Power distribution panel / transformer monitoring · BACnet points list

Vertiv Liebert RXA / TFX power panel BACnet points list

Updated 6 November 2026

Short answer

The Liebert RXA / TFX power panel reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, output, panel and branch circuit electrical data, Binary Values carry events and Multi-state Values carry status, breaker states and resets. Panel and branch objects repeat per panel and branch, so the list is long.

This page lists 1414 BACnet objects for the Vertiv Liebert RXA / TFX power panel — 77 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert RXA / TFX power panel
Equipment
Power distribution panel / transformer monitoring
Equipment type
Other equipment
BACnet objects
1414 (77 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Liebert RXA, Liebert TFX, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 1414 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert RXA / TFX power panel

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 157582_1Acknowledge / reset eventsWrite
MV 124123_1Normal, warning or alarm stateRead
AV 257601_1Output voltage A-BRead
AV 287604_1Output voltage A-NRead
BV 17570_1Transformer high temperatureRead

Network setup

Watch out for

Vertiv Liebert RXA / TFX power panel BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

1414 of 1414 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert RXA / TFX power panel BACnet Points List
DescriptionStates
BVmin17570_1Transformer High TemperatureReadActive = alarm
BV27571_1Transformer Temperature Sensor FailureReadActive = alarm
BV37572_1Metering Board Communication FailReadActive = alarm
BV47573_1Accessory Board Communication FailReadActive = alarm
BV57574_1System MisconfigurationReadActive = alarm
BV67575_1System Firmware IncompatibilityReadActive = alarm
BV77576_1Main Input Breaker 1 TrippedReadActive = alarm
BV87577_1Main Input Breaker 1 Accessory ErrorReadActive = alarm
BV97578_1Main Input Breaker 1 Open FailReadActive = alarm
BV107579_1Main Input Breaker 2 TrippedReadActive = alarm
BV117580_1Main Input Breaker 2 Accessory ErrorReadActive = alarm
BV127581_1Main Input Breaker 2 Open FailReadActive = alarm
BV237588_1Loss of Communication (System Diagnostic 1)ReadActive = alarm
BV247589_1No Initial Communication (System Diagnostic 1)ReadActive = alarm
BV257590_1Misconfiguration (System Diagnostic 1)ReadActive = alarm
BV267591_1Firmware Incompatibility (System Diagnostic 1)ReadActive = alarm
BV278119_1Communication Bus Error (System Diagnostic 1)ReadActive = alarm
BV387588_2Loss of Communication (System Diagnostic 2)ReadActive = alarm
BV397589_2No Initial Communication (System Diagnostic 2)ReadActive = alarm
BV407590_2Misconfiguration (System Diagnostic 2)ReadActive = alarm
BV417591_2Firmware Incompatibility (System Diagnostic 2)ReadActive = alarm
BV428119_2Communication Bus Error (System Diagnostic 2)ReadActive = alarm
BV9687588_64Loss of Communication (System Diagnostic 64)ReadActive = alarm
BV9697589_64No Initial Communication (System Diagnostic 64)ReadActive = alarm
BV9707590_64Misconfiguration (System Diagnostic 64)ReadActive = alarm
BV9717591_64Firmware Incompatibility (System Diagnostic 64)ReadActive = alarm
BV9728119_64Communication Bus Error (System Diagnostic 64)ReadActive = alarm
BV9837697_1Output OvervoltageReadActive = alarm
BV9847698_1Output UndervoltageReadActive = alarm
BV9857699_1Phase OvercurrentReadActive = alarm
BV9867700_1Neutral OvercurrentReadActive = alarm
BV9877701_1Ground OvercurrentReadActive = alarm
BV9887702_1Output Frequency DeviationReadActive = alarm
BV9897704_1Input 1 OvervoltageReadActive = alarm
BV9907705_1Input 1 UndervoltageReadActive = alarm
BV9917706_1Input 1 Phase LossReadActive = alarm
BV9927707_1Input 1 Invalid Phase RotationReadActive = alarm
BV9937708_1Input 1 Frequency DeviationReadActive = alarm
BV9947709_1Input 1 High Voltage THDReadActive = alarm
BV9957710_1Input 2 OvervoltageReadActive = alarm
BV9967711_1Input 2 UndervoltageReadActive = alarm
BV9977712_1Input 2 Phase LossReadActive = alarm
BV9987713_1Input 2 Invalid Phase RotationReadActive = alarm
BV9997714_1Input 2 Frequency DeviationReadActive = alarm
BV10007715_1Input 2 High Voltage THDReadActive = alarm
BV10117792_1Panelboard Phase Overcurrent (Branch PB 1)ReadActive = alarm
BV10127793_1Panelboard Neutral Overcurrent (Branch PB 1)ReadActive = alarm
BV10137794_1Panelboard Ground Overcurrent (Branch PB 1)ReadActive = alarm
BV10147795_1Panelboard Main Breaker Tripped (Branch PB 1)ReadActive = alarm
BV10157796_1Panelboard Main Breaker Accessory Error (Branch PB 1)ReadActive = alarm
BV10168253_1Panelboard Overvoltage (Branch PB 1)ReadActive = alarm
BV10178254_1Panelboard Undervoltage (Branch PB 1)ReadActive = alarm
BV10188255_1Panelboard Frequency Deviation (Branch PB 1)ReadActive = alarm
BV10198435_1Panelboard Main Breaker Open Fail (Branch PB 1)ReadActive = alarm
BV10267822_1_1Branch Phase Overcurrent (Branch PB 1 Branch 1)ReadActive = alarm
BV10277823_1_1Branch Phase Undercurrent (Branch PB 1 Branch 1)ReadActive = alarm
BV10288259_1_1Branch Neutral Overcurrent (Branch PB 1 Branch 1)ReadActive = alarm
BV10298436_1_1Load Loss Detected (Branch PB 1 Branch 1)ReadActive = alarm
BV10387822_1_2Branch Phase Overcurrent (Branch PB 1 Branch 2)ReadActive = alarm
BV10397823_1_2Branch Phase Undercurrent (Branch PB 1 Branch 2)ReadActive = alarm
BV10408259_1_2Branch Neutral Overcurrent (Branch PB 1 Branch 2)ReadActive = alarm
BV10418436_1_2Load Loss Detected (Branch PB 1 Branch 2)ReadActive = alarm
BV15187822_1_42Branch Phase Overcurrent (Branch PB 1 Branch 42)ReadActive = alarm
BV15197823_1_42Branch Phase Undercurrent (Branch PB 1 Branch 42)ReadActive = alarm
BV15208259_1_42Branch Neutral Overcurrent (Branch PB 1 Branch 42)ReadActive = alarm
BV15218436_1_42Load Loss Detected (Branch PB 1 Branch 42)ReadActive = alarm
BV15307792_2Panelboard Phase Overcurrent (Branch PB 2)ReadActive = alarm
BV15317793_2Panelboard Neutral Overcurrent (Branch PB 2)ReadActive = alarm
BV15327794_2Panelboard Ground Overcurrent (Branch PB 2)ReadActive = alarm
BV15337795_2Panelboard Main Breaker Tripped (Branch PB 2)ReadActive = alarm
BV15347796_2Panelboard Main Breaker Accessory Error (Branch PB 2)ReadActive = alarm
BV15358253_2Panelboard Overvoltage (Branch PB 2)ReadActive = alarm
BV15368254_2Panelboard Undervoltage (Branch PB 2)ReadActive = alarm
BV15378255_2Panelboard Frequency Deviation (Branch PB 2)ReadActive = alarm
BV15388435_2Panelboard Main Breaker Open Fail (Branch PB 2)ReadActive = alarm
BV15457822_2_1Branch Phase Overcurrent (Branch PB 2 Branch 1)ReadActive = alarm
BV15467823_2_1Branch Phase Undercurrent (Branch PB 2 Branch 1)ReadActive = alarm
BV15478259_2_1Branch Neutral Overcurrent (Branch PB 2 Branch 1)ReadActive = alarm
BV15488436_2_1Load Loss Detected (Branch PB 2 Branch 1)ReadActive = alarm
BV15577822_2_2Branch Phase Overcurrent (Branch PB 2 Branch 2)ReadActive = alarm
BV15587823_2_2Branch Phase Undercurrent (Branch PB 2 Branch 2)ReadActive = alarm
BV15598259_2_2Panelboard Frequency Deviation (Branch PB 2 Branch 2)ReadActive = alarm
BV15608436_2_2Load Loss Detected (Branch PB 2 Branch 2)ReadActive = alarm
BV20377822_2_42Branch Phase Overcurrent (Branch PB 2 Branch 42)ReadActive = alarm
BV20387823_2_42Branch Phase Undercurrent (Branch PB 2 Branch 42)ReadActive = alarm
BV20398259_2_42Branch Neutral Overcurrent (Branch PB 2 Branch 42)ReadActive = alarm
BV20408436_2_42Load Loss Detected (Branch PB 2 Branch 42)ReadActive = alarm
BV67207792_12Panelboard Phase Overcurrent (Branch PB 12)ReadActive = alarm
BV67217793_12Panelboard Neutral Overcurrent (Branch PB 12)ReadActive = alarm
BV67227794_12Panelboard Ground Overcurrent (Branch PB 12)ReadActive = alarm
BV67237795_12Panelboard Main Breaker Tripped (Branch PB 12)ReadActive = alarm
BV67247796_12Panelboard Main Breaker Accessory Error (Branch PB 12)ReadActive = alarm
BV67258253_12Panelboard Overvoltage (Branch PB 12)ReadActive = alarm
BV67268254_12Panelboard Undervoltage (Branch PB 12)ReadActive = alarm
BV67278255_12Panelboard Frequency Deviation (Branch PB 12)ReadActive = alarm
BV67288435_12Panelboard Main Breaker Open Fail (Branch PB 12)ReadActive = alarm
BV67357822_12_1Branch Phase Overcurrent (Branch PB 12 Branch 1)ReadActive = alarm
BV67367823_12_1Branch Phase Undercurrent (Branch PB 12 Branch 1)ReadActive = alarm
BV67378259_12_1Branch Neutral Overcurrent (Branch PB 12 Branch 1)ReadActive = alarm
BV67388436_12_1Load Loss Detected (Branch PB 12 Branch 1)ReadActive = alarm
BV67477822_12_2Branch Phase Overcurrent (Branch PB 12 Branch 2)ReadActive = alarm
BV67487823_12_2Branch Phase Undercurrent (Branch PB 12 Branch 2)ReadActive = alarm
BV67498259_12_2Branch Neutral Overcurrent (Branch PB 12 Branch 2)ReadActive = alarm
BV67508436_12_2Load Loss Detected (Branch PB 12 Branch 2)ReadActive = alarm
BV72277822_12_42Branch Phase Overcurrent (Branch PB 12 Branch 42)ReadActive = alarm
BV72287823_12_42Branch Phase Undercurrent (Branch PB 12 Branch 42)ReadActive = alarm
BV72298259_12_42Branch Neutral Overcurrent (Branch PB 12 Branch 42)ReadActive = alarm
BV72308436_12_42Load Loss Detected (Branch PB 12 Branch 42)ReadActive = alarm
BV72397896_1Panelboard Phase Overcurrent (Subfeed PB 1)ReadActive = alarm
BV72407897_1Panelboard Neutral Overcurrent (Subfeed PB 1)ReadActive = alarm
BV72417898_1Panelboard Ground Overcurrent (Subfeed PB 1)ReadActive = alarm
BV72427899_1Panelboard Main Breaker Tripped (Subfeed PB 1)ReadActive = alarm
BV72437900_1Panelboard Main Breaker Accessory Error (Subfeed PB 1)ReadActive = alarm
BV72448262_1Panelboard Overvoltage (Subfeed PB 1)ReadActive = alarm
BV72458263_1Panelboard Undervoltage (Subfeed PB 1)ReadActive = alarm
BV72468264_1Panelboard Frequency Deviation (Subfeed PB 1)ReadActive = alarm
BV72547953_1_1Subfeed Phase Overcurrent (Subfeed PB 1 Subfeed 1)ReadActive = alarm
BV72557954_1_1Subfeed Neutral Overcurrent (Subfeed PB 1 Subfeed 1)ReadActive = alarm
BV72567955_1_1Subfeed Ground Overcurrent (Subfeed PB 1 Subfeed 1)ReadActive = alarm
BV72577956_1_1Subfeed Breaker Tripped (Subfeed PB 1 Subfeed 1)ReadActive = alarm
BV72587957_1_1Subfeed Breaker Accessory Error (Subfeed PB 1 Subfeed 1)ReadActive = alarm
BV72697953_1_2Subfeed Phase Overcurrent (Subfeed PB 1 Subfeed 2)ReadActive = alarm
BV72707954_1_2Subfeed Neutral Overcurrent (Subfeed PB 1 Subfeed 2)ReadActive = alarm
BV72717955_1_2Subfeed Ground Overcurrent (Subfeed PB 1 Subfeed 2)ReadActive = alarm
BV72727956_1_2Subfeed Breaker Tripped (Subfeed PB 1 Subfeed 2)ReadActive = alarm
BV72737957_1_2Subfeed Breaker Accessory Error (Subfeed PB 1 Subfeed 2)ReadActive = alarm
BV74197953_1_12Subfeed Phase Overcurrent (Subfeed PB 1 Subfeed 12)ReadActive = alarm
BV74207954_1_12Subfeed Neutral Overcurrent (Subfeed PB 1 Subfeed 12)ReadActive = alarm
BV74217955_1_12Subfeed Ground Overcurrent (Subfeed PB 1 Subfeed 12)ReadActive = alarm
BV74227956_1_12Subfeed Breaker Tripped (Subfeed PB 1 Subfeed 12)ReadActive = alarm
BV74237957_1_12Subfeed Breaker Accessory Error (Subfeed PB 1 Subfeed 12)ReadActive = alarm
BV74347896_2Panelboard Phase Overcurrent (Subfeed PB 2)ReadActive = alarm
BV74357897_2Panelboard Neutral Overcurrent (Subfeed PB 2)ReadActive = alarm
BV74367898_2Panelboard Ground Overcurrent (Subfeed PB 2)ReadActive = alarm
BV74377899_2Panelboard Main Breaker Tripped (Subfeed PB 2)ReadActive = alarm
BV74387900_2Panelboard Main Breaker Accessory Error (Subfeed PB 2)ReadActive = alarm
BV74398262_2Panelboard Overvoltage (Subfeed PB 2)ReadActive = alarm
BV74408263_2Panelboard Undervoltage (Subfeed PB 2)ReadActive = alarm
BV74418264_2Panelboard Frequency Deviation (Subfeed PB 2)ReadActive = alarm
BV74497953_2_1Subfeed Phase Overcurrent (Subfeed PB 2 Subfeed 1)ReadActive = alarm
BV74507954_2_1Subfeed Neutral Overcurrent (Subfeed PB 2 Subfeed 1)ReadActive = alarm
BV74517955_2_1Subfeed Ground Overcurrent (Subfeed PB 2 Subfeed 1)ReadActive = alarm
BV74527956_2_1Subfeed Breaker Tripped (Subfeed PB 2 Subfeed 1)ReadActive = alarm
BV74537957_2_1Subfeed Breaker Accessory Error (Subfeed PB 2 Subfeed 1)ReadActive = alarm
BV74647953_2_2Subfeed Phase Overcurrent (Subfeed PB 2 Subfeed 2)ReadActive = alarm
BV74657954_2_2Subfeed Neutral Overcurrent (Subfeed PB 2 Subfeed 2)ReadActive = alarm
BV74667955_2_2Subfeed Ground Overcurrent (Subfeed PB 2 Subfeed 2)ReadActive = alarm
BV74677956_2_2Subfeed Breaker Tripped (Subfeed PB 2 Subfeed 2)ReadActive = alarm
BV74687957_2_2Subfeed Breaker Accessory Error (Subfeed PB 2 Subfeed 2)ReadActive = alarm
BV76147953_2_12Subfeed Phase Overcurrent (Subfeed PB 2 Subfeed 12)ReadActive = alarm
BV76157954_2_12Subfeed Neutral Overcurrent (Subfeed PB 2 Subfeed 12)ReadActive = alarm
BV76167955_2_12Subfeed Ground Overcurrent (Subfeed PB 2 Subfeed 12)ReadActive = alarm
BV76177956_2_12Subfeed Breaker Tripped (Subfeed PB 2 Subfeed 12)ReadActive = alarm
BV76187957_2_12Subfeed Breaker Accessory Error (Subfeed PB 2 Subfeed 12)ReadActive = alarm
BV76298029_1Subfeed Phase Overcurrent (Subfeed 1)ReadActive = alarm
BV76308030_1Subfeed Neutral Overcurrent (Subfeed 1)ReadActive = alarm
BV76318031_1Subfeed Ground Overcurrent (Subfeed 1)ReadActive = alarm
BV76328032_1Subfeed Breaker Tripped (Subfeed 1)ReadActive = alarm
BV76338033_1Subfeed Breaker Accessory Error (Subfeed 1)ReadActive = alarm
BV76348267_1Subfeed Overvoltage (Subfeed 1)ReadActive = alarm
BV76358268_1Subfeed Undervoltage (Subfeed 1)ReadActive = alarm
BV76368269_1Subfeed Frequency Deviation (Subfeed 1)ReadActive = alarm
BV76448029_2Subfeed Phase Overcurrent (Subfeed 2)ReadActive = alarm
BV76458030_2Subfeed Neutral Overcurrent (Subfeed 2)ReadActive = alarm
BV76468031_2Subfeed Ground Overcurrent (Subfeed 2)ReadActive = alarm
BV76478032_2Subfeed Breaker Tripped (Subfeed 2)ReadActive = alarm
BV76488033_2Subfeed Breaker Accessory Error (Subfeed 2)ReadActive = alarm
BV76498267_2Subfeed Overvoltage (Subfeed 2)ReadActive = alarm
BV76508268_2Subfeed Undervoltage (Subfeed 2)ReadActive = alarm
BV76518269_2Subfeed Frequency Deviation (Subfeed 2)ReadActive = alarm
BV81548029_36Subfeed Phase Overcurrent (Subfeed 36)ReadActive = alarm
BV81558030_36Subfeed Neutral Overcurrent (Subfeed 36)ReadActive = alarm
BV81568031_36Subfeed Ground Overcurrent (Subfeed 36)ReadActive = alarm
BV81578032_36Subfeed Breaker Tripped (Subfeed 36)ReadActive = alarm
BV81588033_36Subfeed Breaker Accessory Error (Subfeed 36)ReadActive = alarm
BV81598267_36Subfeed Overvoltage (Subfeed 36)ReadActive = alarm
BV81608268_36Subfeed Undervoltage (Subfeed 36)ReadActive = alarm
BV81618269_36Subfeed Frequency Deviation (Subfeed 36)ReadActive = alarm
BV81698045_1External Input Contact State (External Input Contact 1)ReadActive = alarm
BV81808045_2External Input Contact State (External Input Contact 2)ReadActive = alarm
BV81918047_1Internal Input Contact State (Internal Input Contact 1)ReadActive = alarm
BV82028047_2Internal Input Contact State (Internal Input Contact 2)ReadActive = alarm
BV82688047_8Internal Input Contact State (Internal Input Contact 8)ReadActive = alarm
AV14293_1System Date and TimeSecs since Epoch(UTC)Write
AV148123_1System Power RatingkVARead
AV157592_1System Current RatingARead
AV167593_1Input 1 FrequencyHzRead
AV177594_1Input 2 FrequencyHzRead
AV188124_1System FrequencyHzRead
AV197595_1Input 1 Voltage (L-L) A-BVRead
AV207596_1Input 1 Voltage (L-L) B-CVRead
AV217597_1Input 1 Voltage (L-L) C-AVRead
AV227598_1Input 2 Voltage (L-L) A-BVRead
AV237599_1Input 2 Voltage (L-L) B-CVRead
AV247600_1Input 2 Voltage (L-L) C-AVRead
AVmin257601_1Output Voltage (L-L) A-BVRead
AV267602_1Output Voltage (L-L) B-CVRead
AV277603_1Output Voltage (L-L) C-AVRead
AVmin287604_1Output Voltage (L-N) A-NVRead
AV297605_1Output Voltage (L-N) B-NVRead
AV307606_1Output Voltage (L-N) C-NVRead
AV317607_1Current Ph AARead
AV327608_1Current Ph BARead
AV337609_1Current Ph CARead
AV347610_1Neutral CurrentARead
AV357611_1Ground CurrentARead
AV367612_1Current Load Ph A%Read
AV377613_1Current Load Ph B%Read
AV387614_1Current Load Ph C%Read
AV397615_1Highest Phase Current Load%Read
AV407616_1Real PowerkWRead
AV417617_1Apparent PowerkVARead
AV427618_1Apparent Power Load%Read
AV437619_1Power Factor Ph ARead
AV447620_1Power Factor Ph BRead
AV457621_1Power Factor Ph CRead
AV467622_1Power Factor TotalRead
AV477623_1EnergykWhRead
AV487624_1Peak Current Ph AARead
AV497625_1Peak Current Ph BARead
AV507626_1Peak Current Ph CARead
AV517627_1Peak DemandkWRead
AV527628_1Current Crest Factor Ph ARead
AV537629_1Current Crest Factor Ph BRead
AV547630_1Current Crest Factor Ph CRead
AV557631_1K-Factor Ph ARead
AV567632_1K-Factor Ph BRead
AV577633_1K-Factor Ph CRead
AV587634_1Highest Phase K-FactorRead
AV597635_1iTHD Ph A%Read
AV607636_1iTHD Ph B%Read
AV617637_1iTHD Ph C%Read
AV627638_1Current 3rd Harmonic Ph A%Read
AV637639_1Current 3rd Harmonic Ph B%Read
AV647640_1Current 3rd Harmonic Ph C%Read
AV657641_1Current 5th Harmonic Ph A%Read
AV667642_1Current 5th Harmonic Ph B%Read
AV677643_1Current 5th Harmonic Ph C%Read
AV687644_1Current 7th Harmonic Ph A%Read
AV697645_1Current 7th Harmonic Ph B%Read
AV707646_1Current 7th Harmonic Ph C%Read
AV717647_1Current 9th Harmonic Ph A%Read
AV727648_1Current 9th Harmonic Ph B%Read
AV737649_1Current 9th Harmonic Ph C%Read
AV747650_1Input 1 vTHD Ph A%Read
AV757651_1Input 1 vTHD Ph B%Read
AV767652_1Input 1 vTHD Ph C%Read
AV777653_1Input 1 Voltage 3rd Harmonic Ph A%Read
AV787654_1Input 1 Voltage 3rd Harmonic Ph B%Read
AV797655_1Input 1 Voltage 3rd Harmonic Ph C%Read
AV807656_1Input 1 Voltage 5th Harmonic Ph A%Read
AV817657_1Input 1 Voltage 5th Harmonic Ph B%Read
AV827658_1Input 1 Voltage 5th Harmonic Ph C%Read
AV837659_1Input 1 Voltage 7th Harmonic Ph A%Read
AV847660_1Input 1 Voltage 7th Harmonic Ph B%Read
AV857661_1Input 1 Voltage 7th Harmonic Ph C%Read
AV867662_1Input 1 Voltage 9th Harmonic Ph A%Read
AV877663_1Input 1 Voltage 9th Harmonic Ph B%Read
AV887664_1Input 1 Voltage 9th Harmonic C%Read
AV897665_1Input 2 vTHD Ph A%Read
AV907666_1Input 2 vTHD Ph B%Read
AV917667_1Input 2 vTHD Ph C%Read
AV927668_1Input 2 Voltage 3rd Harmonic Ph A%Read
AV937669_1Input 2 Voltage 3rd Harmonic Ph B%Read
AV947670_1Input 2 Voltage 3rd Harmonic Ph C%Read
AV957671_1Input 2 Voltage 5th Harmonic Ph A%Read
AV967672_1Input 2 Voltage 5th Harmonic Ph B%Read
AV977673_1Input 2 Voltage 5th Harmonic Ph C%Read
AV987674_1Input 2 Voltage 7th Harmonic Ph A%Read
AV997675_1Input 2 Voltage 7th Harmonic Ph B%Read
AV1007676_1Input 2 Voltage 7th Harmonic Ph C%Read
AV1017677_1Input 2 Voltage 9th Harmonic Ph A%Read
AV1027678_1Input 2 Voltage 9th Harmonic Ph B%Read
AV1037679_1Input 2 Voltage 9th Harmonic Ph C%Read
AV1047680_1Output vTHD Ph A%Read
AV1057681_1Output vTHD Ph B%Read
AV1067682_1Output vTHD Ph C%Read
AV1077683_1Output Voltage 3rd Harmonic A%Read
AV1087684_1Output Voltage 3rd Harmonic B%Read
AV1097685_1Output Voltage 3rd Harmonic C%Read
AV1107686_1Output Voltage 5th Harmonic A%Read
AV1117687_1Output Voltage 5th Harmonic B%Read
AV1127688_1Output Voltage 5th Harmonic C%Read
AV1137689_1Output Voltage 7th Harmonic A%Read
AV1147690_1Output Voltage 7th Harmonic B%Read
AV1157691_1Output Voltage 7th Harmonic C%Read
AV1167692_1Output Voltage 9th Harmonic A%Read
AV1177693_1Output Voltage 9th Harmonic B%Read
AV1187694_1Output Voltage 9th Harmonic C%Read
AV1197716_1Phase Overcurrent Alarm Threshold%Read
AV1207717_1Phase Overcurrent Warning Threshold%Read
AV1217718_1Neutral Overcurrent Alarm Threshold%Read
AV1227719_1Ground Overcurrent Alarm ThresholdARead
AV1238084_1Input 1 Phase Overvoltage Alarm Threshold%Read
AV1248085_1Input 1 Phase Undervoltage Alarm Threshold%Read
AV1258086_1Input 2 Phase Overvoltage Alarm Threshold%Read
AV1268087_1Input 2 Phase Undervoltage Alarm Threshold%Read
AV1278088_1Output Phase Overvoltage Alarm Threshold%Read
AV1288089_1Output Phase Undervoltage Alarm Threshold%Read
AV1297720_1Voltage Over THD Alarm Threshold%Read
AV1308276_1Neutral Overcurrent Warning Threshold%Read
AV1407727_1Panelboard Total Pole Positions (Branch PB 1)Read
AV1417728_1Panelboard Available Pole Positions (Branch PB 1)Read
AV1427729_1Panelboard Main Breaker Current Rating (Branch PB 1)ARead
AV1437730_1Panelboard Current Ph A (Branch PB 1)ARead
AV1447731_1Panelboard Current Ph B (Branch PB 1)ARead
AV1457732_1Panelboard Current Ph C (Branch PB 1)ARead
AV1467733_1Panelboard Neutral Current (Branch PB 1)ARead
AV1477734_1Panelboard Ground Current (Branch PB 1)ARead
AV1487735_1Panelboard Current Load Ph A (Branch PB 1)%Read
AV1497736_1Panelboard Current Load Ph B (Branch PB 1)%Read
AV1507737_1Panelboard Current Load Ph C (Branch PB 1)%Read
AV1517738_1Panelboard Highest Phase Current Load (Branch PB 1)%Read
AV1527739_1Panelboard Voltage (L-L) A-B (Branch PB 1)VRead
AV1537740_1Panelboard Voltage (L-L) B-C (Branch PB 1)VRead
AV1547741_1Panelboard Voltage (L-L) C-A (Branch PB 1)VRead
AV1557742_1Panelboard Voltage (L-N) A-N (Branch PB 1)VRead
AV1567743_1Panelboard Voltage (L-N) B-N (Branch PB 1)VRead
AV1577744_1Panelboard Voltage (L-N) C-N (Branch PB 1)VRead
AV1587745_1Panelboard Frequency (Branch PB 1)HzRead
AV1597746_1Panelboard Real Power (Branch PB 1)kWRead
AV1607747_1Panelboard Apparent Power (Branch PB 1)kVARead
AV1617748_1Panelboard Power Factor Ph A (Branch PB 1)Read
AV1627749_1Panelboard Power Factor Ph B (Branch PB 1)Read
AV1637750_1Panelboard Power Factor Ph C (Branch PB 1)Read
AV1647751_1Panelboard Power Factor Total (Branch PB 1)Read
AV1657752_1Panelboard Energy (Branch PB 1)kWhRead
AV1667753_1Panelboard Peak Current Ph A (Branch PB 1)ARead
AV1677754_1Panelboard Peak Current Ph B (Branch PB 1)ARead
AV1687755_1Panelboard Peak Current Ph C (Branch PB 1)ARead
AV1697756_1Panelboard Highest Phase Peak Current (Branch PB 1)ARead
AV1707757_1Panelboard Peak Demand (Branch PB 1)kWRead
AV1717758_1Panelboard Current Crest Factor Ph A (Branch PB 1)Read
AV1727759_1Panelboard Current Crest Factor Ph B (Branch PB 1)Read
AV1737760_1Panelboard Current Crest Factor Ph C (Branch PB 1)Read
AV1747761_1Panelboard iTHD Ph A (Branch PB 1)%Read
AV1757762_1Panelboard iTHD Ph B (Branch PB 1)%Read
AV1767763_1Panelboard iTHD Ph C (Branch PB 1)%Read
AV1777764_1Panelboard Current 3rd Harmonic Ph A (Branch PB 1)%Read
AV1787765_1Panelboard Current 3rd Harmonic Ph B (Branch PB 1)%Read
AV1797766_1Panelboard Current 3rd Harmonic Ph C (Branch PB 1)%Read
AV1807767_1Panelboard Current 5th Harmonic Ph A (Branch PB 1)%Read
AV1817768_1Panelboard Current 5th Harmonic Ph B (Branch PB 1)%Read
AV1827769_1Panelboard Current 5th Harmonic Ph C (Branch PB 1)%Read
AV1837770_1Panelboard Current 7th Harmonic Ph A (Branch PB 1)%Read
AV1847771_1Panelboard Current 7th Harmonic Ph B (Branch PB 1)%Read
AV1857772_1Panelboard Current 7th Harmonic Ph C (Branch PB 1)%Read
AV1867773_1Panelboard Current 9th Harmonic Ph A (Branch PB 1)%Read
AV1877774_1Panelboard Current 9th Harmonic Ph B (Branch PB 1)%Read
AV1887775_1Panelboard Current 9th Harmonic Ph C (Branch PB 1)%Read
AV1897776_1Panelboard vTHD Ph A (Branch PB 1)%Read
AV1907777_1Panelboard vTHD Ph B (Branch PB 1)%Read
AV1917778_1Panelboard vTHD Ph C (Branch PB 1)%Read
AV1927779_1Panelboard Voltage 3rd Harmonic Ph A (Branch PB 1)%Read
AV1937780_1Panelboard Voltage 3rd Harmonic Ph B (Branch PB 1)%Read
AV1947781_1Panelboard Voltage 3rd Harmonic Ph C (Branch PB 1)%Read
AV1957782_1Panelboard Voltage 5th Harmonic Ph A (Branch PB 1)%Read
AV1967783_1Panelboard Voltage 5th Harmonic Ph B (Branch PB 1)%Read
AV1977784_1Panelboard Voltage 5th Harmonic Ph C (Branch PB 1)%Read
AV1987785_1Panelboard Voltage 7th Harmonic Ph A (Branch PB 1)%Read
AV1997786_1Panelboard Voltage 7th Harmonic Ph B (Branch PB 1)%Read
AV2007787_1Panelboard Voltage 7th Harmonic Ph C (Branch PB 1)%Read
AV2017788_1Panelboard Voltage 9th Harmonic Ph A (Branch PB 1)%Read
AV2027789_1Panelboard Voltage 9th Harmonic Ph B (Branch PB 1)%Read
AV2037790_1Panelboard Voltage 9th Harmonic Ph C (Branch PB 1)%Read
AV2047798_1Panelboard Phase Overcurrent Warning Threshold (Branch PB 1)%Read
AV2057799_1Panelboard Phase Overcurrent Alarm Threshold (Branch PB 1)%Read
AV2067800_1Panelboard Neutral Overcurrent Alarm Threshold (Branch PB 1)%Read
AV2077801_1Panelboard Ground Overcurrent Alarm Threshold (Branch PB 1)ARead
AV2088277_1Panelboard Neutral Overcurrent Warning Threshold (Branch PB 1)%Read
AV2098256_1Panelboard Phase Overvoltage Alarm Threshold (Branch PB 1)%Read
AV2108257_1Panelboard Phase Undervoltage Alarm Threshold (Branch PB 1)%Read
AV2187808_1_1Branch Position (Branch PB 1 Branch 1)Read
AV2197809_1_1Branch Current Rating (Branch PB 1 Branch 1)ARead
AV2207810_1_1Branch Current L1 (Branch PB 1 Branch 1)ARead
AV2217811_1_1Branch Current L2 (Branch PB 1 Branch 1)ARead
AV2227812_1_1Branch Current L3 (Branch PB 1 Branch 1)ARead
AV2237813_1_1Branch Real Power (Branch PB 1 Branch 1)kWRead
AV2247814_1_1Branch Power Factor (Branch PB 1 Branch 1)Read
AV2257815_1_1Branch Energy (Branch PB 1 Branch 1)kWhRead
AV2267816_1_1Branch Highest Phase Current Load (Branch PB 1 Branch 1)%Read
AV2277817_1_1Branch Peak Current L1 (Branch PB 1 Branch 1)ARead
AV2287818_1_1Branch Peak Current L2 (Branch PB 1 Branch 1)ARead
AV2297819_1_1Branch Peak Current L3 (Branch PB 1 Branch 1)ARead
AV2307820_1_1Branch Highest Phase Peak Current (Branch PB 1 Branch 1)ARead
AV2317821_1_1Branch Peak Demand (Branch PB 1 Branch 1)kWRead
AV2327825_1_1Branch Overcurrent Warning Threshold (Branch PB 1 Branch 1)%Read
AV2337826_1_1Branch Overcurrent Alarm Threshold (Branch PB 1 Branch 1)%Read
AV2347827_1_1Branch Low Current Alarm Threshold (Branch PB 1 Branch 1)%Read
AV2358258_1_1Branch Current Neutral (Branch PB 1 Branch 1)ARead
AV2368260_1_1Branch Neutral Overcurrent Warning Threshold (Branch PB 1 Branch 1)%Read
AV2378261_1_1Branch Neutral Overcurrent Alarm Threshold (Branch PB 1 Branch 1)%Read
AV2388437_1_1Load Loss Min Load (Branch PB 1 Branch 1)%Read
AV2457808_1_2Branch Position (Branch PB 1 Branch 2)Read
AV2467809_1_2Branch Current Rating (Branch PB 1 Branch 2)ARead
AV2477810_1_2Branch Current L1 (Branch PB 1 Branch 2)ARead
AV2487811_1_2Branch Current L2 (Branch PB 1 Branch 2)ARead
AV2497812_1_2Branch Current L3 (Branch PB 1 Branch 2)ARead
AV2507813_1_2Branch Real Power (Branch PB 1 Branch 2)kWRead
AV2517814_1_2Branch Power Factor (Branch PB 1 Branch 2)Read
AV2527815_1_2Branch Energy (Branch PB 1 Branch 2)kWhRead
AV2537816_1_2Branch Highest Phase Current Load (Branch PB 1 Branch 2)%Read
AV2547817_1_2Branch Peak Current L1 (Branch PB 1 Branch 2)ARead
AV2557818_1_2Branch Peak Current L2 (Branch PB 1 Branch 2)ARead
AV2567819_1_2Branch Peak Current L3 (Branch PB 1 Branch 2)ARead
AV2577820_1_2Branch Highest Phase Peak Current (Branch PB 1 Branch 2)ARead
AV2587821_1_2Branch Peak Demand (Branch PB 1 Branch 2)kWRead
AV2597825_1_2Branch Overcurrent Warning Threshold (Branch PB 1 Branch 2)%Read
AV2607826_1_2Branch Overcurrent Alarm Threshold (Branch PB 1 Branch 2)%Read
AV2617827_1_2Branch Low Current Alarm Threshold (Branch PB 1 Branch 2)%Read
AV2628258_1_2Branch Current Neutral (Branch PB 1 Branch 2)ARead
AV2638260_1_2Branch Neutral Overcurrent Warning Threshold (Branch PB 1 Branch 2)%Read
AV2648261_1_2Branch Neutral Overcurrent Alarm Threshold (Branch PB 1 Branch 2)%Read
AV2658437_1_2Load Loss Min Load (Branch PB 1 Branch 2)%Read
AV13257808_1_42Branch Position (Branch PB 1 Branch 42)Read
AV13267809_1_42Branch Current Rating (Branch PB 1 Branch 42)ARead
AV13277810_1_42Branch Current L1 (Branch PB 1 Branch 42)ARead
AV13287811_1_42Branch Current L2 (Branch PB 1 Branch 42)ARead
AV13297812_1_42Branch Current L3 (Branch PB 1 Branch 42)ARead
AV13307813_1_42Branch Real Power (Branch PB 1 Branch 42)kWRead
AV13317814_1_42Branch Power Factor (Branch PB 1 Branch 42)Read
AV13327815_1_42Branch Energy (Branch PB 1 Branch 42)kWhRead
AV13337816_1_42Branch Highest Phase Current Load (Branch PB 1 Branch 42)%Read
AV13347817_1_42Branch Peak Current L1 (Branch PB 1 Branch 42)ARead
AV13357818_1_42Branch Peak Current L2 (Branch PB 1 Branch 42)ARead
AV13367819_1_42Branch Peak Current L3 (Branch PB 1 Branch 42)ARead
AV13377820_1_42Branch Highest Phase Peak Current (Branch PB 1 Branch 42)ARead
AV13387821_1_42Branch Peak Demand (Branch PB 1 Branch 42)kWRead
AV13397825_1_42Branch Overcurrent Warning Threshold (Branch PB 1 Branch 42)%Read
AV13407826_1_42Branch Overcurrent Alarm Threshold (Branch PB 1 Branch 42)%Read
AV13417827_1_42Branch Low Current Alarm Threshold (Branch PB 1 Branch 42)%Read
AV13428258_1_42Branch Current Neutral (Branch PB 1 Branch 42)ARead
AV13438260_1_42Branch Neutral Overcurrent Warning Threshold (Branch PB 1 Branch 42)%Read
AV13448261_1_42Branch Neutral Overcurrent Alarm Threshold (Branch PB 1 Branch 42)%Read
AV13458437_1_42Load Loss Min Load (Branch PB 1 Branch 42)%Read
AV13527727_2Panelboard Total Pole Positions (Branch PB 2)Read
AV13537728_2Panelboard Available Pole Positions (Branch PB 2)Read
AV13547729_2Panelboard Main Breaker Current Rating (Branch PB 2)ARead
AV13557730_2Panelboard Current Ph A (Branch PB 2)ARead
AV13567731_2Panelboard Current Ph B (Branch PB 2)ARead
AV13577732_2Panelboard Current Ph C (Branch PB 2)ARead
AV13587733_2Panelboard Neutral Current (Branch PB 2)ARead
AV13597734_2Panelboard Ground Current (Branch PB 2)ARead
AV13607735_2Panelboard Current Load Ph A (Branch PB 2)%Read
AV13617736_2Panelboard Current Load Ph B (Branch PB 2)%Read
AV13627737_2Panelboard Current Load Ph C (Branch PB 2)%Read
AV13637738_2Panelboard Highest Phase Current Load (Branch PB 2)%Read
AV13647739_2Panelboard Voltage (L-L) A-B (Branch PB 2)VRead
AV13657740_2Panelboard Voltage (L-L) B-C (Branch PB 2)VRead
AV13667741_2Panelboard Voltage (L-L) C-A (Branch PB 2)VRead
AV13677742_2Panelboard Voltage (L-N) A-N (Branch PB 2)VRead
AV13687743_2Panelboard Voltage (L-N) B-N (Branch PB 2)VRead
AV13697744_2Panelboard Voltage (L-N) C-N (Branch PB 2)VRead
AV13707745_2Panelboard Frequency (Branch PB 2)HzRead
AV13717746_2Panelboard Real Power (Branch PB 2)kWRead
AV13727747_2Panelboard Apparent Power (Branch PB 2)kVARead
AV13737748_2Panelboard Power Factor Ph A (Branch PB 2)Read
AV13747749_2Panelboard Power Factor Ph B (Branch PB 2)Read
AV13757750_2Panelboard Power Factor Ph C (Branch PB 2)Read
AV13767751_2Panelboard Power Factor Total (Branch PB 2)Read
AV13777752_2Panelboard Energy (Branch PB 2)kWhRead
AV13787753_2Panelboard Peak Current Ph A (Branch PB 2)ARead
AV13797754_2Panelboard Peak Current Ph B (Branch PB 2)ARead
AV13807755_2Panelboard Peak Current Ph C (Branch PB 2)ARead
AV13817756_2Panelboard Highest Phase Peak Current (Branch PB 2)ARead
AV13827757_2Panelboard Peak Demand (Branch PB 2)kWRead
AV13837758_2Panelboard Current Crest Factor Ph A (Branch PB 2)Read
AV13847759_2Panelboard Current Crest Factor Ph B (Branch PB 2)Read
AV13857760_2Panelboard Current Crest Factor Ph C (Branch PB 2)Read
AV13867761_2Panelboard iTHD Ph A (Branch PB 2)%Read
AV13877762_2Panelboard iTHD Ph B (Branch PB 2)%Read
AV13887763_2Panelboard iTHD Ph C (Branch PB 2)%Read
AV13897764_2Panelboard Current 3rd Harmonic Ph A (Branch PB 2)%Read
AV13907765_2Panelboard Current 3rd Harmonic Ph B (Branch PB 2)%Read
AV13917766_2Panelboard Current 3rd Harmonic Ph C (Branch PB 2)%Read
AV13927767_2Panelboard Current 5th Harmonic Ph A (Branch PB 2)%Read
AV13937768_2Panelboard Current 5th Harmonic Ph B (Branch PB 2)%Read
AV13947769_2Panelboard Current 5th Harmonic Ph C (Branch PB 2)%Read
AV13957770_2Panelboard Current 7th Harmonic Ph A (Branch PB 2)%Read
AV13967771_2Panelboard Current 7th Harmonic Ph B (Branch PB 2)%Read
AV13977772_2Panelboard Current 7th Harmonic Ph C (Branch PB 2)%Read
AV13987773_2Panelboard Current 9th Harmonic Ph A (Branch PB 2)%Read
AV13997774_2Panelboard Current 9th Harmonic Ph B (Branch PB 2)%Read
AV14007775_2Panelboard Current 9th Harmonic Ph C (Branch PB 2)%Read
AV14017776_2Panelboard vTHD Ph A (Branch PB 2)%Read
AV14027777_2Panelboard vTHD Ph B (Branch PB 2)%Read
AV14037778_2Panelboard vTHD Ph C (Branch PB 2)%Read
AV14047779_2Panelboard Voltage 3rd Harmonic Ph A (Branch PB 2)%Read
AV14057780_2Panelboard Voltage 3rd Harmonic Ph B (Branch PB 2)%Read
AV14067781_2Panelboard Voltage 3rd Harmonic Ph C (Branch PB 2)%Read
AV14077782_2Panelboard Voltage 5th Harmonic Ph A (Branch PB 2)%Read
AV14087783_2Panelboard Voltage 5th Harmonic Ph B (Branch PB 2)%Read
AV14097784_2Panelboard Voltage 5th Harmonic Ph C (Branch PB 2)%Read
AV14107785_2Panelboard Voltage 7th Harmonic Ph A (Branch PB 2)%Read
AV14117786_2Panelboard Voltage 7th Harmonic Ph B (Branch PB 2)%Read
AV14127787_2Panelboard Voltage 7th Harmonic Ph C (Branch PB 2)%Read
AV14137788_2Panelboard Voltage 9th Harmonic Ph A (Branch PB 2)%Read
AV14147789_2Panelboard Voltage 9th Harmonic Ph B (Branch PB 2)%Read
AV14157790_2Panelboard Voltage 9th Harmonic Ph C (Branch PB 2)%Read
AV14167798_2Panelboard Phase Overcurrent Warning Threshold (Branch PB 2)%Read
AV14177799_2Panelboard Phase Overcurrent Alarm Threshold (Branch PB 2)%Read
AV14187800_2Panelboard Neutral Overcurrent Alarm Threshold (Branch PB 2)%Read
AV14197801_2Panelboard Ground Overcurrent Alarm Threshold (Branch PB 2)ARead
AV14208277_2Panelboard Neutral Overcurrent Warning Threshold (Branch PB 2)%Read
AV14218256_2Panelboard Phase Overvoltage Alarm Threshold (Branch PB 2)%Read
AV14228257_2Panelboard Phase Undervoltage Alarm Threshold (Branch PB 2)%Read
AV14307808_2_1Branch Position (Branch PB 2 Branch 1)Read
AV14317809_2_1Branch Current Rating (Branch PB 2 Branch 1)ARead
AV14327810_2_1Branch Current L1 (Branch PB 2 Branch 1)ARead
AV14337811_2_1Branch Current L2 (Branch PB 2 Branch 1)ARead
AV14347812_2_1Branch Current L3 (Branch PB 2 Branch 1)ARead
AV14357813_2_1Branch Real Power (Branch PB 2 Branch 1)kWRead
AV14367814_2_1Branch Power Factor (Branch PB 2 Branch 1)Read
AV14377815_2_1Branch Energy (Branch PB 2 Branch 1)kWhRead
AV14387816_2_1Branch Highest Phase Current Load (Branch PB 2 Branch 1)%Read
AV14397817_2_1Branch Peak Current L1 (Branch PB 2 Branch 1)ARead
AV14407818_2_1Branch Peak Current L2 (Branch PB 2 Branch 1)ARead
AV14417819_2_1Branch Peak Current L3 (Branch PB 2 Branch 1)ARead
AV14427820_2_1Branch Highest Phase Peak Current (Branch PB 2 Branch 1)ARead
AV14437821_2_1Branch Peak Demand (Branch PB 2 Branch 1)kWRead
AV14447825_2_1Branch Overcurrent Warning Threshold (Branch PB 2 Branch 1)%Read
AV14457826_2_1Branch Overcurrent Alarm Threshold (Branch PB 2 Branch 1)%Read
AV14467827_2_1Branch Low Current Alarm Threshold (Branch PB 2 Branch 1)%Read
AV14478258_2_1Branch Current Neutral (Branch PB 2 Branch 1)ARead
AV14488260_2_1Branch Neutral Overcurrent Warning Threshold (Branch PB 2 Branch 1)%Read
AV14498261_2_1Branch Neutral Overcurrent Alarm Threshold (Branch PB 2 Branch 1)%Read
AV14508437_2_1Load Loss Min Load (Branch PB 2 Branch 1)%Read
AV14577808_2_2Branch Position (Branch PB 2 Branch 2)Read
AV14587809_2_2Branch Current Rating (Branch PB 2 Branch 2)ARead
AV14597810_2_2Branch Current L1 (Branch PB 2 Branch 2)ARead
AV14607811_2_2Branch Current L2 (Branch PB 2 Branch 2)ARead
AV14617812_2_2Branch Current L3 (Branch PB 2 Branch 2)ARead
AV14627813_2_2Branch Real Power (Branch PB 2 Branch 2)kWRead
AV14637814_2_2Branch Power Factor (Branch PB 2 Branch 2)Read
AV14647815_2_2Branch Energy (Branch PB 2 Branch 2)kWhRead
AV14657816_2_2Branch Highest Phase Current Load (Branch PB 2 Branch 2)%Read
AV14667817_2_2Branch Peak Current L1 (Branch PB 2 Branch 2)ARead
AV14677818_2_2Branch Peak Current L2 (Branch PB 2 Branch 2)ARead
AV14687819_2_2Branch Peak Current L3 (Branch PB 2 Branch 2)ARead
AV14697820_2_2Branch Highest Phase Peak Current (Branch PB 2 Branch 2)ARead
AV14707821_2_2Branch Peak Demand (Branch PB 2 Branch 2)kWRead
AV14717825_2_2Branch Overcurrent Warning Threshold (Branch PB 2 Branch 2)%Read
AV14727826_2_2Branch Overcurrent Alarm Threshold (Branch PB 2 Branch 2)%Read
AV14737827_2_2Branch Low Current Alarm Threshold (Branch PB 2 Branch 2)%Read
AV14748258_2_2Branch Current Neutral (Branch PB 2 Branch 2)ARead
AV14758260_2_2Branch Neutral Overcurrent Warning Threshold (Branch PB 2 Branch 2)%Read
AV14768261_2_2Branch Neutral Overcurrent Alarm Threshold (Branch PB 2 Branch 2)%Read
AV14778437_2_2Load Loss Min Load (Branch PB 2 Branch 2)%Read
AV25377808_2_42Branch Position (Branch PB 2 Branch 42)Read
AV25387809_2_42Branch Current Rating (Branch PB 2 Branch 42)ARead
AV25397810_2_42Branch Current L1 (Branch PB 2 Branch 42)ARead
AV25407811_2_42Branch Current L2 (Branch PB 2 Branch 42)ARead
AV25417812_2_42Branch Current L3 (Branch PB 2 Branch 42)ARead
AV25427813_2_42Branch Real Power (Branch PB 2 Branch 42)kWRead
AV25437814_2_42Branch Power Factor (Branch PB 2 Branch 42)Read
AV25447815_2_42Branch Energy (Branch PB 2 Branch 42)kWhRead
AV25457816_2_42Branch Highest Phase Current Load (Branch PB 2 Branch 42)%Read
AV25467817_2_42Branch Peak Current L1 (Branch PB 2 Branch 42)ARead
AV25477818_2_42Branch Peak Current L2 (Branch PB 2 Branch 42)ARead
AV25487819_2_42Branch Peak Current L3 (Branch PB 2 Branch 42)ARead
AV25497820_2_42Branch Highest Phase Peak Current (Branch PB 2 Branch 42)ARead
AV25507821_2_42Branch Peak Demand (Branch PB 2 Branch 42)kWRead
AV25517825_2_42Branch Overcurrent Warning Threshold (Branch PB 2 Branch 42)%Read
AV25527826_2_42Branch Overcurrent Alarm Threshold (Branch PB 2 Branch 42)%Read
AV25537827_2_42Branch Low Current Alarm Threshold (Branch PB 2 Branch 42)%Read
AV25548258_2_42Branch Current Neutral (Branch PB 2 Branch 42)ARead
AV25558260_2_42Branch Neutral Overcurrent Warning Threshold (Branch PB 2 Branch 42)%Read
AV25568261_2_42Branch Neutral Overcurrent Alarm Threshold (Branch PB 2 Branch 42)%Read
AV25578437_2_42Load Loss Min Load (Branch PB 2 Branch 42)%Read
AV134727727_12Panelboard Total Pole Positions (Branch PB 12)Read
AV134737728_12Panelboard Available Pole Positions (Branch PB 12)Read
AV134747729_12Panelboard Main Breaker Current Rating (Branch PB 12)ARead
AV134757730_12Panelboard Current Ph A (Branch PB 12)ARead
AV134767731_12Panelboard Current Ph B (Branch PB 12)ARead
AV134777732_12Panelboard Current Ph C (Branch PB 12)ARead
AV134787733_12Panelboard Neutral Current (Branch PB 12)ARead
AV134797734_12Panelboard Ground Current (Branch PB 12)ARead
AV134807735_12Panelboard Current Load Ph A (Branch PB 12)%Read
AV134817736_12Panelboard Current Load Ph B (Branch PB 12)%Read
AV134827737_12Panelboard Current Load Ph C (Branch PB 12)%Read
AV134837738_12Panelboard Highest Phase Current Load (Branch PB 12)%Read
AV134847739_12Panelboard Voltage (L-L) A-B (Branch PB 12)VRead
AV134857740_12Panelboard Voltage (L-L) B-C (Branch PB 12)VRead
AV134867741_12Panelboard Voltage (L-L) C-A (Branch PB 12)VRead
AV134877742_12Panelboard Voltage (L-N) A-N (Branch PB 12)VRead
AV134887743_12Panelboard Voltage (L-N) B-N (Branch PB 12)VRead
AV134897744_12Panelboard Voltage (L-N) C-N (Branch PB 12)VRead
AV134907745_12Panelboard Frequency (Branch PB 12)HzRead
AV134917746_12Panelboard Real Power (Branch PB 12)kWRead
AV134927747_12Panelboard Apparent Power (Branch PB 12)kVARead
AV134937748_12Panelboard Power Factor Ph A (Branch PB 12)Read
AV134947749_12Panelboard Power Factor Ph B (Branch PB 12)Read
AV134957750_12Panelboard Power Factor Ph C (Branch PB 12)Read
AV134967751_12Panelboard Power Factor Total (Branch PB 12)Read
AV134977752_12Panelboard Energy (Branch PB 12)kWhRead
AV134987753_12Panelboard Peak Current Ph A (Branch PB 12)ARead
AV134997754_12Panelboard Peak Current Ph B (Branch PB 12)ARead
AV135007755_12Panelboard Peak Current Ph C (Branch PB 12)ARead
AV135017756_12Panelboard Highest Phase Peak Current (Branch PB 12)ARead
AV135027757_12Panelboard Peak Demand (Branch PB 12)kWRead
AV135037758_12Panelboard Current Crest Factor Ph A (Branch PB 12)Read
AV135047759_12Panelboard Current Crest Factor Ph B (Branch PB 12)Read
AV135057760_12Panelboard Current Crest Factor Ph C (Branch PB 12)Read
AV135067761_12Panelboard iTHD Ph A (Branch PB 12)%Read
AV135077762_12Panelboard iTHD Ph B (Branch PB 12)%Read
AV135087763_12Panelboard iTHD Ph C (Branch PB 12)%Read
AV135097764_12Panelboard Current 3rd Harmonic Ph A (Branch PB 12)%Read
AV135107765_12Panelboard Current 3rd Harmonic Ph B (Branch PB 12)%Read
AV135117766_12Panelboard Current 3rd Harmonic Ph C (Branch PB 12)%Read
AV135127767_12Panelboard Current 5th Harmonic Ph A (Branch PB 12)%Read
AV135137768_12Panelboard Current 5th Harmonic Ph B (Branch PB 12)%Read
AV135147769_12Panelboard Current 5th Harmonic Ph C (Branch PB 12)%Read
AV135157770_12Panelboard Current 7th Harmonic Ph A (Branch PB 12)%Read
AV135167771_12Panelboard Current 7th Harmonic Ph B (Branch PB 12)%Read
AV135177772_12Panelboard Current 7th Harmonic Ph C (Branch PB 12)%Read
AV135187773_12Panelboard Current 9th Harmonic Ph A (Branch PB 12)%Read
AV135197774_12Panelboard Current 9th Harmonic Ph B (Branch PB 12)%Read
AV135207775_12Panelboard Current 9th Harmonic Ph C (Branch PB 12)%Read
AV135217776_12Panelboard vTHD Ph A (Branch PB 12)%Read
AV135227777_12Panelboard vTHD Ph B (Branch PB 12)%Read
AV135237778_12Panelboard vTHD Ph C (Branch PB 12)%Read
AV135247779_12Panelboard Voltage 3rd Harmonic Ph A (Branch PB 12)%Read
AV135257780_12Panelboard Voltage 3rd Harmonic Ph B (Branch PB 12)%Read
AV135267781_12Panelboard Voltage 3rd Harmonic Ph C (Branch PB 12)%Read
AV135277782_12Panelboard Voltage 5th Harmonic Ph A (Branch PB 12)%Read
AV135287783_12Panelboard Voltage 5th Harmonic Ph B (Branch PB 12)%Read
AV135297784_12Panelboard Voltage 5th Harmonic Ph C (Branch PB 12)%Read
AV135307785_12Panelboard Voltage 7th Harmonic Ph A (Branch PB 12)%Read
AV135317786_12Panelboard Voltage 7th Harmonic Ph B (Branch PB 12)%Read
AV135327787_12Panelboard Voltage 7th Harmonic Ph C (Branch PB 12)%Read
AV135337788_12Panelboard Voltage 9th Harmonic Ph A (Branch PB 12)%Read
AV135347789_12Panelboard Voltage 9th Harmonic Ph B (Branch PB 12)%Read
AV135357790_12Panelboard Voltage 9th Harmonic Ph C (Branch PB 12)%Read
AV135367798_12Panelboard Phase Overcurrent Warning Threshold (Branch PB 12)%Read
AV135377799_12Panelboard Phase Overcurrent Alarm Threshold (Branch PB 12)%Read
AV135387800_12Panelboard Neutral Overcurrent Alarm Threshold (Branch PB 12)%Read
AV135397801_12Panelboard Ground Overcurrent Alarm Threshold (Branch PB 12)ARead
AV135408277_12Panelboard Neutral Overcurrent Warning Threshold (Branch PB 12)%Read
AV135418256_12Panelboard Phase Overvoltage Alarm Threshold (Branch PB 12)%Read
AV135428257_12Panelboard Phase Undervoltage Alarm Threshold (Branch PB 12)%Read
AV135507808_12_1Branch Position (Branch PB 12 Branch 1)Read
AV135517809_12_1Branch Current Rating (Branch PB 12 Branch 1)ARead
AV135527810_12_1Branch Current L1 (Branch PB 12 Branch 1)ARead
AV135537811_12_1Branch Current L2 (Branch PB 12 Branch 1)ARead
AV135547812_12_1Branch Current L3 (Branch PB 12 Branch 1)ARead
AV135557813_12_1Branch Real Power (Branch PB 12 Branch 1)kWRead
AV135567814_12_1Branch Power Factor (Branch PB 12 Branch 1)Read
AV135577815_12_1Branch Energy (Branch PB 12 Branch 1)kWhRead
AV135587816_12_1Branch Highest Phase Current Load (Branch PB 12 Branch 1)%Read
AV135597817_12_1Branch Peak Current L1 (Branch PB 12 Branch 1)ARead
AV135607818_12_1Branch Peak Current L2 (Branch PB 12 Branch 1)ARead
AV135617819_12_1Branch Peak Current L3 (Branch PB 12 Branch 1)ARead
AV135627820_12_1Branch Highest Phase Peak Current (Branch PB 12 Branch 1)ARead
AV135637821_12_1Branch Peak Demand (Branch PB 12 Branch 1)kWRead
AV135647825_12_1Branch Overcurrent Warning Threshold (Branch PB 12 Branch 1)%Read
AV135657826_12_1Branch Overcurrent Alarm Threshold (Branch PB 12 Branch 1)%Read
AV135667827_12_1Branch Low Current Alarm Threshold (Branch PB 12 Branch 1)%Read
AV135678258_12_1Branch Current Neutral (Branch PB 12 Branch 1)ARead
AV135688260_12_1Branch Neutral Overcurrent Warning Threshold (Branch PB 12 Branch 1)%Read
AV135698261_12_1Branch Neutral Overcurrent Alarm Threshold (Branch PB 12 Branch 1)%Read
AV135708437_12_1Load Loss Min Load (Branch PB 12 Branch 1)%Read
AV135777808_12_2Branch Position (Branch PB 12 Branch 2)Read
AV135787809_12_2Branch Current Rating (Branch PB 12 Branch 2)ARead
AV135797810_12_2Branch Current L1 (Branch PB 12 Branch 2)ARead
AV135807811_12_2Branch Current L2 (Branch PB 12 Branch 2)ARead
AV135817812_12_2Branch Current L3 (Branch PB 12 Branch 2)ARead
AV135827813_12_2Branch Real Power (Branch PB 12 Branch 2)kWRead
AV135837814_12_2Branch Power Factor (Branch PB 12 Branch 2)Read
AV135847815_12_2Branch Energy (Branch PB 12 Branch 2)kWhRead
AV135857816_12_2Branch Highest Phase Current Load (Branch PB 12 Branch 2)%Read
AV135867817_12_2Branch Peak Current L1 (Branch PB 12 Branch 2)ARead
AV135877818_12_2Branch Peak Current L2 (Branch PB 12 Branch 2)ARead
AV135887819_12_2Branch Peak Current L3 (Branch PB 12 Branch 2)ARead
AV135897820_12_2Branch Highest Phase Peak Current (Branch PB 12 Branch 2)ARead
AV135907821_12_2Branch Peak Demand (Branch PB 12 Branch 2)kWRead
AV135917825_12_2Branch Overcurrent Warning Threshold (Branch PB 12 Branch 2)%Read
AV135927826_12_2Branch Overcurrent Alarm Threshold (Branch PB 12 Branch 2)%Read
AV135937827_12_2Branch Low Current Alarm Threshold (Branch PB 12 Branch 2)%Read
AV135948258_12_2Branch Current Neutral (Branch PB 12 Branch 2)ARead
AV135958260_12_2Branch Neutral Overcurrent Warning Threshold (Branch PB 12 Branch 2)%Read
AV135968261_12_2Branch Neutral Overcurrent Alarm Threshold (Branch PB 12 Branch 2)%Read
AV135978437_12_2Load Loss Min Load (Branch PB 12 Branch 2)%Read
AV146577808_12_42Branch Position (Branch PB 12 Branch 42)Read
AV146587809_12_42Branch Current Rating (Branch PB 12 Branch 42)ARead
AV146597810_12_42Branch Current L1 (Branch PB 12 Branch 42)ARead
AV146607811_12_42Branch Current L2 (Branch PB 12 Branch 42)ARead
AV146617812_12_42Branch Current L3 (Branch PB 12 Branch 42)ARead
AV146627813_12_42Branch Real Power (Branch PB 12 Branch 42)kWRead
AV146637814_12_42Branch Power Factor (Branch PB 12 Branch 42)Read
AV146647815_12_42Branch Energy (Branch PB 12 Branch 42)kWhRead
AV146657816_12_42Branch Highest Phase Current Load (Branch PB 12 Branch 42)%Read
AV146667817_12_42Branch Peak Current L1 (Branch PB 12 Branch 42)ARead
AV146677818_12_42Branch Peak Current L2 (Branch PB 12 Branch 42)ARead
AV146687819_12_42Branch Peak Current L3 (Branch PB 12 Branch 42)ARead
AV146697820_12_42Branch Highest Phase Peak Current (Branch PB 12 Branch 42)ARead
AV146707821_12_42Branch Peak Demand (Branch PB 12 Branch 42)kWRead
AV146717825_12_42Branch Overcurrent Warning Threshold (Branch PB 12 Branch 42)%Read
AV146727826_12_42Branch Overcurrent Alarm Threshold (Branch PB 12 Branch 42)%Read
AV146737827_12_42Branch Low Current Alarm Threshold (Branch PB 12 Branch 42)%Read
AV146748258_12_42Branch Current Neutral (Branch PB 12 Branch 42)ARead
AV146758260_12_42Branch Neutral Overcurrent Warning Threshold (Branch PB 12 Branch 42)%Read
AV146768261_12_42Branch Neutral Overcurrent Alarm Threshold (Branch PB 12 Branch 42)%Read
AV146778437_12_42Load Loss Min Load (Branch PB 12 Branch 42)%Read
AV146847833_1Panelboard Subfeed Count (Subfeed PB 1)Read
AV146857834_1Panelboard Current Ph A (Subfeed PB 1)ARead
AV146867835_1Panelboard Current Ph B (Subfeed PB 1)ARead
AV146877836_1Panelboard Current Ph C (Subfeed PB 1)ARead
AV146887837_1Panelboard Neutral Current (Subfeed PB 1)ARead
AV146897838_1Panelboard Ground Current (Subfeed PB 1)ARead
AV146907839_1Panelboard Current Load Ph A (Subfeed PB 1)%Read
AV146917840_1Panelboard Current Load Ph B (Subfeed PB 1)%Read
AV146927841_1Panelboard Current Load Ph C (Subfeed PB 1)%Read
AV146937842_1Panelboard Highest Phase Current Load (Subfeed PB 1)%Read
AV146947843_1Panelboard Voltage (L-L) A-B (Subfeed PB 1)VRead
AV146957844_1Panelboard Voltage (L-L) B-C (Subfeed PB 1)VRead
AV146967845_1Panelboard Voltage (L-L) C-A (Subfeed PB 1)VRead
AV146977846_1Panelboard Voltage (L-N) A-N (Subfeed PB 1)VRead
AV146987847_1Panelboard Voltage (L-N) B-N (Subfeed PB 1)VRead
AV146997848_1Panelboard Voltage (L-N) C-N (Subfeed PB 1)VRead
AV147007849_1Panelboard Frequency (Subfeed PB 1)HzRead
AV147017850_1Panelboard Real Power (Subfeed PB 1)kWRead
AV147027851_1Panelboard Apparent Power (Subfeed PB 1)kVARead
AV147037852_1Panelboard Power Factor Ph A (Subfeed PB 1)Read
AV147047853_1Panelboard Power Factor Ph B (Subfeed PB 1)Read
AV147057854_1Panelboard Power Factor Ph C (Subfeed PB 1)Read
AV147067855_1Panelboard Power Factor Total (Subfeed PB 1)Read
AV147077856_1Panelboard Energy (Subfeed PB 1)kWhRead
AV147087857_1Panelboard Peak Current Ph A (Subfeed PB 1)ARead
AV147097858_1Panelboard Peak Current Ph B (Subfeed PB 1)ARead
AV147107859_1Panelboard Peak Current Ph C (Subfeed PB 1)ARead
AV147117860_1Panelboard Highest Phase Peak Current (Subfeed PB 1)ARead
AV147127861_1Panelboard Peak Demand (Subfeed PB 1)kWRead
AV147137862_1Panelboard Current Crest Factor Ph A (Subfeed PB 1)Read
AV147147863_1Panelboard Current Crest Factor Ph B (Subfeed PB 1)Read
AV147157864_1Panelboard Current Crest Factor Ph C (Subfeed PB 1)Read
AV147167865_1Panelboard iTHD Ph A (Subfeed PB 1)%Read
AV147177866_1Panelboard iTHD Ph B (Subfeed PB 1)%Read
AV147187867_1Panelboard iTHD Ph C (Subfeed PB 1)%Read
AV147197868_1Panelboard Current 3rd Harmonic Ph A (Subfeed PB 1)%Read
AV147207869_1Panelboard Current 3rd Harmonic Ph B (Subfeed PB 1)%Read
AV147217870_1Panelboard Current 3rd Harmonic Ph C (Subfeed PB 1)%Read
AV147227871_1Panelboard Current 5th Harmonic Ph A (Subfeed PB 1)%Read
AV147237872_1Panelboard Current 5th Harmonic Ph B (Subfeed PB 1)%Read
AV147247873_1Panelboard Current 5th Harmonic Ph C (Subfeed PB 1)%Read
AV147257874_1Panelboard Current 7th Harmonic Ph A (Subfeed PB 1)%Read
AV147267875_1Panelboard Current 7th Harmonic Ph B (Subfeed PB 1)%Read
AV147277876_1Panelboard Current 7th Harmonic Ph C (Subfeed PB 1)%Read
AV147287877_1Panelboard Current 9th Harmonic Ph A (Subfeed PB 1)%Read
AV147297878_1Panelboard Current 9th Harmonic Ph B (Subfeed PB 1)%Read
AV147307879_1Panelboard Current 9th Harmonic Ph C (Subfeed PB 1)%Read
AV147317880_1Panelboard vTHD Ph A (Subfeed PB 1)%Read
AV147327881_1Panelboard vTHD Ph B (Subfeed PB 1)%Read
AV147337882_1Panelboard vTHD Ph C (Subfeed PB 1)%Read
AV147347883_1Panelboard Voltage 3rd Harmonic Ph A (Subfeed PB 1)%Read
AV147357884_1Panelboard Voltage 3rd Harmonic Ph B (Subfeed PB 1)%Read
AV147367885_1Panelboard Voltage 3rd Harmonic Ph C (Subfeed PB 1)%Read
AV147377886_1Panelboard Voltage 5th Harmonic Ph A (Subfeed PB 1)%Read
AV147387887_1Panelboard Voltage 5th Harmonic Ph B (Subfeed PB 1)%Read
AV147397888_1Panelboard Voltage 5th Harmonic Ph C (Subfeed PB 1)%Read
AV147407889_1Panelboard Voltage 7th Harmonic Ph A (Subfeed PB 1)%Read
AV147417890_1Panelboard Voltage 7th Harmonic Ph B (Subfeed PB 1)%Read
AV147427891_1Panelboard Voltage 7th Harmonic Ph C (Subfeed PB 1)%Read
AV147437892_1Panelboard Voltage 9th Harmonic Ph A (Subfeed PB 1)%Read
AV147447893_1Panelboard Voltage 9th Harmonic Ph B (Subfeed PB 1)%Read
AV147457894_1Panelboard Voltage 9th Harmonic Ph C (Subfeed PB 1)%Read
AV147467902_1Panelboard Phase Overcurrent Warning Threshold (Subfeed PB 1)%Read
AV147477903_1Panelboard Phase Overcurrent Alarm Threshold (Subfeed PB 1)%Read
AV147487904_1Panelboard Neutral Overcurrent Alarm Threshold (Subfeed PB 1)%Read
AV147497905_1Panelboard Ground Overcurrent Alarm Threshold (Subfeed PB 1)ARead
AV147508278_1Panelboard Neutral Overcurrent Warning Threshold (Subfeed PB 1)%Read
AV147518265_1Panelboard Phase Overvoltage Alarm Threshold (Subfeed PB 1)%Read
AV147528266_1Panelboard Phase Undervoltage Alarm Threshold (Subfeed PB 1)%Read
AV147607912_1_1Subfeed Current Rating (Subfeed PB 1 Subfeed 1)ARead
AV147617913_1_1Subfeed Current Ph A (Subfeed PB 1 Subfeed 1)ARead
AV147627914_1_1Subfeed Current Ph B (Subfeed PB 1 Subfeed 1)ARead
AV147637915_1_1Subfeed Current Ph C (Subfeed PB 1 Subfeed 1)ARead
AV147647916_1_1Subfeed Neutral Current (Subfeed PB 1 Subfeed 1)ARead
AV147657917_1_1Subfeed Ground Current (Subfeed PB 1 Subfeed 1)ARead
AV147667918_1_1Subfeed Current Load Ph A (Subfeed PB 1 Subfeed 1)%Read
AV147677919_1_1Subfeed Current Load Ph B (Subfeed PB 1 Subfeed 1)%Read
AV147687920_1_1Subfeed Current Load Ph C (Subfeed PB 1 Subfeed 1)%Read
AV147697921_1_1Subfeed Highest Phase Current Load (Subfeed PB 1 Subfeed 1)%Read
AV147707922_1_1Subfeed Real Power (Subfeed PB 1 Subfeed 1)kWRead
AV147717923_1_1Subfeed Apparent Power (Subfeed PB 1 Subfeed 1)kVARead
AV147727924_1_1Subfeed Power Factor Ph A (Subfeed PB 1 Subfeed 1)Read
AV147737925_1_1Subfeed Power Factor Ph B (Subfeed PB 1 Subfeed 1)Read
AV147747926_1_1Subfeed Power Factor Ph C (Subfeed PB 1 Subfeed 1)Read
AV147757927_1_1Subfeed Power Factor Total (Subfeed PB 1 Subfeed 1)Read
AV147767928_1_1Subfeed Energy (Subfeed PB 1 Subfeed 1)kWhRead
AV147777929_1_1Subfeed Peak Current Ph A (Subfeed PB 1 Subfeed 1)ARead
AV147787930_1_1Subfeed Peak Current Ph B (Subfeed PB 1 Subfeed 1)ARead
AV147797931_1_1Subfeed Peak Current Ph C (Subfeed PB 1 Subfeed 1)ARead
AV147807932_1_1Subfeed Highest Phase Peak Current (Subfeed PB 1 Subfeed 1)ARead
AV147817933_1_1Subfeed Peak Demand (Subfeed PB 1 Subfeed 1)kWRead
AV147827934_1_1Subfeed Current Crest Factor Ph A (Subfeed PB 1 Subfeed 1)Read
AV147837935_1_1Subfeed Current Crest Factor Ph B (Subfeed PB 1 Subfeed 1)Read
AV147847936_1_1Subfeed Current Crest Factor Ph C (Subfeed PB 1 Subfeed 1)Read
AV147857937_1_1Subfeed iTHD Ph A (Subfeed PB 1 Subfeed 1)%Read
AV147867938_1_1Subfeed iTHD Ph B (Subfeed PB 1 Subfeed 1)%Read
AV147877939_1_1Subfeed iTHD Ph C (Subfeed PB 1 Subfeed 1)%Read
AV147887940_1_1Subfeed Current 3rd Harmonic Ph A (Subfeed PB 1 Subfeed 1)%Read
AV147897941_1_1Subfeed Current 3rd Harmonic Ph B (Subfeed PB 1 Subfeed 1)%Read
AV147907942_1_1Subfeed Current 3rd Harmonic Ph C (Subfeed PB 1 Subfeed 1)%Read
AV147917943_1_1Subfeed Current 5th Harmonic Ph A (Subfeed PB 1 Subfeed 1)%Read
AV147927944_1_1Subfeed Current 5th Harmonic Ph B (Subfeed PB 1 Subfeed 1)%Read
AV147937945_1_1Subfeed Current 5th Harmonic Ph C (Subfeed PB 1 Subfeed 1)%Read
AV147947946_1_1Subfeed Current 7th Harmonic Ph A (Subfeed PB 1 Subfeed 1)%Read
AV147957947_1_1Subfeed Current 7th Harmonic Ph B (Subfeed PB 1 Subfeed 1)%Read
AV147967948_1_1Subfeed Current 7th Harmonic Ph C (Subfeed PB 1 Subfeed 1)%Read
AV147977949_1_1Subfeed Current 9th Harmonic Ph A (Subfeed PB 1 Subfeed 1)%Read
AV147987950_1_1Subfeed Current 9th Harmonic Ph B (Subfeed PB 1 Subfeed 1)%Read
AV147997951_1_1Subfeed Current 9th Harmonic Ph C (Subfeed PB 1 Subfeed 1)%Read
AV148007959_1_1Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 1)%Read
AV148017960_1_1Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 1 Subfeed 1)%Read
AV148027961_1_1Subfeed Neutral Overcurrent Threshold (Subfeed PB 1 Subfeed 1)%Read
AV148038279_1_1Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 1)%Read
AV148137912_1_2Subfeed Current Rating (Subfeed PB 1 Subfeed 2)ARead
AV148147913_1_2Subfeed Current Ph A (Subfeed PB 1 Subfeed 2)ARead
AV148157914_1_2Subfeed Current Ph B (Subfeed PB 1 Subfeed 2)ARead
AV148167915_1_2Subfeed Current Ph C (Subfeed PB 1 Subfeed 2)ARead
AV148177916_1_2Subfeed Neutral Current (Subfeed PB 1 Subfeed 2)ARead
AV148187917_1_2Subfeed Ground Current (Subfeed PB 1 Subfeed 2)ARead
AV148197918_1_2Subfeed Current Load Ph A (Subfeed PB 1 Subfeed 2)%Read
AV148207919_1_2Subfeed Current Load Ph B (Subfeed PB 1 Subfeed 2)%Read
AV148217920_1_2Subfeed Current Load Ph C (Subfeed PB 1 Subfeed 2)%Read
AV148227921_1_2Subfeed Highest Phase Current Load (Subfeed PB 1 Subfeed 2)%Read
AV148237922_1_2Subfeed Real Power (Subfeed PB 1 Subfeed 2)kWRead
AV148247923_1_2Subfeed Apparent Power (Subfeed PB 1 Subfeed 2)kVARead
AV148257924_1_2Subfeed Power Factor Ph A (Subfeed PB 1 Subfeed 2)Read
AV148267925_1_2Subfeed Power Factor Ph B (Subfeed PB 1 Subfeed 2)Read
AV148277926_1_2Subfeed Power Factor Ph C (Subfeed PB 1 Subfeed 2)Read
AV148287927_1_2Subfeed Power Factor Total (Subfeed PB 1 Subfeed 2)Read
AV148297928_1_2Subfeed Energy (Subfeed PB 1 Subfeed 2)kWhRead
AV148307929_1_2Subfeed Peak Current Ph A (Subfeed PB 1 Subfeed 2)ARead
AV148317930_1_2Subfeed Peak Current Ph B (Subfeed PB 1 Subfeed 2)ARead
AV148327931_1_2Subfeed Peak Current Ph C (Subfeed PB 1 Subfeed 2)ARead
AV148337932_1_2Subfeed Highest Phase Peak Current (Subfeed PB 1 Subfeed 2)ARead
AV148347933_1_2Subfeed Peak Demand (Subfeed PB 1 Subfeed 2)kWRead
AV148357934_1_2Subfeed Current Crest Factor Ph A (Subfeed PB 1 Subfeed 2)Read
AV148367935_1_2Subfeed Current Crest Factor Ph B (Subfeed PB 1 Subfeed 2)Read
AV148377936_1_2Subfeed Current Crest Factor Ph C (Subfeed PB 1 Subfeed 2)Read
AV148387937_1_2Subfeed iTHD Ph A (Subfeed PB 1 Subfeed 2)%Read
AV148397938_1_2Subfeed iTHD Ph B (Subfeed PB 1 Subfeed 2)%Read
AV148407939_1_2Subfeed iTHD Ph C (Subfeed PB 1 Subfeed 2)%Read
AV148417940_1_2Subfeed Current 3rd Harmonic Ph A (Subfeed PB 1 Subfeed 2)%Read
AV148427941_1_2Subfeed Current 3rd Harmonic Ph B (Subfeed PB 1 Subfeed 2)%Read
AV148437942_1_2Subfeed Current 3rd Harmonic Ph C (Subfeed PB 1 Subfeed 2)%Read
AV148447943_1_2Subfeed Current 5th Harmonic Ph A (Subfeed PB 1 Subfeed 2)%Read
AV148457944_1_2Subfeed Current 5th Harmonic Ph B (Subfeed PB 1 Subfeed 2)%Read
AV148467945_1_2Subfeed Current 5th Harmonic Ph C (Subfeed PB 1 Subfeed 2)%Read
AV148477946_1_2Subfeed Current 7th Harmonic Ph A (Subfeed PB 1 Subfeed 2)%Read
AV148487947_1_2Subfeed Current 7th Harmonic Ph B (Subfeed PB 1 Subfeed 2)%Read
AV148497948_1_2Subfeed Current 7th Harmonic Ph C (Subfeed PB 1 Subfeed 2)%Read
AV148507949_1_2Subfeed Current 9th Harmonic Ph A (Subfeed PB 1 Subfeed 2)%Read
AV148517950_1_2Subfeed Current 9th Harmonic Ph B (Subfeed PB 1 Subfeed 2)%Read
AV148527951_1_2Subfeed Current 9th Harmonic Ph C (Subfeed PB 1 Subfeed 2)%Read
AV148537959_1_2Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 2)%Read
AV148547960_1_2Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 1 Subfeed 2)%Read
AV148557961_1_2Subfeed Neutral Overcurrent Threshold (Subfeed PB 1 Subfeed 2)%Read
AV148568279_1_2Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 2)%Read
AV153437912_1_12Subfeed Current Rating (Subfeed PB 1 Subfeed 12)ARead
AV153447913_1_12Subfeed Current Ph A (Subfeed PB 1 Subfeed 12)ARead
AV153457914_1_12Subfeed Current Ph B (Subfeed PB 1 Subfeed 12)ARead
AV153467915_1_12Subfeed Current Ph C (Subfeed PB 1 Subfeed 12)ARead
AV153477916_1_12Subfeed Neutral Current (Subfeed PB 1 Subfeed 12)ARead
AV153487917_1_12Subfeed Ground Current (Subfeed PB 1 Subfeed 12)ARead
AV153497918_1_12Subfeed Current Load Ph A (Subfeed PB 1 Subfeed 12)%Read
AV153507919_1_12Subfeed Current Load Ph B (Subfeed PB 1 Subfeed 12)%Read
AV153517920_1_12Subfeed Current Load Ph C (Subfeed PB 1 Subfeed 12)%Read
AV153527921_1_12Subfeed Highest Phase Current Load (Subfeed PB 1 Subfeed 12)%Read
AV153537922_1_12Subfeed Real Power (Subfeed PB 1 Subfeed 12)kWRead
AV153547923_1_12Subfeed Apparent Power (Subfeed PB 1 Subfeed 12)kVARead
AV153557924_1_12Subfeed Power Factor Ph A (Subfeed PB 1 Subfeed 12)Read
AV153567925_1_12Subfeed Power Factor Ph B (Subfeed PB 1 Subfeed 12)Read
AV153577926_1_12Subfeed Power Factor Ph C (Subfeed PB 1 Subfeed 12)Read
AV153587927_1_12Subfeed Power Factor Total (Subfeed PB 1 Subfeed 12)Read
AV153597928_1_12Subfeed Energy (Subfeed PB 1 Subfeed 12)kWhRead
AV153607929_1_12Subfeed Peak Current Ph A (Subfeed PB 1 Subfeed 12)ARead
AV153617930_1_12Subfeed Peak Current Ph B (Subfeed PB 1 Subfeed 12)ARead
AV153627931_1_12Subfeed Peak Current Ph C (Subfeed PB 1 Subfeed 12)ARead
AV153637932_1_12Subfeed Highest Phase Peak Current (Subfeed PB 1 Subfeed 12)ARead
AV153647933_1_12Subfeed Peak Demand (Subfeed PB 1 Subfeed 12)kWRead
AV153657934_1_12Subfeed Current Crest Factor Ph A (Subfeed PB 1 Subfeed 12)Read
AV153667935_1_12Subfeed Current Crest Factor Ph B (Subfeed PB 1 Subfeed 12)Read
AV153677936_1_12Subfeed Current Crest Factor Ph C (Subfeed PB 1 Subfeed 12)Read
AV153687937_1_12Subfeed iTHD Ph A (Subfeed PB 1 Subfeed 12)%Read
AV153697938_1_12Subfeed iTHD Ph B (Subfeed PB 1 Subfeed 12)%Read
AV153707939_1_12Subfeed iTHD Ph C (Subfeed PB 1 Subfeed 12)%Read
AV153717940_1_12Subfeed Current 3rd Harmonic Ph A (Subfeed PB 1 Subfeed 12)%Read
AV153727941_1_12Subfeed Current 3rd Harmonic Ph B (Subfeed PB 1 Subfeed 12)%Read
AV153737942_1_12Subfeed Current 3rd Harmonic Ph C (Subfeed PB 1 Subfeed 12)%Read
AV153747943_1_12Subfeed Current 5th Harmonic Ph A (Subfeed PB 1 Subfeed 12)%Read
AV153757944_1_12Subfeed Current 5th Harmonic Ph B (Subfeed PB 1 Subfeed 12)%Read
AV153767945_1_12Subfeed Current 5th Harmonic Ph C (Subfeed PB 1 Subfeed 12)%Read
AV153777946_1_12Subfeed Current 7th Harmonic Ph A (Subfeed PB 1 Subfeed 12)%Read
AV153787947_1_12Subfeed Current 7th Harmonic Ph B (Subfeed PB 1 Subfeed 12)%Read
AV153797948_1_12Subfeed Current 7th Harmonic Ph C (Subfeed PB 1 Subfeed 12)%Read
AV153807949_1_12Subfeed Current 9th Harmonic Ph A (Subfeed PB 1 Subfeed 12)%Read
AV153817950_1_12Subfeed Current 9th Harmonic Ph B (Subfeed PB 1 Subfeed 12)%Read
AV153827951_1_12Subfeed Current 9th Harmonic Ph C (Subfeed PB 1 Subfeed 12)%Read
AV153837959_1_12Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 12)%Read
AV153847960_1_12Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 1 Subfeed 12)%Read
AV153857961_1_12Subfeed Neutral Overcurrent Threshold (Subfeed PB 1 Subfeed 12)%Read
AV153868279_1_12Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 1 Subfeed 12)%Read
AV153967833_2Panelboard Subfeed Count (Subfeed PB 2)Read
AV153977834_2Panelboard Current Ph A (Subfeed PB 2)ARead
AV153987835_2Panelboard Current Ph B (Subfeed PB 2)ARead
AV153997836_2Panelboard Current Ph C (Subfeed PB 2)ARead
AV154007837_2Panelboard Neutral Current (Subfeed PB 2)ARead
AV154017838_2Panelboard Ground Current (Subfeed PB 2)ARead
AV154027839_2Panelboard Current Load Ph A (Subfeed PB 2)%Read
AV154037840_2Panelboard Current Load Ph B (Subfeed PB 2)%Read
AV154047841_2Panelboard Current Load Ph C (Subfeed PB 2)%Read
AV154057842_2Panelboard Highest Phase Current Load (Subfeed PB 2)%Read
AV154067843_2Panelboard Voltage (L-L) A-B (Subfeed PB 2)VRead
AV154077844_2Panelboard Voltage (L-L) B-C (Subfeed PB 2)VRead
AV154087845_2Panelboard Voltage (L-L) C-A (Subfeed PB 2)VRead
AV154097846_2Panelboard Voltage (L-N) A-N (Subfeed PB 2)VRead
AV154107847_2Panelboard Voltage (L-N) B-N (Subfeed PB 2)VRead
AV154117848_2Panelboard Voltage (L-N) C-N (Subfeed PB 2)VRead
AV154127849_2Panelboard Frequency (Subfeed PB 2)HzRead
AV154137850_2Panelboard Real Power (Subfeed PB 2)kWRead
AV154147851_2Panelboard Apparent Power (Subfeed PB 2)kVARead
AV154157852_2Panelboard Power Factor Ph A (Subfeed PB 2)Read
AV154167853_2Panelboard Power Factor Ph B (Subfeed PB 2)Read
AV154177854_2Panelboard Power Factor Ph C (Subfeed PB 2)Read
AV154187855_2Panelboard Power Factor Total (Subfeed PB 2)Read
AV154197856_2Panelboard Energy (Subfeed PB 2)kWhRead
AV154207857_2Panelboard Peak Current Ph A (Subfeed PB 2)ARead
AV154217858_2Panelboard Peak Current Ph B (Subfeed PB 2)ARead
AV154227859_2Panelboard Peak Current Ph C (Subfeed PB 2)ARead
AV154237860_2Panelboard Highest Phase Peak Current (Subfeed PB 2)ARead
AV154247861_2Panelboard Peak Demand (Subfeed PB 2)kWRead
AV154257862_2Panelboard Current Crest Factor Ph A (Subfeed PB 2)Read
AV154267863_2Panelboard Current Crest Factor Ph B (Subfeed PB 2)Read
AV154277864_2Panelboard Current Crest Factor Ph C (Subfeed PB 2)Read
AV154287865_2Panelboard iTHD Ph A (Subfeed PB 2)%Read
AV154297866_2Panelboard iTHD Ph B (Subfeed PB 2)%Read
AV154307867_2Panelboard iTHD Ph C (Subfeed PB 2)%Read
AV154317868_2Panelboard Current 3rd Harmonic Ph A (Subfeed PB 2)%Read
AV154327869_2Panelboard Current 3rd Harmonic Ph B (Subfeed PB 2)%Read
AV154337870_2Panelboard Current 3rd Harmonic Ph C (Subfeed PB 2)%Read
AV154347871_2Panelboard Current 5th Harmonic Ph A (Subfeed PB 2)%Read
AV154357872_2Panelboard Current 5th Harmonic Ph B (Subfeed PB 2)%Read
AV154367873_2Panelboard Current 5th Harmonic Ph C (Subfeed PB 2)%Read
AV154377874_2Panelboard Current 7th Harmonic Ph A (Subfeed PB 2)%Read
AV154387875_2Panelboard Current 7th Harmonic Ph B (Subfeed PB 2)%Read
AV154397876_2Panelboard Current 7th Harmonic Ph C (Subfeed PB 2)%Read
AV154407877_2Panelboard Current 9th Harmonic Ph A (Subfeed PB 2)%Read
AV154417878_2Panelboard Current 9th Harmonic Ph B (Subfeed PB 2)%Read
AV154427879_2Panelboard Current 9th Harmonic Ph C (Subfeed PB 2)%Read
AV154437880_2Panelboard vTHD Ph A (Subfeed PB 2)%Read
AV154447881_2Panelboard vTHD Ph B (Subfeed PB 2)%Read
AV154457882_2Panelboard vTHD Ph C (Subfeed PB 2)%Read
AV154467883_2Panelboard Voltage 3rd Harmonic Ph A (Subfeed PB 2)%Read
AV154477884_2Panelboard Voltage 3rd Harmonic Ph B (Subfeed PB 2)%Read
AV154487885_2Panelboard Voltage 3rd Harmonic Ph C (Subfeed PB 2)%Read
AV154497886_2Panelboard Voltage 5th Harmonic Ph A (Subfeed PB 2)%Read
AV154507887_2Panelboard Voltage 5th Harmonic Ph B (Subfeed PB 2)%Read
AV154517888_2Panelboard Voltage 5th Harmonic Ph C (Subfeed PB 2)%Read
AV154527889_2Panelboard Voltage 7th Harmonic Ph A (Subfeed PB 2)%Read
AV154537890_2Panelboard Voltage 7th Harmonic Ph B (Subfeed PB 2)%Read
AV154547891_2Panelboard Voltage 7th Harmonic Ph C (Subfeed PB 2)%Read
AV154557892_2Panelboard Voltage 9th Harmonic Ph A (Subfeed PB 2)%Read
AV154567893_2Panelboard Voltage 9th Harmonic Ph B (Subfeed PB 2)%Read
AV154577894_2Panelboard Voltage 9th Harmonic Ph C (Subfeed PB 2)%Read
AV154587902_2Panelboard Phase Overcurrent Warning Threshold (Subfeed PB 2)%Read
AV154597903_2Panelboard Phase Overcurrent Alarm Threshold (Subfeed PB 2)%Read
AV154607904_2Panelboard Neutral Overcurrent Alarm Threshold (Subfeed PB 2)%Read
AV154617905_2Panelboard Ground Overcurrent Alarm Threshold (Subfeed PB 2)ARead
AV154628278_2Panelboard Neutral Overcurrent Warning Threshold (Subfeed PB 2)%Read
AV154638265_2Panelboard Phase Overvoltage Alarm Threshold (Subfeed PB 2)%Read
AV154648266_2Panelboard Phase Undervoltage Alarm Threshold (Subfeed PB 2)%Read
AV154727912_2_1Subfeed Current Rating (Subfeed PB 2 Subfeed 1)ARead
AV154737913_2_1Subfeed Current Ph A (Subfeed PB 2 Subfeed 1)ARead
AV154747914_2_1Subfeed Current Ph B (Subfeed PB 2 Subfeed 1)ARead
AV154757915_2_1Subfeed Current Ph C (Subfeed PB 2 Subfeed 1)ARead
AV154767916_2_1Subfeed Neutral Current (Subfeed PB 2 Subfeed 1)ARead
AV154777917_2_1Subfeed Ground Current (Subfeed PB 2 Subfeed 1)ARead
AV154787918_2_1Subfeed Current Load Ph A (Subfeed PB 2 Subfeed 1)%Read
AV154797919_2_1Subfeed Current Load Ph B (Subfeed PB 2 Subfeed 1)%Read
AV154807920_2_1Subfeed Current Load Ph C (Subfeed PB 2 Subfeed 1)%Read
AV154817921_2_1Subfeed Highest Phase Current Load (Subfeed PB 2 Subfeed 1)%Read
AV154827922_2_1Subfeed Real Power (Subfeed PB 2 Subfeed 1)kWRead
AV154837923_2_1Subfeed Apparent Power (Subfeed PB 2 Subfeed 1)kVARead
AV154847924_2_1Subfeed Power Factor Ph A (Subfeed PB 2 Subfeed 1)Read
AV154857925_2_1Subfeed Power Factor Ph B (Subfeed PB 2 Subfeed 1)Read
AV154867926_2_1Subfeed Power Factor Ph C (Subfeed PB 2 Subfeed 1)Read
AV154877927_2_1Subfeed Power Factor Total (Subfeed PB 2 Subfeed 1)Read
AV154887928_2_1Subfeed Energy (Subfeed PB 2 Subfeed 1)kWhRead
AV154897929_2_1Subfeed Peak Current Ph A (Subfeed PB 2 Subfeed 1)ARead
AV154907930_2_1Subfeed Peak Current Ph B (Subfeed PB 2 Subfeed 1)ARead
AV154917931_2_1Subfeed Peak Current Ph C (Subfeed PB 2 Subfeed 1)ARead
AV154927932_2_1Subfeed Highest Phase Peak Current (Subfeed PB 2 Subfeed 1)ARead
AV154937933_2_1Subfeed Peak Demand (Subfeed PB 2 Subfeed 1)kWRead
AV154947934_2_1Subfeed Current Crest Factor Ph A (Subfeed PB 2 Subfeed 1)Read
AV154957935_2_1Subfeed Current Crest Factor Ph B (Subfeed PB 2 Subfeed 1)Read
AV154967936_2_1Subfeed Current Crest Factor Ph C (Subfeed PB 2 Subfeed 1)Read
AV154977937_2_1Subfeed iTHD Ph A (Subfeed PB 2 Subfeed 1)%Read
AV154987938_2_1Subfeed iTHD Ph B (Subfeed PB 2 Subfeed 1)%Read
AV154997939_2_1Subfeed iTHD Ph C (Subfeed PB 2 Subfeed 1)%Read
AV155007940_2_1Subfeed Current 3rd Harmonic Ph A (Subfeed PB 2 Subfeed 1)%Read
AV155017941_2_1Subfeed Current 3rd Harmonic Ph B (Subfeed PB 2 Subfeed 1)%Read
AV155027942_2_1Subfeed Current 3rd Harmonic Ph C (Subfeed PB 2 Subfeed 1)%Read
AV155037943_2_1Subfeed Current 5th Harmonic Ph A (Subfeed PB 2 Subfeed 1)%Read
AV155047944_2_1Subfeed Current 5th Harmonic Ph B (Subfeed PB 2 Subfeed 1)%Read
AV155057945_2_1Subfeed Current 5th Harmonic Ph C (Subfeed PB 2 Subfeed 1)%Read
AV155067946_2_1Subfeed Current 7th Harmonic Ph A (Subfeed PB 2 Subfeed 1)%Read
AV155077947_2_1Subfeed Current 7th Harmonic Ph B (Subfeed PB 2 Subfeed 1)%Read
AV155087948_2_1Subfeed Current 7th Harmonic Ph C (Subfeed PB 2 Subfeed 1)%Read
AV155097949_2_1Subfeed Current 9th Harmonic Ph A (Subfeed PB 2 Subfeed 1)%Read
AV155107950_2_1Subfeed Current 9th Harmonic Ph B (Subfeed PB 2 Subfeed 1)%Read
AV155117951_2_1Subfeed Current 9th Harmonic Ph C (Subfeed PB 2 Subfeed 1)%Read
AV155127959_2_1Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 1)%Read
AV155137960_2_1Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 2 Subfeed 1)%Read
AV155147961_2_1Subfeed Neutral Overcurrent Threshold (Subfeed PB 2 Subfeed 1)%Read
AV155158279_2_1Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 1)%Read
AV155257912_2_2Subfeed Current Rating (Subfeed PB 2 Subfeed 2)ARead
AV155267913_2_2Subfeed Current Ph A (Subfeed PB 2 Subfeed 2)ARead
AV155277914_2_2Subfeed Current Ph B (Subfeed PB 2 Subfeed 2)ARead
AV155287915_2_2Subfeed Current Ph C (Subfeed PB 2 Subfeed 2)ARead
AV155297916_2_2Subfeed Neutral Current (Subfeed PB 2 Subfeed 2)ARead
AV155307917_2_2Subfeed Ground Current (Subfeed PB 2 Subfeed 2)ARead
AV155317918_2_2Subfeed Current Load Ph A (Subfeed PB 2 Subfeed 2)%Read
AV155327919_2_2Subfeed Current Load Ph B (Subfeed PB 2 Subfeed 2)%Read
AV155337920_2_2Subfeed Current Load Ph C (Subfeed PB 2 Subfeed 2)%Read
AV155347921_2_2Subfeed Highest Phase Current Load (Subfeed PB 2 Subfeed 2)%Read
AV155357922_2_2Subfeed Real Power (Subfeed PB 2 Subfeed 2)kWRead
AV155367923_2_2Subfeed Apparent Power (Subfeed PB 2 Subfeed 2)kVARead
AV155377924_2_2Subfeed Power Factor Ph A (Subfeed PB 2 Subfeed 2)Read
AV155387925_2_2Subfeed Power Factor Ph B (Subfeed PB 2 Subfeed 2)Read
AV155397926_2_2Subfeed Power Factor Ph C (Subfeed PB 2 Subfeed 2)Read
AV155407927_2_2Subfeed Power Factor Total (Subfeed PB 2 Subfeed 2)Read
AV155417928_2_2Subfeed Energy (Subfeed PB 2 Subfeed 2)kWhRead
AV155427929_2_2Subfeed Peak Current Ph A (Subfeed PB 2 Subfeed 2)ARead
AV155437930_2_2Subfeed Peak Current Ph B (Subfeed PB 2 Subfeed 2)ARead
AV155447931_2_2Subfeed Peak Current Ph C (Subfeed PB 2 Subfeed 2)ARead
AV155457932_2_2Subfeed Highest Phase Peak Current (Subfeed PB 2 Subfeed 2)ARead
AV155467933_2_2Subfeed Peak Demand (Subfeed PB 2 Subfeed 2)kWRead
AV155477934_2_2Subfeed Current Crest Factor Ph A (Subfeed PB 2 Subfeed 2)Read
AV155487935_2_2Subfeed Current Crest Factor Ph B (Subfeed PB 2 Subfeed 2)Read
AV155497936_2_2Subfeed Current Crest Factor Ph C (Subfeed PB 2 Subfeed 2)Read
AV155507937_2_2Subfeed iTHD Ph A (Subfeed PB 2 Subfeed 2)%Read
AV155517938_2_2Subfeed iTHD Ph B (Subfeed PB 2 Subfeed 2)%Read
AV155527939_2_2Subfeed iTHD Ph C (Subfeed PB 2 Subfeed 2)%Read
AV155537940_2_2Subfeed Current 3rd Harmonic Ph A (Subfeed PB 2 Subfeed 2)%Read
AV155547941_2_2Subfeed Current 3rd Harmonic Ph B (Subfeed PB 2 Subfeed 2)%Read
AV155557942_2_2Subfeed Current 3rd Harmonic Ph C (Subfeed PB 2 Subfeed 2)%Read
AV155567943_2_2Subfeed Current 5th Harmonic Ph A (Subfeed PB 2 Subfeed 2)%Read
AV155577944_2_2Subfeed Current 5th Harmonic Ph B (Subfeed PB 2 Subfeed 2)%Read
AV155587945_2_2Subfeed Current 5th Harmonic Ph C (Subfeed PB 2 Subfeed 2)%Read
AV155597946_2_2Subfeed Current 7th Harmonic Ph A (Subfeed PB 2 Subfeed 2)%Read
AV155607947_2_2Subfeed Current 7th Harmonic Ph B (Subfeed PB 2 Subfeed 2)%Read
AV155617948_2_2Subfeed Current 7th Harmonic Ph C (Subfeed PB 2 Subfeed 2)%Read
AV155627949_2_2Subfeed Current 9th Harmonic Ph A (Subfeed PB 2 Subfeed 2)%Read
AV155637950_2_2Subfeed Current 9th Harmonic Ph B (Subfeed PB 2 Subfeed 2)%Read
AV155647951_2_2Subfeed Current 9th Harmonic Ph C (Subfeed PB 2 Subfeed 2)%Read
AV155657959_2_2Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 2)%Read
AV155667960_2_2Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 2 Subfeed 2)%Read
AV155677961_2_2Subfeed Neutral Overcurrent Threshold (Subfeed PB 2 Subfeed 2)%Read
AV155688279_2_2Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 2)%Read
AV160557912_2_12Subfeed Current Rating (Subfeed PB 2 Subfeed 12)ARead
AV160567913_2_12Subfeed Current Ph A (Subfeed PB 2 Subfeed 12)ARead
AV160577914_2_12Subfeed Current Ph B (Subfeed PB 2 Subfeed 12)ARead
AV160587915_2_12Subfeed Current Ph C (Subfeed PB 2 Subfeed 12)ARead
AV160597916_2_12Subfeed Neutral Current (Subfeed PB 2 Subfeed 12)ARead
AV160607917_2_12Subfeed Ground Current (Subfeed PB 2 Subfeed 12)ARead
AV160617918_2_12Subfeed Current Load Ph A (Subfeed PB 2 Subfeed 12)%Read
AV160627919_2_12Subfeed Current Load Ph B (Subfeed PB 2 Subfeed 12)%Read
AV160637920_2_12Subfeed Current Load Ph C (Subfeed PB 2 Subfeed 12)%Read
AV160647921_2_12Subfeed Highest Phase Current Load (Subfeed PB 2 Subfeed 12)%Read
AV160657922_2_12Subfeed Real Power (Subfeed PB 2 Subfeed 12)kWRead
AV160667923_2_12Subfeed Apparent Power (Subfeed PB 2 Subfeed 12)kVARead
AV160677924_2_12Subfeed Power Factor Ph A (Subfeed PB 2 Subfeed 12)Read
AV160687925_2_12Subfeed Power Factor Ph B (Subfeed PB 2 Subfeed 12)Read
AV160697926_2_12Subfeed Power Factor Ph C (Subfeed PB 2 Subfeed 12)Read
AV160707927_2_12Subfeed Power Factor Total (Subfeed PB 2 Subfeed 12)Read
AV160717928_2_12Subfeed Energy (Subfeed PB 2 Subfeed 12)kWhRead
AV160727929_2_12Subfeed Peak Current Ph A (Subfeed PB 2 Subfeed 12)ARead
AV160737930_2_12Subfeed Peak Current Ph B (Subfeed PB 2 Subfeed 12)ARead
AV160747931_2_12Subfeed Peak Current Ph C (Subfeed PB 2 Subfeed 12)ARead
AV160757932_2_12Subfeed Highest Phase Peak Current (Subfeed PB 2 Subfeed 12)ARead
AV160767933_2_12Subfeed Peak Demand (Subfeed PB 2 Subfeed 12)kWRead
AV160777934_2_12Subfeed Current Crest Factor Ph A (Subfeed PB 2 Subfeed 12)Read
AV160787935_2_12Subfeed Current Crest Factor Ph B (Subfeed PB 2 Subfeed 12)Read
AV160797936_2_12Subfeed Current Crest Factor Ph C (Subfeed PB 2 Subfeed 12)Read
AV160807937_2_12Subfeed iTHD Ph A (Subfeed PB 2 Subfeed 12)%Read
AV160817938_2_12Subfeed iTHD Ph B (Subfeed PB 2 Subfeed 12)%Read
AV160827939_2_12Subfeed iTHD Ph C (Subfeed PB 2 Subfeed 12)%Read
AV160837940_2_12Subfeed Current 3rd Harmonic Ph A (Subfeed PB 2 Subfeed 12)%Read
AV160847941_2_12Subfeed Current 3rd Harmonic Ph B (Subfeed PB 2 Subfeed 12)%Read
AV160857942_2_12Subfeed Current 3rd Harmonic Ph C (Subfeed PB 2 Subfeed 12)%Read
AV160867943_2_12Subfeed Current 5th Harmonic Ph A (Subfeed PB 2 Subfeed 12)%Read
AV160877944_2_12Subfeed Current 5th Harmonic Ph B (Subfeed PB 2 Subfeed 12)%Read
AV160887945_2_12Subfeed Current 5th Harmonic Ph C (Subfeed PB 2 Subfeed 12)%Read
AV160897946_2_12Subfeed Current 7th Harmonic Ph A (Subfeed PB 2 Subfeed 12)%Read
AV160907947_2_12Subfeed Current 7th Harmonic Ph B (Subfeed PB 2 Subfeed 12)%Read
AV160917948_2_12Subfeed Current 7th Harmonic Ph C (Subfeed PB 2 Subfeed 12)%Read
AV160927949_2_12Subfeed Current 9th Harmonic Ph A (Subfeed PB 2 Subfeed 12)%Read
AV160937950_2_12Subfeed Current 9th Harmonic Ph B (Subfeed PB 2 Subfeed 12)%Read
AV160947951_2_12Subfeed Current 9th Harmonic Ph C (Subfeed PB 2 Subfeed 12)%Read
AV160957959_2_12Subfeed Phase Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 12)%Read
AV160967960_2_12Subfeed Phase Overcurrent Alarm Threshold (Subfeed PB 2 Subfeed 12)%Read
AV160977961_2_12Subfeed Neutral Overcurrent Threshold (Subfeed PB 2 Subfeed 12)%Read
AV160988279_2_12Subfeed Neutral Overcurrent Warning Threshold (Subfeed PB 2 Subfeed 12)%Read
AV161087966_1Subfeed Current Rating (Subfeed 1)ARead
AV161097967_1Subfeed Current Ph A (Subfeed 1)ARead
AV161107968_1Subfeed Current Ph B (Subfeed 1)ARead
AV161117969_1Subfeed Current Ph C (Subfeed 1)ARead
AV161127970_1Subfeed Neutral Current (Subfeed 1)ARead
AV161137971_1Subfeed Ground Current (Subfeed 1)ARead
AV161147972_1Subfeed Current Load Ph A (Subfeed 1)%Read
AV161157973_1Subfeed Current Load Ph B (Subfeed 1)%Read
AV161167974_1Subfeed Current Load Ph C (Subfeed 1)%Read
AV161177975_1Subfeed Highest Phase Current Load (Subfeed 1)%Read
AV161187976_1Subfeed Voltage (L-L) A-B (Subfeed 1)VRead
AV161197977_1Subfeed Voltage (L-L) B-C (Subfeed 1)VRead
AV161207978_1Subfeed Voltage (L-L) C-A (Subfeed 1)VRead
AV161217979_1Subfeed Voltage (L-N) A-N (Subfeed 1)VRead
AV161227980_1Subfeed Voltage (L-N) B-N (Subfeed 1)VRead
AV161237981_1Subfeed Voltage (L-N) C-N (Subfeed 1)VRead
AV161247982_1Subfeed Frequency (Subfeed 1)HzRead
AV161257983_1Subfeed Real Power (Subfeed 1)kWRead
AV161267984_1Subfeed Apparent Power (Subfeed 1)kVARead
AV161277985_1Subfeed Power Factor Ph A (Subfeed 1)Read
AV161287986_1Subfeed Power Factor Ph B (Subfeed 1)Read
AV161297987_1Subfeed Power Factor Ph C (Subfeed 1)Read
AV161307988_1Subfeed Power Factor Total (Subfeed 1)Read
AV161317989_1Subfeed Energy (Subfeed 1)kWhRead
AV161327990_1Subfeed Peak Current Ph A (Subfeed 1)ARead
AV161337991_1Subfeed Peak Current Ph B (Subfeed 1)ARead
AV161347992_1Subfeed Peak Current Ph C (Subfeed 1)ARead
AV161357993_1Subfeed Highest Phase Peak Current (Subfeed 1)ARead
AV161367994_1Subfeed Peak Demand (Subfeed 1)kWRead
AV161377995_1Subfeed Current Crest Factor Ph A (Subfeed 1)Read
AV161387996_1Subfeed Current Crest Factor Ph B (Subfeed 1)Read
AV161397997_1Subfeed Current Crest Factor Ph C (Subfeed 1)Read
AV161407998_1Subfeed iTHD Ph A (Subfeed 1)%Read
AV161417999_1Subfeed iTHD Ph B (Subfeed 1)%Read
AV161428000_1Subfeed iTHD Ph C (Subfeed 1)%Read
AV161438001_1Subfeed Current 3rd Harmonic Ph A (Subfeed 1)%Read
AV161448002_1Subfeed Current 3rd Harmonic Ph B (Subfeed 1)%Read
AV161458003_1Subfeed Current 3rd Harmonic Ph C (Subfeed 1)%Read
AV161468004_1Subfeed Current 5th Harmonic Ph A (Subfeed 1)%Read
AV161478005_1Subfeed Current 5th Harmonic Ph B (Subfeed 1)%Read
AV161488006_1Subfeed Current 5th Harmonic Ph C (Subfeed 1)%Read
AV161498007_1Subfeed Current 7th Harmonic Ph A (Subfeed 1)%Read
AV161508008_1Subfeed Current 7th Harmonic Ph B (Subfeed 1)%Read
AV161518009_1Subfeed Current 7th Harmonic Ph C (Subfeed 1)%Read
AV161528010_1Subfeed Current 9th Harmonic Ph A (Subfeed 1)%Read
AV161538011_1Subfeed Current 9th Harmonic Ph B (Subfeed 1)%Read
AV161548012_1Subfeed Current 9th Harmonic Ph C (Subfeed 1)%Read
AV161558013_1Subfeed vTHD Ph A (Subfeed 1)%Read
AV161568014_1Subfeed vTHD Ph B (Subfeed 1)%Read
AV161578015_1Subfeed vTHD Ph C (Subfeed 1)%Read
AV161588016_1Subfeed Voltage 3rd Harmonic Ph A (Subfeed 1)%Read
AV161598017_1Subfeed Voltage 3rd Harmonic Ph B (Subfeed 1)%Read
AV161608018_1Subfeed Voltage 3rd Harmonic Ph C (Subfeed 1)%Read
AV161618019_1Subfeed Voltage 5th Harmonic Ph A (Subfeed 1)%Read
AV161628020_1Subfeed Voltage 5th Harmonic Ph B (Subfeed 1)%Read
AV161638021_1Subfeed Voltage 5th Harmonic Ph C (Subfeed 1)%Read
AV161648022_1Subfeed Voltage 7th Harmonic Ph A (Subfeed 1)%Read
AV161658023_1Subfeed Voltage 7th Harmonic Ph B (Subfeed 1)%Read
AV161668024_1Subfeed Voltage 7th Harmonic Ph C (Subfeed 1)%Read
AV161678025_1Subfeed Voltage 9th Harmonic Ph A (Subfeed 1)%Read
AV161688026_1Subfeed Voltage 9th Harmonic Ph B (Subfeed 1)%Read
AV161698027_1Subfeed Voltage 9th Harmonic Ph C (Subfeed 1)%Read
AV161708035_1Subfeed Phase Overcurrent Warning Threshold (Subfeed 1)%Read
AV161718036_1Subfeed Phase Overcurrent Alarm Threshold (Subfeed 1)%Read
AV161728037_1Subfeed Neutral Overcurrent Threshold (Subfeed 1)Read
AV161738038_1Subfeed Ground Overcurrent Alarm Threshold (Subfeed 1)ARead
AV161748280_1Subfeed Neutral Overcurrent Warning Threshold (Subfeed 1)%Read
AV161758270_1Subfeed Phase Overvoltage Alarm Threshold (Subfeed 1)%Read
AV161768271_1Subfeed Phase Undervoltage Alarm Threshold (Subfeed 1)%Read
AV161847966_2Subfeed Current Rating (Subfeed 2)ARead
AV161857967_2Subfeed Current Ph A (Subfeed 2)ARead
AV161867968_2Subfeed Current Ph B (Subfeed 2)ARead
AV161877969_2Subfeed Current Ph C (Subfeed 2)ARead
AV161887970_2Subfeed Neutral Current (Subfeed 2)ARead
AV161897971_2Subfeed Ground Current (Subfeed 2)ARead
AV161907972_2Subfeed Current Load Ph A (Subfeed 2)%Read
AV161917973_2Subfeed Current Load Ph B (Subfeed 2)%Read
AV161927974_2Subfeed Current Load Ph C (Subfeed 2)%Read
AV161937975_2Subfeed Highest Phase Current Load (Subfeed 2)%Read
AV161947976_2Subfeed Voltage (L-L) A-B (Subfeed 2)VRead
AV161957977_2Subfeed Voltage (L-L) B-C (Subfeed 2)VRead
AV161967978_2Subfeed Voltage (L-L) C-A (Subfeed 2)VRead
AV161977979_2Subfeed Voltage (L-N) A-N (Subfeed 2)VRead
AV161987980_2Subfeed Voltage (L-N) B-N (Subfeed 2)VRead
AV161997981_2Subfeed Voltage (L-N) C-N (Subfeed 2)VRead
AV162007982_2Subfeed Frequency (Subfeed 2)HzRead
AV162017983_2Subfeed Real Power (Subfeed 2)kWRead
AV162027984_2Subfeed Apparent Power (Subfeed 2)kVARead
AV162037985_2Subfeed Power Factor Ph A (Subfeed 2)Read
AV162047986_2Subfeed Power Factor Ph B (Subfeed 2)Read
AV162057987_2Subfeed Power Factor Ph C (Subfeed 2)Read
AV162067988_2Subfeed Power Factor Total (Subfeed 2)Read
AV162077989_2Subfeed Energy (Subfeed 2)kWhRead
AV162087990_2Subfeed Peak Current Ph A (Subfeed 2)ARead
AV162097991_2Subfeed Peak Current Ph B (Subfeed 2)ARead
AV162107992_2Subfeed Peak Current Ph C (Subfeed 2)ARead
AV162117993_2Subfeed Highest Phase Peak Current (Subfeed 2)ARead
AV162127994_2Subfeed Peak Demand (Subfeed 2)kWRead
AV162137995_2Subfeed Current Crest Factor Ph A (Subfeed 2)Read
AV162147996_2Subfeed Current Crest Factor Ph B (Subfeed 2)Read
AV162157997_2Subfeed Current Crest Factor Ph C (Subfeed 2)Read
AV162167998_2Subfeed iTHD Ph A (Subfeed 2)%Read
AV162177999_2Subfeed iTHD Ph B (Subfeed 2)%Read
AV162188000_2Subfeed iTHD Ph C (Subfeed 2)%Read
AV162198001_2Subfeed Current 3rd Harmonic Ph A (Subfeed 2)%Read
AV162208002_2Subfeed Current 3rd Harmonic Ph B (Subfeed 2)%Read
AV162218003_2Subfeed Current 3rd Harmonic Ph C (Subfeed 2)%Read
AV162228004_2Subfeed Current 5th Harmonic Ph A (Subfeed 2)%Read
AV162238005_2Subfeed Current 5th Harmonic Ph B (Subfeed 2)%Read
AV162248006_2Subfeed Current 5th Harmonic Ph C (Subfeed 2)%Read
AV162258007_2Subfeed Current 7th Harmonic Ph A (Subfeed 2)%Read
AV162268008_2Subfeed Current 7th Harmonic Ph B (Subfeed 2)%Read
AV162278009_2Subfeed Current 7th Harmonic Ph C (Subfeed 2)%Read
AV162288010_2Subfeed Current 9th Harmonic Ph A (Subfeed 2)%Read
AV162298011_2Subfeed Current 9th Harmonic Ph B (Subfeed 2)%Read
AV162308012_2Subfeed Current 9th Harmonic Ph C (Subfeed 2)%Read
AV162318013_2Subfeed vTHD Ph A (Subfeed 2)%Read
AV162328014_2Subfeed vTHD Ph B (Subfeed 2)%Read
AV162338015_2Subfeed vTHD Ph C (Subfeed 2)%Read
AV162348016_2Subfeed Voltage 3rd Harmonic Ph A (Subfeed 2)%Read
AV162358017_2Subfeed Voltage 3rd Harmonic Ph B (Subfeed 2)%Read
AV162368018_2Subfeed Voltage 3rd Harmonic Ph C (Subfeed 2)%Read
AV162378019_2Subfeed Voltage 5th Harmonic Ph A (Subfeed 2)%Read
AV162388020_2Subfeed Voltage 5th Harmonic Ph B (Subfeed 2)%Read
AV162398021_2Subfeed Voltage 5th Harmonic Ph C (Subfeed 2)%Read
AV162408022_2Subfeed Voltage 7th Harmonic Ph A (Subfeed 2)%Read
AV162418023_2Subfeed Voltage 7th Harmonic Ph B (Subfeed 2)%Read
AV162428024_2Subfeed Voltage 7th Harmonic Ph C (Subfeed 2)%Read
AV162438025_2Subfeed Voltage 9th Harmonic Ph A (Subfeed 2)%Read
AV162448026_2Subfeed Voltage 9th Harmonic Ph B (Subfeed 2)%Read
AV162458027_2Subfeed Voltage 9th Harmonic Ph C (Subfeed 2)%Read
AV162468035_2Subfeed Phase Overcurrent Warning Threshold (Subfeed 2)%Read
AV162478036_2Subfeed Phase Overcurrent Alarm Threshold (Subfeed 2)%Read
AV162488037_2Subfeed Neutral Overcurrent Threshold (Subfeed 2)Read
AV162498038_2Subfeed Ground Overcurrent Alarm Threshold (Subfeed 2)ARead
AV162508280_2Subfeed Neutral Overcurrent Warning Threshold (Subfeed 2)%Read
AV162518270_2Subfeed Phase Overvoltage Alarm Threshold (Subfeed 2)%Read
AV162528271_2Subfeed Phase Undervoltage Alarm Threshold (Subfeed 2)%Read
AV187687966_36Subfeed Current Rating (Subfeed 36)ARead
AV187697967_36Subfeed Current Ph A (Subfeed 36)ARead
AV187707968_36Subfeed Current Ph B (Subfeed 36)ARead
AV187717969_36Subfeed Current Ph C (Subfeed 36)ARead
AV187727970_36Subfeed Neutral Current (Subfeed 36)ARead
AV187737971_36Subfeed Ground Current (Subfeed 36)ARead
AV187747972_36Subfeed Current Load Ph A (Subfeed 36)%Read
AV187757973_36Subfeed Current Load Ph B (Subfeed 36)%Read
AV187767974_36Subfeed Current Load Ph C (Subfeed 36)%Read
AV187777975_36Subfeed Highest Phase Current Load (Subfeed 36)%Read
AV187787976_36Subfeed Voltage (L-L) A-B (Subfeed 36)VRead
AV187797977_36Subfeed Voltage (L-L) B-C (Subfeed 36)VRead
AV187807978_36Subfeed Voltage (L-L) C-A (Subfeed 36)VRead
AV187817979_36Subfeed Voltage (L-N) A-N (Subfeed 36)VRead
AV187827980_36Subfeed Voltage (L-N) B-N (Subfeed 36)VRead
AV187837981_36Subfeed Voltage (L-N) C-N (Subfeed 36)VRead
AV187847982_36Subfeed Frequency (Subfeed 36)HzRead
AV187857983_36Subfeed Real Power (Subfeed 36)kWRead
AV187867984_36Subfeed Apparent Power (Subfeed 36)kVARead
AV187877985_36Subfeed Power Factor Ph A (Subfeed 36)Read
AV187887986_36Subfeed Power Factor Ph B (Subfeed 36)Read
AV187897987_36Subfeed Power Factor Ph C (Subfeed 36)Read
AV187907988_36Subfeed Power Factor Total (Subfeed 36)Read
AV187917989_36Subfeed Energy (Subfeed 36)kWhRead
AV187927990_36Subfeed Peak Current Ph A (Subfeed 36)ARead
AV187937991_36Subfeed Peak Current Ph B (Subfeed 36)ARead
AV187947992_36Subfeed Peak Current Ph C (Subfeed 36)ARead
AV187957993_36Subfeed Highest Phase Peak Current (Subfeed 36)ARead
AV187967994_36Subfeed Peak Demand (Subfeed 36)kWRead
AV187977995_36Subfeed Current Crest Factor Ph A (Subfeed 36)Read
AV187987996_36Subfeed Current Crest Factor Ph B (Subfeed 36)Read
AV187997997_36Subfeed Current Crest Factor Ph C (Subfeed 36)Read
AV188007998_36Subfeed iTHD Ph A (Subfeed 36)%Read
AV188017999_36Subfeed iTHD Ph B (Subfeed 36)%Read
AV188028000_36Subfeed iTHD Ph C (Subfeed 36)%Read
AV188038001_36Subfeed Current 3rd Harmonic Ph A (Subfeed 36)%Read
AV188048002_36Subfeed Current 3rd Harmonic Ph B (Subfeed 36)%Read
AV188058003_36Subfeed Current 3rd Harmonic Ph C (Subfeed 36)%Read
AV188068004_36Subfeed Current 5th Harmonic Ph A (Subfeed 36)%Read
AV188078005_36Subfeed Current 5th Harmonic Ph B (Subfeed 36)%Read
AV188088006_36Subfeed Current 5th Harmonic Ph C (Subfeed 36)%Read
AV188098007_36Subfeed Current 7th Harmonic Ph A (Subfeed 36)%Read
AV188108008_36Subfeed Current 7th Harmonic Ph B (Subfeed 36)%Read
AV188118009_36Subfeed Current 7th Harmonic Ph C (Subfeed 36)%Read
AV188128010_36Subfeed Current 9th Harmonic Ph A (Subfeed 36)%Read
AV188138011_36Subfeed Current 9th Harmonic Ph B (Subfeed 36)%Read
AV188148012_36Subfeed Current 9th Harmonic Ph C (Subfeed 36)%Read
AV188158013_36Subfeed vTHD Ph A (Subfeed 36)%Read
AV188168014_36Subfeed vTHD Ph B (Subfeed 36)%Read
AV188178015_36Subfeed vTHD Ph C (Subfeed 36)%Read
AV188188016_36Subfeed Voltage 3rd Harmonic Ph A (Subfeed 36)%Read
AV188198017_36Subfeed Voltage 3rd Harmonic Ph B (Subfeed 36)%Read
AV188208018_36Subfeed Voltage 3rd Harmonic Ph C (Subfeed 36)%Read
AV188218019_36Subfeed Voltage 5th Harmonic Ph A (Subfeed 36)%Read
AV188228020_36Subfeed Voltage 5th Harmonic Ph B (Subfeed 36)%Read
AV188238021_36Subfeed Voltage 5th Harmonic Ph C (Subfeed 36)%Read
AV188248022_36Subfeed Voltage 7th Harmonic Ph A (Subfeed 36)%Read
AV188258023_36Subfeed Voltage 7th Harmonic Ph B (Subfeed 36)%Read
AV188268024_36Subfeed Voltage 7th Harmonic Ph C (Subfeed 36)%Read
AV188278025_36Subfeed Voltage 9th Harmonic Ph A (Subfeed 36)%Read
AV188288026_36Subfeed Voltage 9th Harmonic Ph B (Subfeed 36)%Read
AV188298027_36Subfeed Voltage 9th Harmonic Ph C (Subfeed 36)%Read
AV188308035_36Subfeed Phase Overcurrent Warning Threshold (Subfeed 36)%Read
AV188318036_36Subfeed Phase Overcurrent Alarm Threshold (Subfeed 36)%Read
AV188328037_36Subfeed Neutral Overcurrent Threshold (Subfeed 36)Read
AV188338038_36Subfeed Ground Overcurrent Alarm Threshold (Subfeed 36)ARead
AV188348280_36Subfeed Neutral Overcurrent Warning Threshold (Subfeed 36)%Read
AV188358270_36Subfeed Phase Overvoltage Alarm Threshold (Subfeed 36)%Read
AV188368271_36Subfeed Phase Undervoltage Alarm Threshold (Subfeed 36)%Read
MV14553_1Server ClassRead1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR
MVmin124123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MV137059_1Restart ProcedureRead1=Auto, 2=Manual
MV147060_1Overtemperature ShutdownRead1=disabled, 2=enabled
MVmin157582_1System-wide Event Acknowledge/ResetWrite1=Reset, 2=Acknowledge
MV167583_1System-wide Energy ResetWrite1=Reset
MV177584_1System-wide Peak Current ResetWrite1=Reset
MV187585_1System-wide Peak Demand ResetWrite1=Reset
MV197566_1Main Input Breaker 1 StatusRead1=Unknown, 2=Open, 3=Closed
MV207567_1Main Input Breaker 2 StatusRead1=Unknown, 2=Open, 3=Closed
MV297696_1Metering ConfigurationRead1=Master Side, 2=Slave Side
MV307721_1Energy ResetWrite1=Reset
MV317722_1Peak Current ResetWrite1=Reset
MV327723_1Peak Demand ResetWrite1=Reset
MV437725_1Panelboard Status (Branch PB 1)Read1=Normal, 2=Abnormal
MV447791_1Panelboard Main Breaker Status (Branch PB 1)Read1=Unknown, 2=Open, 3=Closed
MV457804_1Panelboard Energy Reset (Branch PB 1)Write1=Reset
MV467805_1Panelboard Peak Current Reset (Branch PB 1)Write1=Reset
MV477806_1Panelboard Peak Demand Reset (Branch PB 1)Write1=Reset
MV587828_1_1Branch Energy Reset (Branch PB 1 Branch 1)Write1=Reset
MV597829_1_1Branch Peak Current Reset (Branch PB 1 Branch 1)Write1=Reset
MV607830_1_1Branch Peak Demand Reset (Branch PB 1 Branch 1)Write1=Reset
MV717828_1_2Branch Energy Reset (Branch PB 1 Branch 2)Write1=Reset
MV727829_1_2Branch Peak Current Reset (Branch PB 1 Branch 2)Write1=Reset
MV737830_1_2Branch Peak Demand Reset (Branch PB 1 Branch 2)Write1=Reset
MV5917828_1_42Branch Energy Reset (Branch PB 1 Branch 42)Write1=Reset
MV5927829_1_42Branch Peak Current Reset (Branch PB 1 Branch 42)Write1=Reset
MV5937830_1_42Branch Peak Demand Reset (Branch PB 1 Branch 42)Write1=Reset
MV6047725_2Panelboard Status (Branch PB 2)Read1=Normal, 2=Abnormal
MV6057791_2Panelboard Main Breaker Status (Branch PB 2)Read1=Unknown, 2=Open, 3=Closed
MV6067804_2Panelboard Energy Reset (Branch PB 2)Write1=Reset
MV6077805_2Panelboard Peak Current Reset (Branch PB 2)Write1=Reset
MV6087806_2Panelboard Peak Demand Reset (Branch PB 2)Write1=Reset
MV6197828_2_1Branch Energy Reset (Branch PB 2 Branch 1)Write1=Reset
MV6207829_2_1Branch Peak Current Reset (Branch PB 2 Branch 1)Write1=Reset
MV6217830_2_1Branch Peak Demand Reset (Branch PB 2 Branch 1)Write1=Reset
MV6327828_2_2Branch Energy Reset (Branch PB 2 Branch 2)Write1=Reset
MV6337829_2_2Branch Peak Current Reset (Branch PB 2 Branch 2)Write1=Reset
MV6347830_2_2Branch Peak Demand Reset (Branch PB 2 Branch 2)Write1=Reset
MV11527828_2_42Branch Energy Reset (Branch PB 2 Branch 42)Write1=Reset
MV11537829_2_42Branch Peak Current Reset (Branch PB 2 Branch 42)Write1=Reset
MV11547830_2_42Branch Peak Demand Reset (Branch PB 2 Branch 42)Write1=Reset
MV62147725_12Panelboard Status (Branch PB 12)Read1=Normal, 2=Abnormal
MV62157791_12Panelboard Main Breaker Status (Branch PB 12)Read1=Unknown, 2=Open, 3=Closed
MV62167804_12Panelboard Energy Reset (Branch PB 12)Write1=Reset
MV62177805_12Panelboard Peak Current Reset (Branch PB 12)Write1=Reset
MV62187806_12Panelboard Peak Demand Reset (Branch PB 12)Write1=Reset
MV62297828_12_1Branch Energy Reset (Branch PB 12 Branch 1)Write1=Reset
MV62307829_12_1Branch Peak Current Reset (Branch PB 12 Branch 1)Write1=Reset
MV62317830_12_1Branch Peak Demand Reset (Branch PB 12 Branch 1)Write1=Reset
MV62427828_12_2Branch Energy Reset (Branch PB 12 Branch 2)Write1=Reset
MV62437829_12_2Branch Peak Current Reset (Branch PB 12 Branch 2)Write1=Reset
MV62447830_12_2Branch Peak Demand Reset (Branch PB 12 Branch 2)Write1=Reset
MV67627828_12_42Branch Energy Reset (Branch PB 12 Branch 42)Write1=Reset
MV67637829_12_42Branch Peak Current Reset (Branch PB 12 Branch 42)Write1=Reset
MV67647830_12_42Branch Peak Demand Reset (Branch PB 12 Branch 42)Write1=Reset
MV67757832_1Panelboard Status (Subfeed PB 1)Read1=Normal, 2=Abnormal
MV67767895_1Panelboard Main Breaker Status (Subfeed PB 1)Read1=Unknown, 2=Open, 3=Closed
MV67777908_1Panelboard Energy Reset (Subfeed PB 1)Write1=Reset
MV67787909_1Panelboard Peak Current Reset (Subfeed PB 1)Write1=Reset
MV67797910_1Panelboard Peak Demand Reset (Subfeed PB 1)Write1=Reset
MV67907952_1_1Subfeed Main Breaker Status (Subfeed PB 1 Subfeed 1)Read1=Unknown, 2=Open, 3=Closed
MV67917962_1_1Subfeed Energy Reset (Subfeed PB 1 Subfeed 1)Write1=Reset
MV67927963_1_1Subfeed Peak Current Reset (Subfeed PB 1 Subfeed 1)Write1=Reset
MV67937964_1_1Subfeed Peak Demand Reset (Subfeed PB 1 Subfeed 1)Write1=Reset
MV68047952_1_2Subfeed Main Breaker Status (Subfeed PB 1 Subfeed 2)Read1=Unknown, 2=Open, 3=Closed
MV68057962_1_2Subfeed Energy Reset (Subfeed PB 1 Subfeed 2)Write1=Reset
MV68067963_1_2Subfeed Peak Current Reset (Subfeed PB 1 Subfeed 2)Write1=Reset
MV68077964_1_2Subfeed Peak Demand Reset (Subfeed PB 1 Subfeed 2)Write1=Reset
MV69447952_1_12Subfeed Main Breaker Status (Subfeed PB 1 Subfeed 12)Read1=Unknown, 2=Open, 3=Closed
MV69457962_1_12Subfeed Energy Reset (Subfeed PB 1 Subfeed 12)Write1=Reset
MV69467963_1_12Subfeed Peak Current Reset (Subfeed PB 1 Subfeed 12)Write1=Reset
MV69477964_1_12Subfeed Peak Demand Reset (Subfeed PB 1 Subfeed 12)Write1=Reset
MV69587832_2Panelboard Status (Subfeed PB 2)Read1=Normal, 2=Abnormal
MV69597895_2Panelboard Main Breaker Status (Subfeed PB 2)Read1=Unknown, 2=Open, 3=Closed
MV69607908_2Panelboard Energy Reset (Subfeed PB 2)Write1=Reset
MV69617909_2Panelboard Peak Current Reset (Subfeed PB 2)Write1=Reset
MV69627910_2Panelboard Peak Demand Reset (Subfeed PB 2)Write1=Reset
MV69737952_2_1Subfeed Main Breaker Status (Subfeed PB 2 Subfeed 1)Read1=Unknown, 2=Open, 3=Closed
MV69747962_2_1Subfeed Energy Reset (Subfeed PB 2 Subfeed 1)Write1=Reset
MV69757963_2_1Subfeed Peak Current Reset (Subfeed PB 2 Subfeed 1)Write1=Reset
MV69767964_2_1Subfeed Peak Demand Reset (Subfeed PB 2 Subfeed 1)Write1=Reset
MV69877952_2_2Subfeed Main Breaker Status (Subfeed PB 2 Subfeed 2)Read1=Unknown, 2=Open, 3=Closed
MV69887962_2_2Subfeed Energy Reset (Subfeed PB 2 Subfeed 2)Write1=Reset
MV69897963_2_2Subfeed Peak Current Reset (Subfeed PB 2 Subfeed 2)Write1=Reset
MV69907964_2_2Subfeed Peak Demand Reset (Subfeed PB 2 Subfeed 2)Write1=Reset
MV71277952_2_12Subfeed Main Breaker Status (Subfeed PB 2 Subfeed 12)Read1=Unknown, 2=Open, 3=Closed
MV71287962_2_12Subfeed Energy Reset (Subfeed PB 2 Subfeed 12)Write1=Reset
MV71297963_2_12Subfeed Peak Current Reset (Subfeed PB 2 Subfeed 12)Write1=Reset
MV71307964_2_12Subfeed Peak Demand Reset (Subfeed PB 2 Subfeed 12)Write1=Reset
MV71418028_1Subfeed Breaker Status (Subfeed 1)Read1=Unknown, 2=Open, 3=Closed
MV71428041_1Subfeed Energy Reset (Subfeed 1)Write1=Reset
MV71438042_1Subfeed Peak Current Reset (Subfeed 1)Write1=Reset
MV71448043_1Subfeed Peak Demand Reset (Subfeed 1)Write1=Reset
MV71558028_2Subfeed Breaker Status (Subfeed 2)Read1=Unknown, 2=Open, 3=Closed
MV71568041_2Subfeed Energy Reset (Subfeed 2)Write1=Reset
MV71578042_2Subfeed Peak Current Reset (Subfeed 2)Write1=Reset
MV71588043_2Subfeed Peak Demand Reset (Subfeed 2)Write1=Reset
MV76318028_36Subfeed Breaker Status (Subfeed 36)Read1=Unknown, 2=Open, 3=Closed
MV76328041_36Subfeed Energy Reset (Subfeed 36)Write1=Reset
MV76338042_36Subfeed Peak Current Reset (Subfeed 36)Write1=Reset
MV76348043_36Subfeed Peak Demand Reset (Subfeed 36)Write1=Reset
Object ID lookup: Vertiv Liebert RXA / TFX power panel point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert RXA / TFX power panel and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert RXA / TFX power panel

How many BACnet points does the Vertiv Liebert RXA / TFX power panel have?

This list has 1414 BACnet objects: 1129 analog values, 183 binary values, 102 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert RXA / TFX power panel BACnet points are writable?

77 of the 1414 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert RXA / TFX power panel BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert RXA / TFX power panel?

Start with MV 15 7582_1 (Acknowledge / reset events); MV 12 4123_1 (Normal, warning or alarm state); AV 25 7601_1 (Output voltage A-B); AV 28 7604_1 (Output voltage A-N); BV 1 7570_1 (Transformer high temperature).

How do I check these points on the real Liebert RXA / TFX power panel?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.