UPS (uninterruptible power supply) · BACnet points list
Vertiv Liebert APM 600 UPS with GHMI BACnet points list
Updated 6 November 2026
The Liebert APM 600 UPS with GHMI reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.
This page lists 252 BACnet objects for the Vertiv Liebert APM 600 UPS with GHMI — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert APM 600 UPS with GHMI
- Equipment
- UPS (uninterruptible power supply)
- Equipment type
- Other equipment
- BACnet objects
- 252 (1 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- APM 600, Liebert APM600, GHMI, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert APM 600 UPS with GHMI
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 325 | 4123_1 | Normal, warning or alarm state | Read |
| MV 324 | 4872_1 | Load on inverter, bypass or battery | Read |
| AV 47 | 4150_1 | Estimated battery runtime, min | Read |
| AV 190 | 4208_1 | Output power, kW | Read |
| AV 1 | 4097_1 | Input voltage, V | Read |
| AV 163 | 4385_1 | Output voltage, V | Read |
| AV 166 | 4204_1 | Output current, A | Read |
| BV 39 | 4168_1 | Load is on battery | Read |
| BV 578 | 4300_1 | Internal communication lost | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert APM 600 UPS with GHMI BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | 5155_1 | Mains Input Neutral Lost | Read | Active = alarm | |
| BV | 2 | 4146_1 | System Input Phs Rotation Error | Read | Active = alarm | |
| BV | 3 | 4122_1 | System Input Power Problem | Read | Active = alarm | |
| BV | 4 | 6061_1 | Input Source Backfeed | Read | Active = alarm | |
| BV | 15 | 4135_1 | Bypass Not Available | Read | Active = alarm | |
| BV | 16 | 4143_1 | Bypass Static Switch Unavailable | Read | Active = alarm | |
| BV | 17 | 4139_1 | Bypass - Excess Auto Retransfers | Read | Active = alarm | |
| BV | 18 | 4298_1 | UPS Output on Bypass | Read | Active = alarm | |
| BV | 19 | 4299_1 | Output Load on Maint. Bypass | Read | Active = alarm | |
| BV | 20 | 5957_1 | Bypass Input Voltage Fault | Read | Active = alarm | |
| BV | 21 | 4216_1 | Bypass Backfeed Detected | Read | Active = alarm | |
| BV | 32 | 4173_1 | Main Battery Disconnect Open | Read | Active = alarm | |
| BV | 33 | 4185_1 | Battery Circuit Breaker 4 Open | Read | Active = alarm | |
| BV | 34 | 4182_1 | Battery Circuit Breaker 3 Open | Read | Active = alarm | |
| BV | 35 | 4179_1 | Battery Circuit Breaker 2 Open | Read | Active = alarm | |
| BV | 36 | 4176_1 | Battery Circuit Breaker 1 Open | Read | Active = alarm | |
| BV | 37 | 4741_1 | Battery Self Test | Read | Active = alarm | |
| BV | 38 | 4200_1 | Battery Charging Inhibited | Read | Active = alarm | |
| BVmin | 39 | 4168_1 | Battery Discharging | Read | Active = alarm | |
| BV | 40 | 4171_1 | Battery Manual Test In Progress | Read | Active = alarm | |
| BV | 41 | 4172_1 | Battery Auto Test In Progress | Read | Active = alarm | |
| BV | 42 | 4322_1 | Battery Test Passed | Read | Active = alarm | |
| BV | 43 | 4323_1 | Battery Test Failed | Read | Active = alarm | |
| BV | 44 | 4219_1 | Battery Over Temperature | Read | Active = alarm | |
| BV | 45 | 4162_1 | Battery Low | Read | Active = alarm | |
| BV | 46 | 4222_1 | Battery Ground Fault | Read | Active = alarm | |
| BV | 47 | 5149_1 | Battery Not Qualified | Read | Active = alarm | |
| BV | 48 | 5150_1 | Battery Terminals Reversed | Read | Active = alarm | |
| BV | 49 | 4166_1 | Battery Capacity Low | Read | Active = alarm | |
| BV | 50 | 6063_1 | Battery Converter Current Limit | Read | Active = alarm | |
| BV | 51 | 6065_1 | Battery Charge Equalization Timeout | Read | Active = alarm | |
| BV | 52 | 6068_1 | Battery Room Alarm | Read | Active = alarm | |
| BV | 53 | 4177_1 | Battery Breaker 1 Open Failure | Read | Active = alarm | |
| BV | 54 | 4180_1 | Battery Breaker 2 Open Failure | Read | Active = alarm | |
| BV | 55 | 4183_1 | Battery Breaker 3 Open Failure | Read | Active = alarm | |
| BV | 56 | 4186_1 | Battery Breaker 4 Open Failure | Read | Active = alarm | |
| BV | 57 | 4170_1 | Battery Equalize | Read | Active = alarm | |
| BV | 58 | 7485_1 | Battery Circuit Breaker Open | Read | Active = alarm | |
| BV | 59 | 7461_1 | Battery Breaker Open Failure | Read | Active = alarm | |
| BV | 62 | 7464_1_1 | Lithium-Ion Battery System Abnormal | Read | Active = alarm | |
| BV | 63 | 7465_1_1 | Lithium-Ion Battery System Disconnect Request | Read | Active = alarm | |
| BV | 64 | 7486_1_1 | Lithium-Ion Battery System Communication Abnormal | Read | Active = alarm | |
| BV | 65 | 7487_1_1 | Lithium-Ion Battery System Warning | Read | Active = alarm | |
| BV | 66 | 7488_1_1 | Lithium-Ion Battery System Fault | Read | Active = alarm | |
| BV | 68 | 6062_1 | Loss of Synchronization | Read | Active = alarm | |
| BV | 79 | 5806_1 | Output Overload | Read | Active = alarm | |
| BV | 80 | 4389_1 | System Output Fault | Read | Active = alarm | |
| BV | 91 | 6438_1 | Power Module Input Current Abnormal (PowerModules 1) | Read | Active = alarm | |
| BV | 92 | 4295_1 | Rectifier Failure (PowerModules 1) | Read | Active = alarm | |
| BV | 93 | 4233_1 | Inverter Failure (PowerModules 1) | Read | Active = alarm | |
| BV | 94 | 5154_1 | DC Bus Abnormal (PowerModules 1) | Read | Active = alarm | |
| BV | 95 | 5153_1 | Load Sharing Fault (PowerModules 1) | Read | Active = alarm | |
| BV | 96 | 6059_1 | Inverter Relay Fault (PowerModules 1) | Read | Active = alarm | |
| BV | 97 | 4164_1 | Battery Charging Error (PowerModules 1) | Read | Active = alarm | |
| BV | 98 | 5151_1 | Battery Converter Failure (PowerModules 1) | Read | Active = alarm | |
| BV | 99 | 6439_1 | Power Module Balancer of DC Bus Failure (PowerModules 1) | Read | Active = alarm | |
| BV | 100 | 4290_1 | Inverter Shutdown - Overload (PowerModules 1) | Read | Active = alarm | |
| BV | 101 | 6440_1 | Power Module Fuse Failure (PowerModules 1) | Read | Active = alarm | |
| BV | 102 | 6441_1 | Power Module Power Supply Failure (PowerModules 1) | Read | Active = alarm | |
| BV | 103 | 5838_1 | Power Module Fan Fault (PowerModules 1) | Read | Active = alarm | |
| BV | 104 | 5839_1 | Power Module Over Temperature (PowerModules 1) | Read | Active = alarm | |
| BV | 105 | 6528_1 | Power Module Lever Unlocked (PowerModules 1) | Read | Active = alarm | |
| BV | 106 | 8098_1 | Power Module Communication status (PowerModules 1) | Read | Active = alarm | |
| BV | 115 | 6438_2 | Power Module Input Current Abnormal (PowerModules 2) | Read | Active = alarm | |
| BV | 116 | 4295_2 | Rectifier Failure (PowerModules 2) | Read | Active = alarm | |
| BV | 117 | 4233_2 | Inverter Failure (PowerModules 2) | Read | Active = alarm | |
| BV | 118 | 5154_2 | DC Bus Abnormal (PowerModules 2) | Read | Active = alarm | |
| BV | 119 | 5153_2 | Load Sharing Fault (PowerModules 2) | Read | Active = alarm | |
| BV | 120 | 6059_2 | Inverter Relay Fault (PowerModules 2) | Read | Active = alarm | |
| BV | 121 | 4164_2 | Battery Charging Error (PowerModules 2) | Read | Active = alarm | |
| BV | 122 | 5151_2 | Battery Converter Failure (PowerModules 2) | Read | Active = alarm | |
| BV | 123 | 6439_2 | Power Module Balancer of DC Bus Failure (PowerModules 2) | Read | Active = alarm | |
| BV | 124 | 4290_2 | Inverter Shutdown - Overload (PowerModules 2) | Read | Active = alarm | |
| BV | 125 | 6440_2 | Power Module Fuse Failure (PowerModules 2) | Read | Active = alarm | |
| BV | 126 | 6441_2 | Power Module Power Supply Failure (PowerModules 2) | Read | Active = alarm | |
| BV | 127 | 5838_2 | Power Module Fan Fault (PowerModules 2) | Read | Active = alarm | |
| BV | 128 | 5839_2 | Power Module Over Temperature (PowerModules 2) | Read | Active = alarm | |
| BV | 129 | 6528_2 | Power Module Lever Unlocked (PowerModules 2) | Read | Active = alarm | |
| BV | 130 | 8098_2 | Power Module Communication status (PowerModules 2) | Read | Active = alarm | |
| BV | 547 | 6438_20 | Power Module Input Current Abnormal (PowerModules 20) | Read | Active = alarm | |
| BV | 548 | 4295_20 | Rectifier Failure (PowerModules 20) | Read | Active = alarm | |
| BV | 549 | 4233_20 | Inverter Failure (PowerModules 20) | Read | Active = alarm | |
| BV | 550 | 5154_20 | DC Bus Abnormal (PowerModules 20) | Read | Active = alarm | |
| BV | 551 | 5153_20 | Load Sharing Fault (PowerModules 20) | Read | Active = alarm | |
| BV | 552 | 6059_20 | Inverter Relay Fault (PowerModules 20) | Read | Active = alarm | |
| BV | 553 | 4164_20 | Battery Charging Error (PowerModules 20) | Read | Active = alarm | |
| BV | 554 | 5151_20 | Battery Converter Failure (PowerModules 20) | Read | Active = alarm | |
| BV | 555 | 6439_20 | Power Module Balancer of DC Bus Failure (PowerModules 20) | Read | Active = alarm | |
| BV | 556 | 4290_20 | Inverter Shutdown - Overload (PowerModules 20) | Read | Active = alarm | |
| BV | 557 | 6440_20 | Power Module Fuse Failure (PowerModules 20) | Read | Active = alarm | |
| BV | 558 | 6441_20 | Power Module Power Supply Failure (PowerModules 20) | Read | Active = alarm | |
| BV | 559 | 5838_20 | Power Module Fan Fault (PowerModules 20) | Read | Active = alarm | |
| BV | 560 | 5839_20 | Power Module Over Temperature (PowerModules 20) | Read | Active = alarm | |
| BV | 561 | 6528_20 | Power Module Lever Unlocked (PowerModules 20) | Read | Active = alarm | |
| BV | 562 | 8098_20 | Power Module Communication status (PowerModules 20) | Read | Active = alarm | |
| BV | 571 | 5817_1 | Loss of Redundancy | Read | Active = alarm | |
| BV | 572 | 6066_1 | Parallel Cable Failure | Read | Active = alarm | |
| BV | 573 | 6064_1 | LBS Cable Failure | Read | Active = alarm | |
| BV | 574 | 6060_1 | Transfer to Bypass - System Overload | Read | Active = alarm | |
| BV | 575 | 5458_1 | Excess ECO Suspends | Read | Active = alarm | |
| BV | 576 | 5157_1 | User Operation Invalid | Read | Active = alarm | |
| BV | 577 | 5156_1 | Load Impact Transfer | Read | Active = alarm | |
| BVmin | 578 | 4300_1 | Internal Communications Failure | Read | Active = alarm | |
| BV | 579 | 4831_1 | MMS Overload | Read | Active = alarm | |
| BV | 580 | 4823_1 | Parallel Comm Warning | Read | Active = alarm | |
| BV | 581 | 4310_1 | Equipment Over Temperature | Read | Active = alarm | |
| BV | 582 | 4758_1 | LBS Inhibited | Read | Active = alarm | |
| BV | 583 | 4315_1 | On Generator | Read | Active = alarm | |
| BV | 584 | 4757_1 | LBS Active | Read | Active = alarm | |
| BV | 585 | 4213_1 | System Shutdown - EPO | Read | Active = alarm | |
| BV | 586 | 5770_1 | Top Outlet Fan Fault | Read | Active = alarm | |
| BV | 587 | 6529_1 | Hardware Mismatch | Read | Active = alarm | |
| BV | 588 | 6536_1 | MMS Capacity Exceeded | Read | Active = alarm | |
| BV | 589 | 4440_1 | Fuse Failure | Read | Active = alarm | |
| AVmin | 1 | 4097_1 | System Input RMS A-B | V | Read | |
| AV | 2 | 4099_1 | System Input RMS B-C | V | Read | |
| AV | 3 | 4101_1 | System Input RMS C-A | V | Read | |
| AV | 4 | 4113_1 | System Input RMS Current Phase A | A | Read | |
| AV | 5 | 4114_1 | System Input RMS Current Phase B | A | Read | |
| AV | 6 | 4115_1 | System Input RMS Current Phase C | A | Read | |
| AV | 7 | 4105_1 | System Input Frequency | Hz | Read | |
| AV | 8 | 4096_1 | System Input RMS A-N | V | Read | |
| AV | 9 | 4098_1 | System Input RMS B-N | V | Read | |
| AV | 10 | 4100_1 | System Input RMS C-N | V | Read | |
| AV | 11 | 4116_1 | System Input Power Factor Phs A | Read | ||
| AV | 12 | 4117_1 | System Input Power Factor Phs B | Read | ||
| AV | 13 | 4118_1 | System Input Power Factor Phs C | Read | ||
| AV | 14 | 4102_1 | System Input Nominal Voltage | V | Read | |
| AV | 15 | 4103_1 | System Input Nominal Frequency | Hz | Read | |
| AV | 16 | 4104_1 | System Input Nominal Current | A | Read | |
| AV | 17 | 4119_1 | System Input Brown Out Count | Read | ||
| AV | 18 | 4120_1 | System Input Black Out Count | Read | ||
| AV | 19 | 6318_1 | System Input Power Phase A | kW | Read | |
| AV | 20 | 6319_1 | System Input Power Phase B | kW | Read | |
| AV | 21 | 6320_1 | System Input Power Phase C | kW | Read | |
| AV | 22 | 8093_1 | System Input Apparent Power Phs A | kVA | Read | |
| AV | 23 | 8094_1 | System Input Apparent Power Phs B | kVA | Read | |
| AV | 24 | 8095_1 | System Input Apparent Power Phs C | kVA | Read | |
| AV | 29 | 4128_1 | Bypass Input Voltage RMS A-N | V | Read | |
| AV | 30 | 4129_1 | Bypass Input Voltage RMS B-N | V | Read | |
| AV | 31 | 4130_1 | Bypass Input Voltage RMS C-N | V | Read | |
| AV | 32 | 4131_1 | Bypass Input Frequency | Hz | Read | |
| AV | 33 | 4125_1 | Bypass Input Voltage RMS A-B | V | Read | |
| AV | 34 | 4126_1 | Bypass Input Voltage RMS B-C | V | Read | |
| AV | 35 | Bypass Input Voltage RMS C-A | V | Read | ||
| AV | 36 | 4259_1 | Bypass Nominal Voltage | V | Read | |
| AV | 37 | 6325_1 | Bypass Power Phase A | kW | Read | |
| AV | 38 | 6326_1 | Bypass Power Phase B | kW | Read | |
| AV | 39 | 6327_1 | Bypass Power Phase C | kW | Read | |
| AV | 40 | 6328_1 | Bypass Apparent Power Phase A | kVA | Read | |
| AV | 41 | 6329_1 | Bypass Apparent Power Phase B | kVA | Read | |
| AV | 42 | 6330_1 | Bypass Apparent Power Phase C | kVA | Read | |
| AVmin | 47 | 4150_1 | Battery Time Remaining | min | Read | |
| AV | 48 | 4149_1 | DC Bus Current | A DC | Read | |
| AV | 49 | 5804_1 | Time Until Next Auto Battery Test | min | Read | |
| AV | 50 | 4153_1 | Battery Percentage Charge | % | Read | |
| AV | 51 | 5845_1 | Number of Discharge Cycles | Read | ||
| AV | 52 | 5846_1 | Accumulated Discharge Time | h | Read | |
| AV | 53 | 5802_1 | Low Battery Warning Time | min | Read | |
| AV | 54 | 5991_1 | Battery Self Test Cycle Time | day | Read | |
| AV | 55 | 4148_1 | DC Bus Voltage | VDC | Read | |
| AV | 56 | 5853_1 | Battery Temperature | °C | Read | |
| AV | 10056 | 5853_1_deg_F | Battery Temperature | °F | Read | |
| AV | 57 | 8281_1 | Positive DC Bus Voltage | VDC | Read | |
| AV | 58 | 8282_1 | Negative DC Bus Voltage | VDC | Read | |
| AV | 67 | 4156_1_1 | Battery Temperature for Cabinet (Battery Cabinets 1) | °C | Read | |
| AV | 10067 | 4156_1_1_deg_F | Battery Temperature for Cabinet (Battery Cabinets 1) | °F | Read | |
| AV | 68 | 4155_1_1 | Battery Volts for Cabinet (Battery Cabinets 1) | VDC | Read | |
| AV | 79 | 4156_1_2 | Battery Temperature for Cabinet (Battery Cabinets 2) | °C | Read | |
| AV | 10079 | 4156_1_2_deg_F | Battery Temperature for Cabinet (Battery Cabinets 2) | °F | Read | |
| AV | 80 | 4155_1_2 | Battery Volts for Cabinet (Battery Cabinets 2) | VDC | Read | |
| AV | 289 | 4156_1_12 | Battery Temperature for Cabinet (Battery Cabinets 12) | °C | Read | |
| AV | 10199 | 4156_1_12_deg_F | Battery Temperature for Cabinet (Battery Cabinets 12) | °F | Read | |
| AV | 200 | 4155_1_12 | Battery Volts for Cabinet (Battery Cabinets 12) | VDC | Read | |
| AVmin | 163 | 4385_1 | System Output Voltage RMS A-N | V | Read | |
| AV | 164 | 4386_1 | System Output Voltage RMS B-N | V | Read | |
| AV | 165 | 4387_1 | System Output Voltage RMS C-N | V | Read | |
| AVmin | 166 | 4204_1 | System Output RMS Current Phs A | A | Read | |
| AV | 167 | 4205_1 | System Output RMS Current Phs B | A | Read | |
| AV | 168 | 4206_1 | System Output RMS Current Phs C | A | Read | |
| AV | 169 | 4207_1 | System Output Frequency | Hz | Read | |
| AV | 170 | 4201_1 | System Output Voltage RMS A-B | V | Read | |
| AV | 171 | 4202_1 | System Output Voltage RMS B-C | V | Read | |
| AV | 172 | 4203_1 | System Output Voltage RMS C-A | V | Read | |
| AV | 173 | 4210_1 | System Output Power Factor Phs A | Read | ||
| AV | 174 | 4211_1 | System Output Power Factor Phs B | Read | ||
| AV | 175 | 4212_1 | System Output Power Factor Phs C | Read | ||
| AV | 176 | 4223_1 | System Output Pct Power Phase A | % | Read | |
| AV | 177 | 4224_1 | System Output Pct Power Phase B | % | Read | |
| AV | 178 | 4225_1 | System Output Pct Power Phase C | % | Read | |
| AV | 179 | 4812_1 | MMS Output Apparent Power | kVA | Read | |
| AV | 180 | 4811_1 | MMS Output Power | kW | Read | |
| AV | 181 | 5159_1 | Output Current Crest Factor Phs A | Read | ||
| AV | 182 | 5160_1 | Output Current Crest Factor Phs B | Read | ||
| AV | 183 | 5161_1 | Output Current Crest Factor Phs C | Read | ||
| AV | 184 | 5859_1 | System Output Power Phase A | kW | Read | |
| AV | 185 | 5860_1 | System Output Power Phase B | kW | Read | |
| AV | 186 | 5959_1 | System Output Power Phase C | kW | Read | |
| AV | 187 | 5868_1 | System Output Apparent Power Phs A | kVA | Read | |
| AV | 188 | 5869_1 | System Output Apparent Power Phs B | kVA | Read | |
| AV | 189 | 5870_1 | System Output Apparent Power Phs C | kVA | Read | |
| AVmin | 190 | 4208_1 | System Output Power | kW | Read | |
| AV | 191 | 4209_1 | System Output Apparent Power | kVA | Read | |
| AV | 192 | 4226_1 | System Output Pct Pwr (VA) Phs A | % | Read | |
| AV | 193 | 4227_1 | System Output Pct Pwr (VA) Phs B | % | Read | |
| AV | 194 | 4228_1 | System Output Pct Pwr (VA) Phs C | % | Read | |
| AV | 195 | 4260_1 | System Output Nominal Voltage | V | Read | |
| AV | 196 | 4261_1 | System Output Nominal Frequency | Hz | Read | |
| AV | 197 | 8097_1 | ECO Suspended Time Remaining | s | Read | |
| AV | 207 | 6442_1 | Power Module Bypass Input Frequency | Hz | Read | |
| AV | 208 | 6443_1 | Power Module Bypass Input Voltage RMS A-N | V | Read | |
| AV | 209 | 6444_1 | Power Module Bypass Input Voltage RMS B-N | V | Read | |
| AV | 210 | 6445_1 | Power Module Bypass Input Voltage RMS C-N | V | Read | |
| AV | 211 | 6446_1 | Power Module Bypass Input Voltage RMS A-B | V | Read | |
| AV | 212 | 6447_1 | Power Module Bypass Input Voltage RMS B-C | V | Read | |
| AV | 213 | 6448_1 | Power Module Bypass Input Voltage RMS C-A | V | Read | |
| AV | 224 | 5824_1 | Number Of Active Power Modules | Read | ||
| AV | 225 | 5823_1 | Number of Installed Power Modules | Read | ||
| AV | 226 | 4291_1 | Inlet Air Temperature | °C | Read | |
| AV | 10226 | 4291_1_deg_F | Inlet Air Temperature | °F | Read | |
| AV | 227 | 6069_1 | Average system efficiency | % | Read | |
| AV | 238 | 4293_1 | System Date and Time | Secs since Epoch(UTC) | Write | |
| AV | 239 | 4292_1 | Total System Operating Time | h | Read | |
| AV | 240 | 5821_1 | System Capacity | kVA | Read | |
| MV | 1 | 4766_1 | Input Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 12 | 6057_1 | External Bypass Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 23 | 4871_1 | UPS Battery Status | Read | 1=Unknown, 2=Normal, 3=Low, 4=Depleted | |
| MV | 24 | 5799_1 | Battery charge status | Read | 1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off) | |
| MV | 25 | 5803_1 | Automatic Battery Test | Read | 1=disabled, 2=enabled | |
| MV | 32 | 7466_1_1 | Lithium-Ion Battery System Status | Read | 1=offline, 2=online | |
| MV | 36 | 4768_1 | Output Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 37 | 4746_1 | Inverter On/Off State | Read | 1=off, 2=on | |
| MV | 48 | 6437_1 | Power Module Sleep Status (PowerModules 1) | Read | 1=Sleeping, 2=Not Sleeping | |
| MV | 49 | 5833_1 | Module Operating Status (PowerModules 1) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 50 | 5864_1 | Inverter Status (PowerModules 1) | Read | 1=Inverter Inactive, 2=Inverter Active | |
| MV | 51 | 8099_1 | Power Module Ready Status (PowerModules 1) | Read | 1=Not ready, 2=Ready | |
| MV | 61 | 6437_2 | Power Module Sleep Status (PowerModules 2) | Read | 1=Sleeping, 2=Not Sleeping | |
| MV | 62 | 5833_2 | Module Operating Status (PowerModules 2) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 63 | 5864_2 | Inverter Status (PowerModules 2) | Read | 1=Inverter Inactive, 2=Inverter Active | |
| MV | 64 | 8099_2 | Power Module Ready Status (PowerModules 2) | Read | 1=Not ready, 2=Ready | |
| MV | 295 | 6437_20 | Power Module Sleep Status (PowerModules 20) | Read | 1=Sleeping, 2=Not Sleeping | |
| MV | 296 | 5833_20 | Module Operating Status (PowerModules 20) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 297 | 5864_20 | Inverter Status (PowerModules 20) | Read | 1=Inverter Inactive, 2=Inverter Active | |
| MV | 298 | 8099_20 | Power Module Ready Status (PowerModules 20) | Read | 1=Not ready, 2=Ready | |
| MV | 308 | 5820_1 | System Set To Operate With | Read | 1=No Redundancy, 2=Redundancy | |
| MV | 309 | 4772_1 | Maintenance Bypass Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 310 | 5454_1 | ECO Mode Operation State | Read | 1=disabled, 2=enabled | |
| MV | 312 | 4874_1 | MMS UPS Output Source | Read | 1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer | |
| MV | 313 | 5448_1 | Intelligent Parallel Operation State | Read | 1=disabled, 2=enabled | |
| MV | 314 | 6537_1 | Application Mode For UPS | Read | 1=UPS Mode, 2=Frequency Converter Mode, 3=Intelligent Paralleling Mode, 4=Intelligent Paralleling Mode Demo, 5=ECO Mode, 6=Intelligent ECO Mode, 7=Intelligent ECO Mode Demo, 8=Testing Mode, 9=Regen Mode, 10=Power Conditioner Mode | |
| MVmin | 324 | 4872_1 | UPS Output Source | Read | 1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer | |
| MVmin | 325 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation |
No points match these filters.
Object ID lookup: Vertiv Liebert APM 600 UPS with GHMI point IDs by name
BV15155_1BV24146_1BV34122_1BV46061_1BV154135_1BV164143_1BV174139_1BV184298_1BV194299_1BV205957_1BV214216_1BV324173_1BV334185_1BV344182_1BV354179_1BV364176_1BV374741_1BV384200_1BV394168_1BV404171_1BV414172_1BV424322_1BV434323_1BV444219_1BV454162_1BV464222_1BV475149_1BV485150_1BV494166_1BV506063_1BV516065_1BV526068_1BV534177_1BV544180_1BV554183_1BV564186_1BV574170_1BV587485_1BV597461_1BV627464_1_1BV637465_1_1BV647486_1_1BV657487_1_1BV667488_1_1BV686062_1BV795806_1BV804389_1BV916438_1BV924295_1BV934233_1BV945154_1BV955153_1BV966059_1BV974164_1BV985151_1BV996439_1BV1004290_1BV1016440_1BV1026441_1BV1035838_1BV1045839_1BV1056528_1BV1068098_1BV1156438_2BV1164295_2BV1174233_2BV1185154_2BV1195153_2BV1206059_2BV1214164_2BV1225151_2BV1236439_2BV1244290_2BV1256440_2BV1266441_2BV1275838_2BV1285839_2BV1296528_2BV1308098_2BV5476438_20BV5484295_20BV5494233_20BV5505154_20BV5515153_20BV5526059_20BV5534164_20BV5545151_20BV5556439_20BV5564290_20BV5576440_20BV5586441_20BV5595838_20BV5605839_20BV5616528_20BV5628098_20BV5715817_1BV5726066_1BV5736064_1BV5746060_1BV5755458_1BV5765157_1BV5775156_1BV5784300_1BV5794831_1BV5804823_1BV5814310_1BV5824758_1BV5834315_1BV5844757_1BV5854213_1BV5865770_1BV5876529_1BV5886536_1BV5894440_1AV14097_1AV24099_1AV34101_1AV44113_1AV54114_1AV64115_1AV74105_1AV84096_1AV94098_1AV104100_1AV114116_1AV124117_1AV134118_1AV144102_1AV154103_1AV164104_1AV174119_1AV184120_1AV196318_1AV206319_1AV216320_1AV228093_1AV238094_1AV248095_1AV294128_1AV304129_1AV314130_1AV324131_1AV334125_1AV344126_1AV35Bypass Input Voltage RMS C-AAV364259_1AV376325_1AV386326_1AV396327_1AV406328_1AV416329_1AV426330_1AV474150_1AV484149_1AV495804_1AV504153_1AV515845_1AV525846_1AV535802_1AV545991_1AV554148_1AV565853_1AV100565853_1_deg_FAV578281_1AV588282_1AV674156_1_1AV100674156_1_1_deg_FAV684155_1_1AV794156_1_2AV100794156_1_2_deg_FAV804155_1_2AV2894156_1_12AV101994156_1_12_deg_FAV2004155_1_12AV1634385_1AV1644386_1AV1654387_1AV1664204_1AV1674205_1AV1684206_1AV1694207_1AV1704201_1AV1714202_1AV1724203_1AV1734210_1AV1744211_1AV1754212_1AV1764223_1AV1774224_1AV1784225_1AV1794812_1AV1804811_1AV1815159_1AV1825160_1AV1835161_1AV1845859_1AV1855860_1AV1865959_1AV1875868_1AV1885869_1AV1895870_1AV1904208_1AV1914209_1AV1924226_1AV1934227_1AV1944228_1AV1954260_1AV1964261_1AV1978097_1AV2076442_1AV2086443_1AV2096444_1AV2106445_1AV2116446_1AV2126447_1AV2136448_1AV2245824_1AV2255823_1AV2264291_1AV102264291_1_deg_FAV2276069_1AV2384293_1AV2394292_1AV2405821_1MV14766_1MV126057_1MV234871_1MV245799_1MV255803_1MV327466_1_1MV364768_1MV374746_1MV486437_1MV495833_1MV505864_1MV518099_1MV616437_2MV625833_2MV635864_2MV648099_2MV2956437_20MV2965833_20MV2975864_20MV2988099_20MV3085820_1MV3094772_1MV3105454_1MV3124874_1MV3135448_1MV3146537_1MV3244872_1MV3254123_1
Integration notes
- Tables 5.114, 5.115, 5.116, pdf pages 1915-1925 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
- The guide leaves the object name of AV 35 (Bypass Input Voltage RMS C-A) blank; the data label is used as the name here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert APM 600 UPS with GHMI and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert APM 600 UPS with GHMI
How many BACnet points does the Vertiv Liebert APM 600 UPS with GHMI have?
This list has 252 BACnet objects: 110 analog values, 114 binary values, 28 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert APM 600 UPS with GHMI BACnet points are writable?
1 of the 252 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert APM 600 UPS with GHMI BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert APM 600 UPS with GHMI?
Start with MV 325 4123_1 (Normal, warning or alarm state); MV 324 4872_1 (Load on inverter, bypass or battery); AV 47 4150_1 (Estimated battery runtime, min); AV 190 4208_1 (Output power, kW); AV 1 4097_1 (Input voltage, V); AV 163 4385_1 (Output voltage, V); AV 166 4204_1 (Output current, A); BV 39 4168_1 (Load is on battery); BV 578 4300_1 (Internal communication lost).
How do I check these points on the real Liebert APM 600 UPS with GHMI?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.