UPS (uninterruptible power supply) · BACnet points list

Vertiv Liebert EPM UPS BACnet points list

Updated 6 November 2026

Short answer

The Liebert EPM UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.

This page lists 146 BACnet objects for the Vertiv Liebert EPM UPS — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert EPM UPS
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
146 (1 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Liebert EPM, EPM, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 146 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert EPM UPS

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 154123_1Normal, warning or alarm stateRead
MV 144872_1Load on inverter, bypass or batteryRead
AV 414150_1Estimated battery runtime, minRead
AV 824208_1Output power, kWRead
AV 14097_1Input voltage, VRead
AV 554385_1Output voltage, VRead
AV 584204_1Output current, ARead
BV 514168_1Load is on batteryRead
BV 404300_1Internal communication lostRead

Network setup

Watch out for

Vertiv Liebert EPM UPS BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

146 of 146 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert EPM UPS BACnet Points List
DescriptionStates
BV14170_1Battery EqualizeReadActive = alarm
BV24200_1Battery Charging InhibitedReadActive = alarm
BV34315_1On GeneratorReadActive = alarm
BV44741_1Battery Self TestReadActive = alarm
BV54176_1Battery Circuit Breaker 1 OpenReadActive = alarm
BV64179_1Battery Circuit Breaker 2 OpenReadActive = alarm
BV74182_1Battery Circuit Breaker 3 OpenReadActive = alarm
BV84185_1Battery Circuit Breaker 4 OpenReadActive = alarm
BV94173_1Main Battery Disconnect OpenReadActive = alarm
BV204122_1System Input Power ProblemReadActive = alarm
BV214295_1Rectifier FailureReadActive = alarm
BV224233_1Inverter FailureReadActive = alarm
BV234135_1Bypass Not AvailableReadActive = alarm
BV244162_1Battery LowReadActive = alarm
BV254758_1LBS InhibitedReadActive = alarm
BV264311_1System Fan FailureReadActive = alarm
BV274310_1Equipment Over TemperatureReadActive = alarm
BV284213_1System Shutdown - EPOReadActive = alarm
BV294143_1Bypass Static Switch UnavailableReadActive = alarm
BV304139_1Bypass - Excess Auto RetransfersReadActive = alarm
BV314823_1Parallel Comm WarningReadActive = alarm
BV324314_1Power Supply FailureReadActive = alarm
BV334219_1Battery Over TemperatureReadActive = alarm
BV344146_1System Input Phs Rotation ErrorReadActive = alarm
BV354440_1Fuse FailureReadActive = alarm
BV365960_1Inverter OverloadReadActive = alarm
BV374831_1MMS OverloadReadActive = alarm
BV384290_1Inverter Shutdown - OverloadReadActive = alarm
BV394389_1System Output FaultReadActive = alarm
BVmin404300_1Internal Communications FailureReadActive = alarm
BV414164_1Battery Charging ErrorReadActive = alarm
BV424382_1System Input Current ImbalanceReadActive = alarm
BV435149_1Battery Not QualifiedReadActive = alarm
BV445150_1Battery Terminals ReversedReadActive = alarm
BV455151_1Battery Converter FailureReadActive = alarm
BV465153_1Load Sharing FaultReadActive = alarm
BV475154_1DC Bus AbnormalReadActive = alarm
BV485155_1Mains Input Neutral LostReadActive = alarm
BV495156_1Load Impact TransferReadActive = alarm
BV505157_1User Operation InvalidReadActive = alarm
BVmin514168_1Battery DischargingReadActive = alarm
BV524298_1UPS Output on BypassReadActive = alarm
BV534299_1Output Load on Maint. BypassReadActive = alarm
BV544166_1Battery Capacity LowReadActive = alarm
BV554834_1MMS On BatteryReadActive = alarm
BV564825_1Loss of RedundancyReadActive = alarm
BV575770_1Top Outlet Fan FaultReadActive = alarm
BV585771_1MMS Over CapacityReadActive = alarm
BV595957_1Bypass Input Voltage FaultReadActive = alarm
BV605839_1Power Module Over TemperatureReadActive = alarm
BV615458_1Excess ECO SuspendsReadActive = alarm
BV624222_1Battery Ground FaultReadActive = alarm
BV634147_1System Input Current LimitReadActive = alarm
BV646059_1Inverter Relay FaultReadActive = alarm
BV656060_1Transfer to Bypass - System OverloadReadActive = alarm
BV666061_1Input Source BackfeedReadActive = alarm
BV676062_1Loss of SynchronizationReadActive = alarm
BV686063_1Battery Converter Current LimitReadActive = alarm
BV696064_1LBS Cable FailureReadActive = alarm
BV706065_1Battery Charge Equalization TimeoutReadActive = alarm
BV716066_1Parallel Cable FailureReadActive = alarm
BV726067_1Battery FaultReadActive = alarm
BV736068_1Battery Room AlarmReadActive = alarm
BV744177_1Battery Breaker 1 Open FailureReadActive = alarm
BV754180_1Battery Breaker 2 Open FailureReadActive = alarm
BV764183_1Battery Breaker 3 Open FailureReadActive = alarm
BV774186_1Battery Breaker 4 Open FailureReadActive = alarm
BV784216_1Bypass Backfeed DetectedReadActive = alarm
AVmin14097_1System Input RMS A-BVRead
AV24099_1System Input RMS B-CVRead
AV34101_1System Input RMS C-AVRead
AV44113_1System Input RMS Current Phase AARead
AV54114_1System Input RMS Current Phase BARead
AV64115_1System Input RMS Current Phase CARead
AV74105_1System Input FrequencyHzRead
AV84096_1System Input RMS A-NVRead
AV94098_1System Input RMS B-NVRead
AV104100_1System Input RMS C-NVRead
AV114116_1System Input Power Factor Phs ARead
AV124117_1System Input Power Factor Phs BRead
AV134118_1System Input Power Factor Phs CRead
AV244128_1Bypass Input Voltage RMS A-NVRead
AV254129_1Bypass Input Voltage RMS B-NVRead
AV264130_1Bypass Input Voltage RMS C-NVRead
AV274131_1Bypass Input FrequencyHzRead
AV284125_1Bypass Input Voltage RMS A-BVRead
AV294126_1Bypass Input Voltage RMS B-CVRead
AV304127_1Bypass Input Voltage RMS C-AVRead
AVmin414150_1Battery Time RemainingminRead
AV424155_1Battery Volts for CabinetVDCRead
AV434156_1Battery Temperature for Cabinet°CRead
AV100434156_1_deg_FBattery Temperature for Cabinet°FRead
AV444149_1DC Bus CurrentA DCRead
AVmin554385_1System Output Voltage RMS A-NVRead
AV564386_1System Output Voltage RMS B-NVRead
AV574387_1System Output Voltage RMS C-NVRead
AVmin584204_1System Output RMS Current Phs AARead
AV594205_1System Output RMS Current Phs BARead
AV604206_1System Output RMS Current Phs CARead
AV614207_1System Output FrequencyHzRead
AV624201_1System Output Voltage RMS A-BVRead
AV634202_1System Output Voltage RMS B-CVRead
AV644203_1System Output Voltage RMS C-AVRead
AV654210_1System Output Power Factor Phs ARead
AV664211_1System Output Power Factor Phs BRead
AV674212_1System Output Power Factor Phs CRead
AV684223_1System Output Pct Power Phase A%Read
AV694224_1System Output Pct Power Phase B%Read
AV704225_1System Output Pct Power Phase C%Read
AV714812_1MMS Output Apparent PowerkVARead
AV724811_1MMS Output PowerkWRead
AV735159_1Output Current Crest Factor Phs ARead
AV745160_1Output Current Crest Factor Phs BRead
AV755161_1Output Current Crest Factor Phs CRead
AV765859_1System Output Power Phase AkWRead
AV775860_1System Output Power Phase BkWRead
AV785959_1System Output Power Phase CkWRead
AV795868_1System Output Apparent Power Phs AkVARead
AV805869_1System Output Apparent Power Phs BkVARead
AV815870_1System Output Apparent Power Phs CkVARead
AVmin824208_1System Output PowerkWRead
AV834209_1System Output Apparent PowerkVARead
AV944102_1System Input Nominal VoltageVRead
AV954103_1System Input Nominal FrequencyHzRead
AV964104_1System Input Nominal CurrentARead
AV974259_1Bypass Nominal VoltageVRead
AV984260_1System Output Nominal VoltageVRead
AV994261_1System Output Nominal FrequencyHzRead
AV1104293_1System Date and TimeWrite
AV1114292_1Total System Operating TimehRead
AV1126069_1Average system efficiency%Read
AV1134291_1Inlet Air Temperature°CRead
AV101134291_1_deg_FInlet Air Temperature°FRead
MV14871_1UPS battery1 statusRead1=Unknown, 2=Normal, 3=Low, 4=Depleted
MV124746_1Inverter On/Off StateRead1=off, 2=on
MV134772_1Maintenance Bypass BreakerRead1=Open, 2=Close, 3=Not Installed
MVmin144872_1UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MVmin154123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MV165454_1ECO Mode Operation StateRead1=disabled, 2=enabled
MV174766_1Input BreakerRead1=Open, 2=Close, 3=Not Installed
MV184769_1Internal Bypass BreakerRead1=Open, 2=Close, 3=Not Installed
MV194768_1Output BreakerRead1=Open, 2=Close, 3=Not Installed
MV206053_1UPS Application ModeRead1=UPS Mode, 2=Frequency converter mode
MV214874_1MMS UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MV225448_1Intelligent Parallel Operation StateRead1=disabled, 2=enabled
MV236054_1Advanced Efficiency ModeRead1=unknown, 2=ECO mode, 3=Intelligent ECO mode, 4=Active Inverter ECO mode
Object ID lookup: Vertiv Liebert EPM UPS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert EPM UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert EPM UPS

How many BACnet points does the Vertiv Liebert EPM UPS have?

This list has 146 BACnet objects: 65 analog values, 68 binary values, 13 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert EPM UPS BACnet points are writable?

1 of the 146 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert EPM UPS BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert EPM UPS?

Start with MV 15 4123_1 (Normal, warning or alarm state); MV 14 4872_1 (Load on inverter, bypass or battery); AV 41 4150_1 (Estimated battery runtime, min); AV 82 4208_1 (Output power, kW); AV 1 4097_1 (Input voltage, V); AV 55 4385_1 (Output voltage, V); AV 58 4204_1 (Output current, A); BV 51 4168_1 (Load is on battery); BV 40 4300_1 (Internal communication lost).

How do I check these points on the real Liebert EPM UPS?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.