UPS (uninterruptible power supply) · BACnet points list

Vertiv Liebert APM 600 UPS with GHMI BACnet points list

Updated 6 November 2026

Short answer

The Liebert APM 600 UPS with GHMI reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.

This page lists 252 BACnet objects for the Vertiv Liebert APM 600 UPS with GHMI — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert APM 600 UPS with GHMI
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
252 (1 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
APM 600, Liebert APM600, GHMI, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 252 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert APM 600 UPS with GHMI

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 3254123_1Normal, warning or alarm stateRead
MV 3244872_1Load on inverter, bypass or batteryRead
AV 474150_1Estimated battery runtime, minRead
AV 1904208_1Output power, kWRead
AV 14097_1Input voltage, VRead
AV 1634385_1Output voltage, VRead
AV 1664204_1Output current, ARead
BV 394168_1Load is on batteryRead
BV 5784300_1Internal communication lostRead

Network setup

Watch out for

Vertiv Liebert APM 600 UPS with GHMI BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

252 of 252 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert APM 600 UPS with GHMI BACnet Points List
DescriptionStates
BV15155_1Mains Input Neutral LostReadActive = alarm
BV24146_1System Input Phs Rotation ErrorReadActive = alarm
BV34122_1System Input Power ProblemReadActive = alarm
BV46061_1Input Source BackfeedReadActive = alarm
BV154135_1Bypass Not AvailableReadActive = alarm
BV164143_1Bypass Static Switch UnavailableReadActive = alarm
BV174139_1Bypass - Excess Auto RetransfersReadActive = alarm
BV184298_1UPS Output on BypassReadActive = alarm
BV194299_1Output Load on Maint. BypassReadActive = alarm
BV205957_1Bypass Input Voltage FaultReadActive = alarm
BV214216_1Bypass Backfeed DetectedReadActive = alarm
BV324173_1Main Battery Disconnect OpenReadActive = alarm
BV334185_1Battery Circuit Breaker 4 OpenReadActive = alarm
BV344182_1Battery Circuit Breaker 3 OpenReadActive = alarm
BV354179_1Battery Circuit Breaker 2 OpenReadActive = alarm
BV364176_1Battery Circuit Breaker 1 OpenReadActive = alarm
BV374741_1Battery Self TestReadActive = alarm
BV384200_1Battery Charging InhibitedReadActive = alarm
BVmin394168_1Battery DischargingReadActive = alarm
BV404171_1Battery Manual Test In ProgressReadActive = alarm
BV414172_1Battery Auto Test In ProgressReadActive = alarm
BV424322_1Battery Test PassedReadActive = alarm
BV434323_1Battery Test FailedReadActive = alarm
BV444219_1Battery Over TemperatureReadActive = alarm
BV454162_1Battery LowReadActive = alarm
BV464222_1Battery Ground FaultReadActive = alarm
BV475149_1Battery Not QualifiedReadActive = alarm
BV485150_1Battery Terminals ReversedReadActive = alarm
BV494166_1Battery Capacity LowReadActive = alarm
BV506063_1Battery Converter Current LimitReadActive = alarm
BV516065_1Battery Charge Equalization TimeoutReadActive = alarm
BV526068_1Battery Room AlarmReadActive = alarm
BV534177_1Battery Breaker 1 Open FailureReadActive = alarm
BV544180_1Battery Breaker 2 Open FailureReadActive = alarm
BV554183_1Battery Breaker 3 Open FailureReadActive = alarm
BV564186_1Battery Breaker 4 Open FailureReadActive = alarm
BV574170_1Battery EqualizeReadActive = alarm
BV587485_1Battery Circuit Breaker OpenReadActive = alarm
BV597461_1Battery Breaker Open FailureReadActive = alarm
BV627464_1_1Lithium-Ion Battery System AbnormalReadActive = alarm
BV637465_1_1Lithium-Ion Battery System Disconnect RequestReadActive = alarm
BV647486_1_1Lithium-Ion Battery System Communication AbnormalReadActive = alarm
BV657487_1_1Lithium-Ion Battery System WarningReadActive = alarm
BV667488_1_1Lithium-Ion Battery System FaultReadActive = alarm
BV686062_1Loss of SynchronizationReadActive = alarm
BV795806_1Output OverloadReadActive = alarm
BV804389_1System Output FaultReadActive = alarm
BV916438_1Power Module Input Current Abnormal (PowerModules 1)ReadActive = alarm
BV924295_1Rectifier Failure (PowerModules 1)ReadActive = alarm
BV934233_1Inverter Failure (PowerModules 1)ReadActive = alarm
BV945154_1DC Bus Abnormal (PowerModules 1)ReadActive = alarm
BV955153_1Load Sharing Fault (PowerModules 1)ReadActive = alarm
BV966059_1Inverter Relay Fault (PowerModules 1)ReadActive = alarm
BV974164_1Battery Charging Error (PowerModules 1)ReadActive = alarm
BV985151_1Battery Converter Failure (PowerModules 1)ReadActive = alarm
BV996439_1Power Module Balancer of DC Bus Failure (PowerModules 1)ReadActive = alarm
BV1004290_1Inverter Shutdown - Overload (PowerModules 1)ReadActive = alarm
BV1016440_1Power Module Fuse Failure (PowerModules 1)ReadActive = alarm
BV1026441_1Power Module Power Supply Failure (PowerModules 1)ReadActive = alarm
BV1035838_1Power Module Fan Fault (PowerModules 1)ReadActive = alarm
BV1045839_1Power Module Over Temperature (PowerModules 1)ReadActive = alarm
BV1056528_1Power Module Lever Unlocked (PowerModules 1)ReadActive = alarm
BV1068098_1Power Module Communication status (PowerModules 1)ReadActive = alarm
BV1156438_2Power Module Input Current Abnormal (PowerModules 2)ReadActive = alarm
BV1164295_2Rectifier Failure (PowerModules 2)ReadActive = alarm
BV1174233_2Inverter Failure (PowerModules 2)ReadActive = alarm
BV1185154_2DC Bus Abnormal (PowerModules 2)ReadActive = alarm
BV1195153_2Load Sharing Fault (PowerModules 2)ReadActive = alarm
BV1206059_2Inverter Relay Fault (PowerModules 2)ReadActive = alarm
BV1214164_2Battery Charging Error (PowerModules 2)ReadActive = alarm
BV1225151_2Battery Converter Failure (PowerModules 2)ReadActive = alarm
BV1236439_2Power Module Balancer of DC Bus Failure (PowerModules 2)ReadActive = alarm
BV1244290_2Inverter Shutdown - Overload (PowerModules 2)ReadActive = alarm
BV1256440_2Power Module Fuse Failure (PowerModules 2)ReadActive = alarm
BV1266441_2Power Module Power Supply Failure (PowerModules 2)ReadActive = alarm
BV1275838_2Power Module Fan Fault (PowerModules 2)ReadActive = alarm
BV1285839_2Power Module Over Temperature (PowerModules 2)ReadActive = alarm
BV1296528_2Power Module Lever Unlocked (PowerModules 2)ReadActive = alarm
BV1308098_2Power Module Communication status (PowerModules 2)ReadActive = alarm
BV5476438_20Power Module Input Current Abnormal (PowerModules 20)ReadActive = alarm
BV5484295_20Rectifier Failure (PowerModules 20)ReadActive = alarm
BV5494233_20Inverter Failure (PowerModules 20)ReadActive = alarm
BV5505154_20DC Bus Abnormal (PowerModules 20)ReadActive = alarm
BV5515153_20Load Sharing Fault (PowerModules 20)ReadActive = alarm
BV5526059_20Inverter Relay Fault (PowerModules 20)ReadActive = alarm
BV5534164_20Battery Charging Error (PowerModules 20)ReadActive = alarm
BV5545151_20Battery Converter Failure (PowerModules 20)ReadActive = alarm
BV5556439_20Power Module Balancer of DC Bus Failure (PowerModules 20)ReadActive = alarm
BV5564290_20Inverter Shutdown - Overload (PowerModules 20)ReadActive = alarm
BV5576440_20Power Module Fuse Failure (PowerModules 20)ReadActive = alarm
BV5586441_20Power Module Power Supply Failure (PowerModules 20)ReadActive = alarm
BV5595838_20Power Module Fan Fault (PowerModules 20)ReadActive = alarm
BV5605839_20Power Module Over Temperature (PowerModules 20)ReadActive = alarm
BV5616528_20Power Module Lever Unlocked (PowerModules 20)ReadActive = alarm
BV5628098_20Power Module Communication status (PowerModules 20)ReadActive = alarm
BV5715817_1Loss of RedundancyReadActive = alarm
BV5726066_1Parallel Cable FailureReadActive = alarm
BV5736064_1LBS Cable FailureReadActive = alarm
BV5746060_1Transfer to Bypass - System OverloadReadActive = alarm
BV5755458_1Excess ECO SuspendsReadActive = alarm
BV5765157_1User Operation InvalidReadActive = alarm
BV5775156_1Load Impact TransferReadActive = alarm
BVmin5784300_1Internal Communications FailureReadActive = alarm
BV5794831_1MMS OverloadReadActive = alarm
BV5804823_1Parallel Comm WarningReadActive = alarm
BV5814310_1Equipment Over TemperatureReadActive = alarm
BV5824758_1LBS InhibitedReadActive = alarm
BV5834315_1On GeneratorReadActive = alarm
BV5844757_1LBS ActiveReadActive = alarm
BV5854213_1System Shutdown - EPOReadActive = alarm
BV5865770_1Top Outlet Fan FaultReadActive = alarm
BV5876529_1Hardware MismatchReadActive = alarm
BV5886536_1MMS Capacity ExceededReadActive = alarm
BV5894440_1Fuse FailureReadActive = alarm
AVmin14097_1System Input RMS A-BVRead
AV24099_1System Input RMS B-CVRead
AV34101_1System Input RMS C-AVRead
AV44113_1System Input RMS Current Phase AARead
AV54114_1System Input RMS Current Phase BARead
AV64115_1System Input RMS Current Phase CARead
AV74105_1System Input FrequencyHzRead
AV84096_1System Input RMS A-NVRead
AV94098_1System Input RMS B-NVRead
AV104100_1System Input RMS C-NVRead
AV114116_1System Input Power Factor Phs ARead
AV124117_1System Input Power Factor Phs BRead
AV134118_1System Input Power Factor Phs CRead
AV144102_1System Input Nominal VoltageVRead
AV154103_1System Input Nominal FrequencyHzRead
AV164104_1System Input Nominal CurrentARead
AV174119_1System Input Brown Out CountRead
AV184120_1System Input Black Out CountRead
AV196318_1System Input Power Phase AkWRead
AV206319_1System Input Power Phase BkWRead
AV216320_1System Input Power Phase CkWRead
AV228093_1System Input Apparent Power Phs AkVARead
AV238094_1System Input Apparent Power Phs BkVARead
AV248095_1System Input Apparent Power Phs CkVARead
AV294128_1Bypass Input Voltage RMS A-NVRead
AV304129_1Bypass Input Voltage RMS B-NVRead
AV314130_1Bypass Input Voltage RMS C-NVRead
AV324131_1Bypass Input FrequencyHzRead
AV334125_1Bypass Input Voltage RMS A-BVRead
AV344126_1Bypass Input Voltage RMS B-CVRead
AV35Bypass Input Voltage RMS C-AVRead
AV364259_1Bypass Nominal VoltageVRead
AV376325_1Bypass Power Phase AkWRead
AV386326_1Bypass Power Phase BkWRead
AV396327_1Bypass Power Phase CkWRead
AV406328_1Bypass Apparent Power Phase AkVARead
AV416329_1Bypass Apparent Power Phase BkVARead
AV426330_1Bypass Apparent Power Phase CkVARead
AVmin474150_1Battery Time RemainingminRead
AV484149_1DC Bus CurrentA DCRead
AV495804_1Time Until Next Auto Battery TestminRead
AV504153_1Battery Percentage Charge%Read
AV515845_1Number of Discharge CyclesRead
AV525846_1Accumulated Discharge TimehRead
AV535802_1Low Battery Warning TimeminRead
AV545991_1Battery Self Test Cycle TimedayRead
AV554148_1DC Bus VoltageVDCRead
AV565853_1Battery Temperature°CRead
AV100565853_1_deg_FBattery Temperature°FRead
AV578281_1Positive DC Bus VoltageVDCRead
AV588282_1Negative DC Bus VoltageVDCRead
AV674156_1_1Battery Temperature for Cabinet (Battery Cabinets 1)°CRead
AV100674156_1_1_deg_FBattery Temperature for Cabinet (Battery Cabinets 1)°FRead
AV684155_1_1Battery Volts for Cabinet (Battery Cabinets 1)VDCRead
AV794156_1_2Battery Temperature for Cabinet (Battery Cabinets 2)°CRead
AV100794156_1_2_deg_FBattery Temperature for Cabinet (Battery Cabinets 2)°FRead
AV804155_1_2Battery Volts for Cabinet (Battery Cabinets 2)VDCRead
AV2894156_1_12Battery Temperature for Cabinet (Battery Cabinets 12)°CRead
AV101994156_1_12_deg_FBattery Temperature for Cabinet (Battery Cabinets 12)°FRead
AV2004155_1_12Battery Volts for Cabinet (Battery Cabinets 12)VDCRead
AVmin1634385_1System Output Voltage RMS A-NVRead
AV1644386_1System Output Voltage RMS B-NVRead
AV1654387_1System Output Voltage RMS C-NVRead
AVmin1664204_1System Output RMS Current Phs AARead
AV1674205_1System Output RMS Current Phs BARead
AV1684206_1System Output RMS Current Phs CARead
AV1694207_1System Output FrequencyHzRead
AV1704201_1System Output Voltage RMS A-BVRead
AV1714202_1System Output Voltage RMS B-CVRead
AV1724203_1System Output Voltage RMS C-AVRead
AV1734210_1System Output Power Factor Phs ARead
AV1744211_1System Output Power Factor Phs BRead
AV1754212_1System Output Power Factor Phs CRead
AV1764223_1System Output Pct Power Phase A%Read
AV1774224_1System Output Pct Power Phase B%Read
AV1784225_1System Output Pct Power Phase C%Read
AV1794812_1MMS Output Apparent PowerkVARead
AV1804811_1MMS Output PowerkWRead
AV1815159_1Output Current Crest Factor Phs ARead
AV1825160_1Output Current Crest Factor Phs BRead
AV1835161_1Output Current Crest Factor Phs CRead
AV1845859_1System Output Power Phase AkWRead
AV1855860_1System Output Power Phase BkWRead
AV1865959_1System Output Power Phase CkWRead
AV1875868_1System Output Apparent Power Phs AkVARead
AV1885869_1System Output Apparent Power Phs BkVARead
AV1895870_1System Output Apparent Power Phs CkVARead
AVmin1904208_1System Output PowerkWRead
AV1914209_1System Output Apparent PowerkVARead
AV1924226_1System Output Pct Pwr (VA) Phs A%Read
AV1934227_1System Output Pct Pwr (VA) Phs B%Read
AV1944228_1System Output Pct Pwr (VA) Phs C%Read
AV1954260_1System Output Nominal VoltageVRead
AV1964261_1System Output Nominal FrequencyHzRead
AV1978097_1ECO Suspended Time RemainingsRead
AV2076442_1Power Module Bypass Input FrequencyHzRead
AV2086443_1Power Module Bypass Input Voltage RMS A-NVRead
AV2096444_1Power Module Bypass Input Voltage RMS B-NVRead
AV2106445_1Power Module Bypass Input Voltage RMS C-NVRead
AV2116446_1Power Module Bypass Input Voltage RMS A-BVRead
AV2126447_1Power Module Bypass Input Voltage RMS B-CVRead
AV2136448_1Power Module Bypass Input Voltage RMS C-AVRead
AV2245824_1Number Of Active Power ModulesRead
AV2255823_1Number of Installed Power ModulesRead
AV2264291_1Inlet Air Temperature°CRead
AV102264291_1_deg_FInlet Air Temperature°FRead
AV2276069_1Average system efficiency%Read
AV2384293_1System Date and TimeSecs since Epoch(UTC)Write
AV2394292_1Total System Operating TimehRead
AV2405821_1System CapacitykVARead
MV14766_1Input BreakerRead1=Open, 2=Close, 3=Not Installed
MV126057_1External Bypass BreakerRead1=Open, 2=Close, 3=Not Installed
MV234871_1UPS Battery StatusRead1=Unknown, 2=Normal, 3=Low, 4=Depleted
MV245799_1Battery charge statusRead1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off)
MV255803_1Automatic Battery TestRead1=disabled, 2=enabled
MV327466_1_1Lithium-Ion Battery System StatusRead1=offline, 2=online
MV364768_1Output BreakerRead1=Open, 2=Close, 3=Not Installed
MV374746_1Inverter On/Off StateRead1=off, 2=on
MV486437_1Power Module Sleep Status (PowerModules 1)Read1=Sleeping, 2=Not Sleeping
MV495833_1Module Operating Status (PowerModules 1)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV505864_1Inverter Status (PowerModules 1)Read1=Inverter Inactive, 2=Inverter Active
MV518099_1Power Module Ready Status (PowerModules 1)Read1=Not ready, 2=Ready
MV616437_2Power Module Sleep Status (PowerModules 2)Read1=Sleeping, 2=Not Sleeping
MV625833_2Module Operating Status (PowerModules 2)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV635864_2Inverter Status (PowerModules 2)Read1=Inverter Inactive, 2=Inverter Active
MV648099_2Power Module Ready Status (PowerModules 2)Read1=Not ready, 2=Ready
MV2956437_20Power Module Sleep Status (PowerModules 20)Read1=Sleeping, 2=Not Sleeping
MV2965833_20Module Operating Status (PowerModules 20)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV2975864_20Inverter Status (PowerModules 20)Read1=Inverter Inactive, 2=Inverter Active
MV2988099_20Power Module Ready Status (PowerModules 20)Read1=Not ready, 2=Ready
MV3085820_1System Set To Operate WithRead1=No Redundancy, 2=Redundancy
MV3094772_1Maintenance Bypass BreakerRead1=Open, 2=Close, 3=Not Installed
MV3105454_1ECO Mode Operation StateRead1=disabled, 2=enabled
MV3124874_1MMS UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MV3135448_1Intelligent Parallel Operation StateRead1=disabled, 2=enabled
MV3146537_1Application Mode For UPSRead1=UPS Mode, 2=Frequency Converter Mode, 3=Intelligent Paralleling Mode, 4=Intelligent Paralleling Mode Demo, 5=ECO Mode, 6=Intelligent ECO Mode, 7=Intelligent ECO Mode Demo, 8=Testing Mode, 9=Regen Mode, 10=Power Conditioner Mode
MVmin3244872_1UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MVmin3254123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
Object ID lookup: Vertiv Liebert APM 600 UPS with GHMI point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert APM 600 UPS with GHMI and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert APM 600 UPS with GHMI

How many BACnet points does the Vertiv Liebert APM 600 UPS with GHMI have?

This list has 252 BACnet objects: 110 analog values, 114 binary values, 28 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert APM 600 UPS with GHMI BACnet points are writable?

1 of the 252 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert APM 600 UPS with GHMI BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert APM 600 UPS with GHMI?

Start with MV 325 4123_1 (Normal, warning or alarm state); MV 324 4872_1 (Load on inverter, bypass or battery); AV 47 4150_1 (Estimated battery runtime, min); AV 190 4208_1 (Output power, kW); AV 1 4097_1 (Input voltage, V); AV 163 4385_1 (Output voltage, V); AV 166 4204_1 (Output current, A); BV 39 4168_1 (Load is on battery); BV 578 4300_1 (Internal communication lost).

How do I check these points on the real Liebert APM 600 UPS with GHMI?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.