- Liebert EXM2 / APM Plus UPS
UPS (uninterruptible power supply) · BACnet points list
Vertiv Liebert EXM2 / APM Plus UPS BACnet points list
Updated 6 November 2026
The Liebert EXM2 / APM Plus UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.
This page lists 252 BACnet objects for the Vertiv Liebert EXM2 / APM Plus UPS — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert EXM2 / APM Plus UPS
- Equipment
- UPS (uninterruptible power supply)
- Equipment type
- Other equipment
- BACnet objects
- 252 (1 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- EXM2, APM Plus, Liebert EXM2, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert EXM2 / APM Plus UPS
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 343 | 4123_1 | Normal, warning or alarm state | Read |
| MV 342 | 4872_1 | Load on inverter, bypass or battery | Read |
| AV 58 | 4150_1 | Estimated battery runtime, min | Read |
| AV 193 | 4208_1 | Output power, kW | Read |
| AV 1 | 4097_1 | Input voltage, V | Read |
| AV 166 | 4385_1 | Output voltage, V | Read |
| AV 169 | 4204_1 | Output current, A | Read |
| BV 38 | 4168_1 | Load is on battery | Read |
| BV 660 | 4300_1 | Internal communication lost | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert EXM2 / APM Plus UPS BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | 5155_1 | Mains Input Neutral Lost | Read | Active = alarm | |
| BV | 2 | 4146_1 | System Input Phs Rotation Error | Read | Active = alarm | |
| BV | 3 | 4122_1 | System Input Power Problem | Read | Active = alarm | |
| BV | 4 | 6061_1 | Input Source Backfeed | Read | Active = alarm | |
| BV | 15 | 4135_1 | Bypass Not Available | Read | Active = alarm | |
| BV | 16 | 4143_1 | Bypass Static Switch Unavailable | Read | Active = alarm | |
| BV | 17 | 4139_1 | Bypass - Excess Auto Retransfers | Read | Active = alarm | |
| BV | 18 | 4298_1 | UPS Output on Bypass | Read | Active = alarm | |
| BV | 19 | 4299_1 | Output Load on Maint. Bypass | Read | Active = alarm | |
| BV | 20 | 4216_1 | Bypass Backfeed Detected | Read | Active = alarm | |
| BV | 21 | 8200_1 | Bypass Control Module Not Available | Read | Active = alarm | |
| BV | 22 | 8201_1 | Bypass Module Not Available | Read | Active = alarm | |
| BV | 24 | 8283_1 | Bypass Unable to Trace | Read | Active = alarm | |
| BV | 35 | 4176_1 | Battery Circuit Breaker 1 Open | Read | Active = alarm | |
| BV | 36 | 4741_1 | Battery Self Test | Read | Active = alarm | |
| BV | 37 | 4200_1 | Battery Charging Inhibited | Read | Active = alarm | |
| BVmin | 38 | 4168_1 | Battery Discharging | Read | Active = alarm | |
| BV | 39 | 4171_1 | Battery Manual Test In Progress | Read | Active = alarm | |
| BV | 40 | 4172_1 | Battery Auto Test In Progress | Read | Active = alarm | |
| BV | 41 | 4323_1 | Battery Test Failed | Read | Active = alarm | |
| BV | 42 | 4219_1 | Battery Over Temperature | Read | Active = alarm | |
| BV | 43 | 4162_1 | Battery Low | Read | Active = alarm | |
| BV | 44 | 4222_1 | Battery Ground Fault | Read | Active = alarm | |
| BV | 45 | 5149_1 | Battery Not Qualified | Read | Active = alarm | |
| BV | 46 | 5150_1 | Battery Terminals Reversed | Read | Active = alarm | |
| BV | 47 | 4166_1 | Battery Capacity Low | Read | Active = alarm | |
| BV | 48 | 6063_1 | Battery Converter Current Limit | Read | Active = alarm | |
| BV | 49 | 6065_1 | Battery Charge Equalization Timeout | Read | Active = alarm | |
| BV | 50 | 6068_1 | Battery Room Alarm | Read | Active = alarm | |
| BV | 51 | 4177_1 | Battery Breaker 1 Open Failure | Read | Active = alarm | |
| BV | 52 | 4170_1 | Battery Equalize | Read | Active = alarm | |
| BV | 53 | 5874_1 | Battery Over Voltage | Read | Active = alarm | |
| BV | 54 | 8273_1 | Battery Temp Abnormal | Read | Active = alarm | |
| BV | 55 | 8194_1 | Battery Management System Rack is Offline Warning | Read | Active = alarm | |
| BV | 56 | 8195_1 | Battery Management System General Warning | Read | Active = alarm | |
| BV | 57 | 8196_1 | Battery Management System Fault | Read | Active = alarm | |
| BV | 58 | 8429_1 | Battery System Communication Abnormal | Read | Active = alarm | |
| BV | 59 | 8430_1 | Battery System Warning | Read | Active = alarm | |
| BV | 60 | 8431_1 | Battery System Fault | Read | Active = alarm | |
| BV | 68 | 6062_1 | Loss of Synchronization | Read | Active = alarm | |
| BV | 79 | 5806_1 | Output Overload | Read | Active = alarm | |
| BV | 80 | 4389_1 | System Output Fault | Read | Active = alarm | |
| BV | 81 | 8284_1 | Output Breaker Open | Read | Active = alarm | |
| BV | 92 | 6438_1 | Power Module Input Current Abnormal (Power Modules 1) | Read | Active = alarm | |
| BV | 93 | 8285_1 | Power Module Input Current High (Power Modules 1) | Read | Active = alarm | |
| BV | 94 | 4295_1 | Rectifier Failure (Power Modules 1) | Read | Active = alarm | |
| BV | 95 | 4233_1 | Inverter Failure (Power Modules 1) | Read | Active = alarm | |
| BV | 96 | 5154_1 | DC Bus Abnormal (Power Modules 1) | Read | Active = alarm | |
| BV | 97 | 5153_1 | Load Sharing Fault (Power Modules 1) | Read | Active = alarm | |
| BV | 98 | 6059_1 | Inverter Relay Fault (Power Modules 1) | Read | Active = alarm | |
| BV | 99 | 4164_1 | Battery Charging Error (Power Modules 1) | Read | Active = alarm | |
| BV | 100 | 5151_1 | Battery Converter Failure (Power Modules 1) | Read | Active = alarm | |
| BV | 101 | 6439_1 | Power Module Balancer of DC Bus Failure (Power Modules 1) | Read | Active = alarm | |
| BV | 102 | 4290_1 | Inverter Shutdown - Overload (Power Modules 1) | Read | Active = alarm | |
| BV | 103 | 6440_1 | Power Module Fuse Failure (Power Modules 1) | Read | Active = alarm | |
| BV | 104 | 6441_1 | Power Module Power Supply Failure (Power Modules 1) | Read | Active = alarm | |
| BV | 105 | 5838_1 | Power Module Fan Fault (Power Modules 1) | Read | Active = alarm | |
| BV | 106 | 5839_1 | Power Module Over Temperature (Power Modules 1) | Read | Active = alarm | |
| BV | 107 | 8098_1 | Power Module Communication status (Power Modules 1) | Read | Active = alarm | |
| BV | 108 | 6528_1 | Power Module Lever Unlocked (Power Modules 1) | Read | Active = alarm | |
| BV | 109 | 8274_1 | Discharger Shutdown (Power Modules 1) | Read | Active = alarm | |
| BV | 120 | 6438_2 | Power Module Input Current Abnormal (Power Modules 2) | Read | Active = alarm | |
| BV | 121 | 8285_2 | Power Module Input Current High (Power Modules 2) | Read | Active = alarm | |
| BV | 122 | 4295_2 | Rectifier Failure (Power Modules 2) | Read | Active = alarm | |
| BV | 123 | 4233_2 | Inverter Failure (Power Modules 2) | Read | Active = alarm | |
| BV | 124 | 5154_2 | DC Bus Abnormal (Power Modules 2) | Read | Active = alarm | |
| BV | 125 | 5153_2 | Load Sharing Fault (Power Modules 2) | Read | Active = alarm | |
| BV | 126 | 6059_2 | Inverter Relay Fault (Power Modules 2) | Read | Active = alarm | |
| BV | 127 | 4164_2 | Battery Charging Error (Power Modules 2) | Read | Active = alarm | |
| BV | 128 | 5151_2 | Battery Converter Failure (Power Modules 2) | Read | Active = alarm | |
| BV | 129 | 6439_2 | Power Module Balancer of DC Bus Failure (Power Modules 2) | Read | Active = alarm | |
| BV | 130 | 4290_2 | Inverter Shutdown - Overload (Power Modules 2) | Read | Active = alarm | |
| BV | 131 | 6440_2 | Power Module Fuse Failure (Power Modules 2) | Read | Active = alarm | |
| BV | 132 | 6441_2 | Power Module Power Supply Failure (Power Modules 2) | Read | Active = alarm | |
| BV | 133 | 5838_2 | Power Module Fan Fault (Power Modules 2) | Read | Active = alarm | |
| BV | 134 | 5839_2 | Power Module Over Temperature (Power Modules 2) | Read | Active = alarm | |
| BV | 135 | 8098_2 | Power Module Communication status (Power Modules 2) | Read | Active = alarm | |
| BV | 136 | 6528_2 | Power Module Lever Unlocked (Power Modules 2) | Read | Active = alarm | |
| BV | 137 | 8274_2 | Discharger Shutdown (Power Modules 2) | Read | Active = alarm | |
| BV | 624 | 6438_20 | Power Module Input Current Abnormal (Power Modules 20) | Read | Active = alarm | |
| BV | 625 | 8285_20 | Power Module Input Current High (Power Modules 20) | Read | Active = alarm | |
| BV | 626 | 4295_20 | Rectifier Failure (Power Modules 20) | Read | Active = alarm | |
| BV | 627 | 4233_20 | Inverter Failure (Power Modules 20) | Read | Active = alarm | |
| BV | 628 | 5154_20 | DC Bus Abnormal (Power Modules 20) | Read | Active = alarm | |
| BV | 629 | 5153_20 | Load Sharing Fault (Power Modules 20) | Read | Active = alarm | |
| BV | 630 | 6059_20 | Inverter Relay Fault (Power Modules 20) | Read | Active = alarm | |
| BV | 631 | 4164_20 | Battery Charging Error (Power Modules 20) | Read | Active = alarm | |
| BV | 632 | 5151_20 | Battery Converter Failure (Power Modules 20) | Read | Active = alarm | |
| BV | 633 | 6439_20 | Power Module Balancer of DC Bus Failure (Power Modules 20) | Read | Active = alarm | |
| BV | 634 | 4290_20 | Inverter Shutdown - Overload (Power Modules 20) | Read | Active = alarm | |
| BV | 635 | 6440_20 | Power Module Fuse Failure (Power Modules 20) | Read | Active = alarm | |
| BV | 636 | 6441_20 | Power Module Power Supply Failure (Power Modules 20) | Read | Active = alarm | |
| BV | 637 | 5838_20 | Power Module Fan Fault (Power Modules 20) | Read | Active = alarm | |
| BV | 638 | 5839_20 | Power Module Over Temperature (Power Modules 20) | Read | Active = alarm | |
| BV | 639 | 8098_20 | Power Module Communication status (Power Modules 20) | Read | Active = alarm | |
| BV | 640 | 6528_20 | Power Module Lever Unlocked (Power Modules 20) | Read | Active = alarm | |
| BV | 641 | 8274_20 | Discharger Shutdown (Power Modules 20) | Read | Active = alarm | |
| BV | 652 | 5817_1 | Loss of Redundancy | Read | Active = alarm | |
| BV | 653 | 6529_1 | Hardware Mismatch | Read | Active = alarm | |
| BV | 654 | 6066_1 | Parallel Cable Failure | Read | Active = alarm | |
| BV | 655 | 6064_1 | LBS Cable Failure | Read | Active = alarm | |
| BV | 656 | 6060_1 | Transfer to Bypass - System Overload | Read | Active = alarm | |
| BV | 657 | 5458_1 | Excess ECO Suspends | Read | Active = alarm | |
| BV | 658 | 5157_1 | User Operation Invalid | Read | Active = alarm | |
| BV | 659 | 5156_1 | Load Impact Transfer | Read | Active = alarm | |
| BVmin | 660 | 4300_1 | Internal Communications Failure | Read | Active = alarm | |
| BV | 661 | 4823_1 | Parallel Comm Warning | Read | Active = alarm | |
| BV | 662 | 4310_1 | Equipment Over Temperature | Read | Active = alarm | |
| BV | 663 | 4758_1 | LBS Inhibited | Read | Active = alarm | |
| BV | 664 | 4315_1 | On Generator | Read | Active = alarm | |
| BV | 665 | 4757_1 | LBS Active | Read | Active = alarm | |
| BV | 666 | 4213_1 | System Shutdown - EPO | Read | Active = alarm | |
| BV | 667 | 6536_1 | MMS Capacity Exceeded | Read | Active = alarm | |
| BV | 668 | 4440_1 | Fuse Failure | Read | Active = alarm | |
| BV | 669 | 5970_1 | Ground Fault | Read | Active = alarm | |
| BV | 670 | 4311_1 | System Fan Failure | Read | Active = alarm | |
| BV | 671 | 8286_1 | Parameter Configuration Failed | Read | Active = alarm | |
| BV | 672 | 4215_1 | System Output Off | Read | Active = alarm | |
| BV | 673 | 8287_1 | Output Disabled | Read | Active = alarm | |
| BV | 674 | 5770_1 | Top Outlet Fan Fault | Read | Active = alarm | |
| BV | 675 | 8100_1 | ECO mode Inhibited | Read | Active = alarm | |
| BV | 676 | 4289_1 | Inverter Transfer Inhibit - Ext | Read | Active = alarm | |
| AVmin | 1 | 4097_1 | System Input RMS A-B | V | Read | |
| AV | 2 | 4099_1 | System Input RMS B-C | V | Read | |
| AV | 3 | 4101_1 | System Input RMS C-A | V | Read | |
| AV | 4 | 4113_1 | System Input RMS Current Phase A | A | Read | |
| AV | 5 | 4114_1 | System Input RMS Current Phase B | A | Read | |
| AV | 6 | 4115_1 | System Input RMS Current Phase C | A | Read | |
| AV | 7 | 4105_1 | System Input Frequency | Hz | Read | |
| AV | 8 | 4096_1 | System Input RMS A-N | V | Read | |
| AV | 9 | 4098_1 | System Input RMS B-N | V | Read | |
| AV | 10 | 4100_1 | System Input RMS C-N | V | Read | |
| AV | 11 | 4116_1 | System Input Power Factor Phs A | Read | ||
| AV | 12 | 4117_1 | System Input Power Factor Phs B | Read | ||
| AV | 13 | 4118_1 | System Input Power Factor Phs C | Read | ||
| AV | 14 | 6318_1 | System Input Power Phase A | kW | Read | |
| AV | 15 | 6319_1 | System Input Power Phase B | kW | Read | |
| AV | 16 | 6320_1 | System Input Power Phase C | kW | Read | |
| AV | 17 | 8093_1 | System Input Apparent Power Phs A | kVA | Read | |
| AV | 18 | 8094_1 | System Input Apparent Power Phs B | kVA | Read | |
| AV | 19 | 8095_1 | System Input Apparent Power Phs C | kVA | Read | |
| AV | 20 | 4102_1 | System Input Nominal Voltage | V | Read | |
| AV | 21 | 4104_1 | System Input Nominal Current | A | Read | |
| AV | 22 | 4119_1 | System Input Brown Out Count | Read | ||
| AV | 23 | 4120_1 | System Input Black Out Count | Read | ||
| AV | 34 | 4128_1 | Bypass Input Voltage RMS A-N | V | Read | |
| AV | 35 | 4129_1 | Bypass Input Voltage RMS B-N | V | Read | |
| AV | 36 | 4130_1 | Bypass Input Voltage RMS C-N | V | Read | |
| AV | 37 | 4131_1 | Bypass Input Frequency | Hz | Read | |
| AV | 38 | 4125_1 | Bypass Input Voltage RMS A-B | V | Read | |
| AV | 39 | 4126_1 | Bypass Input Voltage RMS B-C | V | Read | |
| AV | 40 | 4127_1 | Bypass Input Voltage RMS C-A | V | Read | |
| AV | 41 | 6325_1 | Bypass Power Phase A | kW | Read | |
| AV | 42 | 6326_1 | Bypass Power Phase B | kW | Read | |
| AV | 43 | 6327_1 | Bypass Power Phase C | kW | Read | |
| AV | 44 | 6328_1 | Bypass Apparent Power Phase A | kVA | Read | |
| AV | 45 | 6329_1 | Bypass Apparent Power Phase B | kVA | Read | |
| AV | 46 | 6330_1 | Bypass Apparent Power Phase C | kVA | Read | |
| AV | 47 | 4259_1 | Bypass Nominal Voltage | V | Read | |
| AVmin | 58 | 4150_1 | Battery Time Remaining | min | Read | |
| AV | 59 | 4149_1 | DC Bus Current | A DC | Read | |
| AV | 60 | 5804_1 | Time Until Next Auto Battery Test | min | Read | |
| AV | 61 | 4153_1 | Battery Percentage Charge | % | Read | |
| AV | 62 | 5845_1 | Number of Discharge Cycles | Read | ||
| AV | 63 | 5846_1 | Accumulated Discharge Time | h | Read | |
| AV | 64 | 5802_1 | Low Battery Warning Time | min | Read | |
| AV | 65 | 5991_1 | Battery Self Test Cycle Time | day | Read | |
| AV | 66 | 4148_1 | DC Bus Voltage | VDC | Read | |
| AV | 67 | 5853_1 | Battery Temperature | °C | Read | |
| AV | 10067 | 5853_1_deg_F | Battery Temperature | °F | Read | |
| AV | 68 | 8281_1 | Positive DC Bus Voltage | VDC | Read | |
| AV | 69 | 8282_1 | Negative DC Bus Voltage | VDC | Read | |
| AV | 78 | 4156_1_1 | Battery Temperature for Cabinet (Battery Cabinets 1) | °C | Read | |
| AV | 10078 | 4156_1_1_deg_F | Battery Temperature for Cabinet (Battery Cabinets 1) | °F | Read | |
| AV | 89 | 4156_1_2 | Battery Temperature for Cabinet (Battery Cabinets 2) | °C | Read | |
| AV | 10089 | 4156_1_2_deg_F | Battery Temperature for Cabinet (Battery Cabinets 2) | °F | Read | |
| AV | 155 | 4156_1_8 | Battery Temperature for Cabinet (Battery Cabinets 8) | °C | Read | |
| AV | 10155 | 4156_1_8_deg_F | Battery Temperature for Cabinet (Battery Cabinets 8) | °F | Read | |
| AV | 238 | 4156_1_9 | Battery Temperature for Cabinet (Battery Cabinets 9) | °C | Read | |
| AV | 10238 | 4156_1_9_deg_F | Battery Temperature for Cabinet (Battery Cabinets 9) | °F | Read | |
| AV | 249 | 4156_1_10 | Battery Temperature for Cabinet (Battery Cabinets 10) | °C | Read | |
| AV | 10249 | 4156_1_10_deg_F | Battery Temperature for Cabinet (Battery Cabinets 10) | °F | Read | |
| AV | 359 | 4156_1_20 | Battery Temperature for Cabinet (Battery Cabinets 20) | °C | Read | |
| AV | 10359 | 4156_1_20_deg_F | Battery Temperature for Cabinet (Battery Cabinets 20) | °F | Read | |
| AVmin | 166 | 4385_1 | System Output Voltage RMS A-N | V | Read | |
| AV | 167 | 4386_1 | System Output Voltage RMS B-N | V | Read | |
| AV | 168 | 4387_1 | System Output Voltage RMS C-N | V | Read | |
| AVmin | 169 | 4204_1 | System Output RMS Current Phs A | A | Read | |
| AV | 170 | 4205_1 | System Output RMS Current Phs B | A | Read | |
| AV | 171 | 4206_1 | System Output RMS Current Phs C | A | Read | |
| AV | 172 | 4207_1 | System Output Frequency | Hz | Read | |
| AV | 173 | 4201_1 | System Output Voltage RMS A-B | V | Read | |
| AV | 174 | 4202_1 | System Output Voltage RMS B-C | V | Read | |
| AV | 175 | 4203_1 | System Output Voltage RMS C-A | V | Read | |
| AV | 176 | 4210_1 | System Output Power Factor Phs A | Read | ||
| AV | 177 | 4211_1 | System Output Power Factor Phs B | Read | ||
| AV | 178 | 4212_1 | System Output Power Factor Phs C | Read | ||
| AV | 179 | 4223_1 | System Output Pct Power Phase A | % | Read | |
| AV | 180 | 4224_1 | System Output Pct Power Phase B | % | Read | |
| AV | 181 | 4225_1 | System Output Pct Power Phase C | % | Read | |
| AV | 182 | 4812_1 | MMS Output Apparent Power | kVA | Read | |
| AV | 183 | 4811_1 | MMS Output Power | kW | Read | |
| AV | 184 | 5159_1 | Output Current Crest Factor Phs A | Read | ||
| AV | 185 | 5160_1 | Output Current Crest Factor Phs B | Read | ||
| AV | 186 | 5161_1 | Output Current Crest Factor Phs C | Read | ||
| AV | 187 | 5859_1 | System Output Power Phase A | kW | Read | |
| AV | 188 | 5860_1 | System Output Power Phase B | kW | Read | |
| AV | 189 | 5959_1 | System Output Power Phase C | kW | Read | |
| AV | 190 | 5868_1 | System Output Apparent Power Phs A | kVA | Read | |
| AV | 191 | 5869_1 | System Output Apparent Power Phs B | kVA | Read | |
| AV | 192 | 5870_1 | System Output Apparent Power Phs C | kVA | Read | |
| AVmin | 193 | 4208_1 | System Output Power | kW | Read | |
| AV | 194 | 4209_1 | System Output Apparent Power | kVA | Read | |
| AV | 195 | 4226_1 | System Output Pct Pwr (VA) Phs A | % | Read | |
| AV | 196 | 4227_1 | System Output Pct Pwr (VA) Phs B | % | Read | |
| AV | 197 | 4228_1 | System Output Pct Pwr (VA) Phs C | % | Read | |
| AV | 198 | 8097_1 | ECO Suspended Time Remaining | s | Read | |
| AV | 199 | 4260_1 | System Output Nominal Voltage | V | Read | |
| AV | 200 | 4261_1 | System Output Nominal Frequency | Hz | Read | |
| AV | 211 | 5824_1 | Number Of Active Power Modules | Read | ||
| AV | 212 | 5823_1 | Number of Installed Power Modules | Read | ||
| AV | 213 | 4291_1 | Inlet Air Temperature | °C | Read | |
| AV | 10213 | 4291_1_deg_F | Inlet Air Temperature | °F | Read | |
| AV | 214 | 6069_1 | Average system efficiency | % | Read | |
| AV | 225 | 4293_1 | System Date and Time | Secs since Epoch(UTC) | Write | |
| AV | 226 | 4292_1 | Total System Operating Time | h | Read | |
| AV | 227 | 5821_1 | System Capacity | kVA | Read | |
| MV | 1 | 4766_1 | Input Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 12 | 4769_1 | Internal Bypass Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 23 | 5803_1 | Automatic Battery Test | Read | 1=disabled, 2=enabled | |
| MV | 24 | 4871_1 | UPS Battery Status | Read | 1=Unknown, 2=Normal, 3=Low, 4=Depleted | |
| MV | 25 | 5799_1 | Battery Charge Status | Read | 1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off) | |
| MV | 36 | 4768_1 | Output Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 37 | 4746_1 | Inverter On/Off State | Read | 1=off, 2=on | |
| MV | 48 | 6437_1 | Power Module Sleep Status (Power Modules 1) | Read | 1=Sleeping, 2=Not Sleeping | |
| MV | 49 | 8099_1 | Power Module Ready Status (Power Modules 1) | Read | 1=Not ready, 2=Ready | |
| MV | 50 | 5833_1 | Module Operating Status (Power Modules 1) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 51 | 5864_1 | Inverter Status (Power Modules 1) | Read | 1=Inverter Inactive, 2=Inverter Active | |
| MV | 62 | 6437_2 | Power Module Sleep Status (Power Modules 2) | Read | 1=Sleeping, 2=Not Sleeping | |
| MV | 63 | 8099_2 | Power Module Ready Status (Power Modules 2) | Read | 1=Not ready, 2=Ready | |
| MV | 64 | 5833_2 | Module Operating Status (Power Modules 2) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 65 | 5864_2 | Inverter Status (Power Modules 2) | Read | 1=Inverter Inactive, 2=Inverter Active | |
| MV | 314 | 6437_20 | Power Module Sleep Status (Power Modules 20) | Read | 1=Sleeping, 2=Not Sleeping | |
| MV | 315 | 8099_20 | Power Module Ready Status (Power Modules 20) | Read | 1=Not ready, 2=Ready | |
| MV | 316 | 5833_20 | Module Operating Status (Power Modules 20) | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Fault | |
| MV | 317 | 5864_20 | Inverter Status (Power Modules 20) | Read | 1=Inverter Inactive, 2=Inverter Active | |
| MV | 328 | 8275_1 | Application Mode For UPS | Read | 1=UPS Mode, 2=Frequency Converter Mode, 3=Intelligent Paralleling Mode, 4=Intelligent Paralleling Mode Demo, 5=ECO Mode, 6=Intelligent ECO Mode, 7=Intelligent ECO Mode Demo, 8=Testing Mode, 9=Regen Mode, 10=Power Conditioner Mode, 11=Frequency Converter Mode without Battery, 12=Dynamic Online Mode, 13=Dynamic Online Mode Demo | |
| MV | 329 | 5820_1 | System Set To Operate With | Read | 1=No Redundancy, 2=Redundancy | |
| MV | 330 | 4772_1 | Maintenance Bypass Breaker | Read | 1=Open, 2=Close, 3=Not Installed | |
| MV | 331 | 4874_1 | MMS UPS Output Source | Read | 1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer | |
| MVmin | 342 | 4872_1 | UPS Output Source | Read | 1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer | |
| MVmin | 343 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation |
No points match these filters.
Object ID lookup: Vertiv Liebert EXM2 / APM Plus UPS point IDs by name
BV15155_1BV24146_1BV34122_1BV46061_1BV154135_1BV164143_1BV174139_1BV184298_1BV194299_1BV204216_1BV218200_1BV228201_1BV248283_1BV354176_1BV364741_1BV374200_1BV384168_1BV394171_1BV404172_1BV414323_1BV424219_1BV434162_1BV444222_1BV455149_1BV465150_1BV474166_1BV486063_1BV496065_1BV506068_1BV514177_1BV524170_1BV535874_1BV548273_1BV558194_1BV568195_1BV578196_1BV588429_1BV598430_1BV608431_1BV686062_1BV795806_1BV804389_1BV818284_1BV926438_1BV938285_1BV944295_1BV954233_1BV965154_1BV975153_1BV986059_1BV994164_1BV1005151_1BV1016439_1BV1024290_1BV1036440_1BV1046441_1BV1055838_1BV1065839_1BV1078098_1BV1086528_1BV1098274_1BV1206438_2BV1218285_2BV1224295_2BV1234233_2BV1245154_2BV1255153_2BV1266059_2BV1274164_2BV1285151_2BV1296439_2BV1304290_2BV1316440_2BV1326441_2BV1335838_2BV1345839_2BV1358098_2BV1366528_2BV1378274_2BV6246438_20BV6258285_20BV6264295_20BV6274233_20BV6285154_20BV6295153_20BV6306059_20BV6314164_20BV6325151_20BV6336439_20BV6344290_20BV6356440_20BV6366441_20BV6375838_20BV6385839_20BV6398098_20BV6406528_20BV6418274_20BV6525817_1BV6536529_1BV6546066_1BV6556064_1BV6566060_1BV6575458_1BV6585157_1BV6595156_1BV6604300_1BV6614823_1BV6624310_1BV6634758_1BV6644315_1BV6654757_1BV6664213_1BV6676536_1BV6684440_1BV6695970_1BV6704311_1BV6718286_1BV6724215_1BV6738287_1BV6745770_1BV6758100_1BV6764289_1AV14097_1AV24099_1AV34101_1AV44113_1AV54114_1AV64115_1AV74105_1AV84096_1AV94098_1AV104100_1AV114116_1AV124117_1AV134118_1AV146318_1AV156319_1AV166320_1AV178093_1AV188094_1AV198095_1AV204102_1AV214104_1AV224119_1AV234120_1AV344128_1AV354129_1AV364130_1AV374131_1AV384125_1AV394126_1AV404127_1AV416325_1AV426326_1AV436327_1AV446328_1AV456329_1AV466330_1AV474259_1AV584150_1AV594149_1AV605804_1AV614153_1AV625845_1AV635846_1AV645802_1AV655991_1AV664148_1AV675853_1AV100675853_1_deg_FAV688281_1AV698282_1AV784156_1_1AV100784156_1_1_deg_FAV894156_1_2AV100894156_1_2_deg_FAV1554156_1_8AV101554156_1_8_deg_FAV2384156_1_9AV102384156_1_9_deg_FAV2494156_1_10AV102494156_1_10_deg_FAV3594156_1_20AV103594156_1_20_deg_FAV1664385_1AV1674386_1AV1684387_1AV1694204_1AV1704205_1AV1714206_1AV1724207_1AV1734201_1AV1744202_1AV1754203_1AV1764210_1AV1774211_1AV1784212_1AV1794223_1AV1804224_1AV1814225_1AV1824812_1AV1834811_1AV1845159_1AV1855160_1AV1865161_1AV1875859_1AV1885860_1AV1895959_1AV1905868_1AV1915869_1AV1925870_1AV1934208_1AV1944209_1AV1954226_1AV1964227_1AV1974228_1AV1988097_1AV1994260_1AV2004261_1AV2115824_1AV2125823_1AV2134291_1AV102134291_1_deg_FAV2146069_1AV2254293_1AV2264292_1AV2275821_1MV14766_1MV124769_1MV235803_1MV244871_1MV255799_1MV364768_1MV374746_1MV486437_1MV498099_1MV505833_1MV515864_1MV626437_2MV638099_2MV645833_2MV655864_2MV3146437_20MV3158099_20MV3165833_20MV3175864_20MV3288275_1MV3295820_1MV3304772_1MV3314874_1MV3424872_1MV3434123_1
Integration notes
- Tables 5.146, 5.147, 5.148, pdf pages 2098-2108 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert EXM2 / APM Plus UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert EXM2 / APM Plus UPS
How many BACnet points does the Vertiv Liebert EXM2 / APM Plus UPS have?
This list has 252 BACnet objects: 105 analog values, 122 binary values, 25 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert EXM2 / APM Plus UPS BACnet points are writable?
1 of the 252 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert EXM2 / APM Plus UPS BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert EXM2 / APM Plus UPS?
Start with MV 343 4123_1 (Normal, warning or alarm state); MV 342 4872_1 (Load on inverter, bypass or battery); AV 58 4150_1 (Estimated battery runtime, min); AV 193 4208_1 (Output power, kW); AV 1 4097_1 (Input voltage, V); AV 166 4385_1 (Output voltage, V); AV 169 4204_1 (Output current, A); BV 38 4168_1 (Load is on battery); BV 660 4300_1 (Internal communication lost).
How do I check these points on the real Liebert EXM2 / APM Plus UPS?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT5 UPS
Liebert GXT5 UPS systems.
Also known as: GXT5, Liebert GXT5, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.