053_1 | Loss of Air Flow | Read | Active = alarm | |
| BV | 264 | 4726_1 | Service Required | Read | Active = alarm | |
| BV | 265 | 5120_1 | Master Unit Communication Lost | Read | Active = alarm | |
| BV | 266 | 5119_1 | RAM Battery Issue | Read | Active = alarm | |
| BV | 267 | 4714_1 | Shutdown - Loss Of Power | Read | Active = alarm | |
| BV | 268 | 5121_1 | High Power Shutdown | Read | Active = alarm | |
| BV | 269 | 4720_1 | Smoke Detected | Read | Active = alarm | |
| BV | 271 | 4626_1 | Supply Chilled Water Over Temp | Read | Active = alarm | |
| BV | 272 | 5418_1 | Unit Code Missing | Read | Active = alarm | |
| BV | 273 | 5419_1 | Unit Communication Lost | Read | Active = alarm | |
| BV | 274 | 5114_1 | Water Leakage Detector Sensor Issue | Read | Active = alarm | |
| BV | 275 | 4723_1 | Water Under Floor | Read | Active = alarm | |
| BV | 276 | 5104_1 | Ext Over Temperature | Read | Active = alarm | |
| BV | 277 | 5108_1 | External Fire Detected | Read | Active = alarm | |
| BV | 278 | 5588_1 | Unspecified General Event | Read | Active = alarm | |
| BV | 279 | 5617_1 | Temperature Control Sensor Issue | Read | Active = alarm | |
| BV | 280 | 5906_1 | Airflow Sensor Issue | Read | Active = alarm | |
| BV | 281 | 5907_1 | Ext Air Damper Position Issue | Read | Active = alarm | |
| BV | 282 | 5908_1 | Ext Power Source A Failure | Read | Active = alarm | |
| BV | 283 | 5909_1 | Ext Power Source B Failure | Read | Active = alarm | |
| BV | 284 | 5924_1 | Mixed Mode Lockout | Read | Active = alarm | |
| BV | 350 | 6541_1 | Auto Tune License Expiring | Read | Active = alarm | |
| BV | 351 | 6542_1 | Auto Tune License Expired | Read | Active = alarm | |
| BV | 352 | 6543_1 | Unit In Standby Due To Cooling Loss | Read | Active = alarm | |
| BV | 353 | 6544_1 | Control Units Remote Shutdown Mismatch | Read | Active = alarm | |
| BV | 354 | 6545_1 | Slave Control Unit Communication Lost | Read | Active = alarm | |
| BV | 355 | 6546_1 | Control Units Unit Code Mismatch | Read | Active = alarm | |
| BV | 356 | 5471_1 | Door Open | Read | Active = alarm | |
| BV | 357 | 8192_1 | Water Leakage | Read | Active = alarm | |
| BV | 358 | 8231_1 | PHE Sup Tem Snsr Fail | Read | Active = alarm | |
| BV | 288 | 4703_1_1 | Chilled Water Control Valve Failure (Chilled Water Valve 1) | Read | Active = alarm | |
| BV | 299 | 4703_1_2 | Chilled Water Control Valve Failure (Chilled Water Valve 2) | Read | Active = alarm | |
| BV | 310 | 5110_1_1 | Unit Off | Read | Active = alarm | |
| BV | 311 | 5109_1_1 | Unit On | Read | Active = alarm | |
| BV | 312 | 5112_1_1 | Unit Partial Shutdown | Read | Active = alarm | |
| BV | 313 | 5113_1_1 | Unit Shutdown | Read | Active = alarm | |
| BV | 314 | 5111_1_1 | Unit Standby | Read | Active = alarm | |
| BV | 315 | 5116_1_1 | Maintenance Due | Read | Active = alarm | |
| BV | 316 | 5117_1_1 | Maintenance Completed | Read | Active = alarm | |
| BV | 327 | 5417_1_1 | Digital Output Board Not Detected (iCOM DO Board 1) | Read | Active = alarm | |
| BV | 338 | 5417_1_2 | Digital Output Board Not Detected (iCOM DO Board 2) | Read | Active = alarm | |
| BV | 349 | 5417_1_3 | Digital Output Board Not Detected (iCOM DO Board 3) | Read | Active = alarm | |
| BV | 361 | 5593_1 | Remote Sensor Average Over Temperature | Read | Active = alarm | |
| BV | 362 | 5594_1 | Remote Sensor Average Under Temperature | Read | Active = alarm | |
| BV | 363 | 5595_1 | Remote Sensor System Average Over Temperature | Read | Active = alarm | |
| BV | 364 | 5596_1 | Remote Sensor System Average Under Temperature | Read | Active = alarm | |
| BV | 376 | 5597_1_1 | Remote Sensor Over Temperature (Remote Sensor 1) | Read | Active = alarm | |
| BV | 377 | 5598_1_1 | Remote Sensor Under Temperature (Remote Sensor 1) | Read | Active = alarm | |
| BV | 378 | 5060_1_1 | Remote Sensor Issue (Remote Sensor 1) | Read | Active = alarm | |
| BV | 390 | 5597_1_2 | Remote Sensor Over Temperature (Remote Sensor 2) | Read | Active = alarm | |
| BV | 391 | 5598_1_2 | Remote Sensor Under Temperature (Remote Sensor 2) | Read | Active = alarm | |
| BV | 392 | 5060_1_2 | Remote Sensor Issue (Remote Sensor 2) | Read | Active = alarm | |
| BV | 502 | 5597_1_10 | Remote Sensor Over Temperature (Remote Sensor 10) | Read | Active = alarm | |
| BV | 503 | 5598_1_10 | Remote Sensor Under Temperature (Remote Sensor 10) | Read | Active = alarm | |
| BV | 504 | 5060_1_10 | Remote Sensor Issue (Remote Sensor 10) | Read | Active = alarm | |
| BV | 540 | 5625_1 | EEV Unspecified General Event | Read | Active = alarm | |
| BV | 623 | 5636_1 | Pump Unspecified General Event | Read | Active = alarm | |
| BV | 1001 | 5568_1 | Input Undervoltage | Read | Active = alarm | |
| BV | 1040 | 5967_1 | Modbus Power Meter Communication Lost | Read | Active = alarm | |
| BV | 643 | 5637_1 | Condenser Unit Unspecified General Event | Read | Active = alarm | |
| BV | 1082 | 5536_1_1 | Condenser Outside Air Temp Out of Operating Range (Condenser 1) | Read | Active = alarm | |
| BV | 1084 | 5537_1_1 | Condenser Control Board Issue (Condenser 1) | Read | Active = alarm | |
| BV | 1086 | 5535_1_1 | Condenser Outside Air Temp Sensor Issue (Condenser 1) | Read | Active = alarm | |
| BV | 1088 | 5531_1_1 | Condenser Communication Lost (Condenser 1) | Read | Active = alarm | |
| BV | 1090 | 6100_1_1 | Condenser Remote Shutdown (Condenser 1) | Read | Active = alarm | |
| BV | 218 | 5073_1_1 | Condenser TVSS Issue (Condenser 1) | Read | Active = alarm | |
| BV | 1083 | 5536_1_2 | Condenser Outside Air Temp Out of Operating Range (Condenser 2) | Read | Active = alarm | |
| BV | 1085 | 5537_1_2 | Condenser Control Board Issue (Condenser 2) | Read | Active = alarm | |
| BV | 1087 | 5535_1_2 | Condenser Outside Air Temp Sensor Issue (Condenser 2) | Read | Active = alarm | |
| BV | 1089 | 5531_1_2 | Condenser Communication Lost (Condenser 2) | Read | Active = alarm | |
| BV | 1091 | 6100_1_2 | Condenser Remote Shutdown (Condenser 2) | Read | Active = alarm | |
| BV | 1092 | 5073_1_2 | Condenser TVSS Issue (Condenser 2) | Read | Active = alarm | |
| BV | 1366 | 5073_1_4 | Condenser TVSS Issue (Condenser 4) | Read | Active = alarm | |
| BV | 1335 | 5536_1_4 | Condenser Outside Air Temp Out of Operating Range (Condenser 4) | Read | Active = alarm | |
| BV | 1336 | 5537_1_4 | Condenser Control Board Issue (Condenser 4) | Read | Active = alarm | |
| BV | 1337 | 5535_1_4 | Condenser Outside Air Temp Sensor Issue (Condenser 4) | Read | Active = alarm | |
| BV | 1338 | 5531_1_4 | Condenser Communication Lost (Condenser 4) | Read | Active = alarm | |
| BV | 1339 | 6100_1_4 | Condenser Remote Shutdown (Condenser 4) | Read | Active = alarm | |
| BV | 644 | 5638_1_1 | Condenser Circuit Unspecified General Event | Read | Active = alarm | |
| BV | 1104 | 5541_1_1 | Condenser Refrigerant Pressure Sensor Issue (Circuit 1) | Read | Active = alarm | |
| BV | 1106 | 5540_1_1 | Condenser Refrigerant Pressure Under Threshold (Circuit 1) | Read | Active = alarm | |
| BV | 1108 | 5539_1_1 | Condenser Refrigerant Pressure Over Threshold (Circuit 1) | Read | Active = alarm | |
| BV | 1110 | 5544_1_1 | Condenser Supply Refrigerant Temp Sensor Issue (Circuit 1) | Read | Active = alarm | |
| BV | 1112 | 5543_1_1 | Condenser Supply Refrigerant Under Temp (Circuit 1) | Read | Active = alarm | |
| BV | 1114 | 5542_1_1 | Condenser Supply Refrigerant Over Temp (Circuit 1) | Read | Active = alarm | |
| BV | 1116 | 5545_1_1 | Condenser Max Fan Speed Override (Circuit 1) | Read | Active = alarm | |
| BV | 1105 | 5541_1_2 | Condenser Refrigerant Pressure Sensor Issue (Circuit 2) | Read | Active = alarm | |
| BV | 1107 | 5540_1_2 | Condenser Refrigerant Pressure Under Threshold (Circuit 2) | Read | Active = alarm | |
| BV | 1109 | 5539_1_2 | Condenser Refrigerant Pressure Over Threshold (Circuit 2) | Read | Active = alarm | |
| BV | 1111 | 5544_1_2 | Condenser Supply Refrigerant Temp Sensor Issue (Circuit 2) | Read | Active = alarm | |
| BV | 1113 | 5543_1_2 | Condenser Supply Refrigerant Under Temp (Circuit 2) | Read | Active = alarm | |
| BV | 1115 | 5542_1_2 | Condenser Supply Refrigerant Over Temp (Circuit 2) | Read | Active = alarm | |
| BV | 1117 | 5545_1_2 | Condenser Max Fan Speed Override (Circuit 2) | Read | Active = alarm | |
| BV | 1376 | 5541_1_4 | Condenser Refrigerant Pressure Sensor Issue (Circuit 4) | Read | Active = alarm | |
| BV | 1377 | 5540_1_4 | Condenser Refrigerant Pressure Under Threshold (Circuit 4) | Read | Active = alarm | |
| BV | 1378 | 5539_1_4 | Condenser Refrigerant Pressure Over Threshold (Circuit 4) | Read | Active = alarm | |
| BV | 1379 | 5544_1_4 | Condenser Supply Refrigerant Temp Sensor Issue (Circuit 4) | Read | Active = alarm | |
| BV | 1380 | 5543_1_4 | Condenser Supply Refrigerant Under Temp (Circuit 4) | Read | Active = alarm | |
| BV | 1381 | 5542_1_4 | Condenser Supply Refrigerant Over Temp (Circuit 4) | Read | Active = alarm | |
| BV | 1382 | 5545_1_4 | Condenser Max Fan Speed Override (Circuit 4) | Read | Active = alarm | |
| BV | 1128 | 5277_1_1_1 | Condenser Fan Issue (Condenser 1 Fan 1) | Read | Active = alarm | |
| BV | 1129 | 5277_1_1_2 | Condenser Fan Issue (Condenser 1 Fan 2) | Read | Active = alarm | |
| BV | 1131 | 5277_1_1_4 | Condenser Fan Issue (Condenser 1 Fan 4) | Read | Active = alarm | |
| BV | 1132 | 5277_1_2_1 | Condenser Fan Issue (Condenser 2 Fan 1) | Read | Active = alarm | |
| BV | 1133 | 5277_1_2_2 | Condenser Fan Issue (Condenser 2 Fan 2) | Read | Active = alarm | |
| BV | 1135 | 5277_1_2_4 | Condenser Fan Issue (Condenser 2 Fan 4) | Read | Active = alarm | |
| BV | 1482 | 5277_1_4_1 | Condenser Fan Issue (Condenser 4 Fan 1) | Read | Active = alarm | |
| BV | 1502 | 5277_1_4_2 | Condenser Fan Issue (Condenser 4 Fan 2) | Read | Active = alarm | |
| BV | 1542 | 5277_1_4_4 | Condenser Fan Issue (Condenser 4 Fan 4) | Read | Active = alarm | |
| BV | 1554 | 6691_1_1 | Group Independent On | Read | Active = alarm | |
| BV | 1555 | 6692_1_1 | Group Independent Off | Read | Active = alarm | |
| BV | 1595 | 6822_1 | Audit Log Update | Read | Active = alarm | |
| BV | 1606 | 7163_1 | Modbus Automatic Transfer Switch Communication Lost | Read | Active = alarm | |
| BV | 1617 | 4651_1 | Supply Fluid Temp Sensor Issue | Read | Active = alarm | |
| BV | 1618 | 5295_1 | Return Fluid Temp Sensor Issue | Read | Active = alarm | |
| BV | 1619 | 7474_1 | Flow Sensor Failure | Read | Active = alarm | |
| BV | 1621 | 4645_1 | Supply Fluid Over Temp | Read | Active = alarm | |
| BV | 1622 | 5293_1 | Return Fluid Over Temp | Read | Active = alarm | |
| BV | 1623 | 7476_1 | Pump Operating Without Flow | Read | Active = alarm | |
| BV | 1824 | 8180_1 | Supply Fluid Low Temp | Read | Active = alarm | |
| BV | 1825 | 8181_1 | Return Fluid Low Temp | Read | Active = alarm | |
| BV | 1826 | 8182_1 | Fluid High Differential Pressure | Read | Active = alarm | |
| BV | 1827 | 8183_1 | Fluid Low Differential Pressure | Read | Active = alarm | |
| BV | 1828 | 8184_1 | Fluid Flow Low Inlet Pressure | Read | Active = alarm | |
| BV | 1829 | 8185_1 | Fluid Flow High Supply Pressure | Read | Active = alarm | |
| BV | 1830 | 8186_1 | Fluid Low System Flow | Read | Active = alarm | |
| BV | 1831 | 8187_1 | Fluid Flow Blocked | Read | Active = alarm | |
| BV | 1832 | 8188_1 | Fluid Dewpoint Margin Control | Read | Active = alarm | |
| BV | 1833 | 8189_1 | Fluid Supply Pressure Sensor Issue | Read | Active = alarm | |
| BV | 1834 | 8190_1 | Fluid Return Pressure Sensor Issue | Read | Active = alarm | |
| BV | 1835 | 8191_1 | Fluid Inlet Pressure Sensor Issue | Read | Active = alarm | |
| BV | 1634 | 7483_1_1 | Pump Inverter Failure | Read | Active = alarm | |
| BV | 1635 | 7484_1_1 | Pump Flow Failure | Read | Active = alarm | |
| BV | 1846 | 8170_1_1 | XD Pump Communication Lost | Read | Active = alarm | |
| AV | 5 | 5327_1 | Today's High Air Temperature | °C | Read | |
| AV | 10005 | 5327_1_deg_F | Today's High Air Temperature | °F | Read | |
| AV | 6 | 5328_1 | Today's High Air Temperature Time | Seconds since Midnight | Read | |
| AV | 7 | 5329_1 | Today's Low Air Temperature | °C | Read | |
| AV | 10007 | 5329_1_deg_F | Today's Low Air Temperature | °F | Read | |
| AV | 8 | 5330_1 | Today's Low Air Temperature Time | Seconds since Midnight | Read | |
| AVmin | 19 | 5002_1_1 | Supply Air Temperature | °C | Read | |
| AV | 10019 | 5002_1_1_deg_F | Supply Air Temperature | °F | Read | |
| AV | 33 | 5022_1_1 | High Return Air Temperature Threshold | °C | Write | |
| AV | 10033 | 5022_1_1_deg_F | High Return Air Temperature Threshold | °F | Write | |
| AV | 34 | 5334_1_1 | Low Return Air Temperature Threshold | °C | Write | |
| AV | 10034 | 5334_1_1_deg_F | Low Return Air Temperature Threshold | °F | Write | |
| AV | 35 | 6757_1_1 | Return Sensor Events Initial Delay | s | Write | |
| AV | 45 | 4594_1_1 | Ext Air Sensor A Temperature | °C | Read | |
| AV | 10045 | 4594_1_1_deg_F | Ext Air Sensor A Temperature | °F | Read | |
| AV | 46 | 4597_1_1 | Ext Air Sensor B Temperature | °C | Read | |
| AV | 10046 | 4597_1_1_deg_F | Ext Air Sensor B Temperature | °F | Read | |
| AV | 47 | 5336_1_1 | Ext Air Sensor C Temperature | °C | Read | |
| AV | 10047 | 5336_1_1_deg_F | Ext Air Sensor C Temperature | °F | Read | |
| AV | 48 | 5337_1_1 | Ext Air Sensor A Over Temp Threshold | °C | Write | |
| AV | 10048 | 5337_1_1_deg_F | Ext Air Sensor A Over Temp Threshold | °F | Write | |
| AV | 49 | 5338_1_1 | Ext Air Sensor A Under Temp Threshold | °C | Write | |
| AV | 10049 | 5338_1_1_deg_F | Ext Air Sensor A Under Temp Threshold | °F | Write | |
| AV | 50 | 5574_1_1 | Outside Air Temperature | °C | Read | |
| AV | 10050 | 5574_1_1_deg_F | Outside Air Temperature | °F | Read | |
| AVmin | 60 | 5028_1 | Return Humidity | %RH | Read | |
| AVmin | 61 | 5029_1 | Humidity Set Point | %RH | Write | |
| AV | 63 | 5341_1 | Humidity Proportional Band | %RH | Write | |
| AV | 64 | 5032_1 | Humidity Dead Band | %RH | Write | |
| AV | 65 | 5342_1 | Humidity Control Integration Time | min | Write | |
| AV | 66 | 5033_1 | High Return Humidity Threshold | %RH | Write | |
| AV | 67 | 5035_1 | Low Return Humidity Threshold | %RH | Write | |
| AV | 68 | 5343_1 | Today's High Humidity | %RH | Read | |
| AV | 69 | 5344_1 | Today's High Humidity Time | Seconds since Midnight | Read | |
| AV | 70 | 5345_1 | Today's Low Humidity | %RH | Read | |
| AV | 71 | 5346_1 | Today's Low Humidity Time | Seconds since Midnight | Read | |
| AV | 72 | 6258_1 | Dew Point Proportional Band | °C | Write | |
| AV | 10072 | 6258_1_deg_F | Dew Point Proportional Band | °F | Write | |
| AV | 73 | 6259_1 | Dew Point Dead Band | °C | Write | |
| AV | 10073 | 6259_1_deg_F | Dew Point Dead Band | °F | Write | |
| AV | 74 | 6575_1 | Dew Point Over Temp Threshold | °C | Write | |
| AV | 10074 | 6575_1_deg_F | Dew Point Over Temp Threshold | °F | Write | |
| AV | 75 | 6576_1 | Dew Point Under Temp Threshold | °C | Write | |
| AV | 10075 | 6576_1_deg_F | Dew Point Under Temp Threshold | °F | Write | |
| AV | 82 | 4595_1_1 | Ext Air Sensor A Humidity | %RH | Read | |
| AV | 83 | 4598_1_1 | Ext Air Sensor B Humidity | %RH | Read | |
| AV | 84 | 5347_1_1 | Ext Air Sensor C Humidity | %RH | Read | |
| AV | 85 | 5348_1_1 | Ext Air Sensor A High Humidity Threshold | %RH | Write | |
| AV | 86 | 5350_1_1 | Ext Air Sensor A Low Humidity Threshold | %RH | Write | |
| AV | 87 | 4596_1_1 | Ext Air Sensor A Dew Point Temp | °C | Read | |
| AV | 10087 | 4596_1_1_deg_F | Ext Air Sensor A Dew Point Temp | °F | Read | |
| AV | 88 | 4614_1_1 | Ext Dew Point Over Temp Threshold | °C | Write | |
| AV | 10088 | 4614_1_1_deg_F | Ext Dew Point Over Temp Threshold | °F | Write | |
| AV | 89 | 5576_1_1 | Ext Dew Point Under Temp Threshold | °C | Write | |
| AV | 10089 | 5576_1_1_deg_F | Ext Dew Point Under Temp Threshold | °F | Write | |
| AV | 97 | 5267_1_1 | Compressor Hours (Compressor 1) | h | Write | |
| AV | 98 | 5268_1_1 | Compressor Hours Threshold (Compressor 1) | h | Write | |
| AV | 99 | 5353_1_1 | Dig Scroll Comp Discharge Temp (Compressor 1) | °C | Read | |
| AV | 10099 | 5353_1_1_deg_F | Dig Scroll Comp Discharge Temp (Compressor 1) | °F | Read | |
| AV | 100 | 5619_1_1 | Digital Scroll Compressor Loading (Compressor 1) | % | Read | |
| AV | 101 | 6241_1_1 | Tandem 'B' Compressor Hours (Compressor 1) | h | Write | |
| AV | 102 | 6688_1_1 | Compressor Suction Pressure (Compressor 1) | bar | Read | |
| AV | 110 | 5267_1_2 | Compressor Hours (Compressor 2) | h | Write | |
| AV | 111 | 5268_1_2 | Compressor Hours Threshold (Compressor 2) | h | Write | |
| AV | 112 | 5353_1_2 | Dig Scroll Comp Discharge Temp (Compressor 2) | °C | Read | |
| AV | 10112 | 5353_1_2_deg_F | Dig Scroll Comp Discharge Temp (Compressor 2) | °F | Read | |
| AV | 113 | 5619_1_2 | Digital Scroll Compressor Loading (Compressor 2) | % | Read | |
| AV | 114 | 6241_1_2 | Tandem 'B' Compressor Hours (Compressor 2) | h | Write | |
| AV | 115 | 6688_1_2 | Compressor Suction Pressure (Compressor 2) | bar | Read | |
| AV | 2250 | 5353_1_4 | Dig Scroll Comp Discharge Temp (Compressor 4) | °C | Read | |
| AV | 12250 | 5353_1_4_deg_F | Dig Scroll Comp Discharge Temp (Compressor 4) | °F | Read | |
| AV | 2251 | 5619_1_4 | Digital Scroll Compressor Loading (Compressor 4) | % | Read | |
| AV | 2252 | 5267_1_4 | Compressor Hours (Compressor 4) | h | Write | |
| AV | 2253 | 6241_1_4 | Tandem 'B' Compressor Hours (Compressor 4) | h | Write | |
| AV | 2254 | 5268_1_4 | Compressor Hours Threshold (Compressor 4) | h | Write | |
| AV | 2255 | 6688_1_4 | Compressor Suction Pressure (Compressor 4) | bar | Read | |
| AV | 3007 | 5378_12 | Analog Input Reading | Read | ||
| AV | 268 | 5075_1 | BMS Timeout Period | min | Write | |
| AV | 269 | 4710_1 | Auto Restart Delay | s | Write | |
| AV | 270 | 5314_1 | Standby Units | Write | ||
| AV | 271 | 6121_1 | Unit to Unit Group | Read | ||
| AV | 272 | 6120_1 | Unit to Unit Address | Read | ||
| AVmin | 31 | 4291_1 | Return Air Temperature | °C | Read | |
| AV | 10031 | 4291_1_deg_F | Return Air Temperature | °F | Read | |
| AV | 280 | 5077_1 | Fan Speed | % | Read | |
| AV | 282 | 5379_1 | Free Cooling Valve Open Position | % | Read | |
| AV | 283 | 4870_1 | Maintenance Ramp | % | Read | |
| AV | 284 | 4868_1 | Calculated Next Maintenance Month | Read | ||
| AV | 285 | 4869_1 | Calculated Next Maintenance Year | Read | ||
| AV | 286 | 5380_1 | Hot Water / Hot Gas Valve Open Position | % | Read | |
| AV | 287 | 5080_1 | Reheat Utilization | % | Read | |
| AV | 288 | 5081_1 | Humidifier Utilization | % | Read | |
| AV | 289 | 5079_1 | Dehumidifier Utilization | % | Read | |
| AV | 290 | 5490_1 | Cooling Capacity | % | Read | |
| AV | 291 | 5606_1 | Adjusted Humidity | %RH | Read | |
| AV | 292 | 5004_1 | Return Dew Point | °C | Read | |
| AV | 10292 | 5004_1_deg_F | Return Dew Point | °F | Read | |
| AV | 293 | 5607_1 | Actual Air Temperature Set Point | °C | Read | |
| AV | 10293 | 5607_1_deg_F | Actual Air Temperature Set Point | °F | Read | |
| AV | 294 | 5608_1 | Actual Humidity Set Point | %RH | Read | |
| AV | 295 | 5575_1 | Dew Point Set Point | °C | Write | |
| AV | 10295 | 5575_1_deg_F | Dew Point Set Point | °F | Write | |
| AV | 296 | 5615_1 | Cooling Control Temperature | °C | Read | |
| AV | 10296 | 5615_1_deg_F | Cooling Control Temperature | °F | Read | |
| AV | 297 | 5616_1 | Fan Speed Control Temperature | °C | Read | |
| AV | 10297 | 5616_1_deg_F | Fan Speed Control Temperature | °F | Read | |
| AV | 298 | 5904_1 | Unit Cooling Load | kW | Read | |
| AV | 299 | 6134_1 | Unit Calculated Airflow | m3/h | Read | |
| AV | 300 | 4293_1 | System Date and Time | Secs since Epoch(UTC) | Write | |
| AV | 312 | 5589_1 | Remote Sensor Over Temp Threshold | °C | Write | |
| AV | 10312 | 5589_1_deg_F | Remote Sensor Over Temp Threshold | °F | Write | |
| AV | 313 | 5590_1 | Remote Sensor Under Temp Threshold | °C | Write | |
| AV | 10313 | 5590_1_deg_F | Remote Sensor Under Temp Threshold | °F | Write | |
| AV | 314 | 5007_1 | Remote Sensor Average Temperature | °C | Read | |
| AV | 10314 | 5007_1_deg_F | Remote Sensor Average Temperature | °F | Read | |
| AV | 315 | 5006_1 | Remote Sensor Maximum Temperature | °C | Read | |
| AV | 10315 | 5006_1_deg_F | Remote Sensor Maximum Temperature | °F | Read | |
| AV | 316 | 5591_1 | Remote Sensor System Average Temperature | °C | Read | |
| AV | 10316 | 5591_1_deg_F | Remote Sensor System Average Temperature | °F | Read | |
| AV | 317 | 5592_1 | Remote Sensor System Maximum Temperature | °C | Read | |
| AV | 10317 | 5592_1_deg_F | Remote Sensor System Maximum Temperature | °F | Read | |
| AV | 329 | 5059_1_1 | Remote Sensor Temperature (Remote Sensor 1) | °C | Read | |
| AV | 10329 | 5059_1_1_deg_F | Remote Sensor Temperature (Remote Sensor 1) | °F | Read | |
| AV | 341 | 5059_1_2 | Remote Sensor Temperature (Remote Sensor 2) | °C | Read | |
| AV | 10341 | 5059_1_2_deg_F | Remote Sensor Temperature (Remote Sensor 2) | °F | Read | |
| AV | 437 | 5059_1_10 | Remote Sensor Temperature (Remote Sensor 10) | °C | Read | |
| AV | 10437 | 5059_1_10_deg_F | Remote Sensor Temperature (Remote Sensor 10) | °F | Read | |
| AV | 505 | 5299_1 | Pump Hours Threshold | h | Write | |
| AV | 523 | 5298_1_1 | Pump Hours (Pump 1) | h | Write | |
| AV | 522 | 5634_1_1 | Pump Speed (Pump 1) | % | Read | |
| AV | 535 | 5635_1_1 | Pump Inlet Refrigerant Temperature (Pump 1) | °C | Read | |
| AV | 10535 | 5635_1_1_deg_F | Pump Inlet Refrigerant Temperature (Pump 1) | °F | Read | |
| AV | 537 | 5639_1_1 | Pump Outlet Refrigerant Temperature (Pump 1) | °C | Read | |
| AV | 10537 | 5639_1_1_deg_F | Pump Outlet Refrigerant Temperature (Pump 1) | °F | Read | |
| AV | 526 | 5298_1_2 | Pump Hours (Pump 2) | h | Write | |
| AV | 525 | 5634_1_2 | Pump Speed (Pump 2) | % | Read | |
| AV | 538 | 5635_1_2 | Pump Inlet Refrigerant Temperature (Pump 2) | °C | Read | |
| AV | 10538 | 5635_1_2_deg_F | Pump Inlet Refrigerant Temperature (Pump 2) | °F | Read | |
| AV | 540 | 5639_1_2 | Pump Outlet Refrigerant Temperature (Pump 2) | °C | Read | |
| AV | 10540 | 5639_1_2_deg_F | Pump Outlet Refrigerant Temperature (Pump 2) | °F | Read | |
| AV | 2288 | 5298_1_4 | Pump Hours (Pump 4) | h | Write | |
| AV | 2289 | 5634_1_4 | Pump Speed (Pump 4) | % | Read | |
| AV | 2290 | 5635_1_4 | Pump Inlet Refrigerant Temperature (Pump 4) | °C | Read | |
| AV | 12290 | 5635_1_4_deg_F | Pump Inlet Refrigerant Temperature (Pump 4) | °F | Read | |
| AV | 2291 | 5639_1_4 | Pump Outlet Refrigerant Temperature (Pump 4) | °C | Read | |
| AV | 12291 | 5639_1_4_deg_F | Pump Outlet Refrigerant Temperature (Pump 4) | °F | Read | |
| AV | 810 | 4096_1 | System Input RMS A-N | V | Read | |
| AV | 811 | 4098_1 | System Input RMS B-N | V | Read | |
| AV | 812 | 4100_1 | System Input RMS C-N | V | Read | |
| AV | 813 | 4113_1 | System Input RMS Current Phase A | A | Read | |
| AV | 814 | 4114_1 | System Input RMS Current Phase B | A | Read | |
| AV | 815 | 4115_1 | System Input RMS Current Phase C | A | Read | |
| AV | 816 | 5901_1 | Instantaneous Power | W | Read | |
| AV | 817 | 5900_1 | Energy Consumption | kWh | Write | |
| AV | 1900 | 4097_1 | System Input RMS A-B | V | Read | |
| AV | 1901 | 4099_1 | System Input RMS B-C | V | Read | |
| AV | 1902 | 4101_1 | System Input RMS C-A | V | Read | |
| AV | 901 | 5905_1_1 | Circuit Cooling Load (Cooling Load 1) | kW | Read | |
| AV | 911 | 5905_1_2 | Circuit Cooling Load (Cooling Load 2) | kW | Read | |
| AV | 1960 | 5964_1_1 | Raw Auxiliary Air Temperature | °C | Write | |
| AV | 11960 | 5964_1_1_deg_F | Raw Auxiliary Air Temperature | °F | Write | |
| AV | 1961 | 5965_1_1 | Actual Auxiliary Air Temperature | °C | Read | |
| AV | 11961 | 5965_1_1_deg_F | Actual Auxiliary Air Temperature | °F | Read | |
| AV | 1981 | 6101_1 | Expected Condenser Unit Count | Read | ||
| AV | 529 | 5548_1_1 | Condenser Low Noise Mode Max Fan Speed | % | Write | |
| AV | 530 | 5549_1_1 | Condenser Normal Mode Max Fan Speed | % | Write | |
| AV | 531 | 5552_1_1 | Condenser Low Noise Mode Start Time | Seconds since Midnight | Write | |
| AV | 532 | 5553_1_1 | Condenser Low Noise Mode Stop Time | Seconds since Midnight | Write | |
| AV | 533 | 5550_1_1 | Condenser Low Noise Mode - Interval Days | Write | 1=Monday, 2=Tuesday, 4=Wednesday, 8=Thursday, 16=Friday, 32=Saturday, 64=Sunday | |
| AV | 534 | 5551_1_1 | Condenser Low Noise Mode - Full Days | Write | 1=Monday, 2=Tuesday, 4=Wednesday, 8=Thursday, 16=Friday, 32=Saturday, 64=Sunday | |
| AV | 1992 | 5534_1_1 | Condenser Outside Air Temperature (Condenser 1) | °C | Read | |
| AV | 11992 | 5534_1_1_deg_F | Condenser Outside Air Temperature (Condenser 1) | °F | Read | |
| AV | 1993 | 5534_1_2 | Condenser Outside Air Temperature (Condenser 2) | °C | Read | |
| AV | 11993 | 5534_1_2_deg_F | Condenser Outside Air Temperature (Condenser 2) | °F | Read | |
| AV | 2318 | 5534_1_4 | Condenser Outside Air Temperature (Condenser 4) | °C | Read | |
| AV | 12318 | 5534_1_4_deg_F | Condenser Outside Air Temperature (Condenser 4) | °F | Read | |
| AV | 2004 | 6103_1_1 | Condenser Refrigerant Pressure (Circuit 1) | bar | Read | |
| AV | 2006 | 6102_1_1 | Condenser Supply Refrigerant Temperature (Circuit 1) | °C | Read | |
| AV | 12006 | 6102_1_1_deg_F | Condenser Supply Refrigerant Temperature (Circuit 1) | °F | Read | |
| AV | 2005 | 6103_1_2 | Condenser Refrigerant Pressure (Circuit 2) | bar | Read | |
| AV | 2007 | 6102_1_2 | Condenser Supply Refrigerant Temperature (Circuit 2) | °C | Read | |
| AV | 12007 | 6102_1_2_deg_F | Condenser Supply Refrigerant Temperature (Circuit 2) | °F | Read | |
| AV | 2350 | 6103_1_4 | Condenser Refrigerant Pressure (Circuit 4) | bar | Read | |
| AV | 2351 | 6102_1_4 | Condenser Supply Refrigerant Temperature (Circuit 4) | °C | Read | |
| AV | 12351 | 6102_1_4_deg_F | Condenser Supply Refrigerant Temperature (Circuit 4) | °F | Read | |
| AV | 2018 | 5276_1_1_1 | Condenser Fan Speed (Condenser 1 Fan 1) | % | Read | |
| AV | 2026 | 5538_1_1_1 | Condenser Fan Power (Condenser 1 Fan 1) | W | Read | |
| AV | 2034 | 6244_1_1_1 | Condenser Fan Current (Condenser 1 Fan 1) | A | Read | |
| AV | 2019 | 5276_1_1_2 | Condenser Fan Speed (Condenser 1 Fan 2) | % | Read | |
| AV | 2027 | 5538_1_1_2 | Condenser Fan Power (Condenser 1 Fan 2) | W | Read | |
| AV | 2035 | 6244_1_1_2 | Condenser Fan Current (Condenser 1 Fan 2) | A | Read | |
| AV | 2021 | 5276_1_1_4 | Condenser Fan Speed (Condenser 1 Fan 4) | % | Read | |
| AV | 2029 | 5538_1_1_4 | Condenser Fan Power (Condenser 1 Fan 4) | W | Read | |
| AV | 2037 | 6244_1_1_4 | Condenser Fan Current (Condenser 1 Fan 4) | A | Read | |
| AV | 2022 | 5276_1_2_1 | Condenser Fan Speed (Condenser 2 Fan 1) | % | Read | |
| AV | 2030 | 5538_1_2_1 | Condenser Fan Power (Condenser 2 Fan 1) | W | Read | |
| AV | 2038 | 6244_1_2_1 | Condenser Fan Current (Condenser 2 Fan 1) | A | Read | |
| AV | 2023 | 5276_1_2_2 | Condenser Fan Speed (Condenser 2 Fan 2) | % | Read | |
| AV | 2031 | 5538_1_2_2 | Condenser Fan Power (Condenser 2 Fan 2) | W | Read | |
| AV | 2039 | 6244_1_2_2 | Condenser Fan Current (Condenser 2 Fan 2) | A | Read | |
| AV | 2025 | 5276_1_2_4 | Condenser Fan Speed (Condenser 2 Fan 4) | % | Read | |
| AV | 2033 | 5538_1_2_4 | Condenser Fan Power (Condenser 2 Fan 4) | W | Read | |
| AV | 2041 | 6244_1_2_4 | Condenser Fan Current (Condenser 2 Fan 4) | A | Read | |
| AV | 2423 | 5276_1_4_1 | Condenser Fan Speed (Condenser 4 Fan 1) | % | Read | |
| AV | 2424 | 5538_1_4_1 | Condenser Fan Power (Condenser 4 Fan 1) | W | Read | |
| AV | 2425 | 6244_1_4_1 | Condenser Fan Current (Condenser 4 Fan 1) | A | Read | |
| AV | 2436 | 5276_1_4_2 | Condenser Fan Speed (Condenser 4 Fan 2) | % | Read | |
| AV | 2437 | 5538_1_4_2 | Condenser Fan Power (Condenser 4 Fan 2) | W | Read | |
| AV | 2438 | 6244_1_4_2 | Condenser Fan Current (Condenser 4 Fan 2) | A | Read | |
| AV | 2462 | 5276_1_4_4 | Condenser Fan Speed (Condenser 4 Fan 4) | % | Read | |
| AV | 2463 | 5538_1_4_4 | Condenser Fan Power (Condenser 4 Fan 4) | W | Read | |
| AV | 2464 | 6244_1_4_4 | Condenser Fan Current (Condenser 4 Fan 4) | A | Read | |
| AV | 2476 | 6797_1 | EconoPhase Proportional Band Switchover | % | Write | |
| AV | 2501 | 6820_1 | Event Log Record Counter | Read | ||
| AV | 2502 | 6821_1 | Audit Log Record Counter | Read | ||
| AV | 2526 | 6780_1_1 | Unit Cascade On Delay | min | Write | |
| AV | 2527 | 6781_1_1 | Quick Start Unit Cascade On Delay | s | Write | |
| AV | 2528 | 6779_1_1 | Unit Cascade Control Delay | min | Write | |
| AV | 2529 | 6783_1_1 | Teamwork Average Calculation Unit Count | Write | ||
| AV | 2542 | 6122_1_1 | Networked Unit Rotation Time | Seconds since Midnight | Write | |
| AV | 2543 | 6123_1_1 | Networked Unit Rotation Count | Write | ||
| AV | 2554 | 7130_1_1 | Power Source: L1-L2 voltage (Power Source 1) | V | Read | |
| AV | 2555 | 7131_1_1 | Power Source: L2-L3 voltage (Power Source 1) | V | Read | |
| AV | 2556 | 7132_1_1 | Power Source: L3-L1 voltage (Power Source 1) | V | Read | |
| AV | 2557 | 7133_1_1 | Power Source: Line Frequency (Power Source 1) | Hz | Read | |
| AV | 2558 | 7134_1_1 | Power Source: Breaker Operation Count (Power Source 1) | Read | ||
| AV | 2569 | 7130_1_2 | Power Source: L1-L2 voltage (Power Source 2) | V | Read | |
| AV | 2570 | 7131_1_2 | Power Source: L2-L3 voltage (Power Source 2) | V | Read | |
| AV | 2571 | 7132_1_2 | Power Source: L3-L1 voltage (Power Source 2) | V | Read | |
| AV | 2572 | 7133_1_2 | Power Source: Line Frequency (Power Source 2) | Hz | Read | |
| AV | 2573 | 7134_1_2 | Power Source: Breaker Operation Count (Power Source 2) | Read | ||
| AVmin | 2584 | 4643_1 | Supply Fluid Temperature | °C | Read | |
| AV | 12584 | 4643_1_deg_F | Supply Fluid Temperature | °F | Read | |
| AV | 2585 | 5288_1 | Return Fluid Temperature | °C | Read | |
| AV | 12585 | 5288_1_deg_F | Return Fluid Temperature | °F | Read | |
| AV | 2586 | 7468_1 | Flow Rate | l/min | Read | |
| AV | 2587 | 5491_1 | Cooling Capacity | kW | Read | |
| AV | 2588 | 7469_1 | Pump Speed (Fluid Loop) | % | Read | |
| AV | 2593 | 4644_1 | Supply Fluid Over Temp Threshold | °C | Write | |
| AV | 12593 | 4644_1_deg_F | Supply Fluid Over Temp Threshold | °F | Write | |
| AV | 2594 | 5289_1 | Return Fluid Over Temp Threshold | °C | Write | |
| AV | 12594 | 5289_1_deg_F | Return Fluid Over Temp Threshold | °F | Write | |
| AV | 2605 | 7480_1_1 | Pump Speed (Fluid Pump 1) | % | Read | |
| AV | 2607 | 7482_1_1 | Pump Run Time | h | Read | |
| AV | 2904 | 8167_1_1 | Pump Motor Power | kW | Read | |
| AV | 2905 | 8168_1_1 | Pump Motor Amps | A | Read | |
| AV | 2906 | 8169_1_1 | Inverter Temperature | °C | Read | |
| AV | 12906 | 8169_1_1_deg_F | Inverter Temperature | °F | Read | |
| AV | 2823 | 8132_1 | Unit Fluid Supply Temperature | °C | Read | |
| AV | 12823 | 8132_1_deg_F | Unit Fluid Supply Temperature | °F | Read | |
| AV | 2824 | 8133_1 | Unit Fluid Return Temperature | °C | Read | |
| AV | 12824 | 8133_1_deg_F | Unit Fluid Return Temperature | °F | Read | |
| AV | 2825 | 8134_1 | Unit Fluid Supply Pressure | bar | Read | |
| AV | 2826 | 8135_1 | Unit Fluid Return Pressure | bar | Read | |
| AV | 2827 | 8136_1 | Unit Fluid Pump Speed | % | Read | |
| AV | 2828 | 8137_1 | Unit Fluid Flow | l/min | Read | |
| AV | 2829 | 8138_1 | Unit Fluid Diff Pressure | bar | Read | |
| AV | 2830 | 8139_1 | Unit Fluid Cooling Capacity | kW | Read | |
| AV | 2831 | 8140_1 | System Fluid Flow | l/min | Read | |
| AV | 2832 | 8141_1 | System Fluid Diff Pressure | bar | Read | |
| AV | 2833 | 8142_1 | System Fluid Cooling Capacity | kW | Read | |
| AVmin | 2844 | 8143_1_1 | Fluid Temperature Set Point | °C | Write | |
| AV | 12844 | 8143_1_1_deg_F | Fluid Temperature Set Point | °F | Write | |
| AV | 2845 | 8145_1_1 | Fluid Temperature Proportional Band | °C | Write | |
| AV | 12845 | 8145_1_1_deg_F | Fluid Temperature Proportional Band | °F | Write | |
| AV | 2846 | 8146_1_1 | Fluid Temperature Dead Band | °C | Write | |
| AV | 12846 | 8146_1_1_deg_F | Fluid Temperature Dead Band | °F | Write | |
| AV | 2847 | 8147_1_1 | Fluid Temperature Control Integration Time | min | Write | |
| AV | 2858 | 8149_1_1 | Fluid Flow Set Point | l/min | Write | |
| AV | 2859 | 8150_1_1 | Fluid Flow Proportional Band | l/min | Write | |
| AV | 2860 | 8151_1_1 | Fluid Flow Dead Band | l/min | Write | |
| AV | 2861 | 8152_1_1 | Fluid Flow Control Integration Time | s | Write | |
| AV | 2862 | 8153_1_1 | Fluid Diff Prs Set Point | bar | Write | |
| AV | 2863 | 8154_1_1 | Fluid Diff Prs Prop Band | bar | Write | |
| AV | 2864 | 8155_1_1 | Flow Diff Prs Dead Band | bar | Write | |
| AV | 2865 | 8156_1_1 | Fluid Diff Prs Control Integration Time | s | Write | |
| AV | 2866 | 8157_1_1 | Flow Manual Pump Speed | % | Write | |
| AV | 2867 | 8158_1_1 | Pump Operation Period | day | Write | |
| AV | 2868 | 8159_1_1 | Pump Operation Duration | min | Write | |
| AV | 2869 | 8160_1_1 | Pump Operation Speed | % | Write | |
| AV | 2880 | 8163_1_1 | Dew Point Max Adjust | °C | Write | |
| AV | 12880 | 8163_1_1_deg_F | Dew Point Max Adjust | °F | Write | |
| AV | 2881 | 8164_1_1 | System Dew Point | °C | Read | |
| AV | 12881 | 8164_1_1_deg_F | System Dew Point | °F | Read | |
| AV | 2882 | 8165_1_1 | Unit Dew Point | °C | Read | |
| AV | 12882 | 8165_1_1_deg_F | Unit Dew Point | °F | Read | |
| MV | 1 | 4553_1 | Server Class | Read | 1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR | |
| MV | 35 | 5603_1 | Humidity Control Type | Write | 1=Relative, 2=Compensated, 3=Predictive, 4=Dew Point | |
| MV | 36 | 5618_1 | Humidity Control Sensor | Write | 1=Supply, 2=Remote, 3=Return | |
| MV | 45 | 5264_1_1 | Compressor State (Compressor 1) | Read | 1=off, 2=on | |
| MV | 46 | 5265_1_1 | Compressor Capacity Control State (Compressor 1) | Read | 1=off, 2=on | |
| MV | 47 | 6243_1_1 | Tandem 'B' Compressor State (Compressor 1) | Read | 1=off, 2=on | |
| MV | 57 | 5264_1_2 | Compressor State (Compressor 2) | Read | 1=off, 2=on | |
| MV | 58 | 5265_1_2 | Compressor Capacity Control State (Compressor 2) | Read | 1=off, 2=on | |
| MV | 59 | 6243_1_2 | Tandem 'B' Compressor State (Compressor 2) | Read | 1=off, 2=on | |
| MV | 556 | 5264_1_4 | Compressor State (Compressor 4) | Read | 1=off, 2=on | |
| MV | 557 | 5265_1_4 | Compressor Capacity Control State (Compressor 4) | Read | 1=off, 2=on | |
| MV | 558 | 6243_1_4 | Tandem 'B' Compressor State (Compressor 4) | Read | 1=off, 2=on | |
| MVmin | 93 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation | |
| MVmin | 94 | 4706_1 | Unit Operating State | Read | 1=off, 2=on, 3=standby | |
| MV | 95 | 4707_1 | Unit Control Mode | Read | 1=Internal (Auto), 2=External (Manual) | |
| MV | 96 | 5074_1 | Unit Off Reason | Read | 1=None, 2=User, 3=Alarm, 4=Timer, 5=Monitoring, 6=Remote Off, 7=HCS12 Off | |
| MV | 107 | 5381_1 | Fan State | Read | 1=off, 2=on | |
| MV | 108 | 5382_1 | Cooling State | Read | 1=off, 2=on | |
| MV | 109 | 5383_1 | Free Cooling State | Read | 1=off, 2=on | |
| MV | 110 | 5384_1 | Maintenance Tracking State | Read | 1=off, 2=on | |
| MV | 111 | 5385_1 | Hot Water / Hot Gas State | Read | 1=off, 2=on | |
| MV | 112 | 5386_1 | Electric Reheat State | Read | 1=off, 2=on | |
| MV | 113 | 5387_1 | Dehumidifier State | Read | 1=off, 2=on | |
| MV | 114 | 5388_1 | Humidifier State | Read | 1=off, 2=on | |
| MVmin | 115 | 5143_1 | System On/Off Control | Write | 1=off, 2=on | |
| MV | 500 | 6175_1 | Local Fan Override | Read | 1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection | |
| MV | 501 | 6176_1 | Local Cooling Override | Read | 1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection | |
| MV | 502 | 6177_1 | Local Electric Heat Override | Read | 1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection | |
| MV | 503 | 6178_1 | Local Humidifier Override | Read | 1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection | |
| MV | 504 | 6179_1 | Local Dehumidifier Override | Read | 1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection | |
| MV | 506 | 6524_1 | Automatic Transfer Switch - Active Power Supply | Read | 1=Power Supply 1, 2=Power Supply 2 | |
| MV | 507 | 6525_1 | Automatic Transfer Switch - Power Supply 1 Status | Read | 1=OK, 2=Not OK | |
| MV | 508 | 6526_1 | Automatic Transfer Switch - Power Supply 2 Status | Read | 1=OK, 2=Not OK | |
| MV | 126 | 4718_1 | Customer Input 1 - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 127 | 4719_1 | Customer Input 1 - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 128 | 5098_1 | Customer Input 2 - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 129 | 5099_1 | Customer Input 2 - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 130 | 5100_1 | Customer Input 3 - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 131 | 5101_1 | Customer Input 3 - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 132 | 5102_1 | Customer Input 4 - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 133 | 5103_1 | Customer Input 4 - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 134 | 5389_1 | Ext Free Cooling Lockout - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 135 | 5390_1 | Ext Free Cooling Lockout - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 136 | 5122_1 | Ext Condenser Pump High Water - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 137 | 5123_1 | Ext Condenser Pump High Water - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 138 | 5129_1 | Ext Standby Glycol Pump On - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 139 | 5130_1 | Ext Standby Glycol Pump On - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 140 | 5391_1 | Ext Standby Unit On - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 141 | 5392_1 | Ext Standby Unit On - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 142 | 5086_1 | Ext Humidifier Lockout - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 143 | 5087_1 | Ext Humidifier Lockout - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 144 | 5082_1 | Ext Loss of Flow - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 145 | 5083_1 | Ext Loss of Flow - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 146 | 5090_1 | Ext Over Temperature - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 147 | 5091_1 | Ext Over Temperature - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 148 | 5084_1 | Ext Reheat Lockout - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 149 | 5085_1 | Ext Reheat Lockout - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 150 | 5141_1 | High Power Shutdown - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 151 | 5142_1 | High Power Shutdown - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 152 | 5131_1 | Humidifier Issue - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 153 | 5132_1 | Humidifier Issue - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 154 | 5133_1 | Master Unit Communication Lost - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 155 | 5134_1 | Master Unit Communication Lost - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 156 | 4727_1 | Service Required - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 157 | 4728_1 | Service Required - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 158 | 4715_1 | Shutdown - Loss Of Power - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 159 | 4716_1 | Shutdown - Loss Of Power - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 160 | 4721_1 | Smoke Detected - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 161 | 4722_1 | Smoke Detected - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 162 | 4724_1 | Water Under Floor - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 163 | 4725_1 | Water Under Floor - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 164 | 5088_1 | Ext Compressor Lockout - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 165 | 5089_1 | Ext Compressor Lockout - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 166 | 5135_1 | Clogged Air Filter - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 167 | 5136_1 | Clogged Air Filter - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 168 | 5393_1 | Ext Loss of Air Blower - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 169 | 5394_1 | Ext Loss of Air Blower - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 180 | 5316_1_1 | Compressor High Head Pressure - Event Control (Compressor 1) | Write | 1=disabled, 2=enabled | |
| MV | 181 | 5317_1_1 | Compressor High Head Pressure - Event Type (Compressor 1) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 182 | 5318_1_1 | Compressor Low Suction Pressure - Event Control (Compressor 1) | Write | 1=disabled, 2=enabled | |
| MV | 183 | 5319_1_1 | Compressor Low Suction Pressure - Event Type (Compressor 1) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 184 | 5395_1_1 | Compressor Pump Down Issue - Event Control (Compressor 1) | Write | 1=disabled, 2=enabled | |
| MV | 185 | 5396_1_1 | Compressor Pump Down Issue - Event Type (Compressor 1) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 186 | 5397_1_1 | Compressor Short Cycle - Event Control (Compressor 1) | Write | 1=disabled, 2=enabled | |
| MV | 187 | 5398_1_1 | Compressor Short Cycle - Event Type (Compressor 1) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 188 | 5320_1_1 | Compressor Thermal Overload - Event Control (Compressor 1) | Write | 1=disabled, 2=enabled | |
| MV | 189 | 5321_1_1 | Compressor Thermal Overload - Event Type (Compressor 1) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 190 | 5399_1_1 | Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor 1) | Write | 1=disabled, 2=enabled | |
| MV | 191 | 5400_1_1 | Dig Scroll Comp Discharge Over Temp - Event Type (Compressor 1) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 202 | 5316_1_2 | Compressor High Head Pressure - Event Control (Compressor 2) | Write | 1=disabled, 2=enabled | |
| MV | 203 | 5317_1_2 | Compressor High Head Pressure - Event Type (Compressor 2) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 204 | 5318_1_2 | Compressor Low Suction Pressure - Event Control (Compressor 2) | Write | 1=disabled, 2=enabled | |
| MV | 205 | 5319_1_2 | Compressor Low Suction Pressure - Event Type (Compressor 2) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 206 | 5395_1_2 | Compressor Pump Down Issue - Event Control (Compressor 2) | Write | 1=disabled, 2=enabled | |
| MV | 207 | 5396_1_2 | Compressor Pump Down Issue - Event Type (Compressor 2) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 208 | 5397_1_2 | Compressor Short Cycle - Event Control (Compressor 2) | Write | 1=disabled, 2=enabled | |
| MV | 209 | 5398_1_2 | Compressor Short Cycle - Event Type (Compressor 2) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 210 | 5320_1_2 | Compressor Thermal Overload - Event Control (Compressor 2) | Write | 1=disabled, 2=enabled | |
| MV | 211 | 5321_1_2 | Compressor Thermal Overload - Event Type (Compressor 2) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 212 | 5399_1_2 | Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor 2) | Write | 1=disabled, 2=enabled | |
| MV | 213 | 5400_1_2 | Dig Scroll Comp Discharge Over Temp - Event Type (Compressor 2) | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 224 | 5401_1_1 | Ext Air Sensor A Event Control | Write | 1=disabled, 2=enabled | |
| MV | 225 | 5402_1_1 | Return Air Sensor Event Control | Write | 1=disabled, 2=enabled | |
| MV | 226 | 5403_1_1 | Ext Air Sensor A High Humidity - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 227 | 5404_1_1 | Ext Air Sensor A High Humidity - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 228 | 5405_1_1 | Ext Air Sensor A Low Humidity - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 229 | 5406_1_1 | Ext Air Sensor A Low Humidity - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 230 | 4602_1_1 | Ext Air Sensor A Over Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 231 | 4603_1_1 | Ext Air Sensor A Over Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 232 | 4609_1_1 | Ext Air Sensor A Under Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 233 | 4610_1_1 | Ext Air Sensor A Under Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 234 | 5137_1_1 | High Return Humidity - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 235 | 5138_1_1 | High Return Humidity - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 236 | 5139_1_1 | Low Return Humidity - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 237 | 5140_1_1 | Low Return Humidity - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 238 | 5024_1_1 | Return Air Over Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 239 | 5025_1_1 | Return Air Over Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 240 | 5407_1_1 | Return Air Under Temp - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 241 | 5408_1_1 | Return Air Under Temp - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 242 | 5587_1_1 | Supply Air Over/Under Temperature - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 252 | 5409_1_1 | Fan Hours Exceeded - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 253 | 5410_1_1 | Fan Hours Exceeded - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 256 | 5411_1_1 | Main Fan Overload - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 257 | 5412_1_1 | Main Fan Overload - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 268 | 5413_1_1 | Condenser Issue - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 269 | 5414_1_1 | Condenser Issue - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MV | 280 | 5413_1_2 | Condenser Issue - Event Control | Write | 1=disabled, 2=enabled | |
| MV | 281 | 5414_1_2 | Condenser Issue - Event Type | Write | 1=Message, 2=Warning, 3=Alarm | |
| MVmin | 292 | 4717_1 | System Event Acknowledge/Reset | Write | 1=Reset, 2=Acknowledge | |
| MV | 304 | 5580_1 | Compressor Lockout | Write | 1=disabled, 2=enabled | |
| MV | 363 | 5632_1_1 | PRE Operational Mode (Pump 1) | Read | 1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test | |
| MV | 364 | 5633_1_1 | Pump State (Pump 1) | Read | 1=off, 2=on | |
| MV | 368 | 5632_1_2 | PRE Operational Mode (Pump 2) | Read | 1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test | |
| MV | 369 | 5633_1_2 | Pump State (Pump 2) | Read | 1=off, 2=on | |
| MV | 589 | 5633_1_4 | Pump State (Pump 4) | Read | 1=off, 2=on | |
| MV | 590 | 5632_1_4 | PRE Operational Mode (Pump 4) | Read | 1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test | |
| MV | 395 | 5533_1 | Condenser Refrigerant Type | Read | 1=R22, 2=R407C, 3=R410A | |
| MV | 374 | 5546_1_1 | Condenser Low Noise Mode State | Read | 1=Inactive, 2=Active (Interval), 3=Active (Full Day) | |
| MV | 375 | 5547_1_1 | Condenser Low Noise Mode Schedule Control | Write | 1=disabled, 2=enabled | |
| MV | 406 | 6104_1_1 | Condenser Fan Reversal Requested (Condenser 1) | Write | 1=false, 2=true | |
| MV | 407 | 6104_1_2 | Condenser Fan Reversal Requested (Condenser 2) | Write | 1=false, 2=true | |
| MV | 623 | 6104_1_4 | Condenser Fan Reversal Requested (Condenser 4) | Write | 1=false, 2=true | |
| MV | 635 | 6695_1_1 | Group Independent Operation Enable | Write | 1=disabled, 2=enabled | |
| MV | 636 | 6690_1_1 | Group Independent Operation | Write | 1=No override (default), 2=Override, forced on, 3=Override, forced off | |
| MV | 648 | 6775_1 | Auto Restart Enable | Write | 1=disabled, 2=enabled | |
| MV | 649 | 6777_1 | Virtual Master Enable | Write | 1=disabled, 2=enabled | |
| MV | 662 | 6778_1_1 | Unit Cascade Type | Write | 1=None, 2=Temp/Humidity, 3=Cool/Heat, 4=Cooling, 5=Fan PI, 6=Fan Speed | |
| MV | 663 | 6782_1_1 | Teamwork Temperature Calculation Method | Write | 1=Average, 2=Maximum | |
| MV | 675 | 6130_1_1 | Networked Unit Daily Rotation Frequency | Write | 1=Every 24 hours, 2=Every 12 hours | |
| MV | 676 | 6131_1_1 | Force Networked Unit Rotation | Write | 1=no, 2=yes | |
| MV | 677 | 6129_1_1 | Networked Unit Rotation Frequency | Write | 1=None, 2=Daily, 3=Weekly Monday, 4=Weekly Tuesday, 5=Weekly Wednesday, 6=Weekly Thursday, 7=Weekly Friday, 8=Weekly Saturday, 9=Weekly Sunday, 10=Monthly Monday, 11=Monthly Tuesday, 12=Monthly Wednesday, 13=Monthly Thursday, 14=Monthly Friday, 15=Monthly Saturday, 16=Monthly Sunday | |
| MV | 678 | 6823_1_1 | Start Standby Units on High Temperature | Write | 1=false, 2=true | |
| MV | 700 | 7127_1 | ATS Switch Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Test | |
| MV | 701 | 7128_1 | ATS Load Not Powered Timeout | Read | 1=false, 2=true | |
| MV | 702 | 7129_1 | ATS Non Priority Load Breaker Timeout | Read | 1=false, 2=true | |
| MV | 713 | 7135_1_1 | Power Source: All status are okay (Power Source 1) | Read | 1=false, 2=true | |
| MV | 714 | 7136_1_1 | Power Source: Voltage Is Too Low (Power Source 1) | Read | 1=false, 2=true | |
| MV | 715 | 7137_1_1 | Power Source: Voltage Is Too High (Power Source 1) | Read | 1=false, 2=true | |
| MV | 716 | 7138_1_1 | Power Source: Voltages Are Asymmetric (Power Source 1) | Read | 1=false, 2=true | |
| MV | 717 | 7139_1_1 | Power Source: Voltage Phase Loss (Power Source 1) | Read | 1=false, 2=true | |
| MV | 718 | 7140_1_1 | Power Source: Phase Sequence Issue (Power Source 1) | Read | 1=false, 2=true | |
| MV | 719 | 7141_1_1 | Power Source: Frequency Is Too Low (Power Source 1) | Read | 1=false, 2=true | |
| MV | 720 | 7142_1_1 | Power Source: Frequency Is Too High (Power Source 1) | Read | 1=false, 2=true | |
| MV | 721 | 7143_1_1 | Power Source: Breaker is closed (Power Source 1) | Read | 1=false, 2=true | |
| MV | 722 | 7144_1_1 | Power Source: Breaker command status closed (Power Source 1) | Read | 1=false, 2=true | |
| MV | 723 | 7145_1_1 | Power Source: Breaker withdrawn issue (Power Source 1) | Read | 1=false, 2=true | |
| MV | 724 | 7146_1_1 | Power Source: Breaker Timeout Issue (Power Source 1) | Read | 1=false, 2=true | |
| MV | 725 | 7147_1_1 | Power Source: Line Operating Hour Exceeded (Power Source 1) | Read | 1=false, 2=true | |
| MV | 726 | 7148_1_1 | Power Source: Breaker Operating Hour Exceeded (Power Source 1) | Read | 1=false, 2=true | |
| MV | 737 | 7135_1_2 | Power Source: All status are okay (Power Source 2) | Read | 1=false, 2=true | |
| MV | 738 | 7136_1_2 | Power Source: Voltage Is Too Low (Power Source 2) | Read | 1=false, 2=true | |
| MV | 739 | 7137_1_2 | Power Source: Voltage Is Too High (Power Source 2) | Read | 1=false, 2=true | |
| MV | 740 | 7138_1_2 | Power Source: Voltages Are Asymmetric (Power Source 2) | Read | 1=false, 2=true | |
| MV | 741 | 7139_1_2 | Power Source: Voltage Phase Loss (Power Source 2) | Read | 1=false, 2=true | |
| MV | 742 | 7140_1_2 | Power Source: Phase Sequence Issue (Power Source 2) | Read | 1=false, 2=true | |
| MV | 743 | 7141_1_2 | Power Source: Frequency Is Too Low (Power Source 2) | Read | 1=false, 2=true | |
| MV | 744 | 7142_1_2 | Power Source: Frequency Is Too High (Power Source 2) | Read | 1=false, 2=true | |
| MV | 745 | 7143_1_2 | Power Source: Breaker is closed (Power Source 2) | Read | 1=false, 2=true | |
| MV | 746 | 7144_1_2 | Power Source: Breaker command status closed (Power Source 2) | Read | 1=false, 2=true | |
| MV | 747 | 7145_1_2 | Power Source: Breaker withdrawn issue (Power Source 2) | Read | 1=false, 2=true | |
| MV | 748 | 7146_1_2 | Power Source: Breaker Timeout Issue (Power Source 2) | Read | 1=false, 2=true | |
| MV | 749 | 7147_1_2 | Power Source: Line Operating Hour Exceeded (Power Source 2) | Read | 1=false, 2=true | |
| MV | 750 | 7148_1_2 | Power Source: Breaker Operating Hour Exceeded (Power Source 2) | Read | 1=false, 2=true | |
| MV | 773 | 7479_1_1 | Pump Operating State | Read | 1=off, 2=on | |
| MV | 1209 | 8144_1_1 | Fluid Temperature Control Type | Write | 1=Proportional, 2=Prop+Integral, 3=Adaptive PID, 4=Intelligent | |
| MV | 1220 | 8148_1_1 | Fluid Control Type | Write | 1=Flow Rate, 2=Differential Pressure, 3=Flow Rate with DP Limit, 4=Diff Prs with Flo Limit, 5=Manual | |
| MV | 1231 | 8161_1_1 | Pump Operation Type | Write | 1=Unit On or Standby, 2=Unit On, Off, or Standby | |
| MV | 1242 | 8162_1_1 | Fluid Dew Pnt Margin | Write |
No points match these filters.
Object ID lookup: Vertiv Liebert iCOM XDM precision cooling point IDs by name
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
Integration notes
- Tables 5.56, 5.57, 5.58, pdf pages 1545-1579 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert iCOM XDM precision cooling and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert iCOM XDM precision cooling
How many BACnet points does the Vertiv Liebert iCOM XDM precision cooling have?
This list has 680 BACnet objects: 286 analog values, 206 binary values, 188 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert iCOM XDM precision cooling BACnet points are writable?
211 of the 680 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert iCOM XDM precision cooling BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert iCOM XDM precision cooling?
Start with MV 115 5143_1 (On/off command (1=off, 2=on)); AV 2844 8143_1_1 (Fluid temperature setpoint, °C); AV 61 5029_1 (Humidity setpoint, %RH); MV 292 4717_1 (Acknowledge / reset events); MV 94 4706_1 (Run / standby / off state); MV 93 4123_1 (Normal, warning or alarm state); AV 19 5002_1_1 (Supply air temperature, °C); AV 31 4291_1 (Return air temperature, °C); AV 2584 4643_1 (Supply fluid temperature, °C); AV 60 5028_1 (Return air humidity, %RH).
How do I check these points on the real Liebert iCOM XDM precision cooling?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.