Static transfer switch · BACnet points list

Vertiv Liebert STS2 static transfer switch BACnet points list

Updated 6 November 2026

Short answer

The Liebert STS2 static transfer switch reports to a BMS through a Liebert IntelliSlot card. Analog Values carry source and output measurements and ratings, Binary Values carry events and breaker states, and Multi-state Values carry system status, preferred source and settings.

This page lists 199 BACnet objects for the Vertiv Liebert STS2 static transfer switch — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert STS2 static transfer switch
Equipment
Static transfer switch
Equipment type
Other equipment
BACnet objects
199 (1 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
STS2, Liebert STS2, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 199 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert STS2 static transfer switch

Integration in brief

Fit a Liebert IntelliSlot BACnet card (the guide's compatibility table lists IS-WEBADPT for the STS2), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 124123_1Normal, warning or alarm stateRead
AV 904097_1_1Source 1 input voltage A-BRead
AV 1676648_1_1Output power (printed unit kWh)Read
BV 224300_1Internal communication lostRead

Network setup

Watch out for

Vertiv Liebert STS2 static transfer switch BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

199 of 199 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert STS2 static transfer switch BACnet Points List
DescriptionStates
BV16587_1Transfer Count ClearedReadActive = alarm
BV26588_1Energy Counter ClearedReadActive = alarm
BV36589_1History Logs FullReadActive = alarm
BV46590_1History Logs ClearedReadActive = alarm
BV56591_1Event Log ClearedReadActive = alarm
BV66592_1System Date ChangedReadActive = alarm
BV76593_1System Time ChangedReadActive = alarm
BV86594_1Access Password ChangedReadActive = alarm
BV96595_1Config ModifiedReadActive = alarm
BV206662_1Control Logic FailReadActive = alarm
BV214311_1System Fan FailureReadActive = alarm
BVmin224300_1Internal Communications FailureReadActive = alarm
BV236663_1Power Supply Logic FailReadActive = alarm
BV246664_1External Comms FailureReadActive = alarm
BV256665_1Heat Sink OverTempReadActive = alarm
BV264907_1High Ambient TemperatureReadActive = alarm
BV274310_1Equipment Over TemperatureReadActive = alarm
BV286666_1Automatic Transfer InhibitedReadActive = alarm
BV296667_1Input Source Transfer InhibitedReadActive = alarm
BV304270_1Input Contact 01ReadActive = alarm
BV314271_1Input Contact 02ReadActive = alarm
BV324272_1Input Contact 03ReadActive = alarm
BV334273_1Input Contact 04ReadActive = alarm
BV344274_1Input Contact 05ReadActive = alarm
BV354275_1Input Contact 06ReadActive = alarm
BV364276_1Input Contact 07ReadActive = alarm
BV374277_1Input Contact 08ReadActive = alarm
BV486612_1_1SCR Short (Source Measurements 1)ReadActive = alarm
BV496613_1_1SCR Open (Source Measurements 1)ReadActive = alarm
BV506614_1_1AC Power Supply Fail (Source Measurements 1)ReadActive = alarm
BV516615_1_1DC Power Supply Fail (Source Measurements 1)ReadActive = alarm
BV526616_1_1Voltage Sensor Fail (Source Measurements 1)ReadActive = alarm
BV536617_1_1SCR Sensor Fail (Source Measurements 1)ReadActive = alarm
BV546618_1_1Current Sensor Fail (Source Measurements 1)ReadActive = alarm
BV556619_1_1Gate Drive Fail (Source Measurements 1)ReadActive = alarm
BV566620_1_1Surge Fail (Source Measurements 1)ReadActive = alarm
BV576621_1_1Fast Under Voltage (Source Measurements 1)ReadActive = alarm
BV586622_1_1Slow Under Voltage (Source Measurements 1)ReadActive = alarm
BV596623_1_1Over Voltage (Source Measurements 1)ReadActive = alarm
BV606624_1_1Over/Under Frequency Fail (Source Measurements 1)ReadActive = alarm
BV616625_1_1General Source Failure (Source Measurements 1)ReadActive = alarm
BV626626_1_1Over Current (Source Measurements 1)ReadActive = alarm
BV636627_1_1Peak Current Off Limit (Source Measurements 1)ReadActive = alarm
BV646628_1_1Sync Fail (Source Measurements 1)ReadActive = alarm
BV654146_1_1System Input Phs Rotation Error (Source Measurements 1)ReadActive = alarm
BV666629_1_1Input Over Voltage (Source Measurements 1)ReadActive = alarm
BV676630_1_1Input Under Voltage (Source Measurements 1)ReadActive = alarm
BV686631_1_1Input Over/Under Frequency (Source Measurements 1)ReadActive = alarm
BV698323_1_1Neutral SCR Short (Source Measurements 1)ReadActive = alarm
BV708324_1_1Neutral SCR Open (Source Measurements 1)ReadActive = alarm
BV718325_1_1Input Neutral Over Current (Source Measurements 1)ReadActive = alarm
BV796612_1_2SCR Short (Source Measurements 2)ReadActive = alarm
BV806613_1_2SCR Open (Source Measurements 2)ReadActive = alarm
BV816614_1_2AC Power Supply Fail (Source Measurements 2)ReadActive = alarm
BV826615_1_2DC Power Supply Fail (Source Measurements 2)ReadActive = alarm
BV836616_1_2Voltage Sensor Fail (Source Measurements 2)ReadActive = alarm
BV846617_1_2SCR Sensor Fail (Source Measurements 2)ReadActive = alarm
BV856618_1_2Current Sensor Fail (Source Measurements 2)ReadActive = alarm
BV866619_1_2Gate Drive Fail (Source Measurements 2)ReadActive = alarm
BV876620_1_2Surge Fail (Source Measurements 2)ReadActive = alarm
BV886621_1_2Fast Under Voltage (Source Measurements 2)ReadActive = alarm
BV896622_1_2Slow Under Voltage (Source Measurements 2)ReadActive = alarm
BV906623_1_2Over Voltage (Source Measurements 2)ReadActive = alarm
BV916624_1_2Over/Under Frequency Fail (Source Measurements 2)ReadActive = alarm
BV926625_1_2General Source Failure (Source Measurements 2)ReadActive = alarm
BV936626_1_2Over Current (Source Measurements 2)ReadActive = alarm
BV946627_1_2Peak Current Off Limit (Source Measurements 2)ReadActive = alarm
BV956628_1_2Sync Fail (Source Measurements 2)ReadActive = alarm
BV964146_1_2System Input Phs Rotation Error (Source Measurements 2)ReadActive = alarm
BV976629_1_2Input Over Voltage (Source Measurements 2)ReadActive = alarm
BV986630_1_2Input Under Voltage (Source Measurements 2)ReadActive = alarm
BV996631_1_2Input Over/Under Frequency (Source Measurements 2)ReadActive = alarm
BV1008323_1_2Neutral SCR Short (Source Measurements 2)ReadActive = alarm
BV1018324_1_2Neutral SCR Open (Source Measurements 2)ReadActive = alarm
BV1028325_1_2Input Neutral Over Current (Source Measurements 2)ReadActive = alarm
BV1106635_1_1Voltage Sense FailReadActive = alarm
BV1116636_1_1Load on Alternate SourceReadActive = alarm
BV1126637_1_1Under Voltage FailReadActive = alarm
BV1136638_1_1Output Over CurrentReadActive = alarm
BV1146639_1_1Ground Over CurrentReadActive = alarm
BV1156640_1_1Neutral Over CurrentReadActive = alarm
BV1166641_1_1Load Voltage THDReadActive = alarm
BV1178326_1_1Neutral Snubber FailReadActive = alarm
BV1276676_1CB1 Shunt TripReadActive = alarm
BV1286677_1CB2 Shunt TripReadActive = alarm
BV1296678_1CB6 Neutral OpenReadActive = alarm
BV1306679_1Contactor Neutral FailReadActive = alarm
BV1316680_1CB1 Breaker OpenReadActive = alarm
BV1326681_1CB2 Breaker OpenReadActive = alarm
BV1336682_1CB4 Breaker ClosedReadActive = alarm
BV1346683_1CB5 Breaker ClosedReadActive = alarm
BV1356684_1CB3 Breaker OpenReadActive = alarm
BV1366685_1CB3A Breaker OpenReadActive = alarm
BV1376686_1CB6 Breaker OpenReadActive = alarm
BV1386687_1CB7 Breaker OpenReadActive = alarm
AV14102_1System Input Nominal VoltageVRead
AV26579_1PDU Input Nominal VoltageVRead
AV34104_1System Input Nominal CurrentARead
AV44103_1System Input Nominal FrequencyHzRead
AV154293_1System Date and TimeSecs since Epoch(UTC)Write
AV266602_1Phase Difference LimitdegRead
AV276603_1Input Frequency DeviationHzRead
AV286604_1Retransfer DelaysRead
AV296608_1Load Voltage THD%Read
AV306609_1Neutral Current (% nom)%Read
AV316610_1Ground currentARead
AV326611_1Load Bus Overcurrent (% of nom)%Read
AV436596_1_1Fast Under Voltage (Source Settings 1)%Read
AV446597_1_1Slow Under Voltage (Source Settings 1)%Read
AV456598_1_1Slow Under Voltage Delay (Source Settings 1)CyclesRead
AV466599_1_1Over Voltage (% of nom) (Source Settings 1)%Read
AV476600_1_1Over Voltage Delay (Source Settings 1)QuarterCyclesRead
AV486601_1_1I-PK Transfer Lockout (Source Settings 1)Read
AV596596_1_2Fast Under Voltage (Source Settings 2)%Read
AV606597_1_2Slow Under Voltage (Source Settings 2)%Read
AV616598_1_2Slow Under Voltage Delay (Source Settings 2)CyclesRead
AV626599_1_2Over Voltage (% of nom) (Source Settings 2)%Read
AV636600_1_2Over Voltage Delay (Source Settings 2)QuarterCyclesRead
AV646601_1_2I-PK Transfer Lockout (Source Settings 2)Read
AV756657_1Total Input TransfersRead
AV766658_1Heatsink Temp 1°CRead
AV100766658_1_deg_FHeatsink Temp 1°FRead
AV776659_1Heatsink Temp 2°CRead
AV100776659_1_deg_FHeatsink Temp 2°FRead
AV786660_1Heatsink Temp 3°CRead
AV100786660_1_deg_FHeatsink Temp 3°FRead
AV796661_1Sync. Phase AngledegRead
AVmin904097_1_1System Input RMS A-B (Source Measurements 1)VRead
AV914099_1_1System Input RMS B-C (Source Measurements 1)VRead
AV924101_1_1System Input RMS C-A (Source Measurements 1)VRead
AV934113_1_1System Input RMS Current Phase A (Source Measurements 1)ARead
AV944114_1_1System Input RMS Current Phase B (Source Measurements 1)ARead
AV954115_1_1System Input RMS Current Phase C (Source Measurements 1)ARead
AV964105_1_1System Input Frequency (Source Measurements 1)HzRead
AV974096_1_1System Input RMS A-N (Source Measurements 1)VRead
AV984098_1_1System Input RMS B-N (Source Measurements 1)VRead
AV994100_1_1System Input RMS C-N (Source Measurements 1)VRead
AV1008322_1_1System Input Neutral Current (Source Measurements 1)ARead
AV1074097_1_2System Input RMS A-B (Source Measurements 2)VRead
AV1084099_1_2System Input RMS B-C (Source Measurements 2)VRead
AV1094101_1_2System Input RMS C-A (Source Measurements 2)VRead
AV1104113_1_2System Input RMS Current Phase A (Source Measurements 2)ARead
AV1114114_1_2System Input RMS Current Phase B (Source Measurements 2)ARead
AV1124115_1_2System Input RMS Current Phase C (Source Measurements 2)ARead
AV1134105_1_2System Input Frequency (Source Measurements 2)HzRead
AV1144096_1_2System Input RMS A-N (Source Measurements 2)VRead
AV1154098_1_2System Input RMS B-N (Source Measurements 2)VRead
AV1164100_1_2System Input RMS C-N (Source Measurements 2)VRead
AV1178322_1_2System Input Neutral Current (Source Measurements 2)ARead
AV1246632_1_1Apparent PowerkVARRead
AV1256633_1_1Apparent Power Percentage%Read
AV1266634_1_1PowerkWRead
AV1376642_1_1PDU Input Voltage A-B (PDU Source Measurements 1)VRead
AV1386643_1_1PDU Input Voltage B-C (PDU Source Measurements 1)VRead
AV1396644_1_1PDU Input Voltage C-A (PDU Source Measurements 1)VRead
AV1406645_1_1PDU Input Frequency (PDU Source Measurements 1)HzRead
AV1516642_1_2PDU Input Voltage A-B (PDU Source Measurements 2)VRead
AV1526643_1_2PDU Input Voltage B-C (PDU Source Measurements 2)VRead
AV1536644_1_2PDU Input Voltage C-A (PDU Source Measurements 2)VRead
AV1546645_1_2PDU Input Frequency (PDU Source Measurements 2)HzRead
AV1656646_1_1Neutral CurrentARead
AV1666647_1_1Ground CurrentARead
AVmin1676648_1_1Output PowerkWhRead
AV1684210_1_1System Output Power Factor Phs ARead
AV1694211_1_1System Output Power Factor Phs BRead
AV1704212_1_1System Output Power Factor Phs CRead
AV1716649_1_1Output Voltage THD Phase A%Read
AV1726650_1_1Output Voltage THD Phase B%Read
AV1736651_1_1Output Voltage THD Phase C%Read
AV1746652_1_1Output Current THD Phase A%Read
AV1756653_1_1Output Current THD Phase B%Read
AV1766654_1_1Output Current THD Phase C%Read
AV1775175_1_1Output Current Phs A K-FactorRead
AV1785176_1_1Output Current Phs B K-FactorRead
AV1795177_1_1Output Current Phs C K-FactorRead
AV1805250_1_1Output Current Phs A Crest FactorRead
AV1815251_1_1Output Current Phs B Crest FactorRead
AV1825252_1_1Output Current Phs C Crest FactorRead
MV14553_1Server ClassRead1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR
MVmin124123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MV136581_1Dual Output BreakerRead1=no, 2=yes
MV146582_1PDU InstalledRead1=no, 2=yes
MV156583_1Four Pole SwitchRead1=no, 2=yes
MV166584_1Shunt TripRead1=no, 2=yes
MV176585_1Wye Output TransformerRead1=no, 2=yes
MV186586_1Remote Source SelectRead1=no, 2=yes
MV296605_1Auto Retransfer EnabledRead1=no, 2=yes
MV306606_1I-Peak ResetRead1=automatic, 2=manual
MV316607_1Automatic RestartRead1=disabled, 2=enabled
MV426655_1Active Input SourceRead1=No Source, 2=Source 1, 3=Source 2
MV436656_1Preferred Input SourceRead1=No Source, 2=Source 1, 3=Source 2
MV546668_1CB1 Breaker StateRead1=Open, 2=Close, 3=Not Installed
MV556669_1CB2 Breaker StateRead1=Open, 2=Close, 3=Not Installed
MV566670_1CB3 Breaker StateRead1=Open, 2=Close, 3=Not Installed
MV576671_1CB4 Breaker StateRead1=Open, 2=Close, 3=Not Installed
MV586672_1CB5 Breaker StateRead1=Open, 2=Close, 3=Not Installed
MV596673_1CB3A Breaker StateRead1=Open, 2=Close, 3=Not Installed
MV606674_1CB6 Breaker StateRead1=Open, 2=Close, 3=Not Installed
MV616675_1CB7 Breaker StateRead1=Open, 2=Close, 3=Not Installed
Object ID lookup: Vertiv Liebert STS2 static transfer switch point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert STS2 static transfer switch and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert STS2 static transfer switch

How many BACnet points does the Vertiv Liebert STS2 static transfer switch have?

This list has 199 BACnet objects: 83 analog values, 95 binary values, 21 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert STS2 static transfer switch BACnet points are writable?

1 of the 199 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert STS2 static transfer switch BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert STS2 static transfer switch?

Start with MV 12 4123_1 (Normal, warning or alarm state); AV 90 4097_1_1 (Source 1 input voltage A-B); AV 167 6648_1_1 (Output power (printed unit kWh)); BV 22 4300_1 (Internal communication lost).

How do I check these points on the real Liebert STS2 static transfer switch?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.