UPS (uninterruptible power supply) · BACnet points list
Vertiv Liebert GXT3 / GXT4 UPS BACnet points list
Updated 6 November 2026
The Liebert GXT3 / GXT4 UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.
This page lists 113 BACnet objects for the Vertiv Liebert GXT3 / GXT4 UPS — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert GXT3 / GXT4 UPS
- Equipment
- UPS (uninterruptible power supply)
- Equipment type
- Other equipment
- BACnet objects
- 113 (14 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- GXT3, GXT4, Liebert GXT4, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert GXT3 / GXT4 UPS
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 76 | 4123_1 | Normal, warning or alarm state | Read |
| MV 30 | 4872_1 | Load on inverter, bypass or battery | Read |
| AV 41 | 4150_1 | Estimated battery runtime, min | Read |
| AV 71 | 4208_1 | Output power, W | Read |
| AV 1 | 4096_1 | Input voltage, V | Read |
| AV 61 | 4385_1 | Output voltage, V | Read |
| AV 63 | 4204_1 | Output current, A | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert GXT3 / GXT4 UPS BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | 5568_1 | Input Undervoltage | Read | Active = alarm | |
| BV | 2 | 5569_1 | Input Overvoltage | Read | Active = alarm | |
| BV | 13 | 4135_1 | Bypass Not Available | Read | Active = alarm | |
| BV | 24 | 4741_1 | Battery Self Test | Read | Active = alarm | |
| BV | 25 | 4162_1 | Battery Low | Read | Active = alarm | |
| BV | 26 | 6180_1 | Battery Under Voltage | Read | Active = alarm | |
| BV | 27 | 5874_1 | Battery Over Voltage | Read | Active = alarm | |
| BV | 28 | 4323_1 | Battery Test Failed | Read | Active = alarm | |
| BV | 29 | 6182_1 | Replace Battery | Read | Active = alarm | |
| BV | 40 | 5806_1 | Output Overload | Read | Active = alarm | |
| BV | 41 | 5179_1 | Output Undervoltage | Read | Active = alarm | |
| BV | 42 | 5178_1 | Output Overvoltage | Read | Active = alarm | |
| BV | 43 | 4215_1 | System Output Off | Read | Active = alarm | |
| BV | 60 | 5588_1 | Unspecified General Event | Read | Active = alarm | |
| BV | 61 | 4823_1 | Parallel Comm Warning | Read | Active = alarm | |
| BV | 62 | 4825_1 | Loss of Redundancy | Read | Active = alarm | |
| BV | 63 | 6254_1 | Charger Failure | Read | Active = alarm | |
| BV | 64 | 4295_1 | Rectifier Failure | Read | Active = alarm | |
| BV | 65 | 4233_1 | Inverter Failure | Read | Active = alarm | |
| BV | 66 | 5976_1 | Maintenance Bypass Breaker Closed | Read | Active = alarm | |
| BV | 67 | 4311_1 | System Fan Failure | Read | Active = alarm | |
| BV | 68 | 4229_1 | Emergency Power Off - Latched | Read | Active = alarm | |
| BV | 69 | 6453_1 | Input Wiring Fault | Read | Active = alarm | |
| BV | 70 | 6454_1 | DC to DC Converter Fault | Read | Active = alarm | |
| AVmin | 1 | 4096_1 | System Input RMS L1-N | V | Read | |
| AV | 2 | 4098_1 | System Input RMS L2-N | V | Read | |
| AV | 3 | 4097_1 | System Input RMS L1-L2 | V | Read | |
| AV | 4 | 4113_1 | System Input RMS Current L1 | A | Read | |
| AV | 5 | 4114_1 | System Input RMS Current L2 | A | Read | |
| AV | 6 | 4105_1 | System Input Frequency | Hz | Read | |
| AV | 7 | 4106_1 | System Input Max Voltage L1-N | V | Read | |
| AV | 8 | 4107_1 | System Input Min Voltage L1-N | V | Read | |
| AV | 9 | 4108_1 | System Input Max Voltage L2-N | V | Read | |
| AV | 10 | 4109_1 | System Input Min Voltage L2-N | V | Read | |
| AV | 11 | 4102_1 | System Input Nominal Voltage | V | Read | |
| AV | 12 | 4104_1 | System Input Nominal Current | A | Read | |
| AV | 13 | 4103_1 | System Input Nominal Frequency | Hz | Read | |
| AV | 24 | 4128_1 | Bypass Input Voltage RMS L1-N | V | Read | |
| AV | 25 | 4125_1 | Bypass Input Voltage RMS L1-L2 | V | Read | |
| AV | 26 | 4129_1 | Bypass Input Voltage RMS L2-N | V | Read | |
| AV | 27 | 5570_1 | Bypass Input RMS Current | A | Read | |
| AV | 28 | 5571_1 | Bypass Input RMS Current Line 2 | A | Read | |
| AV | 29 | 4131_1 | Bypass Input Frequency | Hz | Read | |
| AV | 30 | 4259_1 | Bypass Nominal Voltage | V | Read | |
| AVmin | 41 | 4150_1 | Battery Time Remaining | min | Read | |
| AV | 42 | 4153_1 | Battery Percentage Charge | % | Read | |
| AV | 43 | 4148_1 | DC Bus Voltage | VDC | Read | |
| AV | 44 | 6189_1 | DC Bus Nominal Voltage | VDC | Read | |
| AV | 45 | 4898_1 | Battery Rating | AH | Read | |
| AV | 46 | 5802_1 | Low Battery Warning Time | min | Write | |
| AV | 47 | 5800_1 | Number of EBC Installed | Read | ||
| AV | 48 | 6195_1 | Nominal Battery Capacity | min | Read | |
| AV | 49 | 4151_1 | Battery Discharge Time | min | Read | |
| AV | 50 | 5988_1 | Battery Float Voltage | VDC | Read | |
| AVmin | 61 | 4385_1 | System Output Voltage RMS L1-N | V | Read | |
| AV | 62 | 4201_1 | System Output Voltage RMS L1-L2 | V | Read | |
| AVmin | 63 | 4204_1 | System Output RMS Current L1 | A | Read | |
| AV | 64 | 4386_1 | System Output Voltage RMS L2-N | V | Read | |
| AV | 65 | 4205_1 | System Output RMS Current L2 | A | Read | |
| AV | 66 | 4207_1 | System Output Frequency | Hz | Read | |
| AV | 67 | 6184_1 | System Output Max Voltage L1-N | V | Read | |
| AV | 68 | 6185_1 | System Output Min Voltage L1-N | V | Read | |
| AV | 69 | 6213_1 | System Output Max Voltage L2-N | V | Read | |
| AV | 70 | 6214_1 | System Output Min Voltage L2-N | V | Read | |
| AVmin | 71 | 4208_1 | System Output Power | W | Read | |
| AV | 72 | 5859_1 | System Output Power L1 | W | Read | |
| AV | 73 | 5860_1 | System Output Power L2 | W | Read | |
| AV | 74 | 5861_1 | System Output Pct Power | % | Read | |
| AV | 75 | 4223_1 | System Output Pct Power L1 | % | Read | |
| AV | 76 | 4224_1 | System Output Pct Power L2 | % | Read | |
| AV | 77 | 4209_1 | System Output Apparent Power | VA | Read | |
| AV | 78 | 5868_1 | System Output Apparent Power L1 | VA | Read | |
| AV | 79 | 5869_1 | System Output Apparent Power L2 | VA | Read | |
| AV | 80 | 4260_1 | System Output Nominal Voltage | V | Read | |
| AV | 81 | 4264_1 | Output Apparent Power Rating | VA | Read | |
| AV | 82 | 4261_1 | System Output Nominal Frequency | Hz | Read | |
| AV | 83 | 5816_1 | Output On Delay | s | Write | |
| AV | 84 | 5815_1 | Reboot With Delay | s | Write | |
| AV | 85 | 5814_1 | Shutdown After Delay | s | Write | |
| AV | 86 | 5812_1 | Nominal Power Factor | Read | ||
| AV | 97 | 4510_1 | Outlet Group Identifier (Outlet Group 1) | Read | ||
| AV | 108 | 4510_2 | Outlet Group Identifier (Outlet Group 2) | Read | ||
| AV | 119 | 4120_1 | System Input Black Out Count | Read | ||
| AV | 120 | 4119_1 | System Input Brown Out Count | Read | ||
| AV | 121 | 4710_1 | Auto Restart Delay | s | Write | |
| AV | 122 | 4291_1 | Inlet Air Temperature | °C | Read | |
| AV | 10122 | 4291_1_deg_F | Inlet Air Temperature | °F | Read | |
| MV | 1 | 4553_1 | Server Class | Read | 1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR | |
| MV | 12 | 4871_1 | UPS Battery Status | Read | 1=Unknown, 2=Normal, 3=Low, 4=Depleted | |
| MV | 13 | 5799_1 | Battery Charge Status | Read | 1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off) | |
| MV | 14 | 6183_1 | Battery Cabinet Type | Read | 1=Internal, 2=External, 3=LRT | |
| MV | 15 | 6190_1 | Battery Charge Compensating | Read | 1=false, 2=true | |
| MV | 16 | 6192_1 | Battery Charger State | Read | 1=off, 2=on | |
| MV | 17 | 6181_1 | Battery Test Result | Read | 1=Unknown, 2=Passed, 3=Failed, 4=In Progress, 5=System Failure, 6=Inhibited | |
| MV | 18 | 5858_1 | Manual Battery Test | Write | 1=Start Test | |
| MV | 19 | 5803_1 | Automatic Battery Test | Read | 1=disabled, 2=enabled | |
| MVmin | 30 | 4872_1 | UPS Output Source | Read | 1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer | |
| MV | 31 | 6196_1 | Power Factor Correction | Read | 1=off, 2=on | |
| MV | 42 | 4365_1 | Outlet Group Power Control (Outlet Group 1) | Write | 1=Off, 2=On, 3=Cycle Power | |
| MV | 53 | 4365_2 | Outlet Group Power Control (Outlet Group 2) | Write | 1=off, 2=on, 3=Cycle Power | |
| MV | 64 | 6198_1 | ECO Mode Status | Read | 1=off, 2=on | |
| MV | 65 | 5454_1 | ECO Mode Operation State | Write | 1=disabled, 2=enabled | |
| MVmin | 76 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation | |
| MV | 77 | 5831_1 | Auto Restart | Write | 1=disabled, 2=enabled | |
| MV | 78 | 4746_1 | Inverter On/Off State | Read | 1=off, 2=on | |
| MV | 79 | 6197_1 | Shutdown Reason | Read | 1=None, 2=Over Temperature, 3=Overload, 4=DC Bus Overload, 5=Output Short, 6=Line Swap, 7=Low Battery, 8=Remote Command, 9=Input Under Voltage, 10=Power Factor Correction Fail, 11=External Signal Command | |
| MV | 80 | 6200_1 | Abort Command | Write | 1=Issue Command | |
| MV | 81 | 6003_1 | DC Converter Status | Read | 1=off, 2=on | |
| MV | 82 | 6199_1 | UPS Topology | Read | 1=unknown, 2=Offline, 3=Line Interactive, 4=Online | |
| MV | 83 | 6224_1 | Bypass/Inverter Input Config | Read | 1=Single/Combined Source, 2=Dual/Separate Sources | |
| MV | 84 | 6191_1 | Reset Power Statistics | Write | 1=Reset | |
| MV | 85 | 6188_1 | Audible Alarm Control | Write | 1=off, 2=on | |
| MV | 86 | 6257_1 | Silence Audible Alarm | Write | 1=Silence Alarm |
No points match these filters.
Object ID lookup: Vertiv Liebert GXT3 / GXT4 UPS point IDs by name
BV15568_1BV25569_1BV134135_1BV244741_1BV254162_1BV266180_1BV275874_1BV284323_1BV296182_1BV405806_1BV415179_1BV425178_1BV434215_1BV605588_1BV614823_1BV624825_1BV636254_1BV644295_1BV654233_1BV665976_1BV674311_1BV684229_1BV696453_1BV706454_1AV14096_1AV24098_1AV34097_1AV44113_1AV54114_1AV64105_1AV74106_1AV84107_1AV94108_1AV104109_1AV114102_1AV124104_1AV134103_1AV244128_1AV254125_1AV264129_1AV275570_1AV285571_1AV294131_1AV304259_1AV414150_1AV424153_1AV434148_1AV446189_1AV454898_1AV465802_1AV475800_1AV486195_1AV494151_1AV505988_1AV614385_1AV624201_1AV634204_1AV644386_1AV654205_1AV664207_1AV676184_1AV686185_1AV696213_1AV706214_1AV714208_1AV725859_1AV735860_1AV745861_1AV754223_1AV764224_1AV774209_1AV785868_1AV795869_1AV804260_1AV814264_1AV824261_1AV835816_1AV845815_1AV855814_1AV865812_1AV974510_1AV1084510_2AV1194120_1AV1204119_1AV1214710_1AV1224291_1AV101224291_1_deg_FMV14553_1MV124871_1MV135799_1MV146183_1MV156190_1MV166192_1MV176181_1MV185858_1MV195803_1MV304872_1MV316196_1MV424365_1MV534365_2MV646198_1MV655454_1MV764123_1MV775831_1MV784746_1MV796197_1MV806200_1MV816003_1MV826199_1MV836224_1MV846191_1MV856188_1MV866257_1
Integration notes
- Tables 5.166, 5.167, 5.168, pdf pages 2171-2177 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert GXT3 / GXT4 UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert GXT3 / GXT4 UPS
How many BACnet points does the Vertiv Liebert GXT3 / GXT4 UPS have?
This list has 113 BACnet objects: 63 analog values, 24 binary values, 26 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert GXT3 / GXT4 UPS BACnet points are writable?
14 of the 113 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert GXT3 / GXT4 UPS BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert GXT3 / GXT4 UPS?
Start with MV 76 4123_1 (Normal, warning or alarm state); MV 30 4872_1 (Load on inverter, bypass or battery); AV 41 4150_1 (Estimated battery runtime, min); AV 71 4208_1 (Output power, W); AV 1 4096_1 (Input voltage, V); AV 61 4385_1 (Output voltage, V); AV 63 4204_1 (Output current, A).
How do I check these points on the real Liebert GXT3 / GXT4 UPS?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.