- Home
- BACnet points lists
- Vertiv
- Liebert RXA / TFX power panel
Power distribution panel / transformer monitoring · BACnet points list
Vertiv Liebert RXA / TFX power panel BACnet points list
Updated 6 November 2026
The Liebert RXA / TFX power panel reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, output, panel and branch circuit electrical data, Binary Values carry events and Multi-state Values carry status, breaker states and resets. Panel and branch objects repeat per panel and branch, so the list is long.
This page lists 1414 BACnet objects for the Vertiv Liebert RXA / TFX power panel — 77 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert RXA / TFX power panel
- Equipment
- Power distribution panel / transformer monitoring
- Equipment type
- Other equipment
- BACnet objects
- 1414 (77 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Liebert RXA, Liebert TFX, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert RXA / TFX power panel
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 15 | 7582_1 | Acknowledge / reset events | Write |
| MV 12 | 4123_1 | Normal, warning or alarm state | Read |
| AV 25 | 7601_1 | Output voltage A-B | Read |
| AV 28 | 7604_1 | Output voltage A-N | Read |
| BV 1 | 7570_1 | Transformer high temperature | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert RXA / TFX power panel BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 1 | 7570_1 | Transformer High Temperature | Read | Active = alarm | |
| BV | 2 | 7571_1 | Transformer Temperature Sensor Failure | Read | Active = alarm | |
| BV | 3 | 7572_1 | Metering Board Communication Fail | Read | Active = alarm | |
| BV | 4 | 7573_1 | Accessory Board Communication Fail | Read | Active = alarm | |
| BV | 5 | 7574_1 | System Misconfiguration | Read | Active = alarm | |
| BV | 6 | 7575_1 | System Firmware Incompatibility | Read | Active = alarm | |
| BV | 7 | 7576_1 | Main Input Breaker 1 Tripped | Read | Active = alarm | |
| BV | 8 | 7577_1 | Main Input Breaker 1 Accessory Error | Read | Active = alarm | |
| BV | 9 | 7578_1 | Main Input Breaker 1 Open Fail | Read | Active = alarm | |
| BV | 10 | 7579_1 | Main Input Breaker 2 Tripped | Read | Active = alarm | |
| BV | 11 | 7580_1 | Main Input Breaker 2 Accessory Error | Read | Active = alarm | |
| BV | 12 | 7581_1 | Main Input Breaker 2 Open Fail | Read | Active = alarm | |
| BV | 23 | 7588_1 | Loss of Communication (System Diagnostic 1) | Read | Active = alarm | |
| BV | 24 | 7589_1 | No Initial Communication (System Diagnostic 1) | Read | Active = alarm | |
| BV | 25 | 7590_1 | Misconfiguration (System Diagnostic 1) | Read | Active = alarm | |
| BV | 26 | 7591_1 | Firmware Incompatibility (System Diagnostic 1) | Read | Active = alarm | |
| BV | 27 | 8119_1 | Communication Bus Error (System Diagnostic 1) | Read | Active = alarm | |
| BV | 38 | 7588_2 | Loss of Communication (System Diagnostic 2) | Read | Active = alarm | |
| BV | 39 | 7589_2 | No Initial Communication (System Diagnostic 2) | Read | Active = alarm | |
| BV | 40 | 7590_2 | Misconfiguration (System Diagnostic 2) | Read | Active = alarm | |
| BV | 41 | 7591_2 | Firmware Incompatibility (System Diagnostic 2) | Read | Active = alarm | |
| BV | 42 | 8119_2 | Communication Bus Error (System Diagnostic 2) | Read | Active = alarm | |
| BV | 968 | 7588_64 | Loss of Communication (System Diagnostic 64) | Read | Active = alarm | |
| BV | 969 | 7589_64 | No Initial Communication (System Diagnostic 64) | Read | Active = alarm | |
| BV | 970 | 7590_64 | Misconfiguration (System Diagnostic 64) | Read | Active = alarm | |
| BV | 971 | 7591_64 | Firmware Incompatibility (System Diagnostic 64) | Read | Active = alarm | |
| BV | 972 | 8119_64 | Communication Bus Error (System Diagnostic 64) | Read | Active = alarm | |
| BV | 983 | 7697_1 | Output Overvoltage | Read | Active = alarm | |
| BV | 984 | 7698_1 | Output Undervoltage | Read | Active = alarm | |
| BV | 985 | 7699_1 | Phase Overcurrent | Read | Active = alarm | |
| BV | 986 | 7700_1 | Neutral Overcurrent | Read | Active = alarm | |
| BV | 987 | 7701_1 | Ground Overcurrent | Read | Active = alarm | |
| BV | 988 | 7702_1 | Output Frequency Deviation | Read | Active = alarm | |
| BV | 989 | 7704_1 | Input 1 Overvoltage | Read | Active = alarm | |
| BV | 990 | 7705_1 | Input 1 Undervoltage | Read | Active = alarm | |
| BV | 991 | 7706_1 | Input 1 Phase Loss | Read | Active = alarm | |
| BV | 992 | 7707_1 | Input 1 Invalid Phase Rotation | Read | Active = alarm | |
| BV | 993 | 7708_1 | Input 1 Frequency Deviation | Read | Active = alarm | |
| BV | 994 | 7709_1 | Input 1 High Voltage THD | Read | Active = alarm | |
| BV | 995 | 7710_1 | Input 2 Overvoltage | Read | Active = alarm | |
| BV | 996 | 7711_1 | Input 2 Undervoltage | Read | Active = alarm | |
| BV | 997 | 7712_1 | Input 2 Phase Loss | Read | Active = alarm | |
| BV | 998 | 7713_1 | Input 2 Invalid Phase Rotation | Read | Active = alarm | |
| BV | 999 | 7714_1 | Input 2 Frequency Deviation | Read | Active = alarm | |
| BV | 1000 | 7715_1 | Input 2 High Voltage THD | Read | Active = alarm | |
| BV | 1011 | 7792_1 | Panelboard Phase Overcurrent (Branch PB 1) | Read | Active = alarm | |
| BV | 1012 | 7793_1 | Panelboard Neutral Overcurrent (Branch PB 1) | Read | Active = alarm | |
| BV | 1013 | 7794_1 | Panelboard Ground Overcurrent (Branch PB 1) | Read | Active = alarm | |
| BV | 1014 | 7795_1 | Panelboard Main Breaker Tripped (Branch PB 1) | Read | Active = alarm | |
| BV | 1015 | 7796_1 | Panelboard Main Breaker Accessory Error (Branch PB 1) | Read | Active = alarm | |
| BV | 1016 | 8253_1 | Panelboard Overvoltage (Branch PB 1) | Read | Active = alarm | |
| BV | 1017 | 8254_1 | Panelboard Undervoltage (Branch PB 1) | Read | Active = alarm | |
| BV | 1018 | 8255_1 | Panelboard Frequency Deviation (Branch PB 1) | Read | Active = alarm | |
| BV | 1019 | 8435_1 | Panelboard Main Breaker Open Fail (Branch PB 1) | Read | Active = alarm | |
| BV | 1026 | 7822_1_1 | Branch Phase Overcurrent (Branch PB 1 Branch 1) | Read | Active = alarm | |
| BV | 1027 | 7823_1_1 | Branch Phase Undercurrent (Branch PB 1 Branch 1) | Read | Active = alarm | |
| BV | 1028 | 8259_1_1 | Branch Neutral Overcurrent (Branch PB 1 Branch 1) | Read | Active = alarm | |
| BV | 1029 | 8436_1_1 | Load Loss Detected (Branch PB 1 Branch 1) | Read | Active = alarm | |
| BV | 1038 | 7822_1_2 | Branch Phase Overcurrent (Branch PB 1 Branch 2) | Read | Active = alarm | |
| BV | 1039 | 7823_1_2 | Branch Phase Undercurrent (Branch PB 1 Branch 2) | Read | Active = alarm | |
| BV | 1040 | 8259_1_2 | Branch Neutral Overcurrent (Branch PB 1 Branch 2) | Read | Active = alarm | |
| BV | 1041 | 8436_1_2 | Load Loss Detected (Branch PB 1 Branch 2) | Read | Active = alarm | |
| BV | 1518 | 7822_1_42 | Branch Phase Overcurrent (Branch PB 1 Branch 42) | Read | Active = alarm | |
| BV | 1519 | 7823_1_42 | Branch Phase Undercurrent (Branch PB 1 Branch 42) | Read | Active = alarm | |
| BV | 1520 | 8259_1_42 | Branch Neutral Overcurrent (Branch PB 1 Branch 42) | Read | Active = alarm | |
| BV | 1521 | 8436_1_42 | Load Loss Detected (Branch PB 1 Branch 42) | Read | Active = alarm | |
| BV | 1530 | 7792_2 | Panelboard Phase Overcurrent (Branch PB 2) | Read | Active = alarm | |
| BV | 1531 | 7793_2 | Panelboard Neutral Overcurrent (Branch PB 2) | Read | Active = alarm | |
| BV | 1532 | 7794_2 | Panelboard Ground Overcurrent (Branch PB 2) | Read | Active = alarm | |
| BV | 1533 | 7795_2 | Panelboard Main Breaker Tripped (Branch PB 2) | Read | Active = alarm | |
| BV | 1534 | 7796_2 | Panelboard Main Breaker Accessory Error (Branch PB 2) | Read | Active = alarm | |
| BV | 1535 | 8253_2 | Panelboard Overvoltage (Branch PB 2) | Read | Active = alarm | |
| BV | 1536 | 8254_2 | Panelboard Undervoltage (Branch PB 2) | Read | Active = alarm | |
| BV | 1537 | 8255_2 | Panelboard Frequency Deviation (Branch PB 2) | Read | Active = alarm | |
| BV | 1538 | 8435_2 | Panelboard Main Breaker Open Fail (Branch PB 2) | Read | Active = alarm | |
| BV | 1545 | 7822_2_1 | Branch Phase Overcurrent (Branch PB 2 Branch 1) | Read | Active = alarm | |
| BV | 1546 | 7823_2_1 | Branch Phase Undercurrent (Branch PB 2 Branch 1) | Read | Active = alarm | |
| BV | 1547 | 8259_2_1 | Branch Neutral Overcurrent (Branch PB 2 Branch 1) | Read | Active = alarm | |
| BV | 1548 | 8436_2_1 | Load Loss Detected (Branch PB 2 Branch 1) | Read | Active = alarm | |
| BV | 1557 | 7822_2_2 | Branch Phase Overcurrent (Branch PB 2 Branch 2) | Read | Active = alarm | |
| BV | 1558 | 7823_2_2 | Branch Phase Undercurrent (Branch PB 2 Branch 2) | Read | Active = alarm | |
| BV | 1559 | 8259_2_2 | Panelboard Frequency Deviation (Branch PB 2 Branch 2) | Read | Active = alarm | |
| BV | 1560 | 8436_2_2 | Load Loss Detected (Branch PB 2 Branch 2) | Read | Active = alarm | |
| BV | 2037 | 7822_2_42 | Branch Phase Overcurrent (Branch PB 2 Branch 42) | Read | Active = alarm | |
| BV | 2038 | 7823_2_42 | Branch Phase Undercurrent (Branch PB 2 Branch 42) | Read | Active = alarm | |
| BV | 2039 | 8259_2_42 | Branch Neutral Overcurrent (Branch PB 2 Branch 42) | Read | Active = alarm | |
| BV | 2040 | 8436_2_42 | Load Loss Detected (Branch PB 2 Branch 42) | Read | Active = alarm | |
| BV | 6720 | 7792_12 | Panelboard Phase Overcurrent (Branch PB 12) | Read | Active = alarm | |
| BV | 6721 | 7793_12 | Panelboard Neutral Overcurrent (Branch PB 12) | Read | Active = alarm | |
| BV | 6722 | 7794_12 | Panelboard Ground Overcurrent (Branch PB 12) | Read | Active = alarm | |
| BV | 6723 | 7795_12 | Panelboard Main Breaker Tripped (Branch PB 12) | Read | Active = alarm | |
| BV | 6724 | 7796_12 | Panelboard Main Breaker Accessory Error (Branch PB 12) | Read | Active = alarm | |
| BV | 6725 | 8253_12 | Panelboard Overvoltage (Branch PB 12) | Read | Active = alarm | |
| BV | 6726 | 8254_12 | Panelboard Undervoltage (Branch PB 12) | Read | Active = alarm | |
| BV | 6727 | 8255_12 | Panelboard Frequency Deviation (Branch PB 12) | Read | Active = alarm | |
| BV | 6728 | 8435_12 | Panelboard Main Breaker Open Fail (Branch PB 12) | Read | Active = alarm | |
| BV | 6735 | 7822_12_1 | Branch Phase Overcurrent (Branch PB 12 Branch 1) | Read | Active = alarm | |
| BV | 6736 | 7823_12_1 | Branch Phase Undercurrent (Branch PB 12 Branch 1) | Read | Active = alarm | |
| BV | 6737 | 8259_12_1 | Branch Neutral Overcurrent (Branch PB 12 Branch 1) | Read | Active = alarm | |
| BV | 6738 | 8436_12_1 | Load Loss Detected (Branch PB 12 Branch 1) | Read | Active = alarm | |
| BV | 6747 | 7822_12_2 | Branch Phase Overcurrent (Branch PB 12 Branch 2) | Read | Active = alarm | |
| BV | 6748 | 7823_12_2 | Branch Phase Undercurrent (Branch PB 12 Branch 2) | Read | Active = alarm | |
| BV | 6749 | 8259_12_2 | Branch Neutral Overcurrent (Branch PB 12 Branch 2) | Read | Active = alarm | |
| BV | 6750 | 8436_12_2 | Load Loss Detected (Branch PB 12 Branch 2) | Read | Active = alarm | |
| BV | 7227 | 7822_12_42 | Branch Phase Overcurrent (Branch PB 12 Branch 42) | Read | Active = alarm | |
| BV | 7228 | 7823_12_42 | Branch Phase Undercurrent (Branch PB 12 Branch 42) | Read | Active = alarm | |
| BV | 7229 | 8259_12_42 | Branch Neutral Overcurrent (Branch PB 12 Branch 42) | Read | Active = alarm | |
| BV | 7230 | 8436_12_42 | Load Loss Detected (Branch PB 12 Branch 42) | Read | Active = alarm | |
| BV | 7239 | 7896_1 | Panelboard Phase Overcurrent (Subfeed PB 1) | Read | Active = alarm | |
| BV | 7240 | 7897_1 | Panelboard Neutral Overcurrent (Subfeed PB 1) | Read | Active = alarm | |
| BV | 7241 | 7898_1 | Panelboard Ground Overcurrent (Subfeed PB 1) | Read | Active = alarm | |
| BV | 7242 | 7899_1 | Panelboard Main Breaker Tripped (Subfeed PB 1) | Read | Active = alarm | |
| BV | 7243 | 7900_1 | Panelboard Main Breaker Accessory Error (Subfeed PB 1) | Read | Active = alarm | |
| BV | 7244 | 8262_1 | Panelboard Overvoltage (Subfeed PB 1) | Read | Active = alarm | |
| BV | 7245 | 8263_1 | Panelboard Undervoltage (Subfeed PB 1) | Read | Active = alarm | |
| BV | 7246 | 8264_1 | Panelboard Frequency Deviation (Subfeed PB 1) | Read | Active = alarm | |
| BV | 7254 | 7953_1_1 | Subfeed Phase Overcurrent (Subfeed PB 1 Subfeed 1) | Read | Active = alarm | |
| BV | 7255 | 7954_1_1 | Subfeed Neutral Overcurrent (Subfeed PB 1 Subfeed 1) | Read | Active = alarm | |
| BV | 7256 | 7955_1_1 | Subfeed Ground Overcurrent (Subfeed PB 1 Subfeed 1) | Read | Active = alarm | |
| BV | 7257 | 7956_1_1 | Subfeed Breaker Tripped (Subfeed PB 1 Subfeed 1) | Read | Active = alarm | |
| BV | 7258 | 7957_1_1 | Subfeed Breaker Accessory Error (Subfeed PB 1 Subfeed 1) | Read | Active = alarm | |
| BV | 7269 | 7953_1_2 | Subfeed Phase Overcurrent (Subfeed PB 1 Subfeed 2) | Read | Active = alarm | |
| BV | 7270 | 7954_1_2 | Subfeed Neutral Overcurrent (Subfeed PB 1 Subfeed 2) | Read | Active = alarm | |
| BV | 7271 | 7955_1_2 | Subfeed Ground Overcurrent (Subfeed PB 1 Subfeed 2) | Read | Active = alarm | |
| BV | 7272 | 7956_1_2 | Subfeed Breaker Tripped (Subfeed PB 1 Subfeed 2) | Read | Active = alarm | |
| BV | 7273 | 7957_1_2 | Subfeed Breaker Accessory Error (Subfeed PB 1 Subfeed 2) | Read | Active = alarm | |
| BV | 7419 | 7953_1_12 | Subfeed Phase Overcurrent (Subfeed PB 1 Subfeed 12) | Read | Active = alarm | |
| BV | 7420 | 7954_1_12 | Subfeed Neutral Overcurrent (Subfeed PB 1 Subfeed 12) | Read | Active = alarm | |
| BV | 7421 | 7955_1_12 | Subfeed Ground Overcurrent (Subfeed PB 1 Subfeed 12) | Read | Active = alarm | |
| BV | 7422 | 7956_1_12 | Subfeed Breaker Tripped (Subfeed PB 1 Subfeed 12) | Read | Active = alarm | |
| BV | 7423 | 7957_1_12 | Subfeed Breaker Accessory Error (Subfeed PB 1 Subfeed 12) | Read | Active = alarm | |
| BV | 7434 | 7896_2 | Panelboard Phase Overcurrent (Subfeed PB 2) | Read | Active = alarm | |
| BV | 7435 | 7897_2 | Panelboard Neutral Overcurrent (Subfeed PB 2) | Read | Active = alarm | |
| BV | 7436 | 7898_2 | Panelboard Ground Overcurrent (Subfeed PB 2) | Read | Active = alarm | |
| BV | 7437 | 7899_2 | Panelboard Main Breaker Tripped (Subfeed PB 2) | Read | Active = alarm | |
| BV | 7438 | 7900_2 | Panelboard Main Breaker Accessory Error (Subfeed PB 2) | Read | Active = alarm | |
| BV | 7439 | 8262_2 | Panelboard Overvoltage (Subfeed PB 2) | Read | Active = alarm | |
| BV | 7440 | 8263_2 | Panelboard Undervoltage (Subfeed PB 2) | Read | Active = alarm | |
| BV | 7441 | 8264_2 | Panelboard Frequency Deviation (Subfeed PB 2) | Read | Active = alarm | |
| BV | 7449 | 7953_2_1 | Subfeed Phase Overcurrent (Subfeed PB 2 Subfeed 1) | Read | Active = alarm | |
| BV | 7450 | 7954_2_1 | Subfeed Neutral Overcurrent (Subfeed PB 2 Subfeed 1) | Read | Active = alarm | |
| BV | 7451 | 7955_2_1 | Subfeed Ground Overcurrent (Subfeed PB 2 Subfeed 1) | Read | Active = alarm | |
| BV | 7452 | 7956_2_1 | Subfeed Breaker Tripped (Subfeed PB 2 Subfeed 1) | Read | Active = alarm | |
| BV | 7453 | 7957_2_1 | Subfeed Breaker Accessory Error (Subfeed PB 2 Subfeed 1) | Read | Active = alarm | |
| BV | 7464 | 7953_2_2 | Subfeed Phase Overcurrent (Subfeed PB 2 Subfeed 2) | Read | Active = alarm | |
| BV | 7465 | 7954_2_2 | Subfeed Neutral Overcurrent (Subfeed PB 2 Subfeed 2) | Read | Active = alarm | |
| BV | 7466 | 7955_2_2 | Subfeed Ground Overcurrent (Subfeed PB 2 Subfeed 2) | Read | Active = alarm | |
| BV | 7467 | 7956_2_2 | Subfeed Breaker Tripped (Subfeed PB 2 Subfeed 2) | Read | Active = alarm | |
| BV | 7468 | 7957_2_2 | Subfeed Breaker Accessory Error (Subfeed PB 2 Subfeed 2) | Read | Active = alarm | |
| BV | 7614 | 7953_2_12 | Subfeed Phase Overcurrent (Subfeed PB 2 Subfeed 12) | Read | Active = alarm | |
| BV | 7615 | 7954_2_12 | Subfeed Neutral Overcurrent (Subfeed PB 2 Subfeed 12) | Read | Active = alarm | |
| BV | 7616 | 7955_2_12 | Subfeed Ground Overcurrent (Subfeed PB 2 Subfeed 12) | Read | Active = alarm | |
| BV | 7617 | 7956_2_12 | Subfeed Breaker Tripped (Subfeed PB 2 Subfeed 12) | Read | Active = alarm | |
| BV | 7618 | 7957_2_12 | Subfeed Breaker Accessory Error (Subfeed PB 2 Subfeed 12) | Read | Active = alarm | |
| BV | 7629 | 8029_1 | Subfeed Phase Overcurrent (Subfeed 1) | Read | Active = alarm | |
| BV | 7630 | 8030_1 | Subfeed Neutral Overcurrent (Subfeed 1) | Read | Active = alarm | |
| BV | 7631 | 8031_1 | Subfeed Ground Overcurrent (Subfeed 1) | Read | Active = alarm | |
| BV | 7632 | 8032_1 | Subfeed Breaker Tripped (Subfeed 1) | Read | Active = alarm | |
| BV | 7633 | 8033_1 | Subfeed Breaker Accessory Error (Subfeed 1) | Read | Active = alarm | |
| BV | 7634 | 8267_1 | Subfeed Overvoltage (Subfeed 1) | Read | Active = alarm | |
| BV | 7635 | 8268_1 | Subfeed Undervoltage (Subfeed 1) | Read | Active = alarm | |
| BV | 7636 | 8269_1 | Subfeed Frequency Deviation (Subfeed 1) | Read | Active = alarm | |
| BV | 7644 | 8029_2 | Subfeed Phase Overcurrent (Subfeed 2) | Read | Active = alarm | |
| BV | 7645 | 8030_2 | Subfeed Neutral Overcurrent (Subfeed 2) | Read | Active = alarm | |
| BV | 7646 | 8031_2 | Subfeed Ground Overcurrent (Subfeed 2) | Read | Active = alarm | |
| BV | 7647 | 8032_2 | Subfeed Breaker Tripped (Subfeed 2) | Read | Active = alarm | |
| BV | 7648 | 8033_2 | Subfeed Breaker Accessory Error (Subfeed 2) | Read | Active = alarm | |
| BV | 7649 | 8267_2 | Subfeed Overvoltage (Subfeed 2) | Read | Active = alarm | |
| BV | 7650 | 8268_2 | Subfeed Undervoltage (Subfeed 2) | Read | Active = alarm | |
| BV | 7651 | 8269_2 | Subfeed Frequency Deviation (Subfeed 2) | Read | Active = alarm | |
| BV | 8154 | 8029_36 | Subfeed Phase Overcurrent (Subfeed 36) | Read | Active = alarm | |
| BV | 8155 | 8030_36 | Subfeed Neutral Overcurrent (Subfeed 36) | Read | Active = alarm | |
| BV | 8156 | 8031_36 | Subfeed Ground Overcurrent (Subfeed 36) | Read | Active = alarm | |
| BV | 8157 | 8032_36 | Subfeed Breaker Tripped (Subfeed 36) | Read | Active = alarm | |
| BV | 8158 | 8033_36 | Subfeed Breaker Accessory Error (Subfeed 36) | Read | Active = alarm | |
| BV | 8159 | 8267_36 | Subfeed Overvoltage (Subfeed 36) | Read | Active = alarm | |
| BV | 8160 | 8268_36 | Subfeed Undervoltage (Subfeed 36) | Read | Active = alarm | |
| BV | 8161 | 8269_36 | Subfeed Frequency Deviation (Subfeed 36) | Read | Active = alarm | |
| BV | 8169 | 8045_1 | External Input Contact State (External Input Contact 1) | Read | Active = alarm | |
| BV | 8180 | 8045_2 | External Input Contact State (External Input Contact 2) | Read | Active = alarm | |
| BV | 8191 | 8047_1 | Internal Input Contact State (Internal Input Contact 1) | Read | Active = alarm | |
| BV | 8202 | 8047_2 | Internal Input Contact State (Internal Input Contact 2) | Read | Active = alarm | |
| BV | 8268 | 8047_8 | Internal Input Contact State (Internal Input Contact 8) | Read | Active = alarm | |
| AV | 1 | 4293_1 | System Date and Time | Secs since Epoch(UTC) | Write | |
| AV | 14 | 8123_1 | System Power Rating | kVA | Read | |
| AV | 15 | 7592_1 | System Current Rating | A | Read | |
| AV | 16 | 7593_1 | Input 1 Frequency | Hz | Read | |
| AV | 17 | 7594_1 | Input 2 Frequency | Hz | Read | |
| AV | 18 | 8124_1 | System Frequency | Hz | Read | |
| AV | 19 | 7595_1 | Input 1 Voltage (L-L) A-B | V | Read | |
| AV | 20 | 7596_1 | Input 1 Voltage (L-L) B-C | V | Read | |
| AV | 21 | 7597_1 | Input 1 Voltage (L-L) C-A | V | Read | |
| AV | 22 | 7598_1 | Input 2 Voltage (L-L) A-B | V | Read | |
| AV | 23 | 7599_1 | Input 2 Voltage (L-L) B-C | V | Read | |
| AV | 24 | 7600_1 | Input 2 Voltage (L-L) C-A | V | Read | |
| AVmin | 25 | 7601_1 | Output Voltage (L-L) A-B | V | Read | |
| AV | 26 | 7602_1 | Output Voltage (L-L) B-C | V | Read | |
| AV | 27 | 7603_1 | Output Voltage (L-L) C-A | V | Read | |
| AVmin | 28 | 7604_1 | Output Voltage (L-N) A-N | V | Read | |
| AV | 29 | 7605_1 | Output Voltage (L-N) B-N | V | Read | |
| AV | 30 | 7606_1 | Output Voltage (L-N) C-N | V | Read | |
| AV | 31 | 7607_1 | Current Ph A | A | Read | |
| AV | 32 | 7608_1 | Current Ph B | A | Read | |
| AV | 33 | 7609_1 | Current Ph C | A | Read | |
| AV | 34 | 7610_1 | Neutral Current | A | Read | |
| AV | 35 | 7611_1 | Ground Current | A | Read | |
| AV | 36 | 7612_1 | Current Load Ph A | % | Read | |
| AV | 37 | 7613_1 | Current Load Ph B | % | Read | |
| AV | 38 | 7614_1 | Current Load Ph C | % | Read | |
| AV | 39 | 7615_1 | Highest Phase Current Load | % | Read | |
| AV | 40 | 7616_1 | Real Power | kW | Read | |
| AV | 41 | 7617_1 | Apparent Power | kVA | Read | |
| AV | 42 | 7618_1 | Apparent Power Load | % | Read | |
| AV | 43 | 7619_1 | Power Factor Ph A | Read | ||
| AV | 44 | 7620_1 | Power Factor Ph B | Read | ||
| AV | 45 | 7621_1 | Power Factor Ph C | Read | ||
| AV | 46 | 7622_1 | Power Factor Total | Read | ||
| AV | 47 | 7623_1 | Energy | kWh | Read | |
| AV | 48 | 7624_1 | Peak Current Ph A | A | Read | |
| AV | 49 | 7625_1 | Peak Current Ph B | A | Read | |
| AV | 50 | 7626_1 | Peak Current Ph C | A | Read | |
| AV | 51 | 7627_1 | Peak Demand | kW | Read | |
| AV | 52 | 7628_1 | Current Crest Factor Ph A | Read | ||
| AV | 53 | 7629_1 | Current Crest Factor Ph B | Read | ||
| AV | 54 | 7630_1 | Current Crest Factor Ph C | Read | ||
| AV | 55 | 7631_1 | K-Factor Ph A | Read | ||
| AV | 56 | 7632_1 | K-Factor Ph B | Read | ||
| AV | 57 | 7633_1 | K-Factor Ph C | Read | ||
| AV | 58 | 7634_1 | Highest Phase K-Factor | Read | ||
| AV | 59 | 7635_1 | iTHD Ph A | % | Read | |
| AV | 60 | 7636_1 | iTHD Ph B | % | Read | |
| AV | 61 | 7637_1 | iTHD Ph C | % | Read | |
| AV | 62 | 7638_1 | Current 3rd Harmonic Ph A | % | Read | |
| AV | 63 | 7639_1 | Current 3rd Harmonic Ph B | % | Read | |
| AV | 64 | 7640_1 | Current 3rd Harmonic Ph C | % | Read | |
| AV | 65 | 7641_1 | Current 5th Harmonic Ph A | % | Read | |
| AV | 66 | 7642_1 | Current 5th Harmonic Ph B | % | Read | |
| AV | 67 | 7643_1 | Current 5th Harmonic Ph C | % | Read | |
| AV | 68 | 7644_1 | Current 7th Harmonic Ph A | % | Read | |
| AV | 69 | 7645_1 | Current 7th Harmonic Ph B | % | Read | |
| AV | 70 | 7646_1 | Current 7th Harmonic Ph C | % | Read | |
| AV | 71 | 7647_1 | Current 9th Harmonic Ph A | % | Read | |
| AV | 72 | 7648_1 | Current 9th Harmonic Ph B | % | Read | |
| AV | 73 | 7649_1 | Current 9th Harmonic Ph C | % | Read | |
| AV | 74 | 7650_1 | Input 1 vTHD Ph A | % | Read | |
| AV | 75 | 7651_1 | Input 1 vTHD Ph B | % | Read | |
| AV | 76 | 7652_1 | Input 1 vTHD Ph C | % | Read | |
| AV | 77 | 7653_1 | Input 1 Voltage 3rd Harmonic Ph A | % | Read | |
| AV | 78 | 7654_1 | Input 1 Voltage 3rd Harmonic Ph B | % | Read | |
| AV | 79 | 7655_1 | Input 1 Voltage 3rd Harmonic Ph C | % | Read | |
| AV | 80 | 7656_1 | Input 1 Voltage 5th Harmonic Ph A | % | Read | |
| AV | 81 | 7657_1 | Input 1 Voltage 5th Harmonic Ph B | % | Read | |
| AV | 82 | 7658_1 | Input 1 Voltage 5th Harmonic Ph C | % | Read | |
| AV | 83 | 7659_1 | Input 1 Voltage 7th Harmonic Ph A | % | Read | |
| AV | 84 | 7660_1 | Input 1 Voltage 7th Harmonic Ph B | % | Read | |
| AV | 85 | 7661_1 | Input 1 Voltage 7th Harmonic Ph C | % | Read | |
| AV | 86 | 7662_1 | Input 1 Voltage 9th Harmonic Ph A | % | Read | |
| AV | 87 | 7663_1 | Input 1 Voltage 9th Harmonic Ph B | % | Read | |
| AV | 88 | 7664_1 | Input 1 Voltage 9th Harmonic C | % | Read | |
| AV | 89 | 7665_1 | Input 2 vTHD Ph A | % | Read | |
| AV | 90 | 7666_1 | Input 2 vTHD Ph B | % | Read | |
| AV | 91 | 7667_1 | Input 2 vTHD Ph C | % | Read | |
| AV | 92 | 7668_1 | Input 2 Voltage 3rd Harmonic Ph A | % | Read | |
| AV | 93 | 7669_1 | Input 2 Voltage 3rd Harmonic Ph B | % | Read | |
| AV | 94 | 7670_1 | Input 2 Voltage 3rd Harmonic Ph C | % | Read | |
| AV | 95 | 7671_1 | Input 2 Voltage 5th Harmonic Ph A | % | Read | |
| AV | 96 | 7672_1 | Input 2 Voltage 5th Harmonic Ph B | % | Read | |
| AV | 97 | 7673_1 | Input 2 Voltage 5th Harmonic Ph C | % | Read | |
| AV | 98 | 7674_1 | Input 2 Voltage 7th Harmonic Ph A | % | Read | |
| AV | 99 | 7675_1 | Input 2 Voltage 7th Harmonic Ph B | % | Read | |
| AV | 100 | 7676_1 | Input 2 Voltage 7th Harmonic Ph C | % | Read | |
| AV | 101 | 7677_1 | Input 2 Voltage 9th Harmonic Ph A | % | Read | |
| AV | 102 | 7678_1 | Input 2 Voltage 9th Harmonic Ph B | % | Read | |
| AV | 103 | 7679_1 | Input 2 Voltage 9th Harmonic Ph C | % | Read | |
| AV | 104 | 7680_1 | Output vTHD Ph A | % | Read | |
| AV | 105 | 7681_1 | Output vTHD Ph B | % | Read | |
| AV | 106 | 7682_1 | Output vTHD Ph C | % | Read | |
| AV | 107 | 7683_1 | Output Voltage 3rd Harmonic A | % | Read | |
| AV | 108 | 7684_1 | Output Voltage 3rd Harmonic B | % | Read | |
| AV | 109 | 7685_1 | Output Voltage 3rd Harmonic C | % | Read | |
| AV | 110 | 7686_1 | Output Voltage 5th Harmonic A | % | Read | |
| AV | 111 | 7687_1 | Output Voltage 5th Harmonic B | % | Read | |
| AV | 112 | 7688_1 | Output Voltage 5th Harmonic C | % | Read | |
| AV | 113 | 7689_1 | Output Voltage 7th Harmonic A | % | Read | |
| AV | 114 | 7690_1 | Output Voltage 7th Harmonic B | % | Read | |
| AV | 115 | 7691_1 | Output Voltage 7th Harmonic C | % | Read | |
| AV | 116 | 7692_1 | Output Voltage 9th Harmonic A | % | Read | |
| AV | 117 | 7693_1 | Output Voltage 9th Harmonic B | % | Read | |
| AV | 118 | 7694_1 | Output Voltage 9th Harmonic C | % | Read | |
| AV | 119 | 7716_1 | Phase Overcurrent Alarm Threshold | % | Read | |
| AV | 120 | 7717_1 | Phase Overcurrent Warning Threshold | % | Read | |
| AV | 121 | 7718_1 | Neutral Overcurrent Alarm Threshold | % | Read | |
| AV | 122 | 7719_1 | Ground Overcurrent Alarm Threshold | A | Read | |
| AV | 123 | 8084_1 | Input 1 Phase Overvoltage Alarm Threshold | % | Read | |
| AV | 124 | 8085_1 | Input 1 Phase Undervoltage Alarm Threshold | % | Read | |
| AV | 125 | 8086_1 | Input 2 Phase Overvoltage Alarm Threshold | % | Read | |
| AV | 126 | 8087_1 | Input 2 Phase Undervoltage Alarm Threshold | % | Read | |
| AV | 127 | 8088_1 | Output Phase Overvoltage Alarm Threshold | % | Read | |
| AV | 128 | 8089_1 | Output Phase Undervoltage Alarm Threshold | % | Read | |
| AV | 129 | 7720_1 | Voltage Over THD Alarm Threshold | % | Read | |
| AV | 130 | 8276_1 | Neutral Overcurrent Warning Threshold | % | Read | |
| AV | 140 | 7727_1 | Panelboard Total Pole Positions (Branch PB 1) | Read | ||
| AV | 141 | 7728_1 | Panelboard Available Pole Positions (Branch PB 1) | Read | ||
| AV | 142 | 7729_1 | Panelboard Main Breaker Current Rating (Branch PB 1) | A | Read | |
| AV | 143 | 7730_1 | Panelboard Current Ph A (Branch PB 1) | A | Read | |
| AV | 144 | 7731_1 | Panelboard Current Ph B (Branch PB 1) | A | Read | |
| AV | 145 | 7732_1 | Panelboard Current Ph C (Branch PB 1) | A | Read | |
| AV | 146 | 7733_1 | Panelboard Neutral Current (Branch PB 1) | A | Read | |
| AV | 147 | 7734_1 | Panelboard Ground Current (Branch PB 1) | A | Read | |
| AV | 148 | 7735_1 | Panelboard Current Load Ph A (Branch PB 1) | % | Read | |
| AV | 149 | 7736_1 | Panelboard Current Load Ph B (Branch PB 1) | % | Read | |
| AV | 150 | 7737_1 | Panelboard Current Load Ph C (Branch PB 1) | % | Read | |
| AV | 151 | 7738_1 | Panelboard Highest Phase Current Load (Branch PB 1) | % | Read | |
| AV | 152 | 7739_1 | Panelboard Voltage (L-L) A-B (Branch PB 1) | V | Read | |
| AV | 153 | 7740_1 | Panelboard Voltage (L-L) B-C (Branch PB 1) | V | Read | |
| AV | 154 | 7741_1 | Panelboard Voltage (L-L) C-A (Branch PB 1) | V | Read | |
| AV | 155 | 7742_1 | Panelboard Voltage (L-N) A-N (Branch PB 1) | V | Read | |
| AV | 156 | 7743_1 | Panelboard Voltage (L-N) B-N (Branch PB 1) | V | Read | |
| AV | 157 | 7744_1 | Panelboard Voltage (L-N) C-N (Branch PB 1) | V | Read | |
| AV | 158 | 7745_1 | Panelboard Frequency (Branch PB 1) | Hz | Read | |
| AV | 159 | 7746_1 | Panelboard Real Power (Branch PB 1) | kW | Read | |
| AV | 160 | 7747_1 | Panelboard Apparent Power (Branch PB 1) | kVA | Read | |
| AV | 161 | 7748_1 | Panelboard Power Factor Ph A (Branch PB 1) | Read | ||
| AV | 162 | 7749_1 | Panelboard Power Factor Ph B (Branch PB 1) | Read | ||
| AV | 163 | 7750_1 | Panelboard Power Factor Ph C (Branch PB 1) | Read | ||
| AV | 164 | 7751_1 | Panelboard Power Factor Total (Branch PB 1) | Read | ||
| AV | 165 | 7752_1 | Panelboard Energy (Branch PB 1) | kWh | Read | |
| AV | 166 | 7753_1 | Panelboard Peak Current Ph A (Branch PB 1) | A | Read | |
| AV | 167 | 7754_1 | Panelboard Peak Current Ph B (Branch PB 1) | A | Read | |
| AV | 168 | 7755_1 | Panelboard Peak Current Ph C (Branch PB 1) | A | Read | |
| AV | 169 | 7756_1 | Panelboard Highest Phase Peak Current (Branch PB 1) | A | Read | |
| AV | 170 | 7757_1 | Panelboard Peak Demand (Branch PB 1) | kW | Read | |
| AV | 171 | 7758_1 | Panelboard Current Crest Factor Ph A (Branch PB 1) | Read | ||
| AV | 172 | 7759_1 | Panelboard Current Crest Factor Ph B (Branch PB 1) | Read | ||
| AV | 173 | 7760_1 | Panelboard Current Crest Factor Ph C (Branch PB 1) | Read | ||
| AV | 174 | 7761_1 | Panelboard iTHD Ph A (Branch PB 1) | % | Read | |
| AV | 175 | 7762_1 | Panelboard iTHD Ph B (Branch PB 1) | % | Read | |
| AV | 176 | 7763_1 | Panelboard iTHD Ph C (Branch PB 1) | % | Read | |
| AV | 177 | 7764_1 | Panelboard Current 3rd Harmonic Ph A (Branch PB 1) | % | Read | |
| AV | 178 | 7765_1 | Panelboard Current 3rd Harmonic Ph B (Branch PB 1) | % | Read | |
| AV | 179 | 7766_1 | Panelboard Current 3rd Harmonic Ph C (Branch PB 1) | % | Read | |
| AV | 180 | 7767_1 | Panelboard Current 5th Harmonic Ph A (Branch PB 1) | % | Read | |
| AV | 181 | 7768_1 | Panelboard Current 5th Harmonic Ph B (Branch PB 1) | % | Read | |
| AV | 182 | 7769_1 | Panelboard Current 5th Harmonic Ph C (Branch PB 1) | % | Read | |
| AV | 183 | 7770_1 | Panelboard Current 7th Harmonic Ph A (Branch PB 1) | % | Read | |
| AV | 184 | 7771_1 | Panelboard Current 7th Harmonic Ph B (Branch PB 1) | % | Read | |
| AV | 185 | 7772_1 | Panelboard Current 7th Harmonic Ph C (Branch PB 1) | % | Read | |
| AV | 186 | 7773_1 | Panelboard Current 9th Harmonic Ph A (Branch PB 1) | % | Read | |
| AV | 187 | 7774_1 | Panelboard Current 9th Harmonic Ph B (Branch PB 1) | % | Read | |
| AV | 188 | 7775_1 | Panelboard Current 9th Harmonic Ph C (Branch PB 1) | % | Read | |
| AV | 189 | 7776_1 | Panelboard vTHD Ph A (Branch PB 1) | % | Read | |
| AV | 190 | 7777_1 | Panelboard vTHD Ph B (Branch PB 1) | % | Read | |
| AV | 191 | 7778_1 | Panelboard vTHD Ph C (Branch PB 1) | % | Read | |
| AV | 192 | 7779_1 | Panelboard Voltage 3rd Harmonic Ph A (Branch PB 1) | % | Read | |
| AV | 193 | 7780_1 | Panelboard Voltage 3rd Harmonic Ph B (Branch PB 1) | % | Read | |
| AV | 194 | 7781_1 | Panelboard Voltage 3rd Harmonic Ph C (Branch PB 1) | % | Read | |
| AV | 195 | 7782_1 | Panelboard Voltage 5th Harmonic Ph A (Branch PB 1) | % | Read | |
| AV | 196 | 7783_1 | Panelboard Voltage 5th Harmonic Ph B (Branch PB 1) | % | Read | |
| AV | 197 | 7784_1 | Panelboard Voltage 5th Harmonic Ph C (Branch PB 1) | % | Read | |
| AV | 198 | 7785_1 | Panelboard Voltage 7th Harmonic Ph A (Branch PB 1) | % | Read | |
| AV | 199 | 7786_1 | Panelboard Voltage 7th Harmonic Ph B (Branch PB 1) | % | Read | |
| AV | 200 | 7787_1 | Panelboard Voltage 7th Harmonic Ph C (Branch PB 1) | % | Read | |
| AV | 201 | 7788_1 | Panelboard Voltage 9th Harmonic Ph A (Branch PB 1) | % | Read | |
| AV | 202 | 7789_1 | Panelboard Voltage 9th Harmonic Ph B (Branch PB 1) | % | Read | |
| AV | 203 | 7790_1 | Panelboard Voltage 9th Harmonic Ph C (Branch PB 1) | % | Read | |
| AV | 204 | 7798_1 | Panelboard Phase Overcurrent Warning Threshold (Branch PB 1) | % | Read | |
| AV | 205 | 7799_1 | Panelboard Phase Overcurrent Alarm Threshold (Branch PB 1) | % | Read | |
| AV | 206 | 7800_1 | Panelboard Neutral Overcurrent Alarm Threshold (Branch PB 1) | % | Read | |
| AV | 207 | 7801_1 | Panelboard Ground Overcurrent Alarm Threshold (Branch PB 1) | A | Read | |
| AV | 208 | 8277_1 | Panelboard Neutral Overcurrent Warning Threshold (Branch PB 1) | % | Read | |
| AV | 209 | 8256_1 | Panelboard Phase Overvoltage Alarm Threshold (Branch PB 1) | % | Read | |
| AV | 210 | 8257_1 | Panelboard Phase Undervoltage Alarm Threshold (Branch PB 1) | % | Read | |
| AV | 218 | 7808_1_1 | Branch Position (Branch PB 1 Branch 1) | Read | ||
| AV | 219 | 7809_1_1 | Branch Current Rating (Branch PB 1 Branch 1) | A | Read | |
| AV | 220 | 7810_1_1 | Branch Current L1 (Branch PB 1 Branch 1) | A | Read | |
| AV | 221 | 7811_1_1 | Branch Current L2 (Branch PB 1 Branch 1) | A | Read | |
| AV | 222 | 7812_1_1 | Branch Current L3 (Branch PB 1 Branch 1) | A | Read | |
| AV | 223 | 7813_1_1 | Branch Real Power (Branch PB 1 Branch 1) | kW | Read | |
| AV | 224 | 7814_1_1 | Branch Power Factor (Branch PB 1 Branch 1) | Read | ||
| AV | 225 | 7815_1_1 | Branch Energy (Branch PB 1 Branch 1) | kWh | Read | |
| AV | 226 | 7816_1_1 | Branch Highest Phase Current Load (Branch PB 1 Branch 1) | % | Read | |
| AV | 227 | 7817_1_1 | Branch Peak Current L1 (Branch PB 1 Branch 1) | A | Read | |
| AV | 228 | 7818_1_1 | Branch Peak Current L2 (Branch PB 1 Branch 1) | A | Read | |
| AV | 229 | 7819_1_1 | Branch Peak Current L3 (Branch PB 1 Branch 1) | A | Read | |
| AV | 230 | 7820_1_1 | Branch Highest Phase Peak Current (Branch PB 1 Branch 1) | A | Read | |
| AV | 231 | 7821_1_1 | Branch Peak Demand (Branch PB 1 Branch 1) | kW | Read | |
| AV | 232 | 7825_1_1 | Branch Overcurrent Warning Threshold (Branch PB 1 Branch 1) | % | Read | |
| AV | 233 | 7826_1_1 | Branch Overcurrent Alarm Threshold (Branch PB 1 Branch 1) | % | Read | |
| AV | 234 | 7827_1_1 | Branch Low Current Alarm Threshold (Branch PB 1 Branch 1) | % | Read | |
| AV | 235 | 8258_1_1 | Branch Current Neutral (Branch PB 1 Branch 1) | A | Read | |
| AV | 236 | 8260_1_1 | Branch Neutral Overcurrent Warning Threshold (Branch PB 1 Branch 1) | % | Read | |
| AV | 237 | 8261_1_1 | Branch Neutral Overcurrent Alarm Threshold (Branch PB 1 Branch 1) | % | Read | |
| AV | 238 | 8437_1_1 | Load Loss Min Load (Branch PB 1 Branch 1) | % | Read | |
| AV | 245 | 7808_1_2 | Branch Position (Branch PB 1 Branch 2) | Read | ||
| AV | 246 | 7809_1_2 | Branch Current Rating (Branch PB 1 Branch 2) | A | Read | |
| AV | 247 | 7810_1_2 | Branch Current L1 (Branch PB 1 Branch 2) | A | Read | |
| AV | 248 | 7811_1_2 | Branch Current L2 (Branch PB 1 Branch 2) | A | Read | |
| AV | 249 | 7812_1_2 | Branch Current L3 (Branch PB 1 Branch 2) | A | Read | |
| AV | 250 | 7813_1_2 | Branch Real Power (Branch PB 1 Branch 2) | kW | Read | |
| AV | 251 | 7814_1_2 | Branch Power Factor (Branch PB 1 Branch 2) | Read | ||
| AV | 252 | 7815_1_2 | Branch Energy (Branch PB 1 Branch 2) | kWh | Read | |
| AV | 253 | 7816_1_2 | Branch Highest Phase Current Load (Branch PB 1 Branch 2) | % | Read | |
| AV | 254 | 7817_1_2 | Branch Peak Current L1 (Branch PB 1 Branch 2) | A | Read | |
| AV | 255 | 7818_1_2 | Branch Peak Current L2 (Branch PB 1 Branch 2) | A | Read | |
| AV | 256 | 7819_1_2 | Branch Peak Current L3 (Branch PB 1 Branch 2) | A | Read | |
| AV | 257 | 7820_1_2 | Branch Highest Phase Peak Current (Branch PB 1 Branch 2) | A | Read | |
| AV | 258 | 7821_1_2 | Branch Peak Demand (Branch PB 1 Branch 2) | kW | Read | |
| AV | 259 | 7825_1_2 | Branch Overcurrent Warning Threshold (Branch PB 1 Branch 2) | % | Read | |
| AV | 260 | 7826_1_2 | Branch Overcurrent Alarm Threshold (Branch PB 1 Branch 2) | % | Read | |
| AV | 261 | 7827_1_2 | Branch Low Current Alarm Threshold (Branch PB 1 Branch 2) | % | Read | |
| AV | 262 | 8258_1_2 | Branch Current Neutral (Branch PB 1 Branch 2) | A | Read | |
| AV | 263 | 8260_1_2 | Branch Neutral Overcurrent Warning Threshold (Branch PB 1 Branch 2) | % | Read | |
| AV | 264 | 8261_1_2 | Branch Neutral Overcurrent Alarm Threshold (Branch PB 1 Branch 2) | % | Read | |
| AV | 265 | 8437_1_2 | Load Loss Min Load (Branch PB 1 Branch 2) | % | Read | |
| AV | 1325 | 7808_1_42 | Branch Position (Branch PB 1 Branch 42) | Read | ||
| AV | 1326 | 7809_1_42 | Branch Current Rating (Branch PB 1 Branch 42) | A | Read | |
| AV | 1327 | 7810_1_42 | Branch Current L1 (Branch PB 1 Branch 42) | A | Read | |
| AV | 1328 | 7811_1_42 | Branch Current L2 (Branch PB 1 Branch 42) | A | Read | |
| AV | 1329 | 7812_1_42 | Branch Current L3 (Branch PB 1 Branch 42) | A | Read | |
| AV | 1330 | 7813_1_42 | Branch Real Power (Branch PB 1 Branch 42) | kW | Read | |
| AV | 1331 | 7814_1_42 | Branch Power Factor (Branch PB 1 Branch 42) | Read | ||
| AV | 1332 | 7815_1_42 | Branch Energy (Branch PB 1 Branch 42) | kWh | Read | |
| AV | 1333 | 7816_1_42 | Branch Highest Phase Current Load (Branch PB 1 Branch 42) | % | Read | |
| AV | 1334 | 7817_1_42 | Branch Peak Current L1 (Branch PB 1 Branch 42) | A | Read | |
| AV | 1335 | 7818_1_42 | Branch Peak Current L2 (Branch PB 1 Branch 42) | A | Read | |
| AV | 1336 | 7819_1_42 | Branch Peak Current L3 (Branch PB 1 Branch 42) | A | Read | |
| AV | 1337 | 7820_1_42 | Branch Highest Phase Peak Current (Branch PB 1 Branch 42) | A | Read | |
| AV | 1338 | 7821_1_42 | Branch Peak Demand (Branch PB 1 Branch 42) | kW | Read | |
| AV | 1339 | 7825_1_42 | Branch Overcurrent Warning Threshold (Branch PB 1 Branch 42) | % | Read | |
| AV | 1340 | 7826_1_42 | Branch Overcurrent Alarm Threshold (Branch PB 1 Branch 42) | % | Read | |
| AV | 1341 | 7827_1_42 | Branch Low Current Alarm Threshold (Branch PB 1 Branch 42) | % | Read | |
| AV | 1342 | 8258_1_42 | Branch Current Neutral (Branch PB 1 Branch 42) | A | Read | |
| AV | 1343 | 8260_1_42 | Branch Neutral Overcurrent Warning Threshold (Branch PB 1 Branch 42) | % | Read | |
| AV | 1344 | 8261_1_42 | Branch Neutral Overcurrent Alarm Threshold (Branch PB 1 Branch 42) | % | Read | |
| AV | 1345 | 8437_1_42 | Load Loss Min Load (Branch PB 1 Branch 42) | % | Read | |
| AV | 1352 | 7727_2 | Panelboard Total Pole Positions (Branch PB 2) | Read | ||
| AV | 1353 | 7728_2 | Panelboard Available Pole Positions (Branch PB 2) | Read | ||
| AV | 1354 | 7729_2 | Panelboard Main Breaker Current Rating (Branch PB 2) | A | Read | |
| AV | 1355 | 7730_2 | Panelboard Current Ph A (Branch PB 2) | A | Read | |
| AV | 1356 | 7731_2 | Panelboard Current Ph B (Branch PB 2) | A | Read | |
| AV | 1357 | 7732_2 | Panelboard Current Ph C (Branch PB 2) | A | Read | |
| AV | 1358 | 7733_2 | Panelboard Neutral Current (Branch PB 2) | A | Read | |
| AV | 1359 | 7734_2 | Panelboard Ground Current (Branch PB 2) | A | Read | |
| AV | 1360 | 7735_2 | Panelboard Current Load Ph A (Branch PB 2) | % | Read | |
| AV | 1361 | 7736_2 | Panelboard Current Load Ph B (Branch PB 2) | % | Read | |
| AV | 1362 | 7737_2 | Panelboard Current Load Ph C (Branch PB 2) | % | Read | |
| AV | 1363 | 7738_2 | Panelboard Highest Phase Current Load (Branch PB 2) | % | Read | |
| AV | 1364 | 7739_2 | Panelboard Voltage (L-L) A-B (Branch PB 2) | V | Read | |
| AV | 1365 | 7740_2 | Panelboard Voltage (L-L) B-C (Branch PB 2) | V | Read | |
| AV | 1366 | 7741_2 | Panelboard Voltage (L-L) C-A (Branch PB 2) | V | Read | |
| AV | 1367 | 7742_2 | Panelboard Voltage (L-N) A-N (Branch PB 2) | V | Read | |
| AV | 1368 | 7743_2 | Panelboard Voltage (L-N) B-N (Branch PB 2) | V | Read | |
| AV | 1369 | 7744_2 | Panelboard Voltage (L-N) C-N (Branch PB 2) | V | Read | |
| AV | 1370 | 7745_2 | Panelboard Frequency (Branch PB 2) | Hz | Read | |
| AV | 1371 | 7746_2 | Panelboard Real Power (Branch PB 2) | kW | Read | |
| AV | 1372 | 7747_2 | Panelboard Apparent Power (Branch PB 2) | kVA | Read | |
| AV | 1373 | 7748_2 | Panelboard Power Factor Ph A (Branch PB 2) | Read | ||
| AV | 1374 | 7749_2 | Panelboard Power Factor Ph B (Branch PB 2) | Read | ||
| AV | 1375 | 7750_2 | Panelboard Power Factor Ph C (Branch PB 2) | Read | ||
| AV | 1376 | 7751_2 | Panelboard Power Factor Total (Branch PB 2) | Read | ||
| AV | 1377 | 7752_2 | Panelboard Energy (Branch PB 2) | kWh | Read | |
| AV | 1378 | 7753_2 | Panelboard Peak Current Ph A (Branch PB 2) | A | Read | |
| AV | 1379 | 7754_2 | Panelboard Peak Current Ph B (Branch PB 2) | A | Read | |
| AV | 1380 | 7755_2 | Panelboard Peak Current Ph C (Branch PB 2) | A | Read | |
| AV | 1381 | 7756_2 | Panelboard Highest Phase Peak Current (Branch PB 2) | A | Read | |
| AV | 1382 | 7757_2 | Panelboard Peak Demand (Branch PB 2) | kW | Read | |
| AV | 1383 | 7758_2 | Panelboard Current Crest Factor Ph A (Branch PB 2) | Read | ||
| AV | 1384 | 7759_2 | Panelboard Current Crest Factor Ph B (Branch PB 2) | Read | ||
| AV | 1385 | 7760_2 | Panelboard Current Crest Factor Ph C (Branch PB 2) | Read | ||
| AV | 1386 | 7761_2 | Panelboard iTHD Ph A (Branch PB 2) | % | Read | |
| AV | 1387 | 7762_2 | Panelboard iTHD Ph B (Branch PB 2) | % | Read | |
| AV | 1388 | 7763_2 | Panelboard iTHD Ph C (Branch PB 2) | % | Read | |
| AV | 1389 | 7764_2 | Panelboard Current 3rd Harmonic Ph A (Branch PB 2) | % | Read | |
| AV | 1390 | 7765_2 | Panelboard Current 3rd Harmonic Ph B (Branch PB 2) | % | Read | |
| AV | 1391 | 7766_2 | Panelboard Current 3rd Harmonic Ph C (Branch PB 2) | % | Read | |
| AV | 1392 | 7767_2 | Panelboard Current 5th Harmonic Ph A (Branch PB 2) | % | Read | |
| AV | 1393 | 7768_2 | Panelboard Current 5th Harmonic Ph B (Branch PB 2) | % | Read | |
| AV | 1394 | 7769_2 | Panelboard Current 5th Harmonic Ph C (Branch PB 2) | % | Read | |
| AV | 1395 | 7770_2 | Panelboard Current 7th Harmonic Ph A (Branch PB 2) | % | Read | |
| AV | 1396 | 7771_2 | Panelboard Current 7th Harmonic Ph B (Branch PB 2) | % | Read | |
| AV | 1397 | 7772_2 | Panelboard Current 7th Harmonic Ph C (Branch PB 2) | % | Read | |
| AV | 1398 | 7773_2 | Panelboard Current 9th Harmonic Ph A (Branch PB 2) | % | Read | |
| AV | 1399 | 7774_2 | Panelboard Current 9th Harmonic Ph B (Branch PB 2) | % | Read | |
| AV | 1400 | 7775_2 | Panelboard Current 9th Harmonic Ph C (Branch PB 2) | % | Read | |
| AV | 1401 | 7776_2 | Panelboard vTHD Ph A (Branch PB 2) | % | Read | |
| AV | 1402 | 7777_2 | Panelboard vTHD Ph B (Branch PB 2) | % | Read | |
| AV | 1403 | 7778_2 | Panelboard vTHD Ph C (Branch PB 2) | % | Read | |
| AV | 1404 | 7779_2 | Panelboard Voltage 3rd Harmonic Ph A (Branch PB 2) | % | Read | |
| AV | 1405 | 7780_2 | Panelboard Voltage 3rd Harmonic Ph B (Branch PB 2) | % | Read | |
| AV | 1406 | 7781_2 | Panelboard Voltage 3rd Harmonic Ph C (Branch PB 2) | % | Read | |
| AV | 1407 | 7782_2 | Panelboard Voltage 5th Harmonic Ph A (Branch PB 2) | % | Read | |
| AV | 1408 | 7783_2 | Panelboard Voltage 5th Harmonic Ph B (Branch PB 2) | % | Read | |
| AV | 1409 | 7784_2 | Panelboard Voltage 5th Harmonic Ph C (Branch PB 2) | % | Read | |
| AV | 1410 | 7785_2 | Panelboard Voltage 7th Harmonic Ph A (Branch PB 2) | % | Read | |
| AV | 1411 | 7786_2 | Panelboard Voltage 7th Harmonic Ph B (Branch PB 2) | % | Read | |
| AV | 1412 | 7787_2 | Panelboard Voltage 7th Harmonic Ph C (Branch PB 2) | % | Read | |
| AV | 1413 | 7788_2 | Panelboard Voltage 9th Harmonic Ph A (Branch PB 2) | % | Read | |
| AV | 1414 | 7789_2 | Panelboard Voltage 9th Harmonic Ph B (Branch PB 2) | % | Read | |
| AV | 1415 | 7790_2 | Panelboard Voltage 9th Harmonic Ph C (Branch PB 2) | % | Read | |
| AV | 1416 | 7798_2 | Panelboard Phase Overcurrent Warning Threshold (Branch PB 2) | % | Read | |
| AV | 1417 | 7799_2 | Panelboard Phase Overcurrent Alarm Threshold (Branch PB 2) | % | Read | |
| AV | 1418 | 7800_2 | Panelboard Neutral Overcurrent Alarm Threshold (Branch PB 2) | % | Read | |
| AV | 1419 | 7801_2 | Panelboard Ground Overcurrent Alarm Threshold (Branch PB 2) | A | Read | |
| AV | 1420 | 8277_2 | Panelboard Neutral Overcurrent Warning Threshold (Branch PB 2) | % | Read | |
| AV | 1421 | 8256_2 | Panelboard Phase Overvoltage Alarm Threshold (Branch PB 2) | % | Read | |
| AV | 1422 | 8257_2 | Panelboard Phase Undervoltage Alarm Threshold (Branch PB 2) | % | Read | |
| AV | 1430 | 7808_2_1 | Branch Position (Branch PB 2 Branch 1) | Read | ||
| AV | 1431 | 7809_2_1 | Branch Current Rating (Branch PB 2 Branch 1) | A | Read | |
| AV | 1432 | 7810_2_1 | Branch Current L1 (Branch PB 2 Branch 1) | A | Read | |
| AV | 1433 | 7811_2_1 | Branch Current L2 (Branch PB 2 Branch 1) | A | Read | |
| AV | 1434 | 7812_2_1 | Branch Current L3 (Branch PB 2 Branch 1) | A | Read | |
| AV | 1435 | 7813_2_1 | Branch Real Power (Branch PB 2 Branch 1) | kW | Read | |
| AV | 1436 | 7814_2_1 | Branch Power Factor (Branch PB 2 Branch 1) | Read | ||
| AV | 1437 | 7815_2_1 | Branch Energy (Branch PB 2 Branch 1) | kWh | Read | |
| AV | 1438 | 7816_2_1 | Branch Highest Phase Current Load (Branch PB 2 Branch 1) | % | Read | |
| AV | 1439 | 7817_2_1 | Branch Peak Current L1 (Branch PB 2 Branch 1) | A | Read | |
| AV | 1440 | 7818_2_1 | Branch Peak Current L2 (Branch PB 2 Branch 1) | A | Read | |
| AV | 1441 | 7819_2_1 | Branch Peak Current L3 (Branch PB 2 Branch 1) | A | Read | |
| AV | 1442 | 7820_2_1 | Branch Highest Phase Peak Current (Branch PB 2 Branch 1) | A | Read | |
| AV | 1443 | 7821_2_1 | Branch Peak Demand (Branch PB 2 Branch 1) | kW | Read | |
| AV | 1444 | 7825_2_1 | Branch Overcurrent Warning Threshold (Branch PB 2 Branch 1) | % | Read | |
| AV | 1445 | 7826_2_1 | Branch Overcurrent Alarm Threshold (Branch PB 2 Branch 1) | % | Read | |
| AV | 1446 | 7827_2_1 | Branch Low Current Alarm Threshold (Branch PB 2 Branch 1) | % | Read | |
| AV | 1447 | 8258_2_1 | Branch Current Neutral (Branch PB 2 Branch 1) | A | Read | |
| AV | 1448 | 8260_2_1 | Branch Neutral Overcurrent Warning Threshold (Branch PB 2 Branch 1) | % | Read | |
| AV | 1449 | 8261_2_1 | Branch Neutral Overcurrent Alarm Threshold (Branch PB 2 Branch 1) | % | Read | |
| AV | 1450 | 8437_2_1 | Load Loss Min Load (Branch PB 2 Branch 1) | % | Read | |
| AV | 1457 | 7808_2_2 | Branch Position (Branch PB 2 Branch 2) | Read | ||
| AV | 1458 | 7809_2_2 | Branch Current Rating (Branch PB 2 Branch 2) | A | Read | |
| AV | 1459 | 7810_2_2 | Branch Current L1 (Branch PB 2 Branch 2) | A | Read | |
| AV | 1460 | 7811_2_2 | Branch Current L2 (Branch PB 2 Branch 2) | A | Read | |
| AV | 1461 | 7812_2_2 | Branch Current L3 (Branch PB 2 Branch 2) | A | Read | |
| AV | 1462 | 7813_2_2 | Branch Real Power (Branch PB 2 Branch 2) | kW | Read | |
| AV | 1463 | 7814_2_2 | Branch Power Factor (Branch PB 2 Branch 2) | Read | ||
| AV | 1464 | 7815_2_2 | Branch Energy (Branch PB 2 Branch 2) | kWh | Read | |
| AV | 1465 | 7816_2_2 | Branch Highest Phase Current Load (Branch PB 2 Branch 2) | % | Read | |
| AV | 1466 | 7817_2_2 | Branch Peak Current L1 (Branch PB 2 Branch 2) | A | Read | |
| AV | 1467 | 7818_2_2 | Branch Peak Current L2 (Branch PB 2 Branch 2) | A | Read | |
| AV | 1468 | 7819_2_2 | Branch Peak Current L3 (Branch PB 2 Branch 2) | A | Read | |
| AV | 1469 | 7820_2_2 | Branch Highest Phase Peak Current (Branch PB 2 Branch 2) | A | Read | |
| AV | 1470 | 7821_2_2 | Branch Peak Demand (Branch PB 2 Branch 2) | kW | Read | |
| AV | 1471 | 7825_2_2 | Branch Overcurrent Warning Threshold (Branch PB 2 Branch 2) | % | Read | |
| AV | 1472 | 7826_2_2 | Branch Overcurrent Alarm Threshold (Branch PB 2 Branch 2) | % | Read | |
| AV | 1473 | 7827_2_2 | Branch Low Current Alarm Threshold (Branch PB 2 Branch 2) | % | Read | |
| AV | 1474 | 8258_2_2 | Branch Current Neutral (Branch PB 2 Branch 2) | A | Read | |
| AV | 1475 | 8260_2_2 | Branch Neutral Overcurrent Warning Threshold (Branch PB 2 Branch 2) | % | Read | |
| AV | 1476 | 8261_2_2 | Branch Neutral Overcurrent Alarm Threshold (Branch PB 2 Branch 2) | % | Read | |
| AV | 1477 | 8437_2_2 | Load Loss Min Load (Branch PB 2 Branch 2) | % | Read | |
| AV | 2537 | 7808_2_42 | Branch Position (Branch PB 2 Branch 42) | Read | ||
| AV | 2538 | 7809_2_42 | Branch Current Rating (Branch PB 2 Branch 42) | A | Read | |
| AV | 2539 | 7810_2_42 | Branch Current L1 (Branch PB 2 Branch 42) | A | Read | |
| AV | 2540 | 7811_2_42 | Branch Current L2 (Branch PB 2 Branch 42) | A | Read | |
| AV | 2541 | 7812_2_42 | Branch Current L3 (Branch PB 2 Branch 42) | A | Read | |
| AV | 2542 | 7813_2_42 | Branch Real Power (Branch PB 2 Branch 42) | kW | Read | |
| AV | 2543 | 7814_2_42 | Branch Power Factor (Branch PB 2 Branch 42) | Read | ||
| AV | 2544 | 7815_2_42 | Branch Energy (Branch PB 2 Branch 42) | kWh | Read | |
| AV | 2545 | 7816_2_42 | Branch Highest Phase Current Load (Branch PB 2 Branch 42) | % | Read | |
| AV | 2546 | 7817_2_42 | Branch Peak Current L1 (Branch PB 2 Branch 42) | A | Read | |
| AV | 2547 | 7818_2_42 | Branch Peak Current L2 (Branch PB 2 Branch 42) | A | Read | |
| AV | 2548 | 7819_2_42 | Branch Peak Current L3 (Branch PB 2 Branch 42) | A | Read | |
| AV | 2549 | 7820_2_42 | Branch Highest Phase Peak Current (Branch PB 2 Branch 42) | A | Read | |
| AV | 2550 | 7821_2_42 | Branch Peak Demand (Branch PB 2 Branch 42) | kW | Read | |
| AV | 2551 | 7825_2_42 | Branch Overcurrent Warning Threshold (Branch PB 2 Branch 42) | % | Read | |
| AV | 2552 | 7826_2_42 | Branch Overcurrent Alarm Threshold (Branch PB 2 Branch 42) | % | Read | |
| AV | 2553 | 7827_2_42 | Branch Low Current Alarm Threshold (Branch PB 2 Branch 42) | % | Read | |
| AV | 2554 | 8258_2_42 | Branch Current Neutral (Branch PB 2 Branch 42) | A | Read | |
| AV | 2555 | 8260_2_42 | Branch Neutral Overcurrent Warning Threshold (Branch PB 2 Branch 42) | % | Read | |
| AV | 2556 | 8261_2_42 | Branch Neutral Overcurrent Alarm Threshold (Branch PB 2 Branch 42) | % | Read | |
| AV | 2557 | 8437_2_42 | Load Loss Min Load (Branch PB 2 Branch 42) | % | Read | |
| AV | 13472 | 7727_12 | Panelboard Total Pole Positions (Branch PB 12) | Read | ||
| AV | 13473 | 7728_12 | Panelboard Available Pole Positions (Branch PB 12) | Read | ||
| AV | 13474 | 7729_12 | Panelboard Main Breaker Current Rating (Branch PB 12) | A | Read | |
| AV | 13475 | 7730_12 | Panelboard Current Ph A (Branch PB 12) | A | Read | |
| AV | 13476 | 7731_12 | Panelboard Current Ph B (Branch PB 12) | A | Read | |
| AV | 13477 | 7732_12 | Panelboard Current Ph C (Branch PB 12) | A | Read | |
| AV | 13478 | 7733_12 | Panelboard Neutral Current (Branch PB 12) | A | Read | |
| AV | 13479 | 7734_12 | Panelboard Ground Current (Branch PB 12) | A | Read | |
| AV | 13480 | 7735_12 | Panelboard Current Load Ph A (Branch PB 12) | % | Read | |
| AV | 13481 | 7736_12 | Panelboard Current Load Ph B (Branch PB 12) | % | Read | |
| AV | 13482 | 7737_12 | Panelboard Current Load Ph C (Branch PB 12) | % | Read | |
| AV | 13483 | 7738_12 | Panelboard Highest Phase Current Load (Branch PB 12) | % | Read | |
| AV | 13484 | 7739_12 | Panelboard Voltage (L-L) A-B (Branch PB 12) | V | Read | |
| AV | 13485 | 7740_12 | Panelboard Voltage (L-L) B-C (Branch PB 12) | V | Read | |
| AV | 13486 | 7741_12 | Panelboard Voltage (L-L) C-A (Branch PB 12) | V | Read | |
| AV | 13487 | 7742_12 | Panelboard Voltage (L-N) A-N (Branch PB 12) | V | Read | |
| AV | 13488 | 7743_12 | Panelboard Voltage (L-N) B-N (Branch PB 12) | V | Read | |
| AV | 13489 | 7744_12 | Panelboard Voltage (L-N) C-N (Branch PB 12) | V | Read | |
| AV | 13490 | 7745_12 | Panelboard Frequency (Branch PB 12) | Hz | Read | |
| AV | 13491 | 7746_12 | Panelboard Real Power (Branch PB 12) | kW | Read | |
| AV | 13492 | 7747_12 | Panelboard Apparent Power (Branch PB 12) | kVA | Read | |
| AV | 13493 | 7748_12 | Panelboard Power Factor Ph A (Branch PB 12) | Read | ||
| AV | 13494 | 7749_12 | Panelboard Power Factor Ph B (Branch PB 12) | Read | ||
| AV | 13495 | 7750_12 | Panelboard Power Factor Ph C (Branch PB 12) | Read | ||
| AV | 13496 | 7751_12 | Panelboard Power Factor Total (Branch PB 12) | Read | ||
| AV | 13497 | 7752_12 | Panelboard Energy (Branch PB 12) | kWh | Read | |
| AV | 13498 | 7753_12 | Panelboard Peak Current Ph A (Branch PB 12) | A | Read | |
| AV | 13499 | 7754_12 | Panelboard Peak Current Ph B (Branch PB 12) | A | Read | |
| AV | 13500 | 7755_12 | Panelboard Peak Current Ph C (Branch PB 12) | A | Read | |
| AV | 13501 | 7756_12 | Panelboard Highest Phase Peak Current (Branch PB 12) | A | Read | |
| AV | 13502 | 7757_12 | Panelboard Peak Demand (Branch PB 12) | kW | Read | |
| AV | 13503 | 7758_12 | Panelboard Current Crest Factor Ph A (Branch PB 12) | Read | ||
| AV | 13504 | 7759_12 | Panelboard Current Crest Factor Ph B (Branch PB 12) | Read | ||
| AV | 13505 | 7760_12 | Panelboard Current Crest Factor Ph C (Branch PB 12) | Read | ||
| AV | 13506 | 7761_12 | Panelboard iTHD Ph A (Branch PB 12) | % | Read | |
| AV | 13507 | 7762_12 | Panelboard iTHD Ph B (Branch PB 12) | % | Read | |
| AV | 13508 | 7763_12 | Panelboard iTHD Ph C (Branch PB 12) | % | Read | |
| AV | 13509 | 7764_12 | Panelboard Current 3rd Harmonic Ph A (Branch PB 12) | % | Read | |
| AV | 13510 | 7765_12 | Panelboard Current 3rd Harmonic Ph B (Branch PB 12) | % | Read | |
| AV | 13511 | 7766_12 | Panelboard Current 3rd Harmonic Ph C (Branch PB 12) | % | Read | |
| AV | 13512 | 7767_12 | Panelboard Current 5th Harmonic Ph A (Branch PB 12) | % | Read | |
| AV | 13513 | 7768_12 | Panelboard Current 5th Harmonic Ph B (Branch PB 12) | % | Read | |
| AV | 13514 | 7769_12 | Panelboard Current 5th Harmonic Ph C (Branch PB 12) | % | Read | |
| AV | 13515 | 7770_12 | Panelboard Current 7th Harmonic Ph A (Branch PB 12) | % | Read | |
| AV | 13516 | 7771_12 | Panelboard Current 7th Harmonic Ph B (Branch PB 12) | % | Read | |
| AV | 13517 | 7772_12 | Panelboard Current 7th Harmonic Ph C (Branch PB 12) | % | Read | |
| AV | 13518 | 7773_12 | Panelboard Current 9th Harmonic Ph A (Branch PB 12) | % | Read | |
| AV | 13519 | 7774_12 | Panelboard Current 9th Harmonic Ph B (Branch PB 12) | % | Read | |
| AV | 13520 | 7775_12 | Panelboard Current 9th Harmonic Ph C (Branch PB 12) | % | Read | |
| AV | 13521 | 7776_12 | Panelboard vTHD Ph A (Branch PB 12) | % | Read | |
| AV | 13522 | 7777_12 | Panelboard vTHD Ph B (Branch PB 12) | % | Read | |
| AV | 13523 | 7778_12 | Panelboard vTHD Ph C (Branch PB 12) | % | Read | |
| AV | 13524 | 7779_12 | Panelboard Voltage 3rd Harmonic Ph A (Branch PB 12) | % | Read | |
| AV | 13525 | 7780_12 | Panelboard Voltage 3rd Harmonic Ph B (Branch PB 12) | % | Read | |
| AV | 13526 | 7781_12 | Panelboard Voltage 3rd Harmonic Ph C (Branch PB 12) | % | Read | |
| AV | 13527 | 7782_12 | Panelboard Voltage 5th Harmonic Ph A (Branch PB 12) | % | Read | |
| AV | 13528 | 7783_12 | Panelboard Voltage 5th Harmonic Ph B (Branch PB 12) | % | Read | |
| AV | 13529 | 7784_12 | Panelboard Voltage 5th Harmonic Ph C (Branch PB 12) | % | Read | |
| AV | 13530 | 7785_12 | Panelboard Voltage 7th Harmonic Ph A (Branch PB 12) | % | Read | |
| AV | 13531 | 7786_12 | Panelboard Voltage 7th Harmonic Ph B (Branch PB 12) | % | Read | |
| AV | 13532 | 7787_12 | Panelboard Voltage 7th Harmonic Ph C (Branch PB 12) | % | Read | |
| AV | 13533 | 7788_12 | Panelboard Voltage 9th Harmonic Ph A (Branch PB 12) | % | Read | |
| AV | 13534 | 7789_12 | Panelboard Voltage 9th Harmonic Ph B (Branch PB 12) | % | Read | |
| AV | 13535 | 7790_12 | Panelboard Voltage 9th Harmonic Ph C (Branch PB 12) | % | Read | |
| AV | 13536 | 7798_12 | Panelboard Phase Overcurrent Warning Threshold (Branch PB 12) | % | Read | |
| AV | 13537 | 7799_12 | Panelboard Phase Overcurrent Alarm Threshold (Branch PB 12) | % | Read | |
| AV | 13538 | 7800_12 | Panelboard Neutral Overcurrent Alarm Threshold (Branch PB 12) | % | Read | |
| AV | 13539 | 7801_12 | Panelboard Ground Overcurrent Alarm Threshold (Branch PB 12) | A | Read | |
| AV | 13540 | 8277_12 | Panelboard Neutral Overcurrent Warning Threshold (Branch PB 12) | % | Read | |
| AV | 13541 | 8256_12 | Panelboard Phase Overvoltage Alarm Threshold (Branch PB 12) | % | Read | |
| AV | 13542 | 8257_12 | Panelboard Phase Undervoltage Alarm Threshold (Branch PB 12) | % | Read | |
| AV | 13550 | 7808_12_1 | Branch Position (Branch PB 12 Branch 1) | Read | ||
| AV | 13551 | 7809_12_1 | Branch Current Rating (Branch PB 12 Branch 1) | A | Read | |
| AV | 13552 | 7810_12_1 | Branch Current L1 (Branch PB 12 Branch 1) | A | Read | |
| AV | 13553 | 7811_12_1 | Branch Current L2 (Branch PB 12 Branch 1) | A | Read | |
| AV | 13554 | 7812_12_1 | Branch Current L3 (Branch PB 12 Branch 1) | A | Read | |
| AV | 13555 | 7813_12_1 | Branch Real Power (Branch PB 12 Branch 1) | kW | Read | |
| AV | 13556 | 7814_12_1 | Branch Power Factor (Branch PB 12 Branch 1) | Read | ||
| AV | 13557 | 7815_12_1 | Branch Energy (Branch PB 12 Branch 1) | kWh | Read | |
| AV | 13558 | 7816_12_1 | Branch Highest Phase Current Load (Branch PB 12 Branch 1) | % | Read | |
| AV | 13559 | 7817_12_1 | Branch Peak Current L1 (Branch PB 12 Branch 1) | A | Read | |
| AV | 13560 | 7818_12_1 | Branch Peak Current L2 (Branch PB 12 Branch 1) | A | Read | |
| AV | 13561 | 7819_12_1 | Branch Peak Current L3 (Branch PB 12 Branch 1) | A | Read | |
| AV | 13562 | 7820_12_1 | Branch Highest Phase Peak Current (Branch PB 12 Branch 1) | A | Read | |
| AV | 13563 | 7821_12_1 | Branch Peak Demand (Branch PB 12 Branch 1) | kW | Read | |
| AV | 13564 | 7825_12_1 | Branch Overcurrent Warning Threshold (Branch PB 12 Branch 1) | % | Read | |
| AV | 13565 | 7826_12_1 | Branch Overcurrent Alarm Threshold (Branch PB 12 Branch 1) | % | Read | |
| AV | 13566 | 7827_12_1 | Branch Low Current Alarm Threshold (Branch PB 12 Branch 1) | % | Read | |
| AV | 13567 | 8258_12_1 | Branch Current Neutral (Branch PB 12 Branch 1) | A | Read | |
| AV | 13568 | 8260_12_1 | Branch Neutral Overcurrent Warning Threshold (Branch PB 12 Branch 1) | % | Read | |
| AV | 13569 | 8261_12_1 | Branch Neutral Overcurrent Alarm Threshold (Branch PB 12 Branch 1) | % | Read | |
| AV | 13570 | 8437_12_1 | Load Loss Min Load (Branch PB 12 Branch 1) | % | Read | |
| AV | 13577 | 7808_12_2 | Branch Position (Branch PB 12 Branch 2) | Read | ||
| AV | 13578 | 7809_12_2 | Branch Current Rating (Branch PB 12 Branch 2) | A | Read | |
| AV | 13579 | 7810_12_2 | Branch Current L1 (Branch PB 12 Branch 2) | A | Read | |
| AV | 13580 | 7811_12_2 | Branch Current L2 (Branch PB 12 Branch 2) | A | Read | |
| AV | 13581 | 7812_12_2 | Branch Current L3 (Branch PB 12 Branch 2) | A | Read | |
| AV | 13582 | 7813_12_2 | Branch Real Power (Branch PB 12 Branch 2) | kW | Read | |
| AV | 13583 | 7814_12_2 | Branch Power Factor (Branch PB 12 Branch 2) | Read | ||
| AV | 13584 | 7815_12_2 | Branch Energy (Branch PB 12 Branch 2) | kWh | Read | |
| AV | 13585 | 7816_12_2 | Branch Highest Phase Current Load (Branch PB 12 Branch 2) | % | Read | |
| AV | 13586 | 7817_12_2 | Branch Peak Current L1 (Branch PB 12 Branch 2) | A | Read | |
| AV | 13587 | 7818_12_2 | Branch Peak Current L2 (Branch PB 12 Branch 2) | A | Read | |
| AV | 13588 | 7819_12_2 | Branch Peak Current L3 (Branch PB 12 Branch 2) | A | Read | |
| AV | 13589 | 7820_12_2 | Branch Highest Phase Peak Current (Branch PB 12 Branch 2) | A | Read | |
| AV | 13590 | 7821_12_2 | Branch Peak Demand (Branch PB 12 Branch 2) | kW | Read | |
| AV | 13591 | 7825_12_2 | Branch Overcurrent Warning Threshold (Branch PB 12 Branch 2) | % | Read | |
| AV | 13592 | 7826_12_2 | Branch Overcurrent Alarm Threshold (Branch PB 12 Branch 2) | % | Read | |
| AV | 13593 | 7827_12_2 | Branch Low Current Alarm Threshold (Branch PB 12 Branch 2) | % | Read | |
| AV | 13594 | 8258_12_2 | Branch Current Neutral (Branch PB 12 Branch 2) | A | Read | |
| AV | 13595 | 8260_12_2 | Branch Neutral Overcurrent Warning Threshold (Branch PB 12 Branch 2) | % | Read | |
| AV | 13596 | 8261_12_2 | Branch Neutral Overcurrent Alarm Threshold (Branch PB 12 Branch 2) | % | Read | |
| AV | 13597 | 8437_12_2 | Load Loss Min Load (Branch PB 12 Branch 2) | % | Read | |
| AV | 14657 | 7808_12_42 | Branch Position (Branch PB 12 Branch 42) | Read | ||
| AV | 14658 | 7809_12_42 | Branch Current Rating (Branch PB 12 Branch 42) | A | Read | |
| AV | 14659 | 7810_12_42 | Branch Current L1 (Branch PB 12 Branch 42) | A | Read | |
| AV | 14660 | 7811_12_42 | Branch Current L2 (Branch PB 12 Branch 42) | A | Read | |
| AV | 14661 | 7812_12_42 | Branch Current L3 (Branch PB 12 Branch 42) | A | Read | |
| AV | 14662 | 7813_12_42 | Branch Real Power (Branch PB 12 Branch 42) | kW | Read | |
| AV | 14663 | 7814_12_42 | Branch Power Factor (Branch PB 12 Branch 42) | Read | ||
| AV | 14664 | 7815_12_42 | Branch Energy (Branch PB 12 Branch 42) | kWh | Read | |
| AV | 14665 | 7816_12_42 | Branch Highest Phase Current Load (Branch PB 12 Branch 42) | % | Read | |
| AV | 14666 | 7817_12_42 | Branch Peak Current L1 (Branch PB 12 Branch 42) | A | Read | |
| AV | 14667 | 7818_12_42 | Branch Peak Current L2 (Branch PB 12 Branch 42) | A | Read | |
| AV | 14668 | 7819_12_42 | Branch Peak Current L3 (Branch PB 12 Branch 42) | A | Read | |
| AV | 14669 | 7820_12_42 | Branch Highest Phase Peak Current (Branch PB 12 Branch 42) | A | Read | |
| AV | 14670 | 7821_12_42 | Branch Peak Demand (Branch PB 12 Branch 42) | kW | Read | |
| AV | 14671 | 7825_12_42 | Branch Overcurrent Warning Threshold (Branch PB 12 Branch 42) | % | Read | |
| AV | 14672 | 7826_12_42 | Branch Overcurrent Alarm Threshold (Branch PB 12 Branch 42) | % | Read | |
| AV | 14673 | 7827_12_42 | Branch Low Current Alarm Threshold (Branch PB 12 Branch 42) | % | Read | |
| AV | 14674 | 8258_12_42 | Branch Current Neutral (Branch PB 12 Branch 42) | A | Read | |
| AV | 14675 | 8260_12_42 | Branch Neutral Overcurrent Warning Threshold (Branch PB 12 Branch 42) | % | Read | |
| AV | 14676 | 8261_12_42 | Branch Neutral Overcurrent Alarm Threshold (Branch PB 12 Branch 42) | % | Read | |
| AV | 14677 | 8437_12_42 | Load Loss Min Load (Branch PB 12 Branch 42) | % | Read | |
| AV | 14684 | 7833_1 | Panelboard Subfeed Count (Subfeed PB 1) | Read | ||
| AV | 14685 | 7834_1 | Panelboard Current Ph A (Subfeed PB 1) | A | Read | |
| AV | 14686 | 7835_1 | Panelboard Current Ph B (Subfeed PB 1) | A | Read | |
| AV | 14687 | 7836_1 | Panelboard Current Ph C (Subfeed PB 1) | A | Read | |
| AV | 14688 | 7837_1 | Panelboard Neutral Current (Subfeed PB 1) | A | Read | |
| AV | 14689 | 7838_1 | Panelboard Ground Current (Subfeed PB 1) | A | Read | |
| AV | 14690 | 7839_1 | Panelboard Current Load Ph A (Subfeed PB 1) | % | Read | |
| AV | 14691 | 7840_1 | Panelboard Current Load Ph B (Subfeed PB 1) | % | Read | |
| AV | 14692 | 7841_1 | Panelboard Current Load Ph C (Subfeed PB 1) | % | Read | |
| AV | 14693 | 7842_1 | Panelboard Highest Phase Current Load (Subfeed PB 1) | % | Read | |
| AV | 14694 | 7843_1 | Panelboard Voltage (L-L) A-B (Subfeed PB 1) | V | Read | |
| AV | 14695 | 7844_1 | Panelboard Voltage (L-L) B-C (Subfeed PB 1) | V | Read | |
| AV | 14696 | 7845_1 | Panelboard Voltage (L-L) C-A (Subfeed PB 1) | V | Read | |
| AV | 14697 | 7846_1 | Panelboard Voltage (L-N) A-N (Subfeed PB 1) | V | Read | |
| AV | 14698 | 7847_1 | Panelboard Voltage (L-N) B-N (Subfeed PB 1) | V | Read | |
| AV | 14699 | 7848_1 | Panelboard Voltage (L-N) C-N (Subfeed PB 1) | V | Read | |
| AV | 14700 | 7849_1 | Panelboard Frequency (Subfeed PB 1) | Hz | Read | |
| AV | 14701 | 7850_1 | Panelboard Real Power (Subfeed PB 1) | kW | Read | |
| AV | 14702 | 7851_1 | Panelboard Apparent Power (Subfeed PB 1) | kVA | Read | |
| AV | 14703 | 7852_1 | Panelboard Power Factor Ph A (Subfeed PB 1) | Read | ||
| AV | 14704 | 7853_1 | Panelboard Power Factor Ph B (Subfeed PB 1) | Read | ||
| AV | 14705 | 7854_1 | Panelboard Power Factor Ph C (Subfeed PB 1) | Read | ||
| AV | 14706 | 7855_1 | Panelboard Power Factor Total (Subfeed PB 1) | Read | ||
| AV | 14707 | 7856_1 | Panelboard Energy (Subfeed PB 1) | kWh | Read | |
| AV | 14708 | 7857_1 | Panelboard Peak Current Ph A (Subfeed PB 1) | A | Read | |
| AV | 14709 | 7858_1 | Panelboard Peak Current Ph B (Subfeed PB 1) | A | Read | |
| AV | 14710 | 7859_1 | Panelboard Peak Current Ph C (Subfeed PB 1) | A | Read | |
| AV | 14711 | 7860_1 | Panelboard Highest Phase Peak Current (Subfeed PB 1) | A | Read | |
| AV | 14712 | 7861_1 | Panelboard Peak Demand (Subfeed PB 1) | kW | Read | |
| AV | 14713 | 7862_1 | Panelboard Current Crest Factor Ph A (Subfeed PB 1) | Read | ||
| AV | 14714 | 7863_1 | Panelboard Current Crest Factor Ph B (Subfeed PB 1) | Read | ||
| AV | 14715 | 7864_1 | Panelboard Current Crest Factor Ph C (Subfeed PB 1) | Read | ||
| AV | 14716 | 7865_1 | Panelboard iTHD Ph A (Subfeed PB 1) | % | Read | |
| AV | 14717 | 7866_1 | Panelboard iTHD Ph B (Subfeed PB 1) | % | Read | |
| AV | 14718 | 7867_1 | Panelboard iTHD Ph C (Subfeed PB 1) | % | Read | |
| AV | 14719 | 7868_1 | Panelboard Current 3rd Harmonic Ph A (Subfeed PB 1) | % | Read | |
| AV | 14720 | 7869_1 | Panelboard Current 3rd Harmonic Ph B (Subfeed PB 1) | % | Read | |
| AV | 14721 | 7870_1 | Panelboard Current 3rd Harmonic Ph C (Subfeed PB 1) | % | Read | |
| AV | 14722 | 7871_1 | Panelboard Current 5th Harmonic Ph A (Subfeed PB 1) | % | Read | |
| AV | 14723 | 7872_1 | Panelboard Current 5th Harmonic Ph B (Subfeed PB 1) | % | Read | |
| AV | 14724 | 7873_1 | Panelboard Current 5th Harmonic Ph C (Subfeed PB 1) | % | Read | |
| AV | 14725 | 7874_1 | Panelboard Current 7th Harmonic Ph A (Subfeed PB 1) | % | Read | |
| AV | 14726 | 7875_1 | Panelboard Current 7th Harmonic Ph B (Subfeed PB 1) | % | Read | |
| AV | 14727 | 7876_1 | Panelboard Current 7th Harmonic Ph C (Subfeed PB 1) | % | Read | |
| AV | 14728 | 7877_1 | Panelboard Current 9th Harmonic Ph A (Subfeed PB 1) | % | Read | |
| AV | 14729 | 7878_1 | Panelboard Current 9th Harmonic Ph B (Subfeed PB 1) | % | Read | |
| AV | 14730 | 7879_1 | Panelboard Current 9th Harmonic Ph C (Subfeed PB 1) | % | Read | |
| AV | 14731 | 7880_1 | Panelboard vTHD Ph A (Subfeed PB 1) | % | Read | |
| AV | 14732 | 7881_1 | Panelboard vTHD Ph B (Subfeed PB 1) | % | Read | |
| AV | 14733 | 7882_1 | Panelboard vTHD Ph C (Subfeed PB 1) | % | Read | |
| AV | 14734 | 7883_1 | Panelboard Voltage 3rd Harmonic Ph A (Subfeed PB 1) | % | Read | |
| AV | 14735 | 7884_1 | Panelboard Voltage 3rd Harmonic Ph B (Subfeed PB 1) | % | Read | |
| AV | 14736 | 7885_1 | Panelboard Voltage 3rd Harmonic Ph C (Subfeed PB 1) | % | Read | |
| AV | 14737 | 7886_1 | Panelboard Voltage 5th Harmonic Ph A (Subfeed PB 1) | % | Read | |
| AV | 14738 | 7887_1 | Panelboard Voltage 5th Harmonic Ph B (Subfeed PB 1) | % | Read | |
| AV | 14739 | 7888_1 | Panelboard Voltage 5th Harmonic Ph C (Subfeed PB 1) | % | Read | |
| AV | 14740 | 7889_1 | Panelboard Voltage 7th Harmonic Ph A (Subfeed PB 1) | % | Read | |
| AV | 14741 | 7890_1 | Panelboard Voltage 7th Harmonic Ph B (Subfeed PB 1) | % | Read | |
| AV | 14742 | 7891_1 | Panelboard Voltage 7th Harmonic Ph C (Subfeed PB 1) | % | Read | |
| AV | 14743 | 7892_1 | Panelboard Voltage 9th Harmonic Ph A (Subfeed PB 1) | % | Read | |
| AV | 14744 | 7893_1 | Panelboard Voltage 9th Harmonic Ph B (Subfeed PB 1) | % | Read | |
| AV | 14745 | 7894_1 | Panelboard Voltage 9th Harmonic Ph C (Subfeed PB 1) | % | Read | |
| AV | 14746 | 7902_1 | Panelboard Phase Overcurrent Warning Threshold (Subfeed PB 1) | % | Read | |
| AV | 14747 | 7903_1 | Panelboard Phase Overcurrent Alarm Threshold (Subfeed PB 1) | % | Read | |
| AV | 14748 | 7904_1 | Panelboard Neutral Overcurrent Alarm Threshold (Subfeed PB 1) | % | Read | |
| AV | 14749 | 7905_1 | Panelboard Ground Overcurrent Alarm Threshold (Subfeed PB 1) | A | Read | |
| AV | 14750 | 8278_1 | Panelboard Neutral Overcurrent Warning Threshold (Subfeed PB 1) | % | Read | |
| AV | 14751 | 8265_1 | Panelboard Phase Overvoltage Alarm Threshold (Subfeed PB 1) | % | Read | |
| AV | 14752 | 8266_1 | Panelboard Phase Undervoltage Alarm Threshold (Subfeed PB 1) | % | Read | |
| AV | 14760 | 7912_1_1 | Subfeed Current Rating (Subfeed PB 1 Subfeed 1) | A | Read | |
| AV | 14761 | 7913_1_1 | Subfeed Current Ph A (Subfeed PB 1 Subfeed 1) | A | Read | |
| AV | 14762 | 7914_1_1 | Subfeed Current Ph B (Subfeed PB 1 Subfeed 1) | A | Read | |
| AV | 14763 | 7915_1_1 | Subfeed Current Ph C (Subfeed PB 1 Subfeed 1) | A | Read | |
| AV | 14764 | 7916_1_1 | Subfeed Neutral Current (Subfeed PB 1 Subfeed 1) | A | Read | |
| AV | 14765 | 7917_1_1 | Subfeed Ground Current (Subfeed PB 1 Subfeed 1) | A | Read | |
| AV | 14766 | 7918_1_1 | Subfeed Current Load Ph A (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14767 | 7919_1_1 | Subfeed Current Load Ph B (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14768 | 7920_1_1 | Subfeed Current Load Ph C (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14769 | 7921_1_1 | Subfeed Highest Phase Current Load (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14770 | 7922_1_1 | Subfeed Real Power (Subfeed PB 1 Subfeed 1) | kW | Read | |
| AV | 14771 | 7923_1_1 | Subfeed Apparent Power (Subfeed PB 1 Subfeed 1) | kVA | Read | |
| AV | 14772 | 7924_1_1 | Subfeed Power Factor Ph A (Subfeed PB 1 Subfeed 1) | Read | ||
| AV | 14773 | 7925_1_1 | Subfeed Power Factor Ph B (Subfeed PB 1 Subfeed 1) | Read | ||
| AV | 14774 | 7926_1_1 | Subfeed Power Factor Ph C (Subfeed PB 1 Subfeed 1) | Read | ||
| AV | 14775 | 7927_1_1 | Subfeed Power Factor Total (Subfeed PB 1 Subfeed 1) | Read | ||
| AV | 14776 | 7928_1_1 | Subfeed Energy (Subfeed PB 1 Subfeed 1) | kWh | Read | |
| AV | 14777 | 7929_1_1 | Subfeed Peak Current Ph A (Subfeed PB 1 Subfeed 1) | A | Read | |
| AV | 14778 | 7930_1_1 | Subfeed Peak Current Ph B (Subfeed PB 1 Subfeed 1) | A | Read | |
| AV | 14779 | 7931_1_1 | Subfeed Peak Current Ph C (Subfeed PB 1 Subfeed 1) | A | Read | |
| AV | 14780 | 7932_1_1 | Subfeed Highest Phase Peak Current (Subfeed PB 1 Subfeed 1) | A | Read | |
| AV | 14781 | 7933_1_1 | Subfeed Peak Demand (Subfeed PB 1 Subfeed 1) | kW | Read | |
| AV | 14782 | 7934_1_1 | Subfeed Current Crest Factor Ph A (Subfeed PB 1 Subfeed 1) | Read | ||
| AV | 14783 | 7935_1_1 | Subfeed Current Crest Factor Ph B (Subfeed PB 1 Subfeed 1) | Read | ||
| AV | 14784 | 7936_1_1 | Subfeed Current Crest Factor Ph C (Subfeed PB 1 Subfeed 1) | Read | ||
| AV | 14785 | 7937_1_1 | Subfeed iTHD Ph A (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14786 | 7938_1_1 | Subfeed iTHD Ph B (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14787 | 7939_1_1 | Subfeed iTHD Ph C (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14788 | 7940_1_1 | Subfeed Current 3rd Harmonic Ph A (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14789 | 7941_1_1 | Subfeed Current 3rd Harmonic Ph B (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14790 | 7942_1_1 | Subfeed Current 3rd Harmonic Ph C (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14791 | 7943_1_1 | Subfeed Current 5th Harmonic Ph A (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14792 | 7944_1_1 | Subfeed Current 5th Harmonic Ph B (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14793 | 7945_1_1 | Subfeed Current 5th Harmonic Ph C (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14794 | 7946_1_1 | Subfeed Current 7th Harmonic Ph A (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14795 | 7947_1_1 | Subfeed Current 7th Harmonic Ph B (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14796 | 7948_1_1 | Subfeed Current 7th Harmonic Ph C (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14797 | 7949_1_1 | Subfeed Current 9th Harmonic Ph A (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14798 | 7950_1_1 | Subfeed Current 9th Harmonic Ph B (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14799 | 7951_1_1 | Subfeed Current 9th Harmonic Ph C (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14800 | 7959_1_1 | Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14801 | 7960_1_1 | Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14802 | 7961_1_1 | Subfeed Neutral Overcurrent Threshold (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14803 | 8279_1_1 | Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 1) | % | Read | |
| AV | 14813 | 7912_1_2 | Subfeed Current Rating (Subfeed PB 1 Subfeed 2) | A | Read | |
| AV | 14814 | 7913_1_2 | Subfeed Current Ph A (Subfeed PB 1 Subfeed 2) | A | Read | |
| AV | 14815 | 7914_1_2 | Subfeed Current Ph B (Subfeed PB 1 Subfeed 2) | A | Read | |
| AV | 14816 | 7915_1_2 | Subfeed Current Ph C (Subfeed PB 1 Subfeed 2) | A | Read | |
| AV | 14817 | 7916_1_2 | Subfeed Neutral Current (Subfeed PB 1 Subfeed 2) | A | Read | |
| AV | 14818 | 7917_1_2 | Subfeed Ground Current (Subfeed PB 1 Subfeed 2) | A | Read | |
| AV | 14819 | 7918_1_2 | Subfeed Current Load Ph A (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14820 | 7919_1_2 | Subfeed Current Load Ph B (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14821 | 7920_1_2 | Subfeed Current Load Ph C (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14822 | 7921_1_2 | Subfeed Highest Phase Current Load (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14823 | 7922_1_2 | Subfeed Real Power (Subfeed PB 1 Subfeed 2) | kW | Read | |
| AV | 14824 | 7923_1_2 | Subfeed Apparent Power (Subfeed PB 1 Subfeed 2) | kVA | Read | |
| AV | 14825 | 7924_1_2 | Subfeed Power Factor Ph A (Subfeed PB 1 Subfeed 2) | Read | ||
| AV | 14826 | 7925_1_2 | Subfeed Power Factor Ph B (Subfeed PB 1 Subfeed 2) | Read | ||
| AV | 14827 | 7926_1_2 | Subfeed Power Factor Ph C (Subfeed PB 1 Subfeed 2) | Read | ||
| AV | 14828 | 7927_1_2 | Subfeed Power Factor Total (Subfeed PB 1 Subfeed 2) | Read | ||
| AV | 14829 | 7928_1_2 | Subfeed Energy (Subfeed PB 1 Subfeed 2) | kWh | Read | |
| AV | 14830 | 7929_1_2 | Subfeed Peak Current Ph A (Subfeed PB 1 Subfeed 2) | A | Read | |
| AV | 14831 | 7930_1_2 | Subfeed Peak Current Ph B (Subfeed PB 1 Subfeed 2) | A | Read | |
| AV | 14832 | 7931_1_2 | Subfeed Peak Current Ph C (Subfeed PB 1 Subfeed 2) | A | Read | |
| AV | 14833 | 7932_1_2 | Subfeed Highest Phase Peak Current (Subfeed PB 1 Subfeed 2) | A | Read | |
| AV | 14834 | 7933_1_2 | Subfeed Peak Demand (Subfeed PB 1 Subfeed 2) | kW | Read | |
| AV | 14835 | 7934_1_2 | Subfeed Current Crest Factor Ph A (Subfeed PB 1 Subfeed 2) | Read | ||
| AV | 14836 | 7935_1_2 | Subfeed Current Crest Factor Ph B (Subfeed PB 1 Subfeed 2) | Read | ||
| AV | 14837 | 7936_1_2 | Subfeed Current Crest Factor Ph C (Subfeed PB 1 Subfeed 2) | Read | ||
| AV | 14838 | 7937_1_2 | Subfeed iTHD Ph A (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14839 | 7938_1_2 | Subfeed iTHD Ph B (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14840 | 7939_1_2 | Subfeed iTHD Ph C (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14841 | 7940_1_2 | Subfeed Current 3rd Harmonic Ph A (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14842 | 7941_1_2 | Subfeed Current 3rd Harmonic Ph B (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14843 | 7942_1_2 | Subfeed Current 3rd Harmonic Ph C (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14844 | 7943_1_2 | Subfeed Current 5th Harmonic Ph A (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14845 | 7944_1_2 | Subfeed Current 5th Harmonic Ph B (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14846 | 7945_1_2 | Subfeed Current 5th Harmonic Ph C (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14847 | 7946_1_2 | Subfeed Current 7th Harmonic Ph A (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14848 | 7947_1_2 | Subfeed Current 7th Harmonic Ph B (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14849 | 7948_1_2 | Subfeed Current 7th Harmonic Ph C (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14850 | 7949_1_2 | Subfeed Current 9th Harmonic Ph A (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14851 | 7950_1_2 | Subfeed Current 9th Harmonic Ph B (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14852 | 7951_1_2 | Subfeed Current 9th Harmonic Ph C (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14853 | 7959_1_2 | Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14854 | 7960_1_2 | Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14855 | 7961_1_2 | Subfeed Neutral Overcurrent Threshold (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 14856 | 8279_1_2 | Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 2) | % | Read | |
| AV | 15343 | 7912_1_12 | Subfeed Current Rating (Subfeed PB 1 Subfeed 12) | A | Read | |
| AV | 15344 | 7913_1_12 | Subfeed Current Ph A (Subfeed PB 1 Subfeed 12) | A | Read | |
| AV | 15345 | 7914_1_12 | Subfeed Current Ph B (Subfeed PB 1 Subfeed 12) | A | Read | |
| AV | 15346 | 7915_1_12 | Subfeed Current Ph C (Subfeed PB 1 Subfeed 12) | A | Read | |
| AV | 15347 | 7916_1_12 | Subfeed Neutral Current (Subfeed PB 1 Subfeed 12) | A | Read | |
| AV | 15348 | 7917_1_12 | Subfeed Ground Current (Subfeed PB 1 Subfeed 12) | A | Read | |
| AV | 15349 | 7918_1_12 | Subfeed Current Load Ph A (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15350 | 7919_1_12 | Subfeed Current Load Ph B (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15351 | 7920_1_12 | Subfeed Current Load Ph C (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15352 | 7921_1_12 | Subfeed Highest Phase Current Load (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15353 | 7922_1_12 | Subfeed Real Power (Subfeed PB 1 Subfeed 12) | kW | Read | |
| AV | 15354 | 7923_1_12 | Subfeed Apparent Power (Subfeed PB 1 Subfeed 12) | kVA | Read | |
| AV | 15355 | 7924_1_12 | Subfeed Power Factor Ph A (Subfeed PB 1 Subfeed 12) | Read | ||
| AV | 15356 | 7925_1_12 | Subfeed Power Factor Ph B (Subfeed PB 1 Subfeed 12) | Read | ||
| AV | 15357 | 7926_1_12 | Subfeed Power Factor Ph C (Subfeed PB 1 Subfeed 12) | Read | ||
| AV | 15358 | 7927_1_12 | Subfeed Power Factor Total (Subfeed PB 1 Subfeed 12) | Read | ||
| AV | 15359 | 7928_1_12 | Subfeed Energy (Subfeed PB 1 Subfeed 12) | kWh | Read | |
| AV | 15360 | 7929_1_12 | Subfeed Peak Current Ph A (Subfeed PB 1 Subfeed 12) | A | Read | |
| AV | 15361 | 7930_1_12 | Subfeed Peak Current Ph B (Subfeed PB 1 Subfeed 12) | A | Read | |
| AV | 15362 | 7931_1_12 | Subfeed Peak Current Ph C (Subfeed PB 1 Subfeed 12) | A | Read | |
| AV | 15363 | 7932_1_12 | Subfeed Highest Phase Peak Current (Subfeed PB 1 Subfeed 12) | A | Read | |
| AV | 15364 | 7933_1_12 | Subfeed Peak Demand (Subfeed PB 1 Subfeed 12) | kW | Read | |
| AV | 15365 | 7934_1_12 | Subfeed Current Crest Factor Ph A (Subfeed PB 1 Subfeed 12) | Read | ||
| AV | 15366 | 7935_1_12 | Subfeed Current Crest Factor Ph B (Subfeed PB 1 Subfeed 12) | Read | ||
| AV | 15367 | 7936_1_12 | Subfeed Current Crest Factor Ph C (Subfeed PB 1 Subfeed 12) | Read | ||
| AV | 15368 | 7937_1_12 | Subfeed iTHD Ph A (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15369 | 7938_1_12 | Subfeed iTHD Ph B (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15370 | 7939_1_12 | Subfeed iTHD Ph C (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15371 | 7940_1_12 | Subfeed Current 3rd Harmonic Ph A (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15372 | 7941_1_12 | Subfeed Current 3rd Harmonic Ph B (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15373 | 7942_1_12 | Subfeed Current 3rd Harmonic Ph C (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15374 | 7943_1_12 | Subfeed Current 5th Harmonic Ph A (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15375 | 7944_1_12 | Subfeed Current 5th Harmonic Ph B (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15376 | 7945_1_12 | Subfeed Current 5th Harmonic Ph C (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15377 | 7946_1_12 | Subfeed Current 7th Harmonic Ph A (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15378 | 7947_1_12 | Subfeed Current 7th Harmonic Ph B (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15379 | 7948_1_12 | Subfeed Current 7th Harmonic Ph C (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15380 | 7949_1_12 | Subfeed Current 9th Harmonic Ph A (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15381 | 7950_1_12 | Subfeed Current 9th Harmonic Ph B (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15382 | 7951_1_12 | Subfeed Current 9th Harmonic Ph C (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15383 | 7959_1_12 | Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15384 | 7960_1_12 | Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15385 | 7961_1_12 | Subfeed Neutral Overcurrent Threshold (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15386 | 8279_1_12 | Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 12) | % | Read | |
| AV | 15396 | 7833_2 | Panelboard Subfeed Count (Subfeed PB 2) | Read | ||
| AV | 15397 | 7834_2 | Panelboard Current Ph A (Subfeed PB 2) | A | Read | |
| AV | 15398 | 7835_2 | Panelboard Current Ph B (Subfeed PB 2) | A | Read | |
| AV | 15399 | 7836_2 | Panelboard Current Ph C (Subfeed PB 2) | A | Read | |
| AV | 15400 | 7837_2 | Panelboard Neutral Current (Subfeed PB 2) | A | Read | |
| AV | 15401 | 7838_2 | Panelboard Ground Current (Subfeed PB 2) | A | Read | |
| AV | 15402 | 7839_2 | Panelboard Current Load Ph A (Subfeed PB 2) | % | Read | |
| AV | 15403 | 7840_2 | Panelboard Current Load Ph B (Subfeed PB 2) | % | Read | |
| AV | 15404 | 7841_2 | Panelboard Current Load Ph C (Subfeed PB 2) | % | Read | |
| AV | 15405 | 7842_2 | Panelboard Highest Phase Current Load (Subfeed PB 2) | % | Read | |
| AV | 15406 | 7843_2 | Panelboard Voltage (L-L) A-B (Subfeed PB 2) | V | Read | |
| AV | 15407 | 7844_2 | Panelboard Voltage (L-L) B-C (Subfeed PB 2) | V | Read | |
| AV | 15408 | 7845_2 | Panelboard Voltage (L-L) C-A (Subfeed PB 2) | V | Read | |
| AV | 15409 | 7846_2 | Panelboard Voltage (L-N) A-N (Subfeed PB 2) | V | Read | |
| AV | 15410 | 7847_2 | Panelboard Voltage (L-N) B-N (Subfeed PB 2) | V | Read | |
| AV | 15411 | 7848_2 | Panelboard Voltage (L-N) C-N (Subfeed PB 2) | V | Read | |
| AV | 15412 | 7849_2 | Panelboard Frequency (Subfeed PB 2) | Hz | Read | |
| AV | 15413 | 7850_2 | Panelboard Real Power (Subfeed PB 2) | kW | Read | |
| AV | 15414 | 7851_2 | Panelboard Apparent Power (Subfeed PB 2) | kVA | Read | |
| AV | 15415 | 7852_2 | Panelboard Power Factor Ph A (Subfeed PB 2) | Read | ||
| AV | 15416 | 7853_2 | Panelboard Power Factor Ph B (Subfeed PB 2) | Read | ||
| AV | 15417 | 7854_2 | Panelboard Power Factor Ph C (Subfeed PB 2) | Read | ||
| AV | 15418 | 7855_2 | Panelboard Power Factor Total (Subfeed PB 2) | Read | ||
| AV | 15419 | 7856_2 | Panelboard Energy (Subfeed PB 2) | kWh | Read | |
| AV | 15420 | 7857_2 | Panelboard Peak Current Ph A (Subfeed PB 2) | A | Read | |
| AV | 15421 | 7858_2 | Panelboard Peak Current Ph B (Subfeed PB 2) | A | Read | |
| AV | 15422 | 7859_2 | Panelboard Peak Current Ph C (Subfeed PB 2) | A | Read | |
| AV | 15423 | 7860_2 | Panelboard Highest Phase Peak Current (Subfeed PB 2) | A | Read | |
| AV | 15424 | 7861_2 | Panelboard Peak Demand (Subfeed PB 2) | kW | Read | |
| AV | 15425 | 7862_2 | Panelboard Current Crest Factor Ph A (Subfeed PB 2) | Read | ||
| AV | 15426 | 7863_2 | Panelboard Current Crest Factor Ph B (Subfeed PB 2) | Read | ||
| AV | 15427 | 7864_2 | Panelboard Current Crest Factor Ph C (Subfeed PB 2) | Read | ||
| AV | 15428 | 7865_2 | Panelboard iTHD Ph A (Subfeed PB 2) | % | Read | |
| AV | 15429 | 7866_2 | Panelboard iTHD Ph B (Subfeed PB 2) | % | Read | |
| AV | 15430 | 7867_2 | Panelboard iTHD Ph C (Subfeed PB 2) | % | Read | |
| AV | 15431 | 7868_2 | Panelboard Current 3rd Harmonic Ph A (Subfeed PB 2) | % | Read | |
| AV | 15432 | 7869_2 | Panelboard Current 3rd Harmonic Ph B (Subfeed PB 2) | % | Read | |
| AV | 15433 | 7870_2 | Panelboard Current 3rd Harmonic Ph C (Subfeed PB 2) | % | Read | |
| AV | 15434 | 7871_2 | Panelboard Current 5th Harmonic Ph A (Subfeed PB 2) | % | Read | |
| AV | 15435 | 7872_2 | Panelboard Current 5th Harmonic Ph B (Subfeed PB 2) | % | Read | |
| AV | 15436 | 7873_2 | Panelboard Current 5th Harmonic Ph C (Subfeed PB 2) | % | Read | |
| AV | 15437 | 7874_2 | Panelboard Current 7th Harmonic Ph A (Subfeed PB 2) | % | Read | |
| AV | 15438 | 7875_2 | Panelboard Current 7th Harmonic Ph B (Subfeed PB 2) | % | Read | |
| AV | 15439 | 7876_2 | Panelboard Current 7th Harmonic Ph C (Subfeed PB 2) | % | Read | |
| AV | 15440 | 7877_2 | Panelboard Current 9th Harmonic Ph A (Subfeed PB 2) | % | Read | |
| AV | 15441 | 7878_2 | Panelboard Current 9th Harmonic Ph B (Subfeed PB 2) | % | Read | |
| AV | 15442 | 7879_2 | Panelboard Current 9th Harmonic Ph C (Subfeed PB 2) | % | Read | |
| AV | 15443 | 7880_2 | Panelboard vTHD Ph A (Subfeed PB 2) | % | Read | |
| AV | 15444 | 7881_2 | Panelboard vTHD Ph B (Subfeed PB 2) | % | Read | |
| AV | 15445 | 7882_2 | Panelboard vTHD Ph C (Subfeed PB 2) | % | Read | |
| AV | 15446 | 7883_2 | Panelboard Voltage 3rd Harmonic Ph A (Subfeed PB 2) | % | Read | |
| AV | 15447 | 7884_2 | Panelboard Voltage 3rd Harmonic Ph B (Subfeed PB 2) | % | Read | |
| AV | 15448 | 7885_2 | Panelboard Voltage 3rd Harmonic Ph C (Subfeed PB 2) | % | Read | |
| AV | 15449 | 7886_2 | Panelboard Voltage 5th Harmonic Ph A (Subfeed PB 2) | % | Read | |
| AV | 15450 | 7887_2 | Panelboard Voltage 5th Harmonic Ph B (Subfeed PB 2) | % | Read | |
| AV | 15451 | 7888_2 | Panelboard Voltage 5th Harmonic Ph C (Subfeed PB 2) | % | Read | |
| AV | 15452 | 7889_2 | Panelboard Voltage 7th Harmonic Ph A (Subfeed PB 2) | % | Read | |
| AV | 15453 | 7890_2 | Panelboard Voltage 7th Harmonic Ph B (Subfeed PB 2) | % | Read | |
| AV | 15454 | 7891_2 | Panelboard Voltage 7th Harmonic Ph C (Subfeed PB 2) | % | Read | |
| AV | 15455 | 7892_2 | Panelboard Voltage 9th Harmonic Ph A (Subfeed PB 2) | % | Read | |
| AV | 15456 | 7893_2 | Panelboard Voltage 9th Harmonic Ph B (Subfeed PB 2) | % | Read | |
| AV | 15457 | 7894_2 | Panelboard Voltage 9th Harmonic Ph C (Subfeed PB 2) | % | Read | |
| AV | 15458 | 7902_2 | Panelboard Phase Overcurrent Warning Threshold (Subfeed PB 2) | % | Read | |
| AV | 15459 | 7903_2 | Panelboard Phase Overcurrent Alarm Threshold (Subfeed PB 2) | % | Read | |
| AV | 15460 | 7904_2 | Panelboard Neutral Overcurrent Alarm Threshold (Subfeed PB 2) | % | Read | |
| AV | 15461 | 7905_2 | Panelboard Ground Overcurrent Alarm Threshold (Subfeed PB 2) | A | Read | |
| AV | 15462 | 8278_2 | Panelboard Neutral Overcurrent Warning Threshold (Subfeed PB 2) | % | Read | |
| AV | 15463 | 8265_2 | Panelboard Phase Overvoltage Alarm Threshold (Subfeed PB 2) | % | Read | |
| AV | 15464 | 8266_2 | Panelboard Phase Undervoltage Alarm Threshold (Subfeed PB 2) | % | Read | |
| AV | 15472 | 7912_2_1 | Subfeed Current Rating (Subfeed PB 2 Subfeed 1) | A | Read | |
| AV | 15473 | 7913_2_1 | Subfeed Current Ph A (Subfeed PB 2 Subfeed 1) | A | Read | |
| AV | 15474 | 7914_2_1 | Subfeed Current Ph B (Subfeed PB 2 Subfeed 1) | A | Read | |
| AV | 15475 | 7915_2_1 | Subfeed Current Ph C (Subfeed PB 2 Subfeed 1) | A | Read | |
| AV | 15476 | 7916_2_1 | Subfeed Neutral Current (Subfeed PB 2 Subfeed 1) | A | Read | |
| AV | 15477 | 7917_2_1 | Subfeed Ground Current (Subfeed PB 2 Subfeed 1) | A | Read | |
| AV | 15478 | 7918_2_1 | Subfeed Current Load Ph A (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15479 | 7919_2_1 | Subfeed Current Load Ph B (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15480 | 7920_2_1 | Subfeed Current Load Ph C (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15481 | 7921_2_1 | Subfeed Highest Phase Current Load (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15482 | 7922_2_1 | Subfeed Real Power (Subfeed PB 2 Subfeed 1) | kW | Read | |
| AV | 15483 | 7923_2_1 | Subfeed Apparent Power (Subfeed PB 2 Subfeed 1) | kVA | Read | |
| AV | 15484 | 7924_2_1 | Subfeed Power Factor Ph A (Subfeed PB 2 Subfeed 1) | Read | ||
| AV | 15485 | 7925_2_1 | Subfeed Power Factor Ph B (Subfeed PB 2 Subfeed 1) | Read | ||
| AV | 15486 | 7926_2_1 | Subfeed Power Factor Ph C (Subfeed PB 2 Subfeed 1) | Read | ||
| AV | 15487 | 7927_2_1 | Subfeed Power Factor Total (Subfeed PB 2 Subfeed 1) | Read | ||
| AV | 15488 | 7928_2_1 | Subfeed Energy (Subfeed PB 2 Subfeed 1) | kWh | Read | |
| AV | 15489 | 7929_2_1 | Subfeed Peak Current Ph A (Subfeed PB 2 Subfeed 1) | A | Read | |
| AV | 15490 | 7930_2_1 | Subfeed Peak Current Ph B (Subfeed PB 2 Subfeed 1) | A | Read | |
| AV | 15491 | 7931_2_1 | Subfeed Peak Current Ph C (Subfeed PB 2 Subfeed 1) | A | Read | |
| AV | 15492 | 7932_2_1 | Subfeed Highest Phase Peak Current (Subfeed PB 2 Subfeed 1) | A | Read | |
| AV | 15493 | 7933_2_1 | Subfeed Peak Demand (Subfeed PB 2 Subfeed 1) | kW | Read | |
| AV | 15494 | 7934_2_1 | Subfeed Current Crest Factor Ph A (Subfeed PB 2 Subfeed 1) | Read | ||
| AV | 15495 | 7935_2_1 | Subfeed Current Crest Factor Ph B (Subfeed PB 2 Subfeed 1) | Read | ||
| AV | 15496 | 7936_2_1 | Subfeed Current Crest Factor Ph C (Subfeed PB 2 Subfeed 1) | Read | ||
| AV | 15497 | 7937_2_1 | Subfeed iTHD Ph A (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15498 | 7938_2_1 | Subfeed iTHD Ph B (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15499 | 7939_2_1 | Subfeed iTHD Ph C (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15500 | 7940_2_1 | Subfeed Current 3rd Harmonic Ph A (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15501 | 7941_2_1 | Subfeed Current 3rd Harmonic Ph B (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15502 | 7942_2_1 | Subfeed Current 3rd Harmonic Ph C (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15503 | 7943_2_1 | Subfeed Current 5th Harmonic Ph A (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15504 | 7944_2_1 | Subfeed Current 5th Harmonic Ph B (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15505 | 7945_2_1 | Subfeed Current 5th Harmonic Ph C (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15506 | 7946_2_1 | Subfeed Current 7th Harmonic Ph A (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15507 | 7947_2_1 | Subfeed Current 7th Harmonic Ph B (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15508 | 7948_2_1 | Subfeed Current 7th Harmonic Ph C (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15509 | 7949_2_1 | Subfeed Current 9th Harmonic Ph A (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15510 | 7950_2_1 | Subfeed Current 9th Harmonic Ph B (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15511 | 7951_2_1 | Subfeed Current 9th Harmonic Ph C (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15512 | 7959_2_1 | Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15513 | 7960_2_1 | Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15514 | 7961_2_1 | Subfeed Neutral Overcurrent Threshold (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15515 | 8279_2_1 | Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 1) | % | Read | |
| AV | 15525 | 7912_2_2 | Subfeed Current Rating (Subfeed PB 2 Subfeed 2) | A | Read | |
| AV | 15526 | 7913_2_2 | Subfeed Current Ph A (Subfeed PB 2 Subfeed 2) | A | Read | |
| AV | 15527 | 7914_2_2 | Subfeed Current Ph B (Subfeed PB 2 Subfeed 2) | A | Read | |
| AV | 15528 | 7915_2_2 | Subfeed Current Ph C (Subfeed PB 2 Subfeed 2) | A | Read | |
| AV | 15529 | 7916_2_2 | Subfeed Neutral Current (Subfeed PB 2 Subfeed 2) | A | Read | |
| AV | 15530 | 7917_2_2 | Subfeed Ground Current (Subfeed PB 2 Subfeed 2) | A | Read | |
| AV | 15531 | 7918_2_2 | Subfeed Current Load Ph A (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15532 | 7919_2_2 | Subfeed Current Load Ph B (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15533 | 7920_2_2 | Subfeed Current Load Ph C (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15534 | 7921_2_2 | Subfeed Highest Phase Current Load (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15535 | 7922_2_2 | Subfeed Real Power (Subfeed PB 2 Subfeed 2) | kW | Read | |
| AV | 15536 | 7923_2_2 | Subfeed Apparent Power (Subfeed PB 2 Subfeed 2) | kVA | Read | |
| AV | 15537 | 7924_2_2 | Subfeed Power Factor Ph A (Subfeed PB 2 Subfeed 2) | Read | ||
| AV | 15538 | 7925_2_2 | Subfeed Power Factor Ph B (Subfeed PB 2 Subfeed 2) | Read | ||
| AV | 15539 | 7926_2_2 | Subfeed Power Factor Ph C (Subfeed PB 2 Subfeed 2) | Read | ||
| AV | 15540 | 7927_2_2 | Subfeed Power Factor Total (Subfeed PB 2 Subfeed 2) | Read | ||
| AV | 15541 | 7928_2_2 | Subfeed Energy (Subfeed PB 2 Subfeed 2) | kWh | Read | |
| AV | 15542 | 7929_2_2 | Subfeed Peak Current Ph A (Subfeed PB 2 Subfeed 2) | A | Read | |
| AV | 15543 | 7930_2_2 | Subfeed Peak Current Ph B (Subfeed PB 2 Subfeed 2) | A | Read | |
| AV | 15544 | 7931_2_2 | Subfeed Peak Current Ph C (Subfeed PB 2 Subfeed 2) | A | Read | |
| AV | 15545 | 7932_2_2 | Subfeed Highest Phase Peak Current (Subfeed PB 2 Subfeed 2) | A | Read | |
| AV | 15546 | 7933_2_2 | Subfeed Peak Demand (Subfeed PB 2 Subfeed 2) | kW | Read | |
| AV | 15547 | 7934_2_2 | Subfeed Current Crest Factor Ph A (Subfeed PB 2 Subfeed 2) | Read | ||
| AV | 15548 | 7935_2_2 | Subfeed Current Crest Factor Ph B (Subfeed PB 2 Subfeed 2) | Read | ||
| AV | 15549 | 7936_2_2 | Subfeed Current Crest Factor Ph C (Subfeed PB 2 Subfeed 2) | Read | ||
| AV | 15550 | 7937_2_2 | Subfeed iTHD Ph A (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15551 | 7938_2_2 | Subfeed iTHD Ph B (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15552 | 7939_2_2 | Subfeed iTHD Ph C (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15553 | 7940_2_2 | Subfeed Current 3rd Harmonic Ph A (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15554 | 7941_2_2 | Subfeed Current 3rd Harmonic Ph B (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15555 | 7942_2_2 | Subfeed Current 3rd Harmonic Ph C (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15556 | 7943_2_2 | Subfeed Current 5th Harmonic Ph A (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15557 | 7944_2_2 | Subfeed Current 5th Harmonic Ph B (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15558 | 7945_2_2 | Subfeed Current 5th Harmonic Ph C (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15559 | 7946_2_2 | Subfeed Current 7th Harmonic Ph A (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15560 | 7947_2_2 | Subfeed Current 7th Harmonic Ph B (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15561 | 7948_2_2 | Subfeed Current 7th Harmonic Ph C (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15562 | 7949_2_2 | Subfeed Current 9th Harmonic Ph A (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15563 | 7950_2_2 | Subfeed Current 9th Harmonic Ph B (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15564 | 7951_2_2 | Subfeed Current 9th Harmonic Ph C (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15565 | 7959_2_2 | Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15566 | 7960_2_2 | Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15567 | 7961_2_2 | Subfeed Neutral Overcurrent Threshold (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 15568 | 8279_2_2 | Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 2) | % | Read | |
| AV | 16055 | 7912_2_12 | Subfeed Current Rating (Subfeed PB 2 Subfeed 12) | A | Read | |
| AV | 16056 | 7913_2_12 | Subfeed Current Ph A (Subfeed PB 2 Subfeed 12) | A | Read | |
| AV | 16057 | 7914_2_12 | Subfeed Current Ph B (Subfeed PB 2 Subfeed 12) | A | Read | |
| AV | 16058 | 7915_2_12 | Subfeed Current Ph C (Subfeed PB 2 Subfeed 12) | A | Read | |
| AV | 16059 | 7916_2_12 | Subfeed Neutral Current (Subfeed PB 2 Subfeed 12) | A | Read | |
| AV | 16060 | 7917_2_12 | Subfeed Ground Current (Subfeed PB 2 Subfeed 12) | A | Read | |
| AV | 16061 | 7918_2_12 | Subfeed Current Load Ph A (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16062 | 7919_2_12 | Subfeed Current Load Ph B (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16063 | 7920_2_12 | Subfeed Current Load Ph C (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16064 | 7921_2_12 | Subfeed Highest Phase Current Load (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16065 | 7922_2_12 | Subfeed Real Power (Subfeed PB 2 Subfeed 12) | kW | Read | |
| AV | 16066 | 7923_2_12 | Subfeed Apparent Power (Subfeed PB 2 Subfeed 12) | kVA | Read | |
| AV | 16067 | 7924_2_12 | Subfeed Power Factor Ph A (Subfeed PB 2 Subfeed 12) | Read | ||
| AV | 16068 | 7925_2_12 | Subfeed Power Factor Ph B (Subfeed PB 2 Subfeed 12) | Read | ||
| AV | 16069 | 7926_2_12 | Subfeed Power Factor Ph C (Subfeed PB 2 Subfeed 12) | Read | ||
| AV | 16070 | 7927_2_12 | Subfeed Power Factor Total (Subfeed PB 2 Subfeed 12) | Read | ||
| AV | 16071 | 7928_2_12 | Subfeed Energy (Subfeed PB 2 Subfeed 12) | kWh | Read | |
| AV | 16072 | 7929_2_12 | Subfeed Peak Current Ph A (Subfeed PB 2 Subfeed 12) | A | Read | |
| AV | 16073 | 7930_2_12 | Subfeed Peak Current Ph B (Subfeed PB 2 Subfeed 12) | A | Read | |
| AV | 16074 | 7931_2_12 | Subfeed Peak Current Ph C (Subfeed PB 2 Subfeed 12) | A | Read | |
| AV | 16075 | 7932_2_12 | Subfeed Highest Phase Peak Current (Subfeed PB 2 Subfeed 12) | A | Read | |
| AV | 16076 | 7933_2_12 | Subfeed Peak Demand (Subfeed PB 2 Subfeed 12) | kW | Read | |
| AV | 16077 | 7934_2_12 | Subfeed Current Crest Factor Ph A (Subfeed PB 2 Subfeed 12) | Read | ||
| AV | 16078 | 7935_2_12 | Subfeed Current Crest Factor Ph B (Subfeed PB 2 Subfeed 12) | Read | ||
| AV | 16079 | 7936_2_12 | Subfeed Current Crest Factor Ph C (Subfeed PB 2 Subfeed 12) | Read | ||
| AV | 16080 | 7937_2_12 | Subfeed iTHD Ph A (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16081 | 7938_2_12 | Subfeed iTHD Ph B (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16082 | 7939_2_12 | Subfeed iTHD Ph C (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16083 | 7940_2_12 | Subfeed Current 3rd Harmonic Ph A (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16084 | 7941_2_12 | Subfeed Current 3rd Harmonic Ph B (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16085 | 7942_2_12 | Subfeed Current 3rd Harmonic Ph C (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16086 | 7943_2_12 | Subfeed Current 5th Harmonic Ph A (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16087 | 7944_2_12 | Subfeed Current 5th Harmonic Ph B (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16088 | 7945_2_12 | Subfeed Current 5th Harmonic Ph C (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16089 | 7946_2_12 | Subfeed Current 7th Harmonic Ph A (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16090 | 7947_2_12 | Subfeed Current 7th Harmonic Ph B (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16091 | 7948_2_12 | Subfeed Current 7th Harmonic Ph C (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16092 | 7949_2_12 | Subfeed Current 9th Harmonic Ph A (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16093 | 7950_2_12 | Subfeed Current 9th Harmonic Ph B (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16094 | 7951_2_12 | Subfeed Current 9th Harmonic Ph C (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16095 | 7959_2_12 | Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16096 | 7960_2_12 | Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16097 | 7961_2_12 | Subfeed Neutral Overcurrent Threshold (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16098 | 8279_2_12 | Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 12) | % | Read | |
| AV | 16108 | 7966_1 | Subfeed Current Rating (Subfeed 1) | A | Read | |
| AV | 16109 | 7967_1 | Subfeed Current Ph A (Subfeed 1) | A | Read | |
| AV | 16110 | 7968_1 | Subfeed Current Ph B (Subfeed 1) | A | Read | |
| AV | 16111 | 7969_1 | Subfeed Current Ph C (Subfeed 1) | A | Read | |
| AV | 16112 | 7970_1 | Subfeed Neutral Current (Subfeed 1) | A | Read | |
| AV | 16113 | 7971_1 | Subfeed Ground Current (Subfeed 1) | A | Read | |
| AV | 16114 | 7972_1 | Subfeed Current Load Ph A (Subfeed 1) | % | Read | |
| AV | 16115 | 7973_1 | Subfeed Current Load Ph B (Subfeed 1) | % | Read | |
| AV | 16116 | 7974_1 | Subfeed Current Load Ph C (Subfeed 1) | % | Read | |
| AV | 16117 | 7975_1 | Subfeed Highest Phase Current Load (Subfeed 1) | % | Read | |
| AV | 16118 | 7976_1 | Subfeed Voltage (L-L) A-B (Subfeed 1) | V | Read | |
| AV | 16119 | 7977_1 | Subfeed Voltage (L-L) B-C (Subfeed 1) | V | Read | |
| AV | 16120 | 7978_1 | Subfeed Voltage (L-L) C-A (Subfeed 1) | V | Read | |
| AV | 16121 | 7979_1 | Subfeed Voltage (L-N) A-N (Subfeed 1) | V | Read | |
| AV | 16122 | 7980_1 | Subfeed Voltage (L-N) B-N (Subfeed 1) | V | Read | |
| AV | 16123 | 7981_1 | Subfeed Voltage (L-N) C-N (Subfeed 1) | V | Read | |
| AV | 16124 | 7982_1 | Subfeed Frequency (Subfeed 1) | Hz | Read | |
| AV | 16125 | 7983_1 | Subfeed Real Power (Subfeed 1) | kW | Read | |
| AV | 16126 | 7984_1 | Subfeed Apparent Power (Subfeed 1) | kVA | Read | |
| AV | 16127 | 7985_1 | Subfeed Power Factor Ph A (Subfeed 1) | Read | ||
| AV | 16128 | 7986_1 | Subfeed Power Factor Ph B (Subfeed 1) | Read | ||
| AV | 16129 | 7987_1 | Subfeed Power Factor Ph C (Subfeed 1) | Read | ||
| AV | 16130 | 7988_1 | Subfeed Power Factor Total (Subfeed 1) | Read | ||
| AV | 16131 | 7989_1 | Subfeed Energy (Subfeed 1) | kWh | Read | |
| AV | 16132 | 7990_1 | Subfeed Peak Current Ph A (Subfeed 1) | A | Read | |
| AV | 16133 | 7991_1 | Subfeed Peak Current Ph B (Subfeed 1) | A | Read | |
| AV | 16134 | 7992_1 | Subfeed Peak Current Ph C (Subfeed 1) | A | Read | |
| AV | 16135 | 7993_1 | Subfeed Highest Phase Peak Current (Subfeed 1) | A | Read | |
| AV | 16136 | 7994_1 | Subfeed Peak Demand (Subfeed 1) | kW | Read | |
| AV | 16137 | 7995_1 | Subfeed Current Crest Factor Ph A (Subfeed 1) | Read | ||
| AV | 16138 | 7996_1 | Subfeed Current Crest Factor Ph B (Subfeed 1) | Read | ||
| AV | 16139 | 7997_1 | Subfeed Current Crest Factor Ph C (Subfeed 1) | Read | ||
| AV | 16140 | 7998_1 | Subfeed iTHD Ph A (Subfeed 1) | % | Read | |
| AV | 16141 | 7999_1 | Subfeed iTHD Ph B (Subfeed 1) | % | Read | |
| AV | 16142 | 8000_1 | Subfeed iTHD Ph C (Subfeed 1) | % | Read | |
| AV | 16143 | 8001_1 | Subfeed Current 3rd Harmonic Ph A (Subfeed 1) | % | Read | |
| AV | 16144 | 8002_1 | Subfeed Current 3rd Harmonic Ph B (Subfeed 1) | % | Read | |
| AV | 16145 | 8003_1 | Subfeed Current 3rd Harmonic Ph C (Subfeed 1) | % | Read | |
| AV | 16146 | 8004_1 | Subfeed Current 5th Harmonic Ph A (Subfeed 1) | % | Read | |
| AV | 16147 | 8005_1 | Subfeed Current 5th Harmonic Ph B (Subfeed 1) | % | Read | |
| AV | 16148 | 8006_1 | Subfeed Current 5th Harmonic Ph C (Subfeed 1) | % | Read | |
| AV | 16149 | 8007_1 | Subfeed Current 7th Harmonic Ph A (Subfeed 1) | % | Read | |
| AV | 16150 | 8008_1 | Subfeed Current 7th Harmonic Ph B (Subfeed 1) | % | Read | |
| AV | 16151 | 8009_1 | Subfeed Current 7th Harmonic Ph C (Subfeed 1) | % | Read | |
| AV | 16152 | 8010_1 | Subfeed Current 9th Harmonic Ph A (Subfeed 1) | % | Read | |
| AV | 16153 | 8011_1 | Subfeed Current 9th Harmonic Ph B (Subfeed 1) | % | Read | |
| AV | 16154 | 8012_1 | Subfeed Current 9th Harmonic Ph C (Subfeed 1) | % | Read | |
| AV | 16155 | 8013_1 | Subfeed vTHD Ph A (Subfeed 1) | % | Read | |
| AV | 16156 | 8014_1 | Subfeed vTHD Ph B (Subfeed 1) | % | Read | |
| AV | 16157 | 8015_1 | Subfeed vTHD Ph C (Subfeed 1) | % | Read | |
| AV | 16158 | 8016_1 | Subfeed Voltage 3rd Harmonic Ph A (Subfeed 1) | % | Read | |
| AV | 16159 | 8017_1 | Subfeed Voltage 3rd Harmonic Ph B (Subfeed 1) | % | Read | |
| AV | 16160 | 8018_1 | Subfeed Voltage 3rd Harmonic Ph C (Subfeed 1) | % | Read | |
| AV | 16161 | 8019_1 | Subfeed Voltage 5th Harmonic Ph A (Subfeed 1) | % | Read | |
| AV | 16162 | 8020_1 | Subfeed Voltage 5th Harmonic Ph B (Subfeed 1) | % | Read | |
| AV | 16163 | 8021_1 | Subfeed Voltage 5th Harmonic Ph C (Subfeed 1) | % | Read | |
| AV | 16164 | 8022_1 | Subfeed Voltage 7th Harmonic Ph A (Subfeed 1) | % | Read | |
| AV | 16165 | 8023_1 | Subfeed Voltage 7th Harmonic Ph B (Subfeed 1) | % | Read | |
| AV | 16166 | 8024_1 | Subfeed Voltage 7th Harmonic Ph C (Subfeed 1) | % | Read | |
| AV | 16167 | 8025_1 | Subfeed Voltage 9th Harmonic Ph A (Subfeed 1) | % | Read | |
| AV | 16168 | 8026_1 | Subfeed Voltage 9th Harmonic Ph B (Subfeed 1) | % | Read | |
| AV | 16169 | 8027_1 | Subfeed Voltage 9th Harmonic Ph C (Subfeed 1) | % | Read | |
| AV | 16170 | 8035_1 | Subfeed Phase Overcurrent Warning Threshold (Subfeed 1) | % | Read | |
| AV | 16171 | 8036_1 | Subfeed Phase Overcurrent Alarm Threshold (Subfeed 1) | % | Read | |
| AV | 16172 | 8037_1 | Subfeed Neutral Overcurrent Threshold (Subfeed 1) | Read | ||
| AV | 16173 | 8038_1 | Subfeed Ground Overcurrent Alarm Threshold (Subfeed 1) | A | Read | |
| AV | 16174 | 8280_1 | Subfeed Neutral Overcurrent Warning Threshold (Subfeed 1) | % | Read | |
| AV | 16175 | 8270_1 | Subfeed Phase Overvoltage Alarm Threshold (Subfeed 1) | % | Read | |
| AV | 16176 | 8271_1 | Subfeed Phase Undervoltage Alarm Threshold (Subfeed 1) | % | Read | |
| AV | 16184 | 7966_2 | Subfeed Current Rating (Subfeed 2) | A | Read | |
| AV | 16185 | 7967_2 | Subfeed Current Ph A (Subfeed 2) | A | Read | |
| AV | 16186 | 7968_2 | Subfeed Current Ph B (Subfeed 2) | A | Read | |
| AV | 16187 | 7969_2 | Subfeed Current Ph C (Subfeed 2) | A | Read | |
| AV | 16188 | 7970_2 | Subfeed Neutral Current (Subfeed 2) | A | Read | |
| AV | 16189 | 7971_2 | Subfeed Ground Current (Subfeed 2) | A | Read | |
| AV | 16190 | 7972_2 | Subfeed Current Load Ph A (Subfeed 2) | % | Read | |
| AV | 16191 | 7973_2 | Subfeed Current Load Ph B (Subfeed 2) | % | Read | |
| AV | 16192 | 7974_2 | Subfeed Current Load Ph C (Subfeed 2) | % | Read | |
| AV | 16193 | 7975_2 | Subfeed Highest Phase Current Load (Subfeed 2) | % | Read | |
| AV | 16194 | 7976_2 | Subfeed Voltage (L-L) A-B (Subfeed 2) | V | Read | |
| AV | 16195 | 7977_2 | Subfeed Voltage (L-L) B-C (Subfeed 2) | V | Read | |
| AV | 16196 | 7978_2 | Subfeed Voltage (L-L) C-A (Subfeed 2) | V | Read | |
| AV | 16197 | 7979_2 | Subfeed Voltage (L-N) A-N (Subfeed 2) | V | Read | |
| AV | 16198 | 7980_2 | Subfeed Voltage (L-N) B-N (Subfeed 2) | V | Read | |
| AV | 16199 | 7981_2 | Subfeed Voltage (L-N) C-N (Subfeed 2) | V | Read | |
| AV | 16200 | 7982_2 | Subfeed Frequency (Subfeed 2) | Hz | Read | |
| AV | 16201 | 7983_2 | Subfeed Real Power (Subfeed 2) | kW | Read | |
| AV | 16202 | 7984_2 | Subfeed Apparent Power (Subfeed 2) | kVA | Read | |
| AV | 16203 | 7985_2 | Subfeed Power Factor Ph A (Subfeed 2) | Read | ||
| AV | 16204 | 7986_2 | Subfeed Power Factor Ph B (Subfeed 2) | Read | ||
| AV | 16205 | 7987_2 | Subfeed Power Factor Ph C (Subfeed 2) | Read | ||
| AV | 16206 | 7988_2 | Subfeed Power Factor Total (Subfeed 2) | Read | ||
| AV | 16207 | 7989_2 | Subfeed Energy (Subfeed 2) | kWh | Read | |
| AV | 16208 | 7990_2 | Subfeed Peak Current Ph A (Subfeed 2) | A | Read | |
| AV | 16209 | 7991_2 | Subfeed Peak Current Ph B (Subfeed 2) | A | Read | |
| AV | 16210 | 7992_2 | Subfeed Peak Current Ph C (Subfeed 2) | A | Read | |
| AV | 16211 | 7993_2 | Subfeed Highest Phase Peak Current (Subfeed 2) | A | Read | |
| AV | 16212 | 7994_2 | Subfeed Peak Demand (Subfeed 2) | kW | Read | |
| AV | 16213 | 7995_2 | Subfeed Current Crest Factor Ph A (Subfeed 2) | Read | ||
| AV | 16214 | 7996_2 | Subfeed Current Crest Factor Ph B (Subfeed 2) | Read | ||
| AV | 16215 | 7997_2 | Subfeed Current Crest Factor Ph C (Subfeed 2) | Read | ||
| AV | 16216 | 7998_2 | Subfeed iTHD Ph A (Subfeed 2) | % | Read | |
| AV | 16217 | 7999_2 | Subfeed iTHD Ph B (Subfeed 2) | % | Read | |
| AV | 16218 | 8000_2 | Subfeed iTHD Ph C (Subfeed 2) | % | Read | |
| AV | 16219 | 8001_2 | Subfeed Current 3rd Harmonic Ph A (Subfeed 2) | % | Read | |
| AV | 16220 | 8002_2 | Subfeed Current 3rd Harmonic Ph B (Subfeed 2) | % | Read | |
| AV | 16221 | 8003_2 | Subfeed Current 3rd Harmonic Ph C (Subfeed 2) | % | Read | |
| AV | 16222 | 8004_2 | Subfeed Current 5th Harmonic Ph A (Subfeed 2) | % | Read | |
| AV | 16223 | 8005_2 | Subfeed Current 5th Harmonic Ph B (Subfeed 2) | % | Read | |
| AV | 16224 | 8006_2 | Subfeed Current 5th Harmonic Ph C (Subfeed 2) | % | Read | |
| AV | 16225 | 8007_2 | Subfeed Current 7th Harmonic Ph A (Subfeed 2) | % | Read | |
| AV | 16226 | 8008_2 | Subfeed Current 7th Harmonic Ph B (Subfeed 2) | % | Read | |
| AV | 16227 | 8009_2 | Subfeed Current 7th Harmonic Ph C (Subfeed 2) | % | Read | |
| AV | 16228 | 8010_2 | Subfeed Current 9th Harmonic Ph A (Subfeed 2) | % | Read | |
| AV | 16229 | 8011_2 | Subfeed Current 9th Harmonic Ph B (Subfeed 2) | % | Read | |
| AV | 16230 | 8012_2 | Subfeed Current 9th Harmonic Ph C (Subfeed 2) | % | Read | |
| AV | 16231 | 8013_2 | Subfeed vTHD Ph A (Subfeed 2) | % | Read | |
| AV | 16232 | 8014_2 | Subfeed vTHD Ph B (Subfeed 2) | % | Read | |
| AV | 16233 | 8015_2 | Subfeed vTHD Ph C (Subfeed 2) | % | Read | |
| AV | 16234 | 8016_2 | Subfeed Voltage 3rd Harmonic Ph A (Subfeed 2) | % | Read | |
| AV | 16235 | 8017_2 | Subfeed Voltage 3rd Harmonic Ph B (Subfeed 2) | % | Read | |
| AV | 16236 | 8018_2 | Subfeed Voltage 3rd Harmonic Ph C (Subfeed 2) | % | Read | |
| AV | 16237 | 8019_2 | Subfeed Voltage 5th Harmonic Ph A (Subfeed 2) | % | Read | |
| AV | 16238 | 8020_2 | Subfeed Voltage 5th Harmonic Ph B (Subfeed 2) | % | Read | |
| AV | 16239 | 8021_2 | Subfeed Voltage 5th Harmonic Ph C (Subfeed 2) | % | Read | |
| AV | 16240 | 8022_2 | Subfeed Voltage 7th Harmonic Ph A (Subfeed 2) | % | Read | |
| AV | 16241 | 8023_2 | Subfeed Voltage 7th Harmonic Ph B (Subfeed 2) | % | Read | |
| AV | 16242 | 8024_2 | Subfeed Voltage 7th Harmonic Ph C (Subfeed 2) | % | Read | |
| AV | 16243 | 8025_2 | Subfeed Voltage 9th Harmonic Ph A (Subfeed 2) | % | Read | |
| AV | 16244 | 8026_2 | Subfeed Voltage 9th Harmonic Ph B (Subfeed 2) | % | Read | |
| AV | 16245 | 8027_2 | Subfeed Voltage 9th Harmonic Ph C (Subfeed 2) | % | Read | |
| AV | 16246 | 8035_2 | Subfeed Phase Overcurrent Warning Threshold (Subfeed 2) | % | Read | |
| AV | 16247 | 8036_2 | Subfeed Phase Overcurrent Alarm Threshold (Subfeed 2) | % | Read | |
| AV | 16248 | 8037_2 | Subfeed Neutral Overcurrent Threshold (Subfeed 2) | Read | ||
| AV | 16249 | 8038_2 | Subfeed Ground Overcurrent Alarm Threshold (Subfeed 2) | A | Read | |
| AV | 16250 | 8280_2 | Subfeed Neutral Overcurrent Warning Threshold (Subfeed 2) | % | Read | |
| AV | 16251 | 8270_2 | Subfeed Phase Overvoltage Alarm Threshold (Subfeed 2) | % | Read | |
| AV | 16252 | 8271_2 | Subfeed Phase Undervoltage Alarm Threshold (Subfeed 2) | % | Read | |
| AV | 18768 | 7966_36 | Subfeed Current Rating (Subfeed 36) | A | Read | |
| AV | 18769 | 7967_36 | Subfeed Current Ph A (Subfeed 36) | A | Read | |
| AV | 18770 | 7968_36 | Subfeed Current Ph B (Subfeed 36) | A | Read | |
| AV | 18771 | 7969_36 | Subfeed Current Ph C (Subfeed 36) | A | Read | |
| AV | 18772 | 7970_36 | Subfeed Neutral Current (Subfeed 36) | A | Read | |
| AV | 18773 | 7971_36 | Subfeed Ground Current (Subfeed 36) | A | Read | |
| AV | 18774 | 7972_36 | Subfeed Current Load Ph A (Subfeed 36) | % | Read | |
| AV | 18775 | 7973_36 | Subfeed Current Load Ph B (Subfeed 36) | % | Read | |
| AV | 18776 | 7974_36 | Subfeed Current Load Ph C (Subfeed 36) | % | Read | |
| AV | 18777 | 7975_36 | Subfeed Highest Phase Current Load (Subfeed 36) | % | Read | |
| AV | 18778 | 7976_36 | Subfeed Voltage (L-L) A-B (Subfeed 36) | V | Read | |
| AV | 18779 | 7977_36 | Subfeed Voltage (L-L) B-C (Subfeed 36) | V | Read | |
| AV | 18780 | 7978_36 | Subfeed Voltage (L-L) C-A (Subfeed 36) | V | Read | |
| AV | 18781 | 7979_36 | Subfeed Voltage (L-N) A-N (Subfeed 36) | V | Read | |
| AV | 18782 | 7980_36 | Subfeed Voltage (L-N) B-N (Subfeed 36) | V | Read | |
| AV | 18783 | 7981_36 | Subfeed Voltage (L-N) C-N (Subfeed 36) | V | Read | |
| AV | 18784 | 7982_36 | Subfeed Frequency (Subfeed 36) | Hz | Read | |
| AV | 18785 | 7983_36 | Subfeed Real Power (Subfeed 36) | kW | Read | |
| AV | 18786 | 7984_36 | Subfeed Apparent Power (Subfeed 36) | kVA | Read | |
| AV | 18787 | 7985_36 | Subfeed Power Factor Ph A (Subfeed 36) | Read | ||
| AV | 18788 | 7986_36 | Subfeed Power Factor Ph B (Subfeed 36) | Read | ||
| AV | 18789 | 7987_36 | Subfeed Power Factor Ph C (Subfeed 36) | Read | ||
| AV | 18790 | 7988_36 | Subfeed Power Factor Total (Subfeed 36) | Read | ||
| AV | 18791 | 7989_36 | Subfeed Energy (Subfeed 36) | kWh | Read | |
| AV | 18792 | 7990_36 | Subfeed Peak Current Ph A (Subfeed 36) | A | Read | |
| AV | 18793 | 7991_36 | Subfeed Peak Current Ph B (Subfeed 36) | A | Read | |
| AV | 18794 | 7992_36 | Subfeed Peak Current Ph C (Subfeed 36) | A | Read | |
| AV | 18795 | 7993_36 | Subfeed Highest Phase Peak Current (Subfeed 36) | A | Read | |
| AV | 18796 | 7994_36 | Subfeed Peak Demand (Subfeed 36) | kW | Read | |
| AV | 18797 | 7995_36 | Subfeed Current Crest Factor Ph A (Subfeed 36) | Read | ||
| AV | 18798 | 7996_36 | Subfeed Current Crest Factor Ph B (Subfeed 36) | Read | ||
| AV | 18799 | 7997_36 | Subfeed Current Crest Factor Ph C (Subfeed 36) | Read | ||
| AV | 18800 | 7998_36 | Subfeed iTHD Ph A (Subfeed 36) | % | Read | |
| AV | 18801 | 7999_36 | Subfeed iTHD Ph B (Subfeed 36) | % | Read | |
| AV | 18802 | 8000_36 | Subfeed iTHD Ph C (Subfeed 36) | % | Read | |
| AV | 18803 | 8001_36 | Subfeed Current 3rd Harmonic Ph A (Subfeed 36) | % | Read | |
| AV | 18804 | 8002_36 | Subfeed Current 3rd Harmonic Ph B (Subfeed 36) | % | Read | |
| AV | 18805 | 8003_36 | Subfeed Current 3rd Harmonic Ph C (Subfeed 36) | % | Read | |
| AV | 18806 | 8004_36 | Subfeed Current 5th Harmonic Ph A (Subfeed 36) | % | Read | |
| AV | 18807 | 8005_36 | Subfeed Current 5th Harmonic Ph B (Subfeed 36) | % | Read | |
| AV | 18808 | 8006_36 | Subfeed Current 5th Harmonic Ph C (Subfeed 36) | % | Read | |
| AV | 18809 | 8007_36 | Subfeed Current 7th Harmonic Ph A (Subfeed 36) | % | Read | |
| AV | 18810 | 8008_36 | Subfeed Current 7th Harmonic Ph B (Subfeed 36) | % | Read | |
| AV | 18811 | 8009_36 | Subfeed Current 7th Harmonic Ph C (Subfeed 36) | % | Read | |
| AV | 18812 | 8010_36 | Subfeed Current 9th Harmonic Ph A (Subfeed 36) | % | Read | |
| AV | 18813 | 8011_36 | Subfeed Current 9th Harmonic Ph B (Subfeed 36) | % | Read | |
| AV | 18814 | 8012_36 | Subfeed Current 9th Harmonic Ph C (Subfeed 36) | % | Read | |
| AV | 18815 | 8013_36 | Subfeed vTHD Ph A (Subfeed 36) | % | Read | |
| AV | 18816 | 8014_36 | Subfeed vTHD Ph B (Subfeed 36) | % | Read | |
| AV | 18817 | 8015_36 | Subfeed vTHD Ph C (Subfeed 36) | % | Read | |
| AV | 18818 | 8016_36 | Subfeed Voltage 3rd Harmonic Ph A (Subfeed 36) | % | Read | |
| AV | 18819 | 8017_36 | Subfeed Voltage 3rd Harmonic Ph B (Subfeed 36) | % | Read | |
| AV | 18820 | 8018_36 | Subfeed Voltage 3rd Harmonic Ph C (Subfeed 36) | % | Read | |
| AV | 18821 | 8019_36 | Subfeed Voltage 5th Harmonic Ph A (Subfeed 36) | % | Read | |
| AV | 18822 | 8020_36 | Subfeed Voltage 5th Harmonic Ph B (Subfeed 36) | % | Read | |
| AV | 18823 | 8021_36 | Subfeed Voltage 5th Harmonic Ph C (Subfeed 36) | % | Read | |
| AV | 18824 | 8022_36 | Subfeed Voltage 7th Harmonic Ph A (Subfeed 36) | % | Read | |
| AV | 18825 | 8023_36 | Subfeed Voltage 7th Harmonic Ph B (Subfeed 36) | % | Read | |
| AV | 18826 | 8024_36 | Subfeed Voltage 7th Harmonic Ph C (Subfeed 36) | % | Read | |
| AV | 18827 | 8025_36 | Subfeed Voltage 9th Harmonic Ph A (Subfeed 36) | % | Read | |
| AV | 18828 | 8026_36 | Subfeed Voltage 9th Harmonic Ph B (Subfeed 36) | % | Read | |
| AV | 18829 | 8027_36 | Subfeed Voltage 9th Harmonic Ph C (Subfeed 36) | % | Read | |
| AV | 18830 | 8035_36 | Subfeed Phase Overcurrent Warning Threshold (Subfeed 36) | % | Read | |
| AV | 18831 | 8036_36 | Subfeed Phase Overcurrent Alarm Threshold (Subfeed 36) | % | Read | |
| AV | 18832 | 8037_36 | Subfeed Neutral Overcurrent Threshold (Subfeed 36) | Read | ||
| AV | 18833 | 8038_36 | Subfeed Ground Overcurrent Alarm Threshold (Subfeed 36) | A | Read | |
| AV | 18834 | 8280_36 | Subfeed Neutral Overcurrent Warning Threshold (Subfeed 36) | % | Read | |
| AV | 18835 | 8270_36 | Subfeed Phase Overvoltage Alarm Threshold (Subfeed 36) | % | Read | |
| AV | 18836 | 8271_36 | Subfeed Phase Undervoltage Alarm Threshold (Subfeed 36) | % | Read | |
| MV | 1 | 4553_1 | Server Class | Read | 1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR | |
| MVmin | 12 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation | |
| MV | 13 | 7059_1 | Restart Procedure | Read | 1=Auto, 2=Manual | |
| MV | 14 | 7060_1 | Overtemperature Shutdown | Read | 1=disabled, 2=enabled | |
| MVmin | 15 | 7582_1 | System-wide Event Acknowledge/Reset | Write | 1=Reset, 2=Acknowledge | |
| MV | 16 | 7583_1 | System-wide Energy Reset | Write | 1=Reset | |
| MV | 17 | 7584_1 | System-wide Peak Current Reset | Write | 1=Reset | |
| MV | 18 | 7585_1 | System-wide Peak Demand Reset | Write | 1=Reset | |
| MV | 19 | 7566_1 | Main Input Breaker 1 Status | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 20 | 7567_1 | Main Input Breaker 2 Status | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 29 | 7696_1 | Metering Configuration | Read | 1=Master Side, 2=Slave Side | |
| MV | 30 | 7721_1 | Energy Reset | Write | 1=Reset | |
| MV | 31 | 7722_1 | Peak Current Reset | Write | 1=Reset | |
| MV | 32 | 7723_1 | Peak Demand Reset | Write | 1=Reset | |
| MV | 43 | 7725_1 | Panelboard Status (Branch PB 1) | Read | 1=Normal, 2=Abnormal | |
| MV | 44 | 7791_1 | Panelboard Main Breaker Status (Branch PB 1) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 45 | 7804_1 | Panelboard Energy Reset (Branch PB 1) | Write | 1=Reset | |
| MV | 46 | 7805_1 | Panelboard Peak Current Reset (Branch PB 1) | Write | 1=Reset | |
| MV | 47 | 7806_1 | Panelboard Peak Demand Reset (Branch PB 1) | Write | 1=Reset | |
| MV | 58 | 7828_1_1 | Branch Energy Reset (Branch PB 1 Branch 1) | Write | 1=Reset | |
| MV | 59 | 7829_1_1 | Branch Peak Current Reset (Branch PB 1 Branch 1) | Write | 1=Reset | |
| MV | 60 | 7830_1_1 | Branch Peak Demand Reset (Branch PB 1 Branch 1) | Write | 1=Reset | |
| MV | 71 | 7828_1_2 | Branch Energy Reset (Branch PB 1 Branch 2) | Write | 1=Reset | |
| MV | 72 | 7829_1_2 | Branch Peak Current Reset (Branch PB 1 Branch 2) | Write | 1=Reset | |
| MV | 73 | 7830_1_2 | Branch Peak Demand Reset (Branch PB 1 Branch 2) | Write | 1=Reset | |
| MV | 591 | 7828_1_42 | Branch Energy Reset (Branch PB 1 Branch 42) | Write | 1=Reset | |
| MV | 592 | 7829_1_42 | Branch Peak Current Reset (Branch PB 1 Branch 42) | Write | 1=Reset | |
| MV | 593 | 7830_1_42 | Branch Peak Demand Reset (Branch PB 1 Branch 42) | Write | 1=Reset | |
| MV | 604 | 7725_2 | Panelboard Status (Branch PB 2) | Read | 1=Normal, 2=Abnormal | |
| MV | 605 | 7791_2 | Panelboard Main Breaker Status (Branch PB 2) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 606 | 7804_2 | Panelboard Energy Reset (Branch PB 2) | Write | 1=Reset | |
| MV | 607 | 7805_2 | Panelboard Peak Current Reset (Branch PB 2) | Write | 1=Reset | |
| MV | 608 | 7806_2 | Panelboard Peak Demand Reset (Branch PB 2) | Write | 1=Reset | |
| MV | 619 | 7828_2_1 | Branch Energy Reset (Branch PB 2 Branch 1) | Write | 1=Reset | |
| MV | 620 | 7829_2_1 | Branch Peak Current Reset (Branch PB 2 Branch 1) | Write | 1=Reset | |
| MV | 621 | 7830_2_1 | Branch Peak Demand Reset (Branch PB 2 Branch 1) | Write | 1=Reset | |
| MV | 632 | 7828_2_2 | Branch Energy Reset (Branch PB 2 Branch 2) | Write | 1=Reset | |
| MV | 633 | 7829_2_2 | Branch Peak Current Reset (Branch PB 2 Branch 2) | Write | 1=Reset | |
| MV | 634 | 7830_2_2 | Branch Peak Demand Reset (Branch PB 2 Branch 2) | Write | 1=Reset | |
| MV | 1152 | 7828_2_42 | Branch Energy Reset (Branch PB 2 Branch 42) | Write | 1=Reset | |
| MV | 1153 | 7829_2_42 | Branch Peak Current Reset (Branch PB 2 Branch 42) | Write | 1=Reset | |
| MV | 1154 | 7830_2_42 | Branch Peak Demand Reset (Branch PB 2 Branch 42) | Write | 1=Reset | |
| MV | 6214 | 7725_12 | Panelboard Status (Branch PB 12) | Read | 1=Normal, 2=Abnormal | |
| MV | 6215 | 7791_12 | Panelboard Main Breaker Status (Branch PB 12) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 6216 | 7804_12 | Panelboard Energy Reset (Branch PB 12) | Write | 1=Reset | |
| MV | 6217 | 7805_12 | Panelboard Peak Current Reset (Branch PB 12) | Write | 1=Reset | |
| MV | 6218 | 7806_12 | Panelboard Peak Demand Reset (Branch PB 12) | Write | 1=Reset | |
| MV | 6229 | 7828_12_1 | Branch Energy Reset (Branch PB 12 Branch 1) | Write | 1=Reset | |
| MV | 6230 | 7829_12_1 | Branch Peak Current Reset (Branch PB 12 Branch 1) | Write | 1=Reset | |
| MV | 6231 | 7830_12_1 | Branch Peak Demand Reset (Branch PB 12 Branch 1) | Write | 1=Reset | |
| MV | 6242 | 7828_12_2 | Branch Energy Reset (Branch PB 12 Branch 2) | Write | 1=Reset | |
| MV | 6243 | 7829_12_2 | Branch Peak Current Reset (Branch PB 12 Branch 2) | Write | 1=Reset | |
| MV | 6244 | 7830_12_2 | Branch Peak Demand Reset (Branch PB 12 Branch 2) | Write | 1=Reset | |
| MV | 6762 | 7828_12_42 | Branch Energy Reset (Branch PB 12 Branch 42) | Write | 1=Reset | |
| MV | 6763 | 7829_12_42 | Branch Peak Current Reset (Branch PB 12 Branch 42) | Write | 1=Reset | |
| MV | 6764 | 7830_12_42 | Branch Peak Demand Reset (Branch PB 12 Branch 42) | Write | 1=Reset | |
| MV | 6775 | 7832_1 | Panelboard Status (Subfeed PB 1) | Read | 1=Normal, 2=Abnormal | |
| MV | 6776 | 7895_1 | Panelboard Main Breaker Status (Subfeed PB 1) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 6777 | 7908_1 | Panelboard Energy Reset (Subfeed PB 1) | Write | 1=Reset | |
| MV | 6778 | 7909_1 | Panelboard Peak Current Reset (Subfeed PB 1) | Write | 1=Reset | |
| MV | 6779 | 7910_1 | Panelboard Peak Demand Reset (Subfeed PB 1) | Write | 1=Reset | |
| MV | 6790 | 7952_1_1 | Subfeed Main Breaker Status (Subfeed PB 1 Subfeed 1) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 6791 | 7962_1_1 | Subfeed Energy Reset (Subfeed PB 1 Subfeed 1) | Write | 1=Reset | |
| MV | 6792 | 7963_1_1 | Subfeed Peak Current Reset (Subfeed PB 1 Subfeed 1) | Write | 1=Reset | |
| MV | 6793 | 7964_1_1 | Subfeed Peak Demand Reset (Subfeed PB 1 Subfeed 1) | Write | 1=Reset | |
| MV | 6804 | 7952_1_2 | Subfeed Main Breaker Status (Subfeed PB 1 Subfeed 2) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 6805 | 7962_1_2 | Subfeed Energy Reset (Subfeed PB 1 Subfeed 2) | Write | 1=Reset | |
| MV | 6806 | 7963_1_2 | Subfeed Peak Current Reset (Subfeed PB 1 Subfeed 2) | Write | 1=Reset | |
| MV | 6807 | 7964_1_2 | Subfeed Peak Demand Reset (Subfeed PB 1 Subfeed 2) | Write | 1=Reset | |
| MV | 6944 | 7952_1_12 | Subfeed Main Breaker Status (Subfeed PB 1 Subfeed 12) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 6945 | 7962_1_12 | Subfeed Energy Reset (Subfeed PB 1 Subfeed 12) | Write | 1=Reset | |
| MV | 6946 | 7963_1_12 | Subfeed Peak Current Reset (Subfeed PB 1 Subfeed 12) | Write | 1=Reset | |
| MV | 6947 | 7964_1_12 | Subfeed Peak Demand Reset (Subfeed PB 1 Subfeed 12) | Write | 1=Reset | |
| MV | 6958 | 7832_2 | Panelboard Status (Subfeed PB 2) | Read | 1=Normal, 2=Abnormal | |
| MV | 6959 | 7895_2 | Panelboard Main Breaker Status (Subfeed PB 2) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 6960 | 7908_2 | Panelboard Energy Reset (Subfeed PB 2) | Write | 1=Reset | |
| MV | 6961 | 7909_2 | Panelboard Peak Current Reset (Subfeed PB 2) | Write | 1=Reset | |
| MV | 6962 | 7910_2 | Panelboard Peak Demand Reset (Subfeed PB 2) | Write | 1=Reset | |
| MV | 6973 | 7952_2_1 | Subfeed Main Breaker Status (Subfeed PB 2 Subfeed 1) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 6974 | 7962_2_1 | Subfeed Energy Reset (Subfeed PB 2 Subfeed 1) | Write | 1=Reset | |
| MV | 6975 | 7963_2_1 | Subfeed Peak Current Reset (Subfeed PB 2 Subfeed 1) | Write | 1=Reset | |
| MV | 6976 | 7964_2_1 | Subfeed Peak Demand Reset (Subfeed PB 2 Subfeed 1) | Write | 1=Reset | |
| MV | 6987 | 7952_2_2 | Subfeed Main Breaker Status (Subfeed PB 2 Subfeed 2) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 6988 | 7962_2_2 | Subfeed Energy Reset (Subfeed PB 2 Subfeed 2) | Write | 1=Reset | |
| MV | 6989 | 7963_2_2 | Subfeed Peak Current Reset (Subfeed PB 2 Subfeed 2) | Write | 1=Reset | |
| MV | 6990 | 7964_2_2 | Subfeed Peak Demand Reset (Subfeed PB 2 Subfeed 2) | Write | 1=Reset | |
| MV | 7127 | 7952_2_12 | Subfeed Main Breaker Status (Subfeed PB 2 Subfeed 12) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 7128 | 7962_2_12 | Subfeed Energy Reset (Subfeed PB 2 Subfeed 12) | Write | 1=Reset | |
| MV | 7129 | 7963_2_12 | Subfeed Peak Current Reset (Subfeed PB 2 Subfeed 12) | Write | 1=Reset | |
| MV | 7130 | 7964_2_12 | Subfeed Peak Demand Reset (Subfeed PB 2 Subfeed 12) | Write | 1=Reset | |
| MV | 7141 | 8028_1 | Subfeed Breaker Status (Subfeed 1) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 7142 | 8041_1 | Subfeed Energy Reset (Subfeed 1) | Write | 1=Reset | |
| MV | 7143 | 8042_1 | Subfeed Peak Current Reset (Subfeed 1) | Write | 1=Reset | |
| MV | 7144 | 8043_1 | Subfeed Peak Demand Reset (Subfeed 1) | Write | 1=Reset | |
| MV | 7155 | 8028_2 | Subfeed Breaker Status (Subfeed 2) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 7156 | 8041_2 | Subfeed Energy Reset (Subfeed 2) | Write | 1=Reset | |
| MV | 7157 | 8042_2 | Subfeed Peak Current Reset (Subfeed 2) | Write | 1=Reset | |
| MV | 7158 | 8043_2 | Subfeed Peak Demand Reset (Subfeed 2) | Write | 1=Reset | |
| MV | 7631 | 8028_36 | Subfeed Breaker Status (Subfeed 36) | Read | 1=Unknown, 2=Open, 3=Closed | |
| MV | 7632 | 8041_36 | Subfeed Energy Reset (Subfeed 36) | Write | 1=Reset | |
| MV | 7633 | 8042_36 | Subfeed Peak Current Reset (Subfeed 36) | Write | 1=Reset | |
| MV | 7634 | 8043_36 | Subfeed Peak Demand Reset (Subfeed 36) | Write | 1=Reset |
No points match these filters.
Object ID lookup: Vertiv Liebert RXA / TFX power panel point IDs by name
BV17570_1BV27571_1BV37572_1BV47573_1BV57574_1BV67575_1BV77576_1BV87577_1BV97578_1BV107579_1BV117580_1BV127581_1BV237588_1BV247589_1BV257590_1BV267591_1BV278119_1BV387588_2BV397589_2BV407590_2BV417591_2BV428119_2BV9687588_64BV9697589_64BV9707590_64BV9717591_64BV9728119_64BV9837697_1BV9847698_1BV9857699_1BV9867700_1BV9877701_1BV9887702_1BV9897704_1BV9907705_1BV9917706_1BV9927707_1BV9937708_1BV9947709_1BV9957710_1BV9967711_1BV9977712_1BV9987713_1BV9997714_1BV10007715_1BV10117792_1BV10127793_1BV10137794_1BV10147795_1BV10157796_1BV10168253_1BV10178254_1BV10188255_1BV10198435_1BV10267822_1_1BV10277823_1_1BV10288259_1_1BV10298436_1_1BV10387822_1_2BV10397823_1_2BV10408259_1_2BV10418436_1_2BV15187822_1_42BV15197823_1_42BV15208259_1_42BV15218436_1_42BV15307792_2BV15317793_2BV15327794_2BV15337795_2BV15347796_2BV15358253_2BV15368254_2BV15378255_2BV15388435_2BV15457822_2_1BV15467823_2_1BV15478259_2_1BV15488436_2_1BV15577822_2_2BV15587823_2_2BV15598259_2_2BV15608436_2_2BV20377822_2_42BV20387823_2_42BV20398259_2_42BV20408436_2_42BV67207792_12BV67217793_12BV67227794_12BV67237795_12BV67247796_12BV67258253_12BV67268254_12BV67278255_12BV67288435_12BV67357822_12_1BV67367823_12_1BV67378259_12_1BV67388436_12_1BV67477822_12_2BV67487823_12_2BV67498259_12_2BV67508436_12_2BV72277822_12_42BV72287823_12_42BV72298259_12_42BV72308436_12_42BV72397896_1BV72407897_1BV72417898_1BV72427899_1BV72437900_1BV72448262_1BV72458263_1BV72468264_1BV72547953_1_1BV72557954_1_1BV72567955_1_1BV72577956_1_1BV72587957_1_1BV72697953_1_2BV72707954_1_2BV72717955_1_2BV72727956_1_2BV72737957_1_2BV74197953_1_12BV74207954_1_12BV74217955_1_12BV74227956_1_12BV74237957_1_12BV74347896_2BV74357897_2BV74367898_2BV74377899_2BV74387900_2BV74398262_2BV74408263_2BV74418264_2BV74497953_2_1BV74507954_2_1BV74517955_2_1BV74527956_2_1BV74537957_2_1BV74647953_2_2BV74657954_2_2BV74667955_2_2BV74677956_2_2BV74687957_2_2BV76147953_2_12BV76157954_2_12BV76167955_2_12BV76177956_2_12BV76187957_2_12BV76298029_1BV76308030_1BV76318031_1BV76328032_1BV76338033_1BV76348267_1BV76358268_1BV76368269_1BV76448029_2BV76458030_2BV76468031_2BV76478032_2BV76488033_2BV76498267_2BV76508268_2BV76518269_2BV81548029_36BV81558030_36BV81568031_36BV81578032_36BV81588033_36BV81598267_36BV81608268_36BV81618269_36BV81698045_1BV81808045_2BV81918047_1BV82028047_2BV82688047_8AV14293_1AV148123_1AV157592_1AV167593_1AV177594_1AV188124_1AV197595_1AV207596_1AV217597_1AV227598_1AV237599_1AV247600_1AV257601_1AV267602_1AV277603_1AV287604_1AV297605_1AV307606_1AV317607_1AV327608_1AV337609_1AV347610_1AV357611_1AV367612_1AV377613_1AV387614_1AV397615_1AV407616_1AV417617_1AV427618_1AV437619_1AV447620_1AV457621_1AV467622_1AV477623_1AV487624_1AV497625_1AV507626_1AV517627_1AV527628_1AV537629_1AV547630_1AV557631_1AV567632_1AV577633_1AV587634_1AV597635_1AV607636_1AV617637_1AV627638_1AV637639_1AV647640_1AV657641_1AV667642_1AV677643_1AV687644_1AV697645_1AV707646_1AV717647_1AV727648_1AV737649_1AV747650_1AV757651_1AV767652_1AV777653_1AV787654_1AV797655_1AV807656_1AV817657_1AV827658_1AV837659_1AV847660_1AV857661_1AV867662_1AV877663_1AV887664_1AV897665_1AV907666_1AV917667_1AV927668_1AV937669_1AV947670_1AV957671_1AV967672_1AV977673_1AV987674_1AV997675_1AV1007676_1AV1017677_1AV1027678_1AV1037679_1AV1047680_1AV1057681_1AV1067682_1AV1077683_1AV1087684_1AV1097685_1AV1107686_1AV1117687_1AV1127688_1AV1137689_1AV1147690_1AV1157691_1AV1167692_1AV1177693_1AV1187694_1AV1197716_1AV1207717_1AV1217718_1AV1227719_1AV1238084_1AV1248085_1AV1258086_1AV1268087_1AV1278088_1AV1288089_1AV1297720_1AV1308276_1AV1407727_1AV1417728_1AV1427729_1AV1437730_1AV1447731_1AV1457732_1AV1467733_1AV1477734_1AV1487735_1AV1497736_1AV1507737_1AV1517738_1AV1527739_1AV1537740_1AV1547741_1AV1557742_1AV1567743_1AV1577744_1AV1587745_1AV1597746_1AV1607747_1AV1617748_1AV1627749_1AV1637750_1AV1647751_1AV1657752_1AV1667753_1AV1677754_1AV1687755_1AV1697756_1AV1707757_1AV1717758_1AV1727759_1AV1737760_1AV1747761_1AV1757762_1AV1767763_1AV1777764_1AV1787765_1AV1797766_1AV1807767_1AV1817768_1AV1827769_1AV1837770_1AV1847771_1AV1857772_1AV1867773_1AV1877774_1AV1887775_1AV1897776_1AV1907777_1AV1917778_1AV1927779_1AV1937780_1AV1947781_1AV1957782_1AV1967783_1AV1977784_1AV1987785_1AV1997786_1AV2007787_1AV2017788_1AV2027789_1AV2037790_1AV2047798_1AV2057799_1AV2067800_1AV2077801_1AV2088277_1AV2098256_1AV2108257_1AV2187808_1_1AV2197809_1_1AV2207810_1_1AV2217811_1_1AV2227812_1_1AV2237813_1_1AV2247814_1_1AV2257815_1_1AV2267816_1_1AV2277817_1_1AV2287818_1_1AV2297819_1_1AV2307820_1_1AV2317821_1_1AV2327825_1_1AV2337826_1_1AV2347827_1_1AV2358258_1_1AV2368260_1_1AV2378261_1_1AV2388437_1_1AV2457808_1_2AV2467809_1_2AV2477810_1_2AV2487811_1_2AV2497812_1_2AV2507813_1_2AV2517814_1_2AV2527815_1_2AV2537816_1_2AV2547817_1_2AV2557818_1_2AV2567819_1_2AV2577820_1_2AV2587821_1_2AV2597825_1_2AV2607826_1_2AV2617827_1_2AV2628258_1_2AV2638260_1_2AV2648261_1_2AV2658437_1_2AV13257808_1_42AV13267809_1_42AV13277810_1_42AV13287811_1_42AV13297812_1_42AV13307813_1_42AV13317814_1_42AV13327815_1_42AV13337816_1_42AV13347817_1_42AV13357818_1_42AV13367819_1_42AV13377820_1_42AV13387821_1_42AV13397825_1_42AV13407826_1_42AV13417827_1_42AV13428258_1_42AV13438260_1_42AV13448261_1_42AV13458437_1_42AV13527727_2AV13537728_2AV13547729_2AV13557730_2AV13567731_2AV13577732_2AV13587733_2AV13597734_2AV13607735_2AV13617736_2AV13627737_2AV13637738_2AV13647739_2AV13657740_2AV13667741_2AV13677742_2AV13687743_2AV13697744_2AV13707745_2AV13717746_2AV13727747_2AV13737748_2AV13747749_2AV13757750_2AV13767751_2AV13777752_2AV13787753_2AV13797754_2AV13807755_2AV13817756_2AV13827757_2AV13837758_2AV13847759_2AV13857760_2AV13867761_2AV13877762_2AV13887763_2AV13897764_2AV13907765_2AV13917766_2AV13927767_2AV13937768_2AV13947769_2AV13957770_2AV13967771_2AV13977772_2AV13987773_2AV13997774_2AV14007775_2AV14017776_2AV14027777_2AV14037778_2AV14047779_2AV14057780_2AV14067781_2AV14077782_2AV14087783_2AV14097784_2AV14107785_2AV14117786_2AV14127787_2AV14137788_2AV14147789_2AV14157790_2AV14167798_2AV14177799_2AV14187800_2AV14197801_2AV14208277_2AV14218256_2AV14228257_2AV14307808_2_1AV14317809_2_1AV14327810_2_1AV14337811_2_1AV14347812_2_1AV14357813_2_1AV14367814_2_1AV14377815_2_1AV14387816_2_1AV14397817_2_1AV14407818_2_1AV14417819_2_1AV14427820_2_1AV14437821_2_1AV14447825_2_1AV14457826_2_1AV14467827_2_1AV14478258_2_1AV14488260_2_1AV14498261_2_1AV14508437_2_1AV14577808_2_2AV14587809_2_2AV14597810_2_2AV14607811_2_2AV14617812_2_2AV14627813_2_2AV14637814_2_2AV14647815_2_2AV14657816_2_2AV14667817_2_2AV14677818_2_2AV14687819_2_2AV14697820_2_2AV14707821_2_2AV14717825_2_2AV14727826_2_2AV14737827_2_2AV14748258_2_2AV14758260_2_2AV14768261_2_2AV14778437_2_2AV25377808_2_42AV25387809_2_42AV25397810_2_42AV25407811_2_42AV25417812_2_42AV25427813_2_42AV25437814_2_42AV25447815_2_42AV25457816_2_42AV25467817_2_42AV25477818_2_42AV25487819_2_42AV25497820_2_42AV25507821_2_42AV25517825_2_42AV25527826_2_42AV25537827_2_42AV25548258_2_42AV25558260_2_42AV25568261_2_42AV25578437_2_42AV134727727_12AV134737728_12AV134747729_12AV134757730_12AV134767731_12AV134777732_12AV134787733_12AV134797734_12AV134807735_12AV134817736_12AV134827737_12AV134837738_12AV134847739_12AV134857740_12AV134867741_12AV134877742_12AV134887743_12AV134897744_12AV134907745_12AV134917746_12AV134927747_12AV134937748_12AV134947749_12AV134957750_12AV134967751_12AV134977752_12AV134987753_12AV134997754_12AV135007755_12AV135017756_12AV135027757_12AV135037758_12AV135047759_12AV135057760_12AV135067761_12AV135077762_12AV135087763_12AV135097764_12AV135107765_12AV135117766_12AV135127767_12AV135137768_12AV135147769_12AV135157770_12AV135167771_12AV135177772_12AV135187773_12AV135197774_12AV135207775_12AV135217776_12AV135227777_12AV135237778_12AV135247779_12AV135257780_12AV135267781_12AV135277782_12AV135287783_12AV135297784_12AV135307785_12AV135317786_12AV135327787_12AV135337788_12AV135347789_12AV135357790_12AV135367798_12AV135377799_12AV135387800_12AV135397801_12AV135408277_12AV135418256_12AV135428257_12AV135507808_12_1AV135517809_12_1AV135527810_12_1AV135537811_12_1AV135547812_12_1AV135557813_12_1AV135567814_12_1AV135577815_12_1AV135587816_12_1AV135597817_12_1AV135607818_12_1AV135617819_12_1AV135627820_12_1AV135637821_12_1AV135647825_12_1AV135657826_12_1AV135667827_12_1AV135678258_12_1AV135688260_12_1AV135698261_12_1AV135708437_12_1AV135777808_12_2AV135787809_12_2AV135797810_12_2AV135807811_12_2AV135817812_12_2AV135827813_12_2AV135837814_12_2AV135847815_12_2AV135857816_12_2AV135867817_12_2AV135877818_12_2AV135887819_12_2AV135897820_12_2AV135907821_12_2AV135917825_12_2AV135927826_12_2AV135937827_12_2AV135948258_12_2AV135958260_12_2AV135968261_12_2AV135978437_12_2AV146577808_12_42AV146587809_12_42AV146597810_12_42AV146607811_12_42AV146617812_12_42AV146627813_12_42AV146637814_12_42AV146647815_12_42AV146657816_12_42AV146667817_12_42AV146677818_12_42AV146687819_12_42AV146697820_12_42AV146707821_12_42AV146717825_12_42AV146727826_12_42AV146737827_12_42AV146748258_12_42AV146758260_12_42AV146768261_12_42AV146778437_12_42AV146847833_1AV146857834_1AV146867835_1AV146877836_1AV146887837_1AV146897838_1AV146907839_1AV146917840_1AV146927841_1AV146937842_1AV146947843_1AV146957844_1AV146967845_1AV146977846_1AV146987847_1AV146997848_1AV147007849_1AV147017850_1AV147027851_1AV147037852_1AV147047853_1AV147057854_1AV147067855_1AV147077856_1AV147087857_1AV147097858_1AV147107859_1AV147117860_1AV147127861_1AV147137862_1AV147147863_1AV147157864_1AV147167865_1AV147177866_1AV147187867_1AV147197868_1AV147207869_1AV147217870_1AV147227871_1AV147237872_1AV147247873_1AV147257874_1AV147267875_1AV147277876_1AV147287877_1AV147297878_1AV147307879_1AV147317880_1AV147327881_1AV147337882_1AV147347883_1AV147357884_1AV147367885_1AV147377886_1AV147387887_1AV147397888_1AV147407889_1AV147417890_1AV147427891_1AV147437892_1AV147447893_1AV147457894_1AV147467902_1AV147477903_1AV147487904_1AV147497905_1AV147508278_1AV147518265_1AV147528266_1AV147607912_1_1AV147617913_1_1AV147627914_1_1AV147637915_1_1AV147647916_1_1AV147657917_1_1AV147667918_1_1AV147677919_1_1AV147687920_1_1AV147697921_1_1AV147707922_1_1AV147717923_1_1AV147727924_1_1AV147737925_1_1AV147747926_1_1AV147757927_1_1AV147767928_1_1AV147777929_1_1AV147787930_1_1AV147797931_1_1AV147807932_1_1AV147817933_1_1AV147827934_1_1AV147837935_1_1AV147847936_1_1AV147857937_1_1AV147867938_1_1AV147877939_1_1AV147887940_1_1AV147897941_1_1AV147907942_1_1AV147917943_1_1AV147927944_1_1AV147937945_1_1AV147947946_1_1AV147957947_1_1AV147967948_1_1AV147977949_1_1AV147987950_1_1AV147997951_1_1AV148007959_1_1AV148017960_1_1AV148027961_1_1AV148038279_1_1AV148137912_1_2AV148147913_1_2AV148157914_1_2AV148167915_1_2AV148177916_1_2AV148187917_1_2AV148197918_1_2AV148207919_1_2AV148217920_1_2AV148227921_1_2AV148237922_1_2AV148247923_1_2AV148257924_1_2AV148267925_1_2AV148277926_1_2AV148287927_1_2AV148297928_1_2AV148307929_1_2AV148317930_1_2AV148327931_1_2AV148337932_1_2AV148347933_1_2AV148357934_1_2AV148367935_1_2AV148377936_1_2AV148387937_1_2AV148397938_1_2AV148407939_1_2AV148417940_1_2AV148427941_1_2AV148437942_1_2AV148447943_1_2AV148457944_1_2AV148467945_1_2AV148477946_1_2AV148487947_1_2AV148497948_1_2AV148507949_1_2AV148517950_1_2AV148527951_1_2AV148537959_1_2AV148547960_1_2AV148557961_1_2AV148568279_1_2AV153437912_1_12AV153447913_1_12AV153457914_1_12AV153467915_1_12AV153477916_1_12AV153487917_1_12AV153497918_1_12AV153507919_1_12AV153517920_1_12AV153527921_1_12AV153537922_1_12AV153547923_1_12AV153557924_1_12AV153567925_1_12AV153577926_1_12AV153587927_1_12AV153597928_1_12AV153607929_1_12AV153617930_1_12AV153627931_1_12AV153637932_1_12AV153647933_1_12AV153657934_1_12AV153667935_1_12AV153677936_1_12AV153687937_1_12AV153697938_1_12AV153707939_1_12AV153717940_1_12AV153727941_1_12AV153737942_1_12AV153747943_1_12AV153757944_1_12AV153767945_1_12AV153777946_1_12AV153787947_1_12AV153797948_1_12AV153807949_1_12AV153817950_1_12AV153827951_1_12AV153837959_1_12AV153847960_1_12AV153857961_1_12AV153868279_1_12AV153967833_2AV153977834_2AV153987835_2AV153997836_2AV154007837_2AV154017838_2AV154027839_2AV154037840_2AV154047841_2AV154057842_2AV154067843_2AV154077844_2AV154087845_2AV154097846_2AV154107847_2AV154117848_2AV154127849_2AV154137850_2AV154147851_2AV154157852_2AV154167853_2AV154177854_2AV154187855_2AV154197856_2AV154207857_2AV154217858_2AV154227859_2AV154237860_2AV154247861_2AV154257862_2AV154267863_2AV154277864_2AV154287865_2AV154297866_2AV154307867_2AV154317868_2AV154327869_2AV154337870_2AV154347871_2AV154357872_2AV154367873_2AV154377874_2AV154387875_2AV154397876_2AV154407877_2AV154417878_2AV154427879_2AV154437880_2AV154447881_2AV154457882_2AV154467883_2AV154477884_2AV154487885_2AV154497886_2AV154507887_2AV154517888_2AV154527889_2AV154537890_2AV154547891_2AV154557892_2AV154567893_2AV154577894_2AV154587902_2AV154597903_2AV154607904_2AV154617905_2AV154628278_2AV154638265_2AV154648266_2AV154727912_2_1AV154737913_2_1AV154747914_2_1AV154757915_2_1AV154767916_2_1AV154777917_2_1AV154787918_2_1AV154797919_2_1AV154807920_2_1AV154817921_2_1AV154827922_2_1AV154837923_2_1AV154847924_2_1AV154857925_2_1AV154867926_2_1AV154877927_2_1AV154887928_2_1AV154897929_2_1AV154907930_2_1AV154917931_2_1AV154927932_2_1AV154937933_2_1AV154947934_2_1AV154957935_2_1AV154967936_2_1AV154977937_2_1AV154987938_2_1AV154997939_2_1AV155007940_2_1AV155017941_2_1AV155027942_2_1AV155037943_2_1AV155047944_2_1AV155057945_2_1AV155067946_2_1AV155077947_2_1AV155087948_2_1AV155097949_2_1AV155107950_2_1AV155117951_2_1AV155127959_2_1AV155137960_2_1AV155147961_2_1AV155158279_2_1AV155257912_2_2AV155267913_2_2AV155277914_2_2AV155287915_2_2AV155297916_2_2AV155307917_2_2AV155317918_2_2AV155327919_2_2AV155337920_2_2AV155347921_2_2AV155357922_2_2AV155367923_2_2AV155377924_2_2AV155387925_2_2AV155397926_2_2AV155407927_2_2AV155417928_2_2AV155427929_2_2AV155437930_2_2AV155447931_2_2AV155457932_2_2AV155467933_2_2AV155477934_2_2AV155487935_2_2AV155497936_2_2AV155507937_2_2AV155517938_2_2AV155527939_2_2AV155537940_2_2AV155547941_2_2AV155557942_2_2AV155567943_2_2AV155577944_2_2AV155587945_2_2AV155597946_2_2AV155607947_2_2AV155617948_2_2AV155627949_2_2AV155637950_2_2AV155647951_2_2AV155657959_2_2AV155667960_2_2AV155677961_2_2AV155688279_2_2AV160557912_2_12AV160567913_2_12AV160577914_2_12AV160587915_2_12AV160597916_2_12AV160607917_2_12AV160617918_2_12AV160627919_2_12AV160637920_2_12AV160647921_2_12AV160657922_2_12AV160667923_2_12AV160677924_2_12AV160687925_2_12AV160697926_2_12AV160707927_2_12AV160717928_2_12AV160727929_2_12AV160737930_2_12AV160747931_2_12AV160757932_2_12AV160767933_2_12AV160777934_2_12AV160787935_2_12AV160797936_2_12AV160807937_2_12AV160817938_2_12AV160827939_2_12AV160837940_2_12AV160847941_2_12AV160857942_2_12AV160867943_2_12AV160877944_2_12AV160887945_2_12AV160897946_2_12AV160907947_2_12AV160917948_2_12AV160927949_2_12AV160937950_2_12AV160947951_2_12AV160957959_2_12AV160967960_2_12AV160977961_2_12AV160988279_2_12AV161087966_1AV161097967_1AV161107968_1AV161117969_1AV161127970_1AV161137971_1AV161147972_1AV161157973_1AV161167974_1AV161177975_1AV161187976_1AV161197977_1AV161207978_1AV161217979_1AV161227980_1AV161237981_1AV161247982_1AV161257983_1AV161267984_1AV161277985_1AV161287986_1AV161297987_1AV161307988_1AV161317989_1AV161327990_1AV161337991_1AV161347992_1AV161357993_1AV161367994_1AV161377995_1AV161387996_1AV161397997_1AV161407998_1AV161417999_1AV161428000_1AV161438001_1AV161448002_1AV161458003_1AV161468004_1AV161478005_1AV161488006_1AV161498007_1AV161508008_1AV161518009_1AV161528010_1AV161538011_1AV161548012_1AV161558013_1AV161568014_1AV161578015_1AV161588016_1AV161598017_1AV161608018_1AV161618019_1AV161628020_1AV161638021_1AV161648022_1AV161658023_1AV161668024_1AV161678025_1AV161688026_1AV161698027_1AV161708035_1AV161718036_1AV161728037_1AV161738038_1AV161748280_1AV161758270_1AV161768271_1AV161847966_2AV161857967_2AV161867968_2AV161877969_2AV161887970_2AV161897971_2AV161907972_2AV161917973_2AV161927974_2AV161937975_2AV161947976_2AV161957977_2AV161967978_2AV161977979_2AV161987980_2AV161997981_2AV162007982_2AV162017983_2AV162027984_2AV162037985_2AV162047986_2AV162057987_2AV162067988_2AV162077989_2AV162087990_2AV162097991_2AV162107992_2AV162117993_2AV162127994_2AV162137995_2AV162147996_2AV162157997_2AV162167998_2AV162177999_2AV162188000_2AV162198001_2AV162208002_2AV162218003_2AV162228004_2AV162238005_2AV162248006_2AV162258007_2AV162268008_2AV162278009_2AV162288010_2AV162298011_2AV162308012_2AV162318013_2AV162328014_2AV162338015_2AV162348016_2AV162358017_2AV162368018_2AV162378019_2AV162388020_2AV162398021_2AV162408022_2AV162418023_2AV162428024_2AV162438025_2AV162448026_2AV162458027_2AV162468035_2AV162478036_2AV162488037_2AV162498038_2AV162508280_2AV162518270_2AV162528271_2AV187687966_36AV187697967_36AV187707968_36AV187717969_36AV187727970_36AV187737971_36AV187747972_36AV187757973_36AV187767974_36AV187777975_36AV187787976_36AV187797977_36AV187807978_36AV187817979_36AV187827980_36AV187837981_36AV187847982_36AV187857983_36AV187867984_36AV187877985_36AV187887986_36AV187897987_36AV187907988_36AV187917989_36AV187927990_36AV187937991_36AV187947992_36AV187957993_36AV187967994_36AV187977995_36AV187987996_36AV187997997_36AV188007998_36AV188017999_36AV188028000_36AV188038001_36AV188048002_36AV188058003_36AV188068004_36AV188078005_36AV188088006_36AV188098007_36AV188108008_36AV188118009_36AV188128010_36AV188138011_36AV188148012_36AV188158013_36AV188168014_36AV188178015_36AV188188016_36AV188198017_36AV188208018_36AV188218019_36AV188228020_36AV188238021_36AV188248022_36AV188258023_36AV188268024_36AV188278025_36AV188288026_36AV188298027_36AV188308035_36AV188318036_36AV188328037_36AV188338038_36AV188348280_36AV188358270_36AV188368271_36MV14553_1MV124123_1MV137059_1MV147060_1MV157582_1MV167583_1MV177584_1MV187585_1MV197566_1MV207567_1MV297696_1MV307721_1MV317722_1MV327723_1MV437725_1MV447791_1MV457804_1MV467805_1MV477806_1MV587828_1_1MV597829_1_1MV607830_1_1MV717828_1_2MV727829_1_2MV737830_1_2MV5917828_1_42MV5927829_1_42MV5937830_1_42MV6047725_2MV6057791_2MV6067804_2MV6077805_2MV6087806_2MV6197828_2_1MV6207829_2_1MV6217830_2_1MV6327828_2_2MV6337829_2_2MV6347830_2_2MV11527828_2_42MV11537829_2_42MV11547830_2_42MV62147725_12MV62157791_12MV62167804_12MV62177805_12MV62187806_12MV62297828_12_1MV62307829_12_1MV62317830_12_1MV62427828_12_2MV62437829_12_2MV62447830_12_2MV67627828_12_42MV67637829_12_42MV67647830_12_42MV67757832_1MV67767895_1MV67777908_1MV67787909_1MV67797910_1MV67907952_1_1MV67917962_1_1MV67927963_1_1MV67937964_1_1MV68047952_1_2MV68057962_1_2MV68067963_1_2MV68077964_1_2MV69447952_1_12MV69457962_1_12MV69467963_1_12MV69477964_1_12MV69587832_2MV69597895_2MV69607908_2MV69617909_2MV69627910_2MV69737952_2_1MV69747962_2_1MV69757963_2_1MV69767964_2_1MV69877952_2_2MV69887962_2_2MV69897963_2_2MV69907964_2_2MV71277952_2_12MV71287962_2_12MV71297963_2_12MV71307964_2_12MV71418028_1MV71428041_1MV71438042_1MV71448043_1MV71558028_2MV71568041_2MV71578042_2MV71588043_2MV76318028_36MV76328041_36MV76338042_36MV76348043_36
Integration notes
- Tables 5.102, 5.103, 5.104, pdf pages 1811-1860 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert RXA / TFX power panel and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert RXA / TFX power panel
How many BACnet points does the Vertiv Liebert RXA / TFX power panel have?
This list has 1414 BACnet objects: 1129 analog values, 183 binary values, 102 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert RXA / TFX power panel BACnet points are writable?
77 of the 1414 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert RXA / TFX power panel BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert RXA / TFX power panel?
Start with MV 15 7582_1 (Acknowledge / reset events); MV 12 4123_1 (Normal, warning or alarm state); AV 25 7601_1 (Output voltage A-B); AV 28 7604_1 (Output voltage A-N); BV 1 7570_1 (Transformer high temperature).
How do I check these points on the real Liebert RXA / TFX power panel?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.