Ceiling-mounted precision split cooling unit · BACnet points list

Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card) BACnet points list

Updated 11 November 2026

Short answer

The Liebert Mini-Mate2 8 ton map is a short legacy list: unit status, temperature and humidity readings and setpoints, an on/off control word and alarm words where several alarms share one object as bits. Only use it with the card variant named in the title.

This page lists 48 BACnet objects for the Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Equipment
Ceiling-mounted precision split cooling unit
Equipment type
VRF & split air conditioners
BACnet objects
48 (8 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 48 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)

Integration in brief

Fit a Liebert iCOM CMS card (BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 4bc01_1Control word: unit on/off and lockouts (bit-coded)Write
AV 11bc02_1Temperature setpointWrite
AV 12bc03_1Humidity setpointWrite
MV 10bs27_1Unit statusRead
AV 5bs01_1Room temperatureRead
AV 6bs02_1Room humidityRead
AV 8bs09_1Cooling capacity, %Read
AV 1ba01_1Alarm word 1 (bit-coded)Read

Network setup

Watch out for

Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

48 of 48 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card) BACnet Points List
DescriptionStates
AVmin5bs01_1Temperature (Status Points (View))Read
AVmin6bs02_1Humidity (Status Points (View))Read
AV13bs03_1CoolingRead0=Off, 1=On
AV14bs04_1HeatingRead0=Off, 1=On
AV15bs05_1HumidificationRead0=Off, 1=On
AV16bs06_1DehumidificationRead0=Off, 1=On
AV17bs07_1Econ-O-CycleRead0=Off, 1=On
AV7bs08_1StagesRead
AVmin8bs09_1% CapacityRead
AV18bs18_1Unit Status (On/Off)Read0=Off, 1=On
MV6bs23_1Cooling/Heating StatusRead1=Idle, 2=Heating, 3=Cooling
MV7bs24_1Humidifier StatusRead1=Off, 2=On
MV8bs25_1Dehumidifying StatusRead1=Off, 2=On
MV9bs26_1Econocycle StatusRead1=Off, 2=On
MVmin10bs27_1Unit StatusRead1=On, 2=On but in Restart Delay, 3=Off by I/O Key, 4=Off by Remote Shutdown, 5=Off by Remote Control
AVmin1ba01_1Bit-packed: Alarm PointsReadBit 0 = Communications; Bit 1 = Local Off; Bit 2 = Remote Off; Bit 3 = High Head Pressure 1; Bit 4 = High Head Pressure 2; Bit 5 = Loss of Airflow; Bit 6 = Standby Glycol Unit On; Bit 8 = Change Filters; Bit 9 = High Temperature; Bit 10 = Low Temperature
AV2ba02_1Bit-packed: Alarm PointsReadBit 0 = High Humidity; Bit 1 = Low Humidity; Bit 2 = Humidifier Problem; Bit 8 = Smoke Detected; Bit 9 = Loss of Water Flow; Bit 10 = Standby Unit On
AV3ba03_1Bit-packed: Alarm PointsReadBit 1 = Short Cycle; Bit 2 = Loss of Power; Bit 6 = Local Alarm 1; Bit 7 = Local Alarm 2; Bit 8 = High Water; Bit 9 = Local Alarm 3
BV1ba21_1CommunicationsRead0=Off, 1=On
BV2ba22_1High Head Pressure 1Read0=Off, 1=On
BV3ba23_1High Head Pressure 2Read0=Off, 1=On
BV4ba24_1Loss of AirflowRead0=Off, 1=On
BV5ba25_1Standby Glycol Unit OnRead0=Off, 1=On
BV6ba26_1Change FiltersRead0=Off, 1=On
BV7ba27_1High TemperatureRead0=Off, 1=On
BV8ba28_1Low TemperatureRead0=Off, 1=On
BV9ba29_1High HumidityRead0=Off, 1=On
BV10ba30_1Low HumidityRead0=Off, 1=On
BV11ba31_1Humidifer ProblemRead0=Off, 1=On
BV12ba32_1Smoke DetectedRead0=Off, 1=On
BV13ba33_1Loss of Water FlowRead0=Off, 1=On
BV14ba34_1Standby Unit OnRead0=Off, 1=On
BV15ba35_1Short CycleRead0=Off, 1=On
BV16ba36_1Loss of PowerRead0=Off, 1=On
BV17ba37_1Custom Alarm 1Read0=Off, 1=On
BV18ba38_1Custom Alarm 2Read0=Off, 1=On
BV20ba40_1Custom Alarm 3Read0=Off, 1=On
BV21ba41_1High WaterRead0=Off, 1=On
AV9bs10_1Temperature (Setpoints (View))Read
AV10bs12_1Humidity (Setpoints (View))Read
AVmin4bc01_1Bit-packed: Control PointsWriteUnit On/Off: Bit 0 - ON = Unit Off Bit 1 - ON = Unit On; Reheat Lockout: Bit 2 - ON = Reheat Lockout Off Bit 3 - ON = Reheat Lockout On; Humidifier Lockout: Bit 4 - ON = Humidifier Lockout Off Bit 5 - ON = Humidifier Lockout On
AVmin11bc02_1Temperature SetpointWrite
AVmin12bc03_1Humidity SetpointWrite
MV3bc21_1On/Off ControlWrite1=Off, 2=On
MV4bc22_1Reheat LockoutWrite1=Off, 2=On
MV5bc23_1Humidifier LockoutWrite1=Off, 2=On
AV22bc25_1Temperature ToleranceWrite
AV24bc27_1Humidity ToleranceWrite
Object ID lookup: Vertiv Liebert Mini-Mate2 8 Ton iCOM CMS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)

How many BACnet points does the Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card) have?

This list has 48 BACnet objects: 20 analog values, 20 binary values, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card) BACnet points are writable?

8 of the 48 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card) BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)?

Start with AV 4 bc01_1 (Control word: unit on/off and lockouts (bit-coded)); AV 11 bc02_1 (Temperature setpoint); AV 12 bc03_1 (Humidity setpoint); MV 10 bs27_1 (Unit status); AV 5 bs01_1 (Room temperature); AV 6 bs02_1 (Room humidity); AV 8 bs09_1 (Cooling capacity, %); AV 1 ba01_1 (Alarm word 1 (bit-coded)).

How do I check these points on the real Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.