UPS (uninterruptible power supply) · BACnet points list

Vertiv Liebert GXT3 / GXT4 UPS BACnet points list

Updated 6 November 2026

Short answer

The Liebert GXT3 / GXT4 UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.

This page lists 113 BACnet objects for the Vertiv Liebert GXT3 / GXT4 UPS — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert GXT3 / GXT4 UPS
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
113 (14 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
GXT3, GXT4, Liebert GXT4, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 113 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert GXT3 / GXT4 UPS

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 764123_1Normal, warning or alarm stateRead
MV 304872_1Load on inverter, bypass or batteryRead
AV 414150_1Estimated battery runtime, minRead
AV 714208_1Output power, WRead
AV 14096_1Input voltage, VRead
AV 614385_1Output voltage, VRead
AV 634204_1Output current, ARead

Network setup

Watch out for

Vertiv Liebert GXT3 / GXT4 UPS BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

113 of 113 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert GXT3 / GXT4 UPS BACnet Points List
DescriptionStates
BV15568_1Input UndervoltageReadActive = alarm
BV25569_1Input OvervoltageReadActive = alarm
BV134135_1Bypass Not AvailableReadActive = alarm
BV244741_1Battery Self TestReadActive = alarm
BV254162_1Battery LowReadActive = alarm
BV266180_1Battery Under VoltageReadActive = alarm
BV275874_1Battery Over VoltageReadActive = alarm
BV284323_1Battery Test FailedReadActive = alarm
BV296182_1Replace BatteryReadActive = alarm
BV405806_1Output OverloadReadActive = alarm
BV415179_1Output UndervoltageReadActive = alarm
BV425178_1Output OvervoltageReadActive = alarm
BV434215_1System Output OffReadActive = alarm
BV605588_1Unspecified General EventReadActive = alarm
BV614823_1Parallel Comm WarningReadActive = alarm
BV624825_1Loss of RedundancyReadActive = alarm
BV636254_1Charger FailureReadActive = alarm
BV644295_1Rectifier FailureReadActive = alarm
BV654233_1Inverter FailureReadActive = alarm
BV665976_1Maintenance Bypass Breaker ClosedReadActive = alarm
BV674311_1System Fan FailureReadActive = alarm
BV684229_1Emergency Power Off - LatchedReadActive = alarm
BV696453_1Input Wiring FaultReadActive = alarm
BV706454_1DC to DC Converter FaultReadActive = alarm
AVmin14096_1System Input RMS L1-NVRead
AV24098_1System Input RMS L2-NVRead
AV34097_1System Input RMS L1-L2VRead
AV44113_1System Input RMS Current L1ARead
AV54114_1System Input RMS Current L2ARead
AV64105_1System Input FrequencyHzRead
AV74106_1System Input Max Voltage L1-NVRead
AV84107_1System Input Min Voltage L1-NVRead
AV94108_1System Input Max Voltage L2-NVRead
AV104109_1System Input Min Voltage L2-NVRead
AV114102_1System Input Nominal VoltageVRead
AV124104_1System Input Nominal CurrentARead
AV134103_1System Input Nominal FrequencyHzRead
AV244128_1Bypass Input Voltage RMS L1-NVRead
AV254125_1Bypass Input Voltage RMS L1-L2VRead
AV264129_1Bypass Input Voltage RMS L2-NVRead
AV275570_1Bypass Input RMS CurrentARead
AV285571_1Bypass Input RMS Current Line 2ARead
AV294131_1Bypass Input FrequencyHzRead
AV304259_1Bypass Nominal VoltageVRead
AVmin414150_1Battery Time RemainingminRead
AV424153_1Battery Percentage Charge%Read
AV434148_1DC Bus VoltageVDCRead
AV446189_1DC Bus Nominal VoltageVDCRead
AV454898_1Battery RatingAHRead
AV465802_1Low Battery Warning TimeminWrite
AV475800_1Number of EBC InstalledRead
AV486195_1Nominal Battery CapacityminRead
AV494151_1Battery Discharge TimeminRead
AV505988_1Battery Float VoltageVDCRead
AVmin614385_1System Output Voltage RMS L1-NVRead
AV624201_1System Output Voltage RMS L1-L2VRead
AVmin634204_1System Output RMS Current L1ARead
AV644386_1System Output Voltage RMS L2-NVRead
AV654205_1System Output RMS Current L2ARead
AV664207_1System Output FrequencyHzRead
AV676184_1System Output Max Voltage L1-NVRead
AV686185_1System Output Min Voltage L1-NVRead
AV696213_1System Output Max Voltage L2-NVRead
AV706214_1System Output Min Voltage L2-NVRead
AVmin714208_1System Output PowerWRead
AV725859_1System Output Power L1WRead
AV735860_1System Output Power L2WRead
AV745861_1System Output Pct Power%Read
AV754223_1System Output Pct Power L1%Read
AV764224_1System Output Pct Power L2%Read
AV774209_1System Output Apparent PowerVARead
AV785868_1System Output Apparent Power L1VARead
AV795869_1System Output Apparent Power L2VARead
AV804260_1System Output Nominal VoltageVRead
AV814264_1Output Apparent Power RatingVARead
AV824261_1System Output Nominal FrequencyHzRead
AV835816_1Output On DelaysWrite
AV845815_1Reboot With DelaysWrite
AV855814_1Shutdown After DelaysWrite
AV865812_1Nominal Power FactorRead
AV974510_1Outlet Group Identifier (Outlet Group 1)Read
AV1084510_2Outlet Group Identifier (Outlet Group 2)Read
AV1194120_1System Input Black Out CountRead
AV1204119_1System Input Brown Out CountRead
AV1214710_1Auto Restart DelaysWrite
AV1224291_1Inlet Air Temperature°CRead
AV101224291_1_deg_FInlet Air Temperature°FRead
MV14553_1Server ClassRead1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR
MV124871_1UPS Battery StatusRead1=Unknown, 2=Normal, 3=Low, 4=Depleted
MV135799_1Battery Charge StatusRead1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off)
MV146183_1Battery Cabinet TypeRead1=Internal, 2=External, 3=LRT
MV156190_1Battery Charge CompensatingRead1=false, 2=true
MV166192_1Battery Charger StateRead1=off, 2=on
MV176181_1Battery Test ResultRead1=Unknown, 2=Passed, 3=Failed, 4=In Progress, 5=System Failure, 6=Inhibited
MV185858_1Manual Battery TestWrite1=Start Test
MV195803_1Automatic Battery TestRead1=disabled, 2=enabled
MVmin304872_1UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MV316196_1Power Factor CorrectionRead1=off, 2=on
MV424365_1Outlet Group Power Control (Outlet Group 1)Write1=Off, 2=On, 3=Cycle Power
MV534365_2Outlet Group Power Control (Outlet Group 2)Write1=off, 2=on, 3=Cycle Power
MV646198_1ECO Mode StatusRead1=off, 2=on
MV655454_1ECO Mode Operation StateWrite1=disabled, 2=enabled
MVmin764123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MV775831_1Auto RestartWrite1=disabled, 2=enabled
MV784746_1Inverter On/Off StateRead1=off, 2=on
MV796197_1Shutdown ReasonRead1=None, 2=Over Temperature, 3=Overload, 4=DC Bus Overload, 5=Output Short, 6=Line Swap, 7=Low Battery, 8=Remote Command, 9=Input Under Voltage, 10=Power Factor Correction Fail, 11=External Signal Command
MV806200_1Abort CommandWrite1=Issue Command
MV816003_1DC Converter StatusRead1=off, 2=on
MV826199_1UPS TopologyRead1=unknown, 2=Offline, 3=Line Interactive, 4=Online
MV836224_1Bypass/Inverter Input ConfigRead1=Single/Combined Source, 2=Dual/Separate Sources
MV846191_1Reset Power StatisticsWrite1=Reset
MV856188_1Audible Alarm ControlWrite1=off, 2=on
MV866257_1Silence Audible AlarmWrite1=Silence Alarm
Object ID lookup: Vertiv Liebert GXT3 / GXT4 UPS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert GXT3 / GXT4 UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert GXT3 / GXT4 UPS

How many BACnet points does the Vertiv Liebert GXT3 / GXT4 UPS have?

This list has 113 BACnet objects: 63 analog values, 24 binary values, 26 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert GXT3 / GXT4 UPS BACnet points are writable?

14 of the 113 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert GXT3 / GXT4 UPS BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert GXT3 / GXT4 UPS?

Start with MV 76 4123_1 (Normal, warning or alarm state); MV 30 4872_1 (Load on inverter, bypass or battery); AV 41 4150_1 (Estimated battery runtime, min); AV 71 4208_1 (Output power, W); AV 1 4096_1 (Input voltage, V); AV 61 4385_1 (Output voltage, V); AV 63 4204_1 (Output current, A).

How do I check these points on the real Liebert GXT3 / GXT4 UPS?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.