Short answer

The Liebert iCOM v4 precision cooling reports to a BMS through a Liebert IntelliSlot card (IS-UNITY-DP for BACnet IP or BACnet MS/TP; some units also IS-IPBML). The object list has Binary Values for events, Analog Values for temperatures, humidity, setpoints and run hours, and Multi-state Values for states and control modes. Objects are created on the card when it discovers the unit, so only options fitted to the unit appear.

This page lists 1416 BACnet objects for the Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW) — 323 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Equipment
Precision cooling unit (computer room air handler)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
1416 (323 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 1416 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1155143_1On/off command (1=off, 2=on)Write
AV 15008_1Air temperature setpoint, °CWrite
AV 205331_1_1Supply air temperature setpoint, °CWrite
MV 2924717_1Acknowledge / reset eventsWrite
MV 944706_1Run / standby / off stateRead
MV 934123_1Normal, warning or alarm stateRead
AV 195002_1_1Supply air temperature, °CRead
AV 314291_1Return air temperature, °CRead
AV 25844643_1Supply fluid temperature, °CRead
AV 605028_1Return air humidity, %RHRead

Network setup

Watch out for

Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

1416 of 1416 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW) BACnet Points List
DescriptionStates
BV12456538_1TSA Control Input IssueReadActive = alarm
BV15015_1_1Supply Air Over TemperatureReadActive = alarm
BV25019_1_1Supply Air Under TemperatureReadActive = alarm
BV35026_1_1Supply Air Sensor IssueReadActive = alarm
BV46530_1_1Supply NTC Air Sensor IssueReadActive = alarm
BV145023_1_1Return Air Over TemperatureReadActive = alarm
BV155335_1_1Return Air Under TemperatureReadActive = alarm
BV165147_1_1Return Air Sensor IssueReadActive = alarm
BV274601_1_1Ext Air Sensor A Over TemperatureReadActive = alarm
BV284608_1_1Ext Air Sensor A Under TemperatureReadActive = alarm
BV294618_1_1Ext Air Sensor A IssueReadActive = alarm
BV305573_1_1Ambient Air Sensor IssueReadActive = alarm
BV314621_1_1External Air Sensor B IssueReadActive = alarm
BV326531_1_1External Air Sensor C IssueReadActive = alarm
BV336532_1_1External Air Sensor D IssueReadActive = alarm
BV346533_1_1External Air Sensor E IssueReadActive = alarm
BV10505966_1_1Aux Air Temp Device Communication LostReadActive = alarm
BV415034_1High Return HumidityReadActive = alarm
BV425036_1Low Return HumidityReadActive = alarm
BV435578_1Dew Point Over TemperatureReadActive = alarm
BV445579_1Dew Point Under TemperatureReadActive = alarm
BV455902_1Return Humidity Sensor IssueReadActive = alarm
BV535349_1_1Ext Air Sensor A High HumidityReadActive = alarm
BV545351_1_1Ext Air Sensor A Low HumidityReadActive = alarm
BV554615_1_1Ext Dew Point Over TemperatureReadActive = alarm
BV565577_1_1Ext Dew Point Under TemperatureReadActive = alarm
BV655067_1Ext Compressor LockoutReadActive = alarm
BV665513_1Compressor Capacity ReducedReadActive = alarm
BV775269_1_1Compressor Hours Exceeded (Compressor 1)ReadActive = alarm
BV785270_1_1Compressor High Head Pressure (Compressor 1)ReadActive = alarm
BV795271_1_1Compressor Low Suction Pressure (Compressor 1)ReadActive = alarm
BV805352_1_1Compressor Short Cycle (Compressor 1)ReadActive = alarm
BV815146_1_1Compressor Pump Down Issue (Compressor 1)ReadActive = alarm
BV825272_1_1Compressor Thermal Overload (Compressor 1)ReadActive = alarm
BV835354_1_1Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 1)ReadActive = alarm
BV845355_1_1Dig Scroll Comp Over Temp (Compressor 1)ReadActive = alarm
BV855514_1_1Compressor Low Pressure Transducer Issue (Compressor 1)ReadActive = alarm
BV865148_1_1Compressor High Pressure Transducer Issue (Compressor 1)ReadActive = alarm
BV875604_1_1Compressor Superheat Over Threshold (Compressor 1)ReadActive = alarm
BV885903_1_1Compressor Low Differential Pressure Lockout (Compressor 1)ReadActive = alarm
BV896758_1_1Compressor Freeze Protection (Compressor 1)ReadActive = alarm
BV975269_1_2Compressor Hours Exceeded (Compressor 2)ReadActive = alarm
BV985270_1_2Compressor High Head Pressure (Compressor 2)ReadActive = alarm
BV995271_1_2Compressor Low Suction Pressure (Compressor 2)ReadActive = alarm
BV1005352_1_2Compressor Short Cycle (Compressor 2)ReadActive = alarm
BV1015146_1_2Compressor Pump Down Issue (Compressor 2)ReadActive = alarm
BV1025272_1_2Compressor Thermal Overload (Compressor 2)ReadActive = alarm
BV1035354_1_2Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 2)ReadActive = alarm
BV1045355_1_2Dig Scroll Comp Over Temp (Compressor 2)ReadActive = alarm
BV1055514_1_2Compressor Low Pressure Transducer Issue (Compressor 2)ReadActive = alarm
BV1065148_1_2Compressor High Pressure Transducer Issue (Compressor 2)ReadActive = alarm
BV1075604_1_2Compressor Superheat Over Threshold (Compressor 2)ReadActive = alarm
BV1085903_1_2Compressor Low Differential Pressure Lockout (Compressor 2)ReadActive = alarm
BV1096758_1_2Compressor Freeze Protection (Compressor 2)ReadActive = alarm
BV12655269_1_3Compressor Hours Exceeded (Compressor 3)ReadActive = alarm
BV12665270_1_3Compressor High Head Pressure (Compressor 3)ReadActive = alarm
BV12675271_1_3Compressor Low Suction Pressure (Compressor 3)ReadActive = alarm
BV12685352_1_3Compressor Short Cycle (Compressor 3)ReadActive = alarm
BV12695146_1_3Compressor Pump Down Issue (Compressor 3)ReadActive = alarm
BV12705272_1_3Compressor Thermal Overload (Compressor 3)ReadActive = alarm
BV12715354_1_3Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 3)ReadActive = alarm
BV12725355_1_3Dig Scroll Comp Over Temp (Compressor 3)ReadActive = alarm
BV12735514_1_3Compressor Low Pressure Transducer Issue (Compressor 3)ReadActive = alarm
BV12745148_1_3Compressor High Pressure Transducer Issue (Compressor 3)ReadActive = alarm
BV12755604_1_3Compressor Superheat Over Threshold (Compressor 3)ReadActive = alarm
BV12765903_1_3Compressor Low Differential Pressure Lockout (Compressor 3)ReadActive = alarm
BV12776758_1_3Compressor Freeze Protection (Compressor 3)ReadActive = alarm
BV12875269_1_4Compressor Hours Exceeded (Compressor 4)ReadActive = alarm
BV12885270_1_4Compressor High Head Pressure (Compressor 4)ReadActive = alarm
BV12895271_1_4Compressor Low Suction Pressure (Compressor 4)ReadActive = alarm
BV12905352_1_4Compressor Short Cycle (Compressor 4)ReadActive = alarm
BV12915146_1_4Compressor Pump Down Issue (Compressor 4)ReadActive = alarm
BV12925272_1_4Compressor Thermal Overload (Compressor 4)ReadActive = alarm
BV12935354_1_4Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 4)ReadActive = alarm
BV12945355_1_4Dig Scroll Comp Over Temp (Compressor 4)ReadActive = alarm
BV12955514_1_4Compressor Low Pressure Transducer Issue (Compressor 4)ReadActive = alarm
BV12965148_1_4Compressor High Pressure Transducer Issue (Compressor 4)ReadActive = alarm
BV12975604_1_4Compressor Superheat Over Threshold (Compressor 4)ReadActive = alarm
BV12985903_1_4Compressor Low Differential Pressure Lockout (Compressor 4)ReadActive = alarm
BV12996758_1_4Compressor Freeze Protection (Compressor 4)ReadActive = alarm
BV1175306_1Free Cooling Valve Hours ExceededReadActive = alarm
BV1185361_1Ext Free Cooling LockoutReadActive = alarm
BV1195362_1Free Cooling Temp Sensor IssueReadActive = alarm
BV1206539_1Chilled Water Valve Hours ExceededReadActive = alarm
BV1305365_1Hot Water / Hot Gas Valve Hours ExceededReadActive = alarm
BV1315068_1Reheater Over TemperatureReadActive = alarm
BV1325070_1Ext Reheat LockoutReadActive = alarm
BV1435368_1_1Electric Reheater Hours Exceeded (Electric Reheater 1)ReadActive = alarm
BV1545368_1_2Electric Reheater Hours Exceeded (Electric Reheater 2)ReadActive = alarm
BV1655368_1_3Electric Reheater Hours Exceeded (Electric Reheater 3)ReadActive = alarm
BV1765037_1Humidifier Hours ExceededReadActive = alarm
BV1775044_1Ext Humidifier LockoutReadActive = alarm
BV1785045_1Humidifier Control Board Not DetectedReadActive = alarm
BV1795042_1Humidifier Cylinder WornReadActive on Alarm Active on Alarm
BV1805043_1Humidifier IssueRead
BV1815041_1Humidifier Low WaterReadActive = alarm
BV1825040_1Humidifier Over CurrentReadActive = alarm
BV1835039_1Humidifier Under CurrentReadActive = alarm
BV1945038_1Dehumidifier Hours ExceededReadActive = alarm
BV2055054_1Fan Hours ExceededReadActive = alarm
BV2065376_1Main Fan OverloadReadActive = alarm
BV2074729_1Fan IssueReadActive = alarm
BV2086540_1FSA Control Input IssueReadActive = alarm
BV16488105_1_1Supply Fan Communication Lost (Supply Fan Status 1)ReadActive = alarm
BV16598105_1_2Supply Fan Communication Lost (Supply Fan Status 2)ReadActive = alarm
BV16708105_1_3Supply Fan Communication Lost (Supply Fan Status 3)ReadActive = alarm
BV16818105_1_4Supply Fan Communication Lost (Supply Fan Status 4)ReadActive = alarm
BV16928105_1_5Supply Fan Communication Lost (Supply Fan Status 5)ReadActive = alarm
BV17038105_1_6Supply Fan Communication Lost (Supply Fan Status 6)ReadActive = alarm
BV17148105_1_7Supply Fan Communication Lost (Supply Fan Status 7)ReadActive = alarm
BV17258105_1_8Supply Fan Communication Lost (Supply Fan Status 8)ReadActive = alarm
BV17368105_1_9Supply Fan Communication Lost (Supply Fan Status 9)ReadActive = alarm
BV17478105_1_10Supply Fan Communication Lost (Supply Fan Status 10)ReadActive = alarm
BV17588105_1_11Supply Fan Communication Lost (Supply Fan Status 11)ReadActive = alarm
BV17698105_1_12Supply Fan Communication Lost (Supply Fan Status 12)ReadActive = alarm
BV17808105_1_13Supply Fan Communication Lost (Supply Fan Status 13)ReadActive = alarm
BV17918105_1_14Supply Fan Communication Lost (Supply Fan Status 14)ReadActive = alarm
BV18028105_1_15Supply Fan Communication Lost (Supply Fan Status 15)ReadActive = alarm
BV18138105_1_16Supply Fan Communication Lost (Supply Fan Status 16)ReadActive = alarm
BV2195072_1Condenser VFD IssueReadActive = alarm
BV2205106_1Ext Condenser Pump High WaterReadActive = alarm
BV10606105_1External Condenser TVSS IssueReadActive = alarm
BV10616106_1External Condenser VFD IssueReadActive = alarm
BV2315377_1_1Condenser Issue (Condenser 1)ReadActive = alarm
BV2425377_1_2Condenser Issue (Condenser 2)ReadActive = alarm
BV2534270_1Customer Input 1ReadActive = alarm
BV2544271_1Customer Input 2ReadActive = alarm
BV2554272_1Customer Input 3ReadActive = alarm
BV2564273_1Customer Input 4ReadActive = alarm
BV2575415_1Ext Loss of Air BlowerReadActive = alarm
BV2585105_1Ext Loss of FlowReadActive = alarm
BV2595107_1Ext Standby Glycol Pump OnReadActive = alarm
BV2605115_1BMS Communications TimeoutReadActive = alarm
BV2615416_1Ext Standby Unit OnReadActive = alarm
BV2625118_1Clogged Air FilterReadActive = alarm
BV2635053_1Loss of Air FlowReadActive = alarm
BV2644726_1Service RequiredReadActive = alarm
BV2655120_1Master Unit Communication LostReadActive = alarm
BV2665119_1RAM Battery IssueReadActive = alarm
BV2674714_1Shutdown - Loss Of PowerReadActive = alarm
BV2685121_1High Power ShutdownReadActive = alarm
BV2694720_1Smoke DetectedReadActive = alarm
BV2704980_1Supply Chilled Water Loss of FlowReadActive = alarm
BV2714626_1Supply Chilled Water Over TempReadActive = alarm
BV2725418_1Unit Code MissingReadActive = alarm
BV2735419_1Unit Communication LostReadActive = alarm
BV2745114_1Water Leakage Detector Sensor IssueReadActive = alarm
BV2754723_1Water Under FloorReadActive = alarm
BV2765104_1Ext Over TemperatureReadActive = alarm
BV2775108_1External Fire DetectedReadActive = alarm
BV2785588_1Unspecified General EventReadActive = alarm
BV2795617_1Temperature Control Sensor IssueReadActive = alarm
BV2805906_1Airflow Sensor IssueReadActive = alarm
BV2815907_1Ext Air Damper Position IssueReadActive = alarm
BV2825908_1Ext Power Source A FailureReadActive = alarm
BV2835909_1Ext Power Source B FailureReadActive = alarm
BV2845924_1Mixed Mode LockoutReadActive = alarm
BV3506541_1Auto Tune License ExpiringReadActive = alarm
BV3516542_1Auto Tune License ExpiredReadActive = alarm
BV3526543_1Unit In Standby Due To Cooling LossReadActive = alarm
BV3536544_1Control Units Remote Shutdown MismatchReadActive = alarm
BV3546545_1Slave Control Unit Communication LostReadActive = alarm
BV3556546_1Control Units Unit Code MismatchReadActive = alarm
BV3565471_1Door OpenReadActive = alarm
BV3578192_1Water LeakageReadActive = alarm
BV3588231_1PHE Sup Tem Snsr FailReadActive = alarm
BV2884703_1_1Chilled Water Control Valve Failure (Chilled Water Valve 1)ReadActive = alarm
BV2994703_1_2Chilled Water Control Valve Failure (Chilled Water Valve 2)ReadActive = alarm
BV3105110_1_1Unit OffReadActive = alarm
BV3115109_1_1Unit OnReadActive = alarm
BV3125112_1_1Unit Partial ShutdownReadActive = alarm
BV3135113_1_1Unit ShutdownReadActive = alarm
BV3145111_1_1Unit StandbyReadActive = alarm
BV3155116_1_1Maintenance DueReadActive = alarm
BV3165117_1_1Maintenance CompletedReadActive = alarm
BV3275417_1_1Digital Output Board Not Detected (iCOM DO Board 1)ReadActive = alarm
BV3385417_1_2Digital Output Board Not Detected (iCOM DO Board 2)ReadActive = alarm
BV3495417_1_3Digital Output Board Not Detected (iCOM DO Board 3)ReadActive = alarm
BV3615593_1Remote Sensor Average Over TemperatureReadActive = alarm
BV3625594_1Remote Sensor Average Under TemperatureReadActive = alarm
BV3635595_1Remote Sensor System Average Over TemperatureReadActive = alarm
BV3645596_1Remote Sensor System Average Under TemperatureReadActive = alarm
BV3765597_1_1Remote Sensor Over Temperature (Remote Sensor 1)ReadActive = alarm
BV3775598_1_1Remote Sensor Under Temperature (Remote Sensor 1)ReadActive = alarm
BV3785060_1_1Remote Sensor Issue (Remote Sensor 1)ReadActive = alarm
BV3905597_1_2Remote Sensor Over Temperature (Remote Sensor 2)ReadActive = alarm
BV3915598_1_2Remote Sensor Under Temperature (Remote Sensor 2)ReadActive = alarm
BV3925060_1_2Remote Sensor Issue (Remote Sensor 2)ReadActive = alarm
BV4045597_1_3Remote Sensor Over Temperature (Remote Sensor 3)ReadActive = alarm
BV4055598_1_3Remote Sensor Under Temperature (Remote Sensor 3)ReadActive = alarm
BV4065060_1_3Remote Sensor Issue (Remote Sensor 3)ReadActive = alarm
BV4185597_1_4Remote Sensor Over Temperature (Remote Sensor 4)ReadActive = alarm
BV4195598_1_4Remote Sensor Under Temperature (Remote Sensor 4)ReadActive on Alarm Active on Alarm
BV4205060_1_4Remote Sensor Issue (Remote Sensor 4)Read
BV4325597_1_5Remote Sensor Over Temperature (Remote Sensor 5)ReadActive = alarm
BV4335598_1_5Remote Sensor Under Temperature (Remote Sensor 5)ReadActive = alarm
BV4345060_1_5Remote Sensor Issue (Remote Sensor 5)ReadActive = alarm
BV4465597_1_6Remote Sensor Over Temperature (Remote Sensor 6)ReadActive = alarm
BV4475598_1_6Remote Sensor Under Temperature (Remote Sensor 6)ReadActive = alarm
BV4485060_1_6Remote Sensor Issue (Remote Sensor 6)ReadActive = alarm
BV4605597_1_7Remote Sensor Over Temperature (Remote Sensor 7)ReadActive = alarm
BV4615598_1_7Remote Sensor Under Temperature (Remote Sensor 7)ReadActive = alarm
BV4625060_1_7Remote Sensor Issue (Remote Sensor 7)ReadActive = alarm
BV4745597_1_8Remote Sensor Over Temperature (Remote Sensor 8)ReadActive = alarm
BV4755598_1_8Remote Sensor Under Temperature (Remote Sensor 8)ReadActive = alarm
BV4765060_1_8Remote Sensor Issue (Remote Sensor 8)ReadActive = alarm
BV4885597_1_9Remote Sensor Over Temperature (Remote Sensor 9)ReadActive = alarm
BV4895598_1_9Remote Sensor Under Temperature (Remote Sensor 9)ReadActive = alarm
BV4905060_1_9Remote Sensor Issue (Remote Sensor 9)ReadActive = alarm
BV5025597_1_10Remote Sensor Over Temperature (Remote Sensor 10)ReadActive = alarm
BV5035598_1_10Remote Sensor Under Temperature (Remote Sensor 10)ReadActive = alarm
BV5045060_1_10Remote Sensor Issue (Remote Sensor 10)ReadActive on Alarm Active on Alarm
BV5165600_1Air Economizer Emergency OverrideRead
BV5175601_1Air Economizer Reduced AirflowReadActive = alarm
BV5405625_1EEV Unspecified General EventReadActive = alarm
BV5635629_1Static Pressure Sensor IssueReadActive = alarm
BV5645630_1High Static PressureReadActive = alarm
BV5655631_1Low Static PressureReadActive = alarm
BV5665910_1Static Pressure Sensor Out of RangeReadActive = alarm
BV5676547_1SSA Control Input IssueReadActive = alarm
BV6235636_1Pump Unspecified General EventReadActive = alarm
BV10015568_1Input Undervoltage (Power Measurement 1)ReadActive = alarm
BV10405967_1Modbus Power Meter Communication Lost (Power Measurement 1)ReadActive = alarm
BV10025568_2Input Undervoltage (Power Measurement 2)ReadActive = alarm
BV10415967_2Modbus Power Meter Communication Lost (Power Measurement 2)ReadActive = alarm
BV10035568_3Input Undervoltage (Power Measurement 3)ReadActive = alarm
BV10425967_3Modbus Power Meter Communication Lost (Power Measurement 3)ReadActive = alarm
BV10045568_4Input Undervoltage (Power Measurement 4)ReadActive = alarm
BV10435967_4Modbus Power Meter Communication Lost (Power Measurement 4)ReadActive = alarm
BV10055568_5Input Undervoltage (Power Measurement 5)ReadActive = alarm
BV10445967_5Modbus Power Meter Communication Lost (Power Measurement 5)ReadActive = alarm
BV10065568_6Input Undervoltage (Power Measurement 6)ReadActive = alarm
BV10455967_6Modbus Power Meter Communication Lost (Power Measurement 6)ReadActive = alarm
BV10215911_1Fluid Temperature Sensor IssueReadActive = alarm
BV10225912_1Fluid Flow Sensor IssueReadActive = alarm
BV10315911_2Fluid Temperature Sensor Issue (Fluid 2)ReadActive = alarm
BV10325912_2Fluid Flow Sensor Issue (Fluid 2)ReadActive = alarm
BV6435637_1Condenser Unit Unspecified General EventReadActive = alarm
BV10825536_1_1Condenser Outside Air Temp Out of Operating Range (Condenser 1)ReadActive = alarm
BV10845537_1_1Condenser Control Board Issue (Condenser 1)ReadActive = alarm
BV10865535_1_1Condenser Outside Air Temp Sensor Issue (Condenser 1)ReadActive = alarm
BV10885531_1_1Condenser Communication Lost (Condenser 1)ReadActive = alarm
BV10906100_1_1Condenser Remote Shutdown (Condenser 1)ReadActive = alarm
BV2185073_1_1Condenser TVSS Issue (Condenser 1)ReadActive = alarm
BV10835536_1_2Condenser Outside Air Temp Out of Operating Range (Condenser 2)ReadActive = alarm
BV10855537_1_2Condenser Control Board Issue (Condenser 2)ReadActive = alarm
BV10875535_1_2Condenser Outside Air Temp Sensor Issue (Condenser 2)ReadActive = alarm
BV10895531_1_2Condenser Communication Lost (Condenser 2)ReadActive = alarm
BV10916100_1_2Condenser Remote Shutdown (Condenser 2)ReadActive = alarm
BV10925073_1_2Condenser TVSS Issue (Condenser 2)ReadActive = alarm
BV13505073_1_3Condenser TVSS Issue (Condenser 3)ReadActive = alarm
BV13195536_1_3Condenser Outside Air Temp Out of Operating Range (Condenser 3)ReadActive = alarm
BV13205537_1_3Condenser Control Board Issue (Condenser 3)ReadActive = alarm
BV13215535_1_3Condenser Outside Air Temp Sensor Issue (Condenser 3)ReadActive = alarm
BV13225531_1_3Condenser Communication Lost (Condenser 3)ReadActive = alarm
BV13236100_1_3Condenser Remote Shutdown (Condenser 3)ReadActive = alarm
BV13665073_1_4Condenser TVSS Issue (Condenser 4)ReadActive = alarm
BV13355536_1_4Condenser Outside Air Temp Out of Operating Range (Condenser 4)ReadActive = alarm
BV13365537_1_4Condenser Control Board Issue (Condenser 4)ReadActive = alarm
BV13375535_1_4Condenser Outside Air Temp Sensor Issue (Condenser 4)ReadActive = alarm
BV13385531_1_4Condenser Communication Lost (Condenser 4)ReadActive = alarm
BV13396100_1_4Condenser Remote Shutdown (Condenser 4)ReadActive = alarm
BV6445638_1_1Condenser Circuit Unspecified General Event (Circuit 1)ReadActive = alarm
BV11045541_1_1Condenser Refrigerant Pressure Sensor Issue (Circuit 1)ReadActive = alarm
BV11065540_1_1Condenser Refrigerant Pressure Under Threshold (Circuit 1)ReadActive = alarm
BV11085539_1_1Condenser Refrigerant Pressure Over Threshold (Circuit 1)ReadActive = alarm
BV11105544_1_1Condenser Supply Refrigerant Temp Sensor Issue (Circuit 1)ReadActive = alarm
BV11125543_1_1Condenser Supply Refrigerant Under Temp (Circuit 1)ReadActive = alarm
BV11145542_1_1Condenser Supply Refrigerant Over Temp (Circuit 1)ReadActive = alarm
BV11165545_1_1Condenser Max Fan Speed Override (Circuit 1)ReadActive = alarm
BV8965638_1_2Condenser Circuit Unspecified General Event (Circuit 2)ReadActive = alarm
BV11055541_1_2Condenser Refrigerant Pressure Sensor Issue (Circuit 2)ReadActive = alarm
BV11075540_1_2Condenser Refrigerant Pressure Under Threshold (Circuit 2)ReadActive = alarm
BV11095539_1_2Condenser Refrigerant Pressure Over Threshold (Circuit 2)ReadActive = alarm
BV11115544_1_2Condenser Supply Refrigerant Temp Sensor Issue (Circuit 2)ReadActive = alarm
BV11135543_1_2Condenser Supply Refrigerant Under Temp (Circuit 2)ReadActive = alarm
BV11155542_1_2Condenser Supply Refrigerant Over Temp (Circuit 2)ReadActive = alarm
BV11175545_1_2Condenser Max Fan Speed Override (Circuit 2)ReadActive = alarm
BV13595541_1_3Condenser Refrigerant Pressure Sensor Issue (Circuit 3)ReadActive = alarm
BV13605540_1_3Condenser Refrigerant Pressure Under Threshold (Circuit 3)ReadActive = alarm
BV13615539_1_3Condenser Refrigerant Pressure Over Threshold (Circuit 3)ReadActive = alarm
BV13625544_1_3Condenser Supply Refrigerant Temp Sensor Issue (Circuit 3)ReadActive = alarm
BV13635543_1_3Condenser Supply Refrigerant Under Temp (Circuit 3)ReadActive = alarm
BV13645542_1_3Condenser Supply Refrigerant Over Temp (Circuit 3)ReadActive = alarm
BV13655545_1_3Condenser Max Fan Speed Override (Circuit 3)ReadActive = alarm
BV13765541_1_4Condenser Refrigerant Pressure Sensor Issue (Circuit 4)ReadActive = alarm
BV13775540_1_4Condenser Refrigerant Pressure Under Threshold (Circuit 4)ReadActive = alarm
BV13785539_1_4Condenser Refrigerant Pressure Over Threshold (Circuit 4)ReadActive = alarm
BV13795544_1_4Condenser Supply Refrigerant Temp Sensor Issue (Circuit 4)ReadActive = alarm
BV13805543_1_4Condenser Supply Refrigerant Under Temp (Circuit 4)ReadActive = alarm
BV13815542_1_4Condenser Supply Refrigerant Over Temp (Circuit 4)ReadActive = alarm
BV13825545_1_4Condenser Max Fan Speed Override (Circuit 4)ReadActive = alarm
BV11285277_1_1_1Condenser Fan Issue (Condenser 1 Fan 1)ReadActive = alarm
BV11295277_1_1_2Condenser Fan Issue (Condenser 1 Fan 2)ReadActive = alarm
BV11305277_1_1_3Condenser Fan Issue (Condenser 1 Fan 3)ReadActive = alarm
BV11315277_1_1_4Condenser Fan Issue (Condenser 1 Fan 4)ReadActive = alarm
BV11325277_1_2_1Condenser Fan Issue (Condenser 2 Fan 1)ReadActive = alarm
BV11335277_1_2_2Condenser Fan Issue (Condenser 2 Fan 2)ReadActive = alarm
BV11345277_1_2_3Condenser Fan Issue (Condenser 2 Fan 3)ReadActive = alarm
BV11355277_1_2_4Condenser Fan Issue (Condenser 2 Fan 4)ReadActive = alarm
BV14025277_1_3_1Condenser Fan Issue (Condenser 3 Fan 1)ReadActive = alarm
BV14225277_1_3_2Condenser Fan Issue (Condenser 3 Fan 2)ReadActive = alarm
BV14425277_1_3_3Condenser Fan Issue (Condenser 3 Fan 3)ReadActive = alarm
BV14625277_1_3_4Condenser Fan Issue (Condenser 3 Fan 4)ReadActive = alarm
BV14825277_1_4_1Condenser Fan Issue (Condenser 4 Fan 1)ReadActive = alarm
BV15025277_1_4_2Condenser Fan Issue (Condenser 4 Fan 2)ReadActive = alarm
BV15225277_1_4_3Condenser Fan Issue (Condenser 4 Fan 3)ReadActive = alarm
BV15425277_1_4_4Condenser Fan Issue (Condenser 4 Fan 4)ReadActive = alarm
BV11466092_1Compressor 1B Thermal OverloadReadActive = alarm
BV11476093_1Compressor 2B Thermal OverloadReadActive = alarm
BV11486094_1Compressor 1B Hours ExceededReadActive = alarm
BV11496095_1Compressor 2B Hours ExceededReadActive = alarm
BV11506303_1Team Static Pressure Sensor FailureReadActive = alarm
BV11516304_1Heating LockoutReadActive = alarm
BV11526305_1Free Cooling Stopped - High Room TempReadActive = alarm
BV11636306_1_1Cold Aisle Temperature/Humidity Team Sensor FailureReadActive = alarm
BV11746309_1_1Cold Aisle Air Sensor Failure (Cold Aisle Sensor 1)ReadActive = alarm
BV11856309_1_2Cold Aisle Air Sensor Failure (Cold Aisle Sensor 2)ReadActive = alarm
BV11966309_1_3Cold Aisle Air Sensor Failure (Cold Aisle Sensor 3)ReadActive = alarm
BV12076310_1Chilled Water Inlet Temperature Control ActiveReadActive = alarm
BV12186313_1_1Chilled Water Inlet Temperature Sensor Failure (Chilled Water Circuit 1)ReadActive = alarm
BV12196314_1_1Chilled Water Outlet Temperature Sensor Failure (Chilled Water Circuit 1)ReadActive = alarm
BV12206315_1_1Chilled Water Flow Meter Sensor Failure (Chilled Water Circuit 1)ReadActive = alarm
BV12316313_1_2Chilled Water Inlet Temperature Sensor Failure (Chilled Water Circuit 2)ReadActive = alarm
BV12326314_1_2Chilled Water Outlet Temperature Sensor Failure (Chilled Water Circuit 2)ReadActive = alarm
BV12336315_1_2Chilled Water Flow Meter Sensor Failure (Chilled Water Circuit 2)ReadActive = alarm
BV15546691_1_1Group Independent OnReadActive = alarm
BV15556692_1_1Group Independent OffReadActive = alarm
BV15676818_1External Supply Fluid High Temperature (Fluid Circuit 1)ReadActive = alarm
BV15686819_1External Supply Fluid Temp Sensor Issue (Fluid Circuit 1)ReadActive = alarm
BV15696824_1External Supply Fluid Flow Issue (Fluid Circuit 1)ReadActive = alarm
BV15708075_1Valve Communications Failure (Fluid Circuit 1)ReadActive = alarm
BV15718076_1Valve Issue (Fluid Circuit 1)ReadActive = alarm
BV15816818_2External Supply Fluid High Temperature (Fluid Circuit 2)ReadActive = alarm
BV15826819_2External Supply Fluid Temp Sensor Issue (Fluid Circuit 2)ReadActive = alarm
BV15836824_2External Supply Fluid Flow Issue (Fluid Circuit 2)ReadActive = alarm
BV15848075_2Valve Communications Failure (Fluid Circuit 2)ReadActive = alarm
BV15858076_2Valve Issue (Fluid Circuit 2)ReadActive = alarm
BV15956822_1Audit Log UpdateReadActive = alarm
BV16067163_1Modbus Automatic Transfer Switch Communication LostReadActive = alarm
BV16174651_1Supply Fluid Temp Sensor IssueReadActive = alarm
BV16185295_1Return Fluid Temp Sensor IssueReadActive = alarm
BV16197474_1Flow Sensor FailureReadActive = alarm
BV16207475_1Check Water SystemReadActive = alarm
BV16214645_1Supply Fluid Over TempReadActive = alarm
BV16225293_1Return Fluid Over TempReadActive = alarm
BV16237476_1Pump Operating Without FlowReadActive = alarm
BV18248180_1Supply Fluid Low TempReadActive = alarm
BV18258181_1Return Fluid Low TempReadActive = alarm
BV18268182_1Fluid High Differential PressureReadActive = alarm
BV18278183_1Fluid Low Differential PressureReadActive = alarm
BV18288184_1Fluid Flow Low Inlet PressureReadActive = alarm
BV18298185_1Fluid Flow High Supply PressureReadActive = alarm
BV18308186_1Fluid Low System FlowReadActive = alarm
BV18318187_1Fluid Flow BlockedReadActive = alarm
BV18328188_1Fluid Dewpoint Margin ControlReadActive = alarm
BV18338189_1Fluid Supply Pressure Sensor IssueReadActive = alarm
BV18348190_1Fluid Return Pressure Sensor IssueReadActive = alarm
BV18358191_1Fluid Inlet Pressure Sensor IssueReadActive = alarm
BV16347483_1_1Pump Inverter Failure (Fluid Pump 1)ReadActive = alarm
BV16357484_1_1Pump Flow Failure (Fluid Pump 1)ReadActive = alarm
BV16367483_1_2Pump Inverter Failure (Fluid Pump 2)ReadActive = alarm
BV16377484_1_2Pump Flow Failure (Fluid Pump 2)ReadActive = alarm
BV18468170_1_1XD Pump Communication Lost (Fluid Pump Status 1)ReadActive = alarm
BV18578170_1_2XD Pump Communication Lost (Fluid Pump Status 2)ReadActive = alarm
AVmin15008_1Air Temperature Set Point°CWrite
AV100015008_1_deg_FAir Temperature Set Point°FWrite
AV25325_1Air Temperature Proportional Band°CWrite
AV100025325_1_deg_FAir Temperature Proportional Band°FWrite
AV35011_1Air Temperature Dead Band°CWrite
AV100035011_1_deg_FAir Temperature Dead Band°FWrite
AV45326_1Air Temperature Control Integration TimeminWrite
AV55327_1Today's High Air Temperature°CRead
AV100055327_1_deg_FToday's High Air Temperature°FRead
AV65328_1Today's High Air Temperature TimeSeconds since MidnightRead
AV75329_1Today's Low Air Temperature°CRead
AV100075329_1_deg_FToday's Low Air Temperature°FRead
AV85330_1Today's Low Air Temperature TimeSeconds since MidnightRead
AVmin195002_1_1Supply Air Temperature°CRead
AV100195002_1_1_deg_FSupply Air Temperature°FRead
AVmin205331_1_1Supply Air Temperature Set Point°CWrite
AV100205331_1_1_deg_FSupply Air Temperature Set Point°FWrite
AV215014_1_1High Supply Air Temperature Threshold°CWrite
AV100215014_1_1_deg_FHigh Supply Air Temperature Threshold°FWrite
AV225018_1_1Low Supply Air Temperature Threshold°CWrite
AV100225018_1_1_deg_FLow Supply Air Temperature Threshold°FWrite
AV236756_1_1Supply Sensor Events Initial DelaysWrite
AV335022_1_1High Return Air Temperature Threshold°CWrite
AV100335022_1_1_deg_FHigh Return Air Temperature Threshold°FWrite
AV345334_1_1Low Return Air Temperature Threshold°CWrite
AV100345334_1_1_deg_FLow Return Air Temperature Threshold°FWrite
AV356757_1_1Return Sensor Events Initial DelaysWrite
AV454594_1_1Ext Air Sensor A Temperature°CRead
AV100454594_1_1_deg_FExt Air Sensor A Temperature°FRead
AV464597_1_1Ext Air Sensor B Temperature°CRead
AV100464597_1_1_deg_FExt Air Sensor B Temperature°FRead
AV475336_1_1Ext Air Sensor C Temperature°CRead
AV100475336_1_1_deg_FExt Air Sensor C Temperature°FRead
AV485337_1_1Ext Air Sensor A Over Temp Threshold°CWrite
AV100485337_1_1_deg_FExt Air Sensor A Over Temp Threshold°FWrite
AV495338_1_1Ext Air Sensor A Under Temp Threshold°CWrite
AV100495338_1_1_deg_FExt Air Sensor A Under Temp Threshold°FWrite
AV505574_1_1Outside Air Temperature°CRead
AV100505574_1_1_deg_FOutside Air Temperature°FRead
AVmin605028_1Return Humidity%RHRead
AV615029_1Humidity Set Point%RHWrite
AV625339_1Return Humidity Set Point%RHWrite
AV635341_1Humidity Proportional Band%RHWrite
AV645032_1Humidity Dead Band%RHWrite
AV655342_1Humidity Control Integration TimeminWrite
AV665033_1High Return Humidity Threshold%RHWrite
AV675035_1Low Return Humidity Threshold%RHWrite
AV685343_1Today's High Humidity%RHRead
AV695344_1Today's High Humidity TimeSeconds since MidnightRead
AV705345_1Today's Low Humidity%RHRead
AV715346_1Today's Low Humidity TimeSeconds since MidnightRead
AV726258_1Dew Point Proportional Band°CWrite
AV100726258_1_deg_FDew Point Proportional Band°FWrite
AV736259_1Dew Point Dead Band°CWrite
AV100736259_1_deg_FDew Point Dead Band°FWrite
AV746575_1Dew Point Over Temp Threshold°CWrite
AV100746575_1_deg_FDew Point Over Temp Threshold°FWrite
AV756576_1Dew Point Under Temp Threshold°CWrite
AV100756576_1_deg_FDew Point Under Temp Threshold°FWrite
AV824595_1_1Ext Air Sensor A Humidity%RHRead
AV834598_1_1Ext Air Sensor B Humidity%RHRead
AV845347_1_1Ext Air Sensor C Humidity%RHRead
AV855348_1_1Ext Air Sensor A High Humidity Threshold%RHWrite
AV865350_1_1Ext Air Sensor A Low Humidity Threshold%RHWrite
AV874596_1_1Ext Air Sensor A Dew Point Temp°CRead
AV100874596_1_1_deg_FExt Air Sensor A Dew Point Temp°FRead
AV884614_1_1Ext Dew Point Over Temp Threshold°CWrite
AV100884614_1_1_deg_FExt Dew Point Over Temp Threshold°FWrite
AV895576_1_1Ext Dew Point Under Temp Threshold°CWrite
AV100895576_1_1_deg_FExt Dew Point Under Temp Threshold°FWrite
AV975267_1_1Compressor Hours (Compressor 1)hWrite
AV985268_1_1Compressor Hours Threshold (Compressor 1)hWrite
AV995353_1_1Dig Scroll Comp Discharge Temp (Compressor 1)°CRead
AV100995353_1_1_deg_FDig Scroll Comp Discharge Temp (Compressor 1)°FRead
AV1005619_1_1Digital Scroll Compressor Loading (Compressor 1)%Read
AV1016241_1_1Tandem 'B' Compressor Hours (Compressor 1)hWrite
AV1026688_1_1Compressor Suction Pressure (Compressor 1)barRead
AV1105267_1_2Compressor Hours (Compressor 2)hWrite
AV1115268_1_2Compressor Hours Threshold (Compressor 2)hWrite
AV1125353_1_2Dig Scroll Comp Discharge Temp (Compressor 2)°CRead
AV101125353_1_2_deg_FDig Scroll Comp Discharge Temp (Compressor 2)°FRead
AV1135619_1_2Digital Scroll Compressor Loading (Compressor 2)%Read
AV1146241_1_2Tandem 'B' Compressor Hours (Compressor 2)hWrite
AV1156688_1_2Compressor Suction Pressure (Compressor 2)barRead
AV22355353_1_3Dig Scroll Comp Discharge Temp (Compressor 3)°CRead
AV122355353_1_3_deg_FDig Scroll Comp Discharge Temp (Compressor 3)°FRead
AV22365619_1_3Digital Scroll Compressor Loading (Compressor 3)%Read
AV22375267_1_3Compressor Hours (Compressor 3)hWrite
AV22386241_1_3Tandem 'B' Compressor Hours (Compressor 3)hWrite
AV22395268_1_3Compressor Hours Threshold (Compressor 3)hWrite
AV22406688_1_3Compressor Suction Pressure (Compressor 3)barRead
AV22505353_1_4Dig Scroll Comp Discharge Temp (Compressor 4)°CRead
AV122505353_1_4_deg_FDig Scroll Comp Discharge Temp (Compressor 4)°FRead
AV22515619_1_4Digital Scroll Compressor Loading (Compressor 4)%Read
AV22525267_1_4Compressor Hours (Compressor 4)hWrite
AV22536241_1_4Tandem 'B' Compressor Hours (Compressor 4)hWrite
AV22545268_1_4Compressor Hours Threshold (Compressor 4)hWrite
AV22556688_1_4Compressor Suction Pressure (Compressor 4)barRead
AV1235356_1Free Cooling Internal Temperature Delta°CWrite
AV101235356_1_deg_FFree Cooling Internal Temperature Delta°FWrite
AV1245358_1Free Cooling Fluid Temperature°CRead
AV101245358_1_deg_FFree Cooling Fluid Temperature°FRead
AV1255360_1Minimum Chilled Water Temp Set Point°CWrite
AV101255360_1_deg_FMinimum Chilled Water Temp Set Point°FWrite
AV1265304_1Free Cooling Valve HourshWrite
AV1275305_1Free Cooling Valve Hours ThresholdhWrite
AV1285614_1Chilled Water Valve HourshWrite
AV1296452_1Chilled Water Valve Operating Hours ThresholdhWrite
AV1306759_1Fluid Free Cooling Lockout Threshold°CWrite
AV101306759_1_deg_FFluid Free Cooling Lockout Threshold°FWrite
AV1385363_1Hot Water / Hot Gas Valve HourshWrite
AV1395364_1Hot Water / Hot Gas Valve Hours ThresholdhWrite
AV1406761_1Dehum Reheat Low Limit Set Point°CWrite
AV101406761_1_deg_FDehum Reheat Low Limit Set Point°FWrite
AV1416762_1Dehum Reheat Low Limit 1°CWrite
AV101416762_1_deg_FDehum Reheat Low Limit 1°FWrite
AV1426763_1Dehum Reheat Low Limit 2°CWrite
AV101426763_1_deg_FDehum Reheat Low Limit 2°FWrite
AV1436764_1Dehum Reheat Proportional Band°CWrite
AV101436764_1_deg_FDehum Reheat Proportional Band°FWrite
AV1505366_1_1Electric Reheater Hours (Electric Reheater 1)hWrite
AV1515367_1_1Electric Reheater Hours Threshold (Electric Reheater 1)hWrite
AV1625366_1_2Electric Reheater Hours (Electric Reheater 2)hWrite
AV1635367_1_2Electric Reheater Hours Threshold (Electric Reheater 2)hWrite
AV1745366_1_3Electric Reheater Hours (Electric Reheater 3)hWrite
AV1755367_1_3Electric Reheater Hours Threshold (Electric Reheater 3)hWrite
AV1865369_1Humidifier HourshWrite
AV1875370_1Humidifier Hours ThresholdhWrite
AV1885445_1Infrared Humidifier Flush Rate%Write
AV1896765_1Return Temp Threshold for Humidifier Disable°CWrite
AV101896765_1_deg_FReturn Temp Threshold for Humidifier Disable°FWrite
AV1906766_1Return Temp Hysteresis for Humidifier Disable°CWrite
AV101906766_1_deg_FReturn Temp Hysteresis for Humidifier Disable°FWrite
AV1995371_1Dehumidifier HourshWrite
AV2005372_1Dehumidifier Hours ThresholdhWrite
AV2115050_1Fan Speed Maximum Set Point%Write
AV2125374_1Fan HourshWrite
AV2135375_1Fan Hours ThresholdhWrite
AV2145051_1Fan Speed Minimum Set Point%Write
AV2155585_1Fan Speed Temperature Set Point°CWrite
AV102155585_1_deg_FFan Speed Temperature Set Point°FWrite
AV2166772_1Fan Back Draft Speed Set PointVDCWrite
AV2176768_1Fan Speed Temp Control Proportional Band°CWrite
AV102176768_1_deg_FFan Speed Temp Control Proportional Band°FWrite
AV2186769_1Fan Speed Temp Control Integration TimeminWrite
AV2196770_1Fan Speed Temperature Dead Band°CWrite
AV102196770_1_deg_FFan Speed Temperature Dead Band°FWrite
AV2208252_1Fan Speed Min Dehum%Write
AV26318103_1_1Fan Power (Supply Fan Status 1)WRead
AV26328104_1_1Fan Current (Supply Fan Status 1)A DCRead
AV26338487_1_1Supply Fan Measured Speed (Supply Fan Status 1)RPMRead
AV26438103_1_2Fan Power (Supply Fan Status 2)WRead
AV26448104_1_2Fan Current (Supply Fan Status 2)A DCRead
AV26458487_1_2Supply Fan Measured Speed (Supply Fan Status 2)RPMRead
AV26558103_1_3Fan Power (Supply Fan Status 3)WRead
AV26568104_1_3Fan Current (Supply Fan Status 3)A DCRead
AV26678103_1_4Fan Power (Supply Fan Status 4)WRead
AV26688104_1_4Fan Current (Supply Fan Status 4)A DCRead
AV26798103_1_5Fan Power (Supply Fan Status 5)WRead
AV26808104_1_5Fan Current (Supply Fan Status 5)A DCRead
AV26918103_1_6Fan Power (Supply Fan Status 6)WRead
AV26928104_1_6Fan Current (Supply Fan Status 6)A DCRead
AV27038103_1_7Fan Power (Supply Fan Status 7)WRead
AV27048104_1_7Fan Current (Supply Fan Status 7)A DCRead
AV27158103_1_8Fan Power (Supply Fan Status 8)WRead
AV27168104_1_8Fan Current (Supply Fan Status 8)A DCRead
AV27278103_1_9Fan Power (Supply Fan Status 9)WRead
AV27288104_1_9Fan Current (Supply Fan Status 9)A DCRead
AV27398103_1_10Fan Power (Supply Fan Status 10)WRead
AV27408104_1_10Fan Current (Supply Fan Status 10)A DCRead
AV27518103_1_11Fan Power (Supply Fan Status 11)WRead
AV27528104_1_11Fan Current (Supply Fan Status 11)A DCRead
AV27638103_1_12Fan Power (Supply Fan Status 12)WRead
AV27648104_1_12Fan Current (Supply Fan Status 12)A DCRead
AV27758103_1_13Fan Power (Supply Fan Status 13)WRead
AV27768104_1_13Fan Current (Supply Fan Status 13)A DCRead
AV27878103_1_14Fan Power (Supply Fan Status 14)WRead
AV27888104_1_14Fan Current (Supply Fan Status 14)A DCRead
AV27998103_1_15Fan Power (Supply Fan Status 15, 16)WRead
AV28008104_1_15Fan Current (Supply Fan Status 15, 16)A DCRead
AV28118103_1_16Fan Power (Supply Fan Status 16)WRead
AV28128104_1_16Fan Current (Supply Fan Status 16)A DCRead
AV28138487_1_16Supply Fan Measured Speed (Supply Fan Status 16)RPMRead
AV2245378_1Analog Input Reading (Analog Inputs 1)Read
AV2355378_2Analog Input Reading (Analog Inputs 2)Read
AV2465378_3Analog Input Reading (Analog Inputs 3)Read
AV2575378_4Analog Input Reading (Analog Inputs 4)Read
AV29305378_5Analog Input Reading (Analog Inputs 5)Read
AV29415378_6Analog Input Reading (Analog Inputs 6)Read
AV29525378_7Analog Input Reading (Analog Inputs 7)Read
AV29635378_8Analog Input Reading (Analog Inputs 8)Read
AV29745378_9Analog Input Reading (Analog Inputs 9)Read
AV29855378_10Analog Input Reading (Analog Inputs 10)Read
AV29965378_11Analog Input Reading (Analog Inputs 11)Read
AV30075378_12Analog Input Reading (Analog Inputs 12)Read
AV30188473_1Analog Output (Analog Outputs 1)%Read
AV30298473_2Analog Output (Analog Outputs 2)%Read
AV30738473_6Analog Output (Analog Outputs 6)%Read
AV2685075_1BMS Timeout PeriodminWrite
AV2694710_1Auto Restart DelaysWrite
AV2705314_1Standby Units (Unit Information)Write
AV2716121_1Unit to Unit GroupRead
AV2726120_1Unit to Unit AddressRead
AV325333_1Return Air Temperature Set Point°CWrite
AV100325333_1_deg_FReturn Air Temperature Set Point°FWrite
AVmin314291_1Return Air Temperature°CRead
AV100314291_1_deg_FReturn Air Temperature°FRead
AV2805077_1Fan Speed%Read
AV2815078_1Compressor Utilization%Read
AV2825379_1Free Cooling Valve Open Position%Read
AV2834870_1Maintenance Ramp%Read
AV2844868_1Calculated Next Maintenance MonthRead
AV2854869_1Calculated Next Maintenance YearRead
AV2865380_1Hot Water / Hot Gas Valve Open Position%Read
AV2875080_1Reheat Utilization%Read
AV2885081_1Humidifier Utilization%Read
AV2895079_1Dehumidifier Utilization%Read
AV2905490_1Cooling Capacity%Read
AV2915606_1Adjusted Humidity%RHRead
AV2925004_1Return Dew Point°CRead
AV102925004_1_deg_FReturn Dew Point°FRead
AV2935607_1Actual Air Temperature Set Point°CRead
AV102935607_1_deg_FActual Air Temperature Set Point°FRead
AV2945608_1Actual Humidity Set Point%RHRead
AV2955575_1Dew Point Set Point°CWrite
AV102955575_1_deg_FDew Point Set Point°FWrite
AV2965615_1Cooling Control Temperature°CRead
AV102965615_1_deg_FCooling Control Temperature°FRead
AV2975616_1Fan Speed Control Temperature°CRead
AV102975616_1_deg_FFan Speed Control Temperature°FRead
AV2985904_1Unit Cooling LoadkWRead
AV2996134_1Unit Calculated Airflowm3/hRead
AV3004293_1System Date and TimeSecs since Epoch (UTC)Write
AV3125589_1Remote Sensor Over Temp Threshold°CWrite
AV103125589_1_deg_FRemote Sensor Over Temp Threshold°FWrite
AV3135590_1Remote Sensor Under Temp Threshold°CWrite
AV103135590_1_deg_FRemote Sensor Under Temp Threshold°FWrite
AV3145007_1Remote Sensor Average Temperature°CRead
AV103145007_1_deg_FRemote Sensor Average Temperature°FRead
AV3155006_1Remote Sensor Maximum Temperature°CRead
AV103155006_1_deg_FRemote Sensor Maximum Temperature°FRead
AV3165591_1Remote Sensor System Average Temperature°CRead
AV103165591_1_deg_FRemote Sensor System Average Temperature°FRead
AV3175592_1Remote Sensor System Maximum Temperature°CRead
AV103175592_1_deg_FRemote Sensor System Maximum Temperature°FRead
AV3295059_1_1Remote Sensor Temperature (Remote Sensor 1)°CRead
AV103295059_1_1_deg_FRemote Sensor Temperature (Remote Sensor 1)°FRead
AV3415059_1_2Remote Sensor Temperature (Remote Sensor 2)°CRead
AV103415059_1_2_deg_FRemote Sensor Temperature (Remote Sensor 2)°FRead
AV3535059_1_3Remote Sensor Temperature (Remote Sensor 3)°CRead
AV103535059_1_3_deg_FRemote Sensor Temperature (Remote Sensor 3)°FRead
AV3655059_1_4Remote Sensor Temperature (Remote Sensor 4)°CRead
AV103655059_1_4_deg_FRemote Sensor Temperature (Remote Sensor 4)°FRead
AV3775059_1_5Remote Sensor Temperature (Remote Sensor 5)°CRead
AV103775059_1_5_deg_FRemote Sensor Temperature (Remote Sensor 5)°FRead
AV3895059_1_6Remote Sensor Temperature (Remote Sensor 6)°CRead
AV103895059_1_6_deg_FRemote Sensor Temperature (Remote Sensor 6)°FRead
AV4015059_1_7Remote Sensor Temperature (Remote Sensor 7)°CRead
AV104015059_1_7_deg_FRemote Sensor Temperature (Remote Sensor 7)°FRead
AV4135059_1_8Remote Sensor Temperature (Remote Sensor 8)°CRead
AV104135059_1_8_deg_FRemote Sensor Temperature (Remote Sensor 8)°FRead
AV4255059_1_9Remote Sensor Temperature (Remote Sensor 9)°CRead
AV104255059_1_9_deg_FRemote Sensor Temperature (Remote Sensor 9)°FRead
AV4375059_1_10Remote Sensor Temperature (Remote Sensor 10)°CRead
AV104375059_1_10_deg_FRemote Sensor Temperature (Remote Sensor 10)°FRead
AV4615626_1Static Pressure Set PointPaWrite
AV21215626_1Static Pressure Set PointPaWrite
AV4625627_1Unit Static PressurePaRead
AV21225627_1Unit Static PressurePaRead
AV4635628_1System Static PressurePaRead
AV21235628_1System Static PressurePaRead
AV5055299_1Pump Hours ThresholdhWrite
AV5235298_1_1Pump Hours (Pump 1)hWrite
AV5225634_1_1Pump Speed (Pump 1)%Read
AV5355635_1_1Pump Inlet Refrigerant Temperature (Pump 1)°CRead
AV105355635_1_1_deg_FPump Inlet Refrigerant Temperature (Pump 1)°FRead
AV5375639_1_1Pump Outlet Refrigerant Temperature (Pump 1)°CRead
AV105375639_1_1_deg_FPump Outlet Refrigerant Temperature (Pump 1)°FRead
AV5265298_1_2Pump Hours (Pump 2)hWrite
AV5255634_1_2Pump Speed (Pump 2)%Read
AV5385635_1_2Pump Inlet Refrigerant Temperature (Pump 2)°CRead
AV105385635_1_2_deg_FPump Inlet Refrigerant Temperature (Pump 2)°FRead
AV5405639_1_2Pump Outlet Refrigerant Temperature (Pump 2)°CRead
AV105405639_1_2_deg_FPump Outlet Refrigerant Temperature (Pump 2)°FRead
AV22745298_1_3Pump Hours (Pump 3)hWrite
AV22755634_1_3Pump Speed (Pump 3)%Read
AV22765635_1_3Pump Inlet Refrigerant Temperature (Pump 3)°CRead
AV122765635_1_3_deg_FPump Inlet Refrigerant Temperature (Pump 3)°FRead
AV22775639_1_3Pump Outlet Refrigerant Temperature (Pump 3)°CRead
AV122775639_1_3_deg_FPump Outlet Refrigerant Temperature (Pump 3)°FRead
AV22885298_1_4Pump Hours (Pump 4)hWrite
AV22895634_1_4Pump Speed (Pump 4)%Read
AV22905635_1_4Pump Inlet Refrigerant Temperature (Pump 4)°CRead
AV122905635_1_4_deg_FPump Inlet Refrigerant Temperature (Pump 4)°FRead
AV22915639_1_4Pump Outlet Refrigerant Temperature (Pump 4)°CRead
AV122915639_1_4_deg_FPump Outlet Refrigerant Temperature (Pump 4)°FRead
AV8104096_1System Input RMS A-N (Power Measurement 1)VRead
AV8114098_1System Input RMS B-N (Power Measurement 1)VRead
AV8124100_1System Input RMS C-N (Power Measurement 1)VRead
AV8134113_1System Input RMS Current Phase A (Power Measurement 1)ARead
AV8144114_1System Input RMS Current Phase B (Power Measurement 1)ARead
AV8154115_1System Input RMS Current Phase C (Power Measurement 1)ARead
AV8165901_1Instantaneous Power (Power Measurement 1)WRead
AV8175900_1Energy Consumption (Power Measurement 1)kWhWrite
AV19004097_1System Input RMS A-B (Power Measurement 1)VRead
AV19014099_1System Input RMS B-C (Power Measurement 1)VRead
AV19024101_1System Input RMS C-A (Power Measurement 1)VRead
AV8204096_2System Input RMS A-N (Power Measurement 2)VRead
AV8214098_2System Input RMS B-N (Power Measurement 2)VRead
AV8224100_2System Input RMS C-N (Power Measurement 2)VRead
AV8234113_2System Input RMS Current Phase A (Power Measurement 2)ARead
AV8244114_2System Input RMS Current Phase B (Power Measurement 2)ARead
AV8254115_2System Input RMS Current Phase C (Power Measurement 2)ARead
AV8265901_2Instantaneous Power (Power Measurement 2)WRead
AV8275900_2Energy Consumption (Power Measurement 2)kWhWrite
AV19104097_2System Input RMS A-B (Power Measurement 2)VRead
AV19114099_2System Input RMS B-C (Power Measurement 2)VRead
AV19124101_2System Input RMS C-A (Power Measurement 2)VRead
AV8304096_3System Input RMS A-N (Power Measurement 3)VRead
AV8314098_3System Input RMS B-N (Power Measurement 3)VRead
AV8324100_3System Input RMS C-N (Power Measurement 3)VRead
AV8334113_3System Input RMS Current Phase A (Power Measurement 3)ARead
AV8344114_3System Input RMS Current Phase B (Power Measurement 3)ARead
AV8354115_3System Input RMS Current Phase C (Power Measurement 3)ARead
AV8365901_3Instantaneous Power (Power Measurement 3)WRead
AV8375900_3Energy Consumption (Power Measurement 3)kWhWrite
AV19204097_3System Input RMS A-B (Power Measurement 3)VRead
AV19214099_3System Input RMS B-C (Power Measurement 3)VRead
AV19224101_3System Input RMS C-A (Power Measurement 3)VRead
AV8404096_4System Input RMS A-N (Power Measurement 4)VRead
AV8414098_4System Input RMS B-N (Power Measurement 4)VRead
AV8424100_4System Input RMS C-N (Power Measurement 4)VRead
AV8434113_4System Input RMS Current Phase A (Power Measurement 4)ARead
AV8444114_4System Input RMS Current Phase B (Power Measurement 4)ARead
AV8454115_4System Input RMS Current Phase C (Power Measurement 4)ARead
AV8465901_4Instantaneous Power (Power Measurement 4)WRead
AV8475900_4Energy Consumption (Power Measurement 4)kWhWrite
AV19304097_4System Input RMS A-B (Power Measurement 4)VRead
AV19314099_4System Input RMS B-C (Power Measurement 4)VRead
AV19324101_4System Input RMS C-A (Power Measurement 4)VRead
AV8504096_5System Input RMS A-N (Power Measurement 5)VRead
AV8514098_5System Input RMS B-N (Power Measurement 5)VRead
AV8524100_5System Input RMS C-N (Power Measurement 5)VRead
AV8534113_5System Input RMS Current Phase A (Power Measurement 5)ARead
AV8544114_5System Input RMS Current Phase B (Power Measurement 5)ARead
AV8554115_5System Input RMS Current Phase C (Power Measurement 5)ARead
AV8565901_5Instantaneous Power (Power Measurement 5)WRead
AV8575900_5Energy Consumption (Power Measurement 5)kWhWrite
AV19404097_5System Input RMS A-B (Power Measurement 5)VRead
AV19414099_5System Input RMS B-C (Power Measurement 5)VRead
AV19424101_5System Input RMS C-A (Power Measurement 5)VRead
AV8604096_6System Input RMS A-N (Power Measurement 6)VRead
AV8614098_6System Input RMS B-N (Power Measurement 6)VRead
AV8624100_6System Input RMS C-N (Power Measurement 6)VRead
AV8634113_6System Input RMS Current Phase A (Power Measurement 6)ARead
AV8644114_6System Input RMS Current Phase B (Power Measurement 6)ARead
AV8654115_6System Input RMS Current Phase C (Power Measurement 6)ARead
AV8665901_6Instantaneous Power (Power Measurement 6)WRead
AV8675900_6Energy Consumption (Power Measurement 6)kWhWrite
AV19504097_6System Input RMS A-B (Power Measurement 6)VRead
AV19514099_6System Input RMS B-C (Power Measurement 6)VRead
AV19524101_6System Input RMS C-A (Power Measurement 6)VRead
AV8715897_1Fluid Input Temperature°CRead
AV108715897_1_deg_FFluid Input Temperature°FRead
AV8725898_1Fluid Output Temperature°CRead
AV108725898_1_deg_FFluid Output Temperature°FRead
AV18715897_2Fluid Input Temperature (Fluid 2)°CRead
AV118715897_2_deg_FFluid Input Temperature (Fluid 2)°FRead
AV18725898_2Fluid Output Temperature (Fluid 2)°CRead
AV118725898_2_deg_FFluid Output Temperature (Fluid 2)°FRead
AV8815899_1Fluid Flow Rate (Circuit)l/minRead
AV8828488_1Fluid Control Valve Position (Circuit)%Read
AV8915899_2Fluid Flow Rate (Circuit 2)l/minRead
AV8928488_2Fluid Control Valve Position (Circuit 2)%Read
AV9015905_1_1Circuit Cooling Load (Cooling Load 1)kWRead
AV9115905_1_2Circuit Cooling Load (Cooling Load 2)kWRead
AV19605964_1_1Raw Auxiliary Air Temperature°CWrite
AV119605964_1_1_deg_FRaw Auxiliary Air Temperature°FWrite
AV19615965_1_1Actual Auxiliary Air Temperature°CRead
AV119615965_1_1_deg_FActual Auxiliary Air Temperature°FRead
AV19816101_1Expected Condenser Unit CountRead
AV5295548_1_1Condenser Low Noise Mode Max Fan Speed%Write
AV5305549_1_1Condenser Normal Mode Max Fan Speed%Write
AV5315552_1_1Condenser Low Noise Mode Start TimeSeconds since MidnightWrite
AV5325553_1_1Condenser Low Noise Mode Stop TimeSeconds since MidnightWrite
AV5335550_1_1Condenser Low Noise Mode - Interval DaysWrite1=Monday, 2=Tuesday, 4=Wednesday, 8=Thursday, 16=Friday, 32=Saturday, 64=Sunday
AV5345551_1_1Condenser Low Noise Mode - Full DaysWrite1=Monday, 2=Tuesday, 4=Wednesday, 8=Thursday, 16=Friday, 32=Saturday, 64=Sunday
AV19925534_1_1Condenser Outside Air Temperature (Condenser 1)°CRead
AV119925534_1_1_deg_FCondenser Outside Air Temperature (Condenser 1)°FRead
AV19935534_1_2Condenser Outside Air Temperature (Condenser 2)°CRead
AV119935534_1_2_deg_FCondenser Outside Air Temperature (Condenser 2)°FRead
AV23075534_1_3Condenser Outside Air Temperature (Condenser 3)°CRead
AV123075534_1_3_deg_FCondenser Outside Air Temperature (Condenser 3)°FRead
AV23185534_1_4Condenser Outside Air Temperature (Condenser 4)°CRead
AV123185534_1_4_deg_FCondenser Outside Air Temperature (Condenser 4)°FRead
AV20046103_1_1Condenser Refrigerant Pressure (Circuit 1)barRead
AV20066102_1_1Condenser Supply Refrigerant Temperature (Circuit 1)°CRead
AV120066102_1_1_deg_FCondenser Supply Refrigerant Temperature (Circuit 1)°FRead
AV20056103_1_2Condenser Refrigerant Pressure (Circuit 2)barRead
AV20076102_1_2Condenser Supply Refrigerant Temperature (Circuit 2)°CRead
AV120076102_1_2_deg_FCondenser Supply Refrigerant Temperature (Circuit 2)°FRead
AV23386103_1_3Condenser Refrigerant Pressure (Circuit 3)barRead
AV23396102_1_3Condenser Supply Refrigerant Temperature (Circuit 3)°CRead
AV123396102_1_3_deg_FCondenser Supply Refrigerant Temperature (Circuit 3)°FRead
AV23506103_1_4Condenser Refrigerant Pressure (Circuit 4)barRead
AV23516102_1_4Condenser Supply Refrigerant Temperature (Circuit 4)°CRead
AV123516102_1_4_deg_FCondenser Supply Refrigerant Temperature (Circuit 4)°FRead
AV20185276_1_1_1Condenser Fan Speed (Condenser 1 Fan 1)%Read
AV20265538_1_1_1Condenser Fan Power (Condenser 1 Fan 1)WRead
AV20346244_1_1_1Condenser Fan Current (Condenser 1 Fan 1)ARead
AV20195276_1_1_2Condenser Fan Speed (Condenser 1 Fan 2)%Read
AV20275538_1_1_2Condenser Fan Power (Condenser 1 Fan 2)WRead
AV20356244_1_1_2Condenser Fan Current (Condenser 1 Fan 2)ARead
AV20205276_1_1_3Condenser Fan Speed (Condenser 1 Fan 3)%Read
AV20285538_1_1_3Condenser Fan Power (Condenser 1 Fan 3)WRead
AV20366244_1_1_3Condenser Fan Current (Condenser 1 Fan 3)ARead
AV20215276_1_1_4Condenser Fan Speed (Condenser 1 Fan 4)%Read
AV20295538_1_1_4Condenser Fan Power (Condenser 1 Fan 4)WRead
AV20376244_1_1_4Condenser Fan Current (Condenser 1 Fan 4)ARead
AV20225276_1_2_1Condenser Fan Speed (Condenser 2 Fan 1)%Read
AV20305538_1_2_1Condenser Fan Power (Condenser 2 Fan 1)WRead
AV20386244_1_2_1Condenser Fan Current (Condenser 2 Fan 1)ARead
AV20235276_1_2_2Condenser Fan Speed (Condenser 2 Fan 2)%Read
AV20315538_1_2_2Condenser Fan Power (Condenser 2 Fan 2)WRead
AV20396244_1_2_2Condenser Fan Current (Condenser 2 Fan 2)ARead
AV20245276_1_2_3Condenser Fan Speed (Condenser 2 Fan 3)%Read
AV20325538_1_2_3Condenser Fan Power (Condenser 2 Fan 3)WRead
AV20406244_1_2_3Condenser Fan Current (Condenser 2 Fan 3)ARead
AV20255276_1_2_4Condenser Fan Speed (Condenser 2 Fan 4)%Read
AV20335538_1_2_4Condenser Fan Power (Condenser 2 Fan 4)WRead
AV20416244_1_2_4Condenser Fan Current (Condenser 2 Fan 4)ARead
AV23715276_1_3_1Condenser Fan Speed (Condenser 3 Fan 1)%Read
AV23725538_1_3_1Condenser Fan Power (Condenser 3 Fan 1)WRead
AV23736244_1_3_1Condenser Fan Current (Condenser 3 Fan 1)ARead
AV23845276_1_3_2Condenser Fan Speed (Condenser 3 Fan 2)%Read
AV23855538_1_3_2Condenser Fan Power (Condenser 3 Fan 2)WRead
AV23866244_1_3_2Condenser Fan Current (Condenser 3 Fan 2)ARead
AV23975276_1_3_3Condenser Fan Speed (Condenser 3 Fan 3)%Read
AV23985538_1_3_3Condenser Fan Power (Condenser 3 Fan 3)WRead
AV23996244_1_3_3Condenser Fan Current (Condenser 3 Fan 3)ARead
AV24105276_1_3_4Condenser Fan Speed (Condenser 3 Fan 4)%Read
AV24115538_1_3_4Condenser Fan Power (Condenser 3 Fan 4)WRead
AV24126244_1_3_4Condenser Fan Current (Condenser 3 Fan 4)ARead
AV24235276_1_4_1Condenser Fan Speed (Condenser 4 Fan 1)%Read
AV24245538_1_4_1Condenser Fan Power (Condenser 4 Fan 1)WRead
AV24256244_1_4_1Condenser Fan Current (Condenser 4 Fan 1)ARead
AV24365276_1_4_2Condenser Fan Speed (Condenser 4 Fan 2)%Read
AV24375538_1_4_2Condenser Fan Power (Condenser 4 Fan 2)WRead
AV24386244_1_4_2Condenser Fan Current (Condenser 4 Fan 2)ARead
AV24495276_1_4_3Condenser Fan Speed (Condenser 4 Fan 3)%Read
AV24505538_1_4_3Condenser Fan Power (Condenser 4 Fan 3)WRead
AV24516244_1_4_3Condenser Fan Current (Condenser 4 Fan 3)ARead
AV24625276_1_4_4Condenser Fan Speed (Condenser 4 Fan 4)%Read
AV24635538_1_4_4Condenser Fan Power (Condenser 4 Fan 4)WRead
AV24646244_1_4_4Condenser Fan Current (Condenser 4 Fan 4)ARead
AV20446085_1Actual Cold Aisle Humidity%RHRead
AV20456086_1Actual Cold Aisle Temperature°CRead
AV120456086_1_deg_FActual Cold Aisle Temperature°FRead
AV20466087_1Cold Aisle Cascade Fan Speed Max Set Point%Read
AV20476088_1Cold Aisle Fan Speed Min Set Point%Read
AV20486089_1Cold Aisle Fan Speed Max Set Point%Read
AV20496096_1Humidification Fan Speed Min Set Point%Read
AV20506097_1Heating Fan Speed Min Set Point%Read
AV20516098_1Dehumidification Fan Speed Min Set Point%Read
AV20526099_1Back Draft Control Fan Speed%Read
AV20536302_1Air Filter Differential Pressure (PCW-PDX)PaRead
AV22136302_1Air Filter Differential Pressure (PCW-PDX)PaRead
AV21476307_1_1Cold Aisle Sensor Air Temperature (Cold Aisle Sensor 1)°CRead
AV121476307_1_1_deg_FCold Aisle Sensor Air Temperature (Cold Aisle Sensor 1)°FRead
AV21486308_1_1Cold Aisle Sensor Humidity (Cold Aisle Sensor 1)%RHRead
AV21596307_1_2Cold Aisle Sensor Air Temperature (Cold Aisle Sensor 2)°CRead
AV121596307_1_2_deg_FCold Aisle Sensor Air Temperature (Cold Aisle Sensor 2)°FRead
AV21606308_1_2Cold Aisle Sensor Humidity (Cold Aisle Sensor 2)%RHRead
AV21716307_1_3Cold Aisle Sensor Air Temperature (Cold Aisle Sensor 3)°CRead
AV121716307_1_3_deg_FCold Aisle Sensor Air Temperature (Cold Aisle Sensor 3)°FRead
AV21726308_1_3Cold Aisle Sensor Humidity (Cold Aisle Sensor 3)%RHRead
AV24886825_1_1Cooling Fluid Source Temperature (Fluid Source 1)°CRead
AV124886825_1_1_deg_FCooling Fluid Source Temperature (Fluid Source 1)°FRead
AV24896825_1_2Cooling Fluid Source Temperature (Fluid Source 2)°CRead
AV124896825_1_2_deg_FCooling Fluid Source Temperature (Fluid Source 2)°FRead
AV21006234_1Super Saver Call For Cooling%Read
AV21356263_1Thermal Control Override - Temperature Call%Write
AV21366265_1Thermal Control Override - Humidity Call%Write
AV21896311_1_1Chilled Water Inlet Temperature (Chilled Water Circuit 1)°CRead
AV121896311_1_1_deg_FChilled Water Inlet Temperature (Chilled Water Circuit 1)°FRead
AV21906312_1_1Chilled Water Outlet Temperature (Chilled Water Circuit 1)°CRead
AV121906312_1_1_deg_FChilled Water Outlet Temperature (Chilled Water Circuit 1)°FRead
AV22016311_1_2Chilled Water Inlet Temperature (Chilled Water Circuit 2)°CRead
AV122016311_1_2_deg_FChilled Water Inlet Temperature (Chilled Water Circuit 2)°FRead
AV22026312_1_2Chilled Water Outlet Temperature (Chilled Water Circuit 2)°CRead
AV122026312_1_2_deg_FChilled Water Outlet Temperature (Chilled Water Circuit 2)°FRead
AV24766797_1EconoPhase Proportional Band Switchover%Write
AV25016820_1Event Log Record CounterRead
AV25026821_1Audit Log Record CounterRead
AV25266780_1_1Unit Cascade On DelayminWrite
AV25276781_1_1Quick Start Unit Cascade On DelaysWrite
AV25286779_1_1Unit Cascade Control DelayminWrite
AV25296783_1_1Teamwork Average Calculation Unit CountWrite
AV25415314_1_1Standby Units (Standby/Rotation)Write
AV25426122_1_1Networked Unit Rotation TimeSeconds since MidnightWrite
AV25436123_1_1Networked Unit Rotation CountWrite
AV25547130_1_1Power Source: L1- L2 voltage (Power Source 1)VRead
AV25557131_1_1Power Source: L2- L3 voltage (Power Source 1)VRead
AV25567132_1_1Power Source: L3- L1 voltage (Power Source 1)VRead
AV25577133_1_1Power Source: Line Frequency (Power Source 1)HzRead
AV25587134_1_1Power Source: Breaker Operation Count (Power Source 1)Read
AV25697130_1_2Power Source: L1- L2 voltage (Power Source 2)VRead
AV25707131_1_2Power Source: L2- L3 voltage (Power Source 2)VRead
AV25717132_1_2Power Source: L3- L1 voltage (Power Source 2)VRead
AV25727133_1_2Power Source: Line Frequency (Power Source 2)HzRead
AV25737134_1_2Power Source: Breaker Operation Count (Power Source 2)Read
AVmin25844643_1Supply Fluid Temperature°CRead
AV125844643_1_deg_FSupply Fluid Temperature°FRead
AV25855288_1Return Fluid Temperature°CRead
AV125855288_1_deg_FReturn Fluid Temperature°FRead
AV25867468_1Flow Ratel/minRead
AV25875491_1Cooling CapacitykWRead
AV25887469_1Pump Speed (Fluid Loop)%Read
AV25897470_1Flow Set Pointl/minWrite
AV25907471_1Flow Proportional Bandl/minWrite
AV25917472_1Flow Dead Bandl/minWrite
AV25927473_1Flow Integration TimesWrite
AV25934644_1Supply Fluid Over Temp Threshold°CWrite
AV125934644_1_deg_FSupply Fluid Over Temp Threshold°FWrite
AV25945289_1Return Fluid Over Temp Threshold°CWrite
AV125945289_1_deg_FReturn Fluid Over Temp Threshold°FWrite
AV26057480_1_1Pump Speed (Fluid Pump 1)%Read
AV26067481_1_1Pump Expected Speed (Fluid Pump 1)%Read
AV26077482_1_1Pump Run Time (Fluid Pump 1)hRead
AV26187480_1_2Pump Speed (Fluid Pump 2)%Read
AV26197481_1_2Pump Expected Speed (Fluid Pump 2)%Read
AV26207482_1_2Pump Run Time (Fluid Pump 2)hRead
AV29048167_1_1Pump Motor Power (Fluid Pump Status 1)kWRead
AV29058168_1_1Pump Motor Amps (Fluid Pump Status 1)ARead
AV29068169_1_1Inverter Temperature (Fluid Pump Status 1)°CRead
AV129068169_1_1_deg_FInverter Temperature (Fluid Pump Status 1)°FRead
AV29178167_1_2Pump Motor Power (Fluid Pump Status 2)kWRead
AV29188168_1_2Pump Motor Amps (Fluid Pump Status 2)ARead
AV29198169_1_2Inverter Temperature (Fluid Pump Status 2)°CRead
AV129198169_1_2_deg_FInverter Temperature (Fluid Pump Status 2)°FRead
AV28238132_1Unit Fluid Supply Temperature°CRead
AV128238132_1_deg_FUnit Fluid Supply Temperature°FRead
AV28248133_1Unit Fluid Return Temperature°CRead
AV128248133_1_deg_FUnit Fluid Return Temperature°FRead
AV28258134_1Unit Fluid Supply PressurebarRead
AV28268135_1Unit Fluid Return PressurebarRead
AV28278136_1Unit Fluid Pump Speed%Read
AV28288137_1Unit Fluid Flowl/minRead
AV28298138_1Unit Fluid Diff PressurebarRead
AV28308139_1Unit Fluid Cooling CapacitykWRead
AV28318140_1System Fluid Flowl/minRead
AV28328141_1System Fluid Diff PressurebarRead
AV28338142_1System Fluid Cooling CapacitykWRead
AV28448143_1_1Fluid Temperature Set Point°CWrite
AV128448143_1_1_deg_FFluid Temperature Set Point°FWrite
AV28458145_1_1Fluid Temperature Proportional Band°CWrite
AV128458145_1_1_deg_FFluid Temperature Proportional Band°FWrite
AV28468146_1_1Fluid Temperature Dead Band°CWrite
AV128468146_1_1_deg_FFluid Temperature Dead Band°FWrite
AV28478147_1_1Fluid Temperature Control Integration TimeminWrite
AV28588149_1_1Fluid Flow Set Pointl/minWrite
AV28598150_1_1Fluid Flow Proportional Bandl/minWrite
AV28608151_1_1Fluid Flow Dead Bandl/minWrite
AV28618152_1_1Fluid Flow Control Integration TimesWrite
AV28628153_1_1Fluid Diff Prs Set PointbarWrite
AV28638154_1_1Fluid Diff Prs Prop BandbarWrite
AV28648155_1_1Flow Diff Prs Dead BandbarWrite
AV28658156_1_1Fluid Diff Prs Control Integration TimesWrite
AV28668157_1_1Flow Manual Pump Speed%Write
AV28678158_1_1Pump Operation PerioddayWrite
AV28688159_1_1Pump Operation DurationminWrite
AV28698160_1_1Pump Operation Speed%Write
AV28808163_1_1Dew Point Max Adjust°CWrite
AV128808163_1_1_deg_FDew Point Max Adjust°FWrite
AV28818164_1_1System Dew Point°CRead
AV128818164_1_1_deg_FSystem Dew Point°FRead
AV28828165_1_1Unit Dew Point°CRead
AV128828165_1_1_deg_FUnit Dew Point°FRead
AV28938230_1_1PHE Fluid Supply Temperature°CRead
AV128938230_1_1_deg_FPHE Fluid Supply Temperature°FRead
MV14553_1Server ClassRead1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR
MV125324_1Air Temperature Control TypeWrite1=Proportional, 2=Prop+Integral, 3=Adaptive PID, 4=Intelligent
MV135012_1Air Temperature Control SensorWrite1=Supply, 2=Remote, 3=Return
MV235332_1_1Supply Air Temperature Sensor ControlWrite1=Disabled, 2=Limit, 3=Control, 4=Temp Only
MV345340_1Humidity Control TypeWrite1=Relative, 2=Compensated, 3=Predictive
MV355603_1Humidity Control TypeWrite1=Relative, 2=Compensated, 3=Predictive, 4=Dew Point
MV365618_1Humidity Control SensorWrite1=Supply, 2=Remote, 3=Return
MV455264_1_1Compressor State (Compressor 1)Read1=off, 2=on
MV465265_1_1Compressor Capacity Control State (Compressor 1)Read1=off, 2=on
MV476243_1_1Tandem 'B' Compressor State (Compressor 1)Read1=off, 2=on
MV575264_1_2Compressor State (Compressor 2)Read1=off, 2=on
MV585265_1_2Compressor Capacity Control State (Compressor 2)Read1=off, 2=on
MV596243_1_2Tandem 'B' Compressor State (Compressor 2)Read1=off, 2=on
MV5435264_1_3Compressor State (Compressor 3)Read1=off, 2=on n
MV5445265_1_3Compressor Capacity Control State (Compressor 3)Read1=off, 2=on
MV5456243_1_3Tandem 'B' Compressor State (Compressor 3)Read1=off, 2=on
MV5565264_1_4Compressor State (Compressor 4)Read1=off, 2=on
MV5575265_1_4Compressor Capacity Control State (Compressor 4)Read1=off, 2=on
MV5586243_1_4Tandem 'B' Compressor State (Compressor 4)Read1=off, 2=on
MV695302_1Free Cooling StatusRead1=off, 2=on, 3=No Support
MV705581_1Free Cooling Internal Control ModeWrite1=Disabled, 2=Contact, 3=Temperature, 4=Set Point
MV715359_1Minimum Chilled Water Temp Set Point EnableWrite1=disabled, 2=enabled
MV725605_1Main Chilled Water ValveWrite1=Valve 1, 2=Valve 2
MV825373_1Fan Control ModeWrite1=Auto, 2=Manual, 3=Economy, 4=Delta
MV835586_1Fan Control SensorWrite1=Supply, 2=Remote, 3=Return, 4=Manual
MV846736_1Fan Back Draft OperationWrite1=Disabled, 2=Standby, 3=Outdoor Temp
MV856771_1Fan Back Draft Control EnableWrite1=disabled, 2=enabled
MV866767_1Fan Speed Temp Control TypeWrite1=Proportional, 2=Prop+Integral, 3=Adaptive PID
MVmin934123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MVmin944706_1Unit Operating StateRead1=off, 2=on, 3=standby
MV954707_1Unit Control ModeRead1=Internal (Auto), 2=External (Manual)
MV965074_1Unit Off ReasonRead1=None, 2=User, 3=Alarm, 4=Timer, 5=Monitoring, 6=Remote Off, 7=HCS12 Off
MV1075381_1Fan StateRead1=off, 2=on
MV1085382_1Cooling StateRead1=off, 2=on
MV1095383_1Free Cooling StateRead1=off, 2=on
MV1105384_1Maintenance Tracking StateRead1=off, 2=on
MV1115385_1Hot Water / Hot Gas StateRead1=off, 2=on
MV1125386_1Electric Reheat StateRead1=off, 2=on
MV1135387_1Dehumidifier StateRead1=off, 2=on
MV1145388_1Humidifier StateRead1=off, 2=on
MVmin1155143_1System On/Off ControlWrite1=off, 2=on
MV5006175_1Local Fan OverrideRead1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection
MV5016176_1Local Cooling OverrideRead1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection
MV5026177_1Local Electric Heat OverrideRead1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection, 1=Normal operation
MV5036178_1Local Humidifier OverrideRead2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection
MV5046179_1Local Dehumidifier OverrideRead1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection
MV5056553_1Master Cooling Fluid SourceWrite1=Supply 1, 2=Supply 2
MV5066524_1Automatic Transfer Switch - Active Power SupplyRead1=Power Supply 1, 2=Power Supply 2
MV5076525_1Automatic Transfer Switch - Power Supply 1 StatusRead1=OK, 2=Not OK
MV5086526_1Automatic Transfer Switch - Power Supply 2 StatusRead1=OK, 2=Not OK
MV1264718_1Customer Input 1 - Event ControlWrite1=disabled, 2=enabled
MV1274719_1Customer Input 1 - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1285098_1Customer Input 2 - Event ControlWrite1=disabled, 2=enabled
MV1295099_1Customer Input 2 - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1305100_1Customer Input 3 - Event ControlWrite1=disabled, 2=enabled
MV1315101_1Customer Input 3 - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1325102_1Customer Input 4 - Event ControlWrite1=disabled, 2=enabled
MV1335103_1Customer Input 4 - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1345389_1Ext Free Cooling Lockout - Event ControlWrite1=disabled, 2=enabled
MV1355390_1Ext Free Cooling Lockout - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1365122_1Ext Condenser Pump High Water - Event ControlWrite1=disabled, 2=enabled
MV1375123_1Ext Condenser Pump High Water - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1385129_1Ext Standby Glycol Pump On - Event ControlWrite1=disabled, 2=enabled
MV1395130_1Ext Standby Glycol Pump On - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1405391_1Ext Standby Unit On - Event ControlWrite1=disabled, 2=enabled
MV1415392_1Ext Standby Unit On - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1425086_1Ext Humidifier Lockout - Event ControlWrite1=disabled, 2=enabled
MV1435087_1Ext Humidifier Lockout - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1445082_1Ext Loss of Flow - Event ControlWrite1=disabled, 2=enabled
MV1455083_1Ext Loss of Flow - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1465090_1Ext Over Temperature - Event ControlWrite1=disabled, 2=enabled
MV1475091_1Ext Over Temperature - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1485084_1Ext Reheat Lockout - Event ControlWrite1=disabled, 2=enabled
MV1495085_1Ext Reheat Lockout - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1505141_1High Power Shutdown - Event ControlWrite1=disabled, 2=enabled
MV1515142_1High Power Shutdown - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1525131_1Humidifier Issue - Event ControlWrite1=disabled, 2=enabled
MV1535132_1Humidifier Issue - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1545133_1Master Unit Communication Lost - Event ControlWrite1=disabled, 2=enabled
MV1555134_1Master Unit Communication Lost - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1564727_1Service Required - Event ControlWrite1=disabled, 2=enabled
MV1574728_1Service Required - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1584715_1Shutdown - Loss Of Power - Event ControlWrite1=disabled, 2=enabled
MV1594716_1Shutdown - Loss Of Power - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1604721_1Smoke Detected - Event ControlWrite1=disabled, 2=enabled
MV1614722_1Smoke Detected - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1624724_1Water Under Floor - Event ControlWrite1=disabled, 2=enabled
MV1634725_1Water Under Floor - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1645088_1Ext Compressor Lockout - Event ControlWrite1=disabled, 2=enabled
MV1655089_1Ext Compressor Lockout - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1665135_1Clogged Air Filter - Event ControlWrite1=disabled, 2=enabled
MV1675136_1Clogged Air Filter - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1685393_1Ext Loss of Air Blower - Event ControlWrite1=disabled, 2=enabled
MV1695394_1Ext Loss of Air Blower - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV1805316_1_1Compressor High Head Pressure - Event Control (Compressor 1)Write1=disabled, 2=enabled
MV1815317_1_1Compressor High Head Pressure - Event Type (Compressor 1)Write1=Message, 2=Warning, 3=Alarm
MV1825318_1_1Compressor Low Suction Pressure - Event Control (Compressor 1)Write1=disabled, 2=enabled
MV1835319_1_1Compressor Low Suction Pressure - Event Type (Compressor 1)Write1=Message, 2=Warning, 3=Alarm
MV1845395_1_1Compressor Pump Down Issue - Event Control (Compressor 1)Write1=disabled, 2=enabled
MV1855396_1_1Compressor Pump Down Issue - Event Type (Compressor 1)Write1=Message, 2=Warning, 3=Alarm
MV1865397_1_1Compressor Short Cycle - Event Control (Compressor 1)Write1=disabled, 2=enabled
MV1875398_1_1Compressor Short Cycle - Event Type (Compressor 1)Write1=Message, 2=Warning, 3=Alarm
MV1885320_1_1Compressor Thermal Overload - Event Control (Compressor 1)Write1=disabled, 2=enabled
MV1895321_1_1Compressor Thermal Overload - Event Type (Compressor 1)Write1=Message, 2=Warning, 3=Alarm
MV1905399_1_1Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor 1)Write1=disabled, 2=enabled
MV1915400_1_1Dig Scroll Comp Discharge Over Temp - Event Type (Compressor 1)Write1=Message, 2=Warning, 3=Alarm
MV2025316_1_2Compressor High Head Pressure - Event Control (Compressor 2)Write1=disabled, 2=enabled
MV2035317_1_2Compressor High Head Pressure - Event Type (Compressor 2)Write1=Message, 2=Warning, 3=Alarm
MV2045318_1_2Compressor Low Suction Pressure - Event Control (Compressor 2)Write1=disabled, 2=enabled
MV2055319_1_2Compressor Low Suction Pressure - Event Type (Compressor 2)Write1=Message, 2=Warning, 3=Alarm
MV2065395_1_2Compressor Pump Down Issue - Event Control (Compressor 2)Write1=disabled, 2=enabled
MV2075396_1_2Compressor Pump Down Issue - Event Type (Compressor 2)Write1=Message, 2=Warning, 3=Alarm
MV2085397_1_2Compressor Short Cycle - Event Control (Compressor 2)Write1=disabled, 2=enabled
MV2095398_1_2Compressor Short Cycle - Event Type (Compressor 2)Write1=Message, 2=Warning, 3=Alarm
MV2105320_1_2Compressor Thermal Overload - Event Control (Compressor 2)Write1=disabled, 2=enabled
MV2115321_1_2Compressor Thermal Overload - Event Type (Compressor 2)Write1=Message, 2=Warning, 3=Alarm
MV2125399_1_2Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor 2)Write1=disabled, 2=enabled
MV2135400_1_2Dig Scroll Comp Discharge Over Temp - Event Type (Compressor 2)Write1=Message, 2=Warning, 3=Alarm
MV2245401_1_1Ext Air Sensor A Event ControlWrite1=disabled, 2=enabled
MV2255402_1_1Return Air Sensor Event ControlWrite1=disabled, 2=enabled
MV2265403_1_1Ext Air Sensor A High Humidity - Event ControlWrite1=disabled, 2=enabled
MV2275404_1_1Ext Air Sensor A High Humidity - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2285405_1_1Ext Air Sensor A Low Humidity - Event ControlWrite1=disabled, 2=enabled
MV2295406_1_1Ext Air Sensor A Low Humidity - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2304602_1_1Ext Air Sensor A Over Temp - Event ControlWrite1=disabled, 2=enabled
MV2314603_1_1Ext Air Sensor A Over Temp - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2324609_1_1Ext Air Sensor A Under Temp - Event ControlWrite1=disabled, 2=enabled
MV2334610_1_1Ext Air Sensor A Under Temp - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2345137_1_1High Return Humidity - Event ControlWrite1=disabled, 2=enabled
MV2355138_1_1High Return Humidity - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2365139_1_1Low Return Humidity - Event ControlWrite1=disabled, 2=enabled
MV2375140_1_1Low Return Humidity - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2385024_1_1Return Air Over Temp - Event ControlWrite1=disabled, 2=enabled
MV2395025_1_1Return Air Over Temp - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2405407_1_1Return Air Under Temp - Event ControlWrite1=disabled, 2=enabled
MV2415408_1_1Return Air Under Temp - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2425587_1_1Supply Air Over/Under Temperature - Event ControlWrite1=disabled, 2=enabled
MV2525409_1_1Fan Hours Exceeded - Event ControlWrite1=disabled, 2=enabled
MV2535410_1_1Fan Hours Exceeded - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2544730_1_1Fan Issue - Event ControlWrite1=disabled, 2=enabled
MV2554731_1_1Fan Issue - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2565411_1_1Main Fan Overload - Event ControlWrite1=disabled, 2=enabled
MV2575412_1_1Main Fan Overload - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2685413_1_1Condenser Issue - Event ControlWrite1=disabled, 2=enabled
MV2695414_1_1Condenser Issue - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MV2805413_1_2Condenser Issue - Event ControlWrite1=disabled, 2=enabled
MV2815414_1_2Condenser Issue - Event TypeWrite1=Message, 2=Warning, 3=Alarm
MVmin2924717_1System Event Acknowledge/ResetWrite1=Reset, 2=Acknowledge
MV3045580_1Compressor LockoutWrite1=disabled, 2=enabled
MV3165582_1Reheater LockoutWrite1=disabled, 2=enabled
MV3176760_1Dehum Reheat Low Limit SensorWrite1=Supply, 2=Remote, 3=Return
MV3285583_1Humidifier LockoutWrite1=disabled, 2=enabled
MV3405599_1Air Economizer AvailabilityRead1=Not Available, 2=Available
MV3415602_1Air Economizer Control SourceWrite1=disabled, 2=internal, 3=external
MV3635632_1_1PRE Operational Mode (Pump 1)Read1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test
MV3645633_1_1Pump State (Pump 1)Read1=off, 2=on
MV3685632_1_2PRE Operational Mode (Pump 2)Read1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test
MV3695633_1_2Pump State (Pump 2)Read1=off, 2=on
MV5775633_1_3Pump State (Pump 3)Read1=off, 2=on
MV5785632_1_3PRE Operational Mode (Pump 3)Read1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test
MV5895633_1_4Pump State (Pump 4)Read1=off, 2=on
MV5905632_1_4PRE Operational Mode (Pump 4)Read1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test
MV3955533_1Condenser Refrigerant TypeRead1=R22, 2=R407C, 3=R410A
MV3745546_1_1Condenser Low Noise Mode StateRead1=Inactive, 2=Active (Interval), 3=Active (Full Day)
MV3755547_1_1Condenser Low Noise Mode Schedule ControlWrite1=disabled, 2=enabled
MV4066104_1_1Condenser Fan Reversal Requested (Condenser 1)Write1=false, 2=true
MV4076104_1_2Condenser Fan Reversal Requested (Condenser 2)Write1=false, 2=true
MV6126104_1_3Condenser Fan Reversal Requested (Condenser 3)Write1=false, 2=true
MV6236104_1_4Condenser Fan Reversal Requested (Condenser 4)Write1=false, 2=true
MV4386081_1Cold Aisle Humidity Calculation MethodRead1=Highest, 2=Average
MV4396082_1Cold Aisle Temperature Calculation MethodRead1=Highest, 2=Average
MV4406083_1Cold Aisle Control EnableRead1=disabled, 2=enabled
MV4416084_1Cold Aisle Force Max Fan/Cooling - Ext ControlRead1=disabled, 2=enabled
MV4426090_1Static Pressure Control EnableRead1=disabled, 2=enabled
MV4436091_1Chilled Water Valve Reset EnableRead1=disabled, 2=enabled
MV5296300_1Underfloor Static Pressure Control EnableRead1=disabled, 2=enabled, 3=visualization only
MV5316301_1Return Damper StatusRead1=closed, 2=open
MV5166261_1Thermal Control OverrideWrite1=disabled, 2=enabled
MV5176262_1Thermal Control Override - Temperature Control TypeWrite1=Cooling, 2=Heating
MV5186264_1Thermal Control Override - Humidity Control TypeWrite1=Dehumidification, 2=Humidification
MV6356695_1_1Group Independent Operation EnableWrite1=disabled, 2=enabled
MV6366690_1_1Group Independent OperationWrite1=No override (default), 2=Override, forced on, 3=Override, forced off
MV6486775_1Auto Restart EnableWrite1=disabled, 2=enabled
MV6496777_1Virtual Master EnableWrite1=disabled, 2=enabled
MV6616784_1_1Teamwork ModeWrite1=No Teamwork Mode, 2=Mode 1 (parallel), 3=Mode 2 (independent), 4=Mode 3 (optimized aisle)
MV6626778_1_1Unit Cascade TypeWrite1=None, 2=Temp/Humidity, 3=Cool/Heat, 4=Cooling, 5=Fan PI, 6=Fan Speed
MV6636782_1_1Teamwork Temperature Calculation MethodWrite1=Average, 2=Maximum
MV6756130_1_1Networked Unit Daily Rotation FrequencyWrite1=Every 24 hours, 2=Every 12 hours
MV6766131_1_1Force Networked Unit RotationWrite1=no, 2=yes
MV6776129_1_1Networked Unit Rotation FrequencyWrite1=None, 2=Daily, 3=Weekly Monday, 4=Weekly Tuesday, 5=Weekly Wednesday, 6=Weekly Thursday, 7=Weekly Friday, 8=Weekly Saturday, 9=Weekly Sunday, 10=Monthly Monday, 11=Monthly Tuesday, 12=Monthly Wednesday, 13=Monthly Thursday, 14=Monthly Friday, 15=Monthly Saturday, 16=Monthly Sunday
MV6786823_1_1Start Standby Units on High TemperatureWrite1=false, 2=true
MV6897564_1Static Pressure Fan ControlWrite1=disabled, 2=Limit, 3=Control, 4=BMS Backup SP Ctrl
MV7007127_1ATS Switch ModeRead1=Off, 2=Manual, 3=Automatic, 4=Test
MV7017128_1ATS Load Not Powered TimeoutRead1=false, 2=true
MV7027129_1ATS Non Priority Load Breaker TimeoutRead1=false, 2=true
MV7137135_1_1Power Source: All status are okay (Power Source 1)Read1=false, 2=true
MV7147136_1_1Power Source: Voltage Is Too Low (Power Source 1)Read1=false, 2=true
MV7157137_1_1Power Source: Voltage Is Too High (Power Source 1)Read1=false, 2=true
MV7167138_1_1Power Source: Voltages Are Asymmetric (Power Source 1)Read1=false, 2=true
MV7177139_1_1Power Source: Voltage Phase Loss (Power Source 1)Read1=false, 2=true
MV7187140_1_1Power Source: Phase Sequence Issue (Power Source 1)Read1=false, 2=true
MV7197141_1_1Power Source: Frequency Is Too Low (Power Source 1)Read1=false, 2=true
MV7207142_1_1Power Source: Frequency Is Too High (Power Source 1)Read1=false, 2=true
MV7217143_1_1Power Source: Breaker is closed (Power Source 1)Read1=false, 2=true
MV7227144_1_1Power Source: Breaker command status closed (Power Source 1)Read1=false, 2=true
MV7237145_1_1Power Source: Breaker withdrawn issue (Power Source 1)Read1=false, 2=true
MV7247146_1_1Power Source: Breaker Timeout Issue (Power Source 1)Read1=false, 2=true
MV7257147_1_1Power Source: Line Operating Hour Exceeded (Power Source 1)Read1=false, 2=true
MV7267148_1_1Power Source: Breaker Operating Hour Exceeded (Power Source 1)Read1=false, 2=true
MV7377135_1_2Power Source: All status are okay (Power Source 2)Read1=false, 2=true
MV7387136_1_2Power Source: Voltage Is Too Low (Power Source 2)Read1=false, 2=true
MV7397137_1_2Power Source: Voltage Is Too High (Power Source 2)Read1=false, 2=true
MV7407138_1_2Power Source: Voltages Are Asymmetric (Power Source 2)Read1=false, 2=true
MV7417139_1_2Power Source: Voltage Phase Loss (Power Source 2)Read1=false, 2=true
MV7427140_1_2Power Source: Phase Sequence Issue (Power Source 2)Read1=false, 2=true
MV7437141_1_2Power Source: Frequency Is Too Low (Power Source 2)Read1=false, 2=true
MV7447142_1_2Power Source: Frequency Is Too High (Power Source 2)Read1=false, 2=true
MV7457143_1_2Power Source: Breaker is closed (Power Source 2)Read1=false, 2=true
MV7467144_1_2Power Source: Breaker command status closed (Power Source 2)Read1=false, 2=true
MV7477145_1_2Power Source: Breaker withdrawn issue (Power Source 2)Read1=false, 2=true
MV7487146_1_2Power Source: Breaker Timeout Issue (Power Source 2)Read1=false, 2=true
MV7497147_1_2Power Source: Line Operating Hour Exceeded (Power Source 2)Read1=false, 2=true
MV7507148_1_2Power Source: Breaker Operating Hour Exceeded (Power Source 2)Read1=false, 2=true
MV7617477_1Force Pump RotateWrite1=Rotate
MV7627478_1Reset Pump Speed CalibrationWrite1=Reset
MV7737479_1_1Pump Operating State (Fluid Pump 1)Read1=off, 2=on
MV7847479_1_2Pump Operating State (Fluid Pump 2)Read1=off, 2=on
MV11758171_1_1Pump Drive Overload (Fluid Pump Status 1)Read1=no, 2=yes
MV11768172_1_1Pump Drive Over Temperature (Fluid Pump Status 1)Read1=no, 2=yes
MV11778173_1_1Pump Drive Warning (Fluid Pump Status 1)Read1=no, 2=yes
MV11788174_1_1Pump Drive Low AC Alarm (Fluid Pump Status 1)Read1=no, 2=yes
MV11798175_1_1Pump Drive Phase Loss Active (Fluid Pump Status 1)Read1=no, 2=yes
MV11808176_1_1Pump Drive Product Identification (Fluid Pump Status 1)Read1=OK, 2=Not OK
MV11818177_1_1Pump Drive Communications (Fluid Pump Status 1)Read1=OK, 2=Not OK
MV11928171_1_2Pump Drive Overload (Fluid Pump Status 2)Read1=no, 2=yes
MV11938172_1_2Pump Drive Over Temperature (Fluid Pump Status 2)Read1=no, 2=yes
MV11948173_1_2Pump Drive Warning (Fluid Pump Status 2)Read1=no, 2=yes
MV11958174_1_2Pump Drive Low AC Alarm (Fluid Pump Status 2)Read1=no, 2=yes
MV11968175_1_2Pump Drive Phase Loss Active (Fluid Pump Status 2)Read1=no, 2=yes
MV11978176_1_2Pump Drive Product Identification (Fluid Pump Status 2)Read1=OK, 2=Not OK
MV11988177_1_2Pump Drive Communications (Fluid Pump Status 2)Read1=OK, 2=Not OK
MV7958101_1_1Communicate At Fan Power OffWrite1=disabled, 2=enabled
MV7968102_1_1Supply Fan Emergency OpWrite1=disabled, 2=enabled
MV8078106_1_1Fan Error: Phase Failure (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8088107_1_1Fan Error: Pwr Mod Overheated (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8098108_1_1Fan Error: Internal Comms Error (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8108109_1_1Fan Error: General Failure (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8118110_1_1Fan Error: Motor Overheated (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8128111_1_1Fan Error: Hall Sensor Error (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8138112_1_1Fan Error: Locked Motor (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8148113_1_1Fan Warning: High Supply Voltage (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8158114_1_1Fan Warning: DC-link voltage high (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8168115_1_1Fan Warning: High Interior Temperature (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8178116_1_1Fan Warning: High Motor Temperature (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8188117_1_1Fan Error: DC-link undervoltage (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8198118_1_1Fan Warning: Identification (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8208193_1_1Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 1)Read1=OK, 2=Not OK
MV8308106_1_2Fan Error: Phase Failure (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8318107_1_2Fan Error: Pwr Mod Overheated (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8328108_1_2Fan Error: Internal Comms Error (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8338109_1_2Fan Error: General Failure (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8348110_1_2Fan Error: Motor Overheated (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8358111_1_2Fan Error: Hall Sensor Error (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8368112_1_2Fan Error: Locked Motor (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8378113_1_2Fan Warning: High Supply Voltage (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8388114_1_2Fan Warning: DC-link voltage high (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8398115_1_2Fan Warning: High Interior Temperature (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8408116_1_2Fan Warning: High Motor Temperature (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8418117_1_2Fan Error: DC-link undervoltage (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8428118_1_2Fan Warning: Identification (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8438193_1_2Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 2)Read1=OK, 2=Not OK
MV8538106_1_3Fan Error: Phase Failure (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8548107_1_3Fan Error: Pwr Mod Overheated (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8558108_1_3Fan Error: Internal Comms Error (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8568109_1_3Fan Error: General Failure (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8578110_1_3Fan Error: Motor Overheated (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8588111_1_3Fan Error: Hall Sensor Error (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8598112_1_3Fan Error: Locked Motor (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8608113_1_3Fan Warning: High Supply Voltage (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8618114_1_3Fan Warning: DC-link voltage high (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8628115_1_3Fan Warning: High Interior Temperature (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8638116_1_3Fan Warning: High Motor Temperature (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8648117_1_3Fan Error: DC-link undervoltage (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8658118_1_3Fan Warning: Identification (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8668193_1_3Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 3)Read1=OK, 2=Not OK
MV8768106_1_4Fan Error: Phase Failure (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8778107_1_4Fan Error: Pwr Mod Overheated (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8788108_1_4Fan Error: Internal Comms Error (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8798109_1_4Fan Error: General Failure (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8808110_1_4Fan Error: Motor Overheated (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8818111_1_4Fan Error: Hall Sensor Error (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8828112_1_4Fan Error: Locked Motor (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8838113_1_4Fan Warning: High Supply Voltage (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8848114_1_4Fan Warning: DC-link voltage high (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8858115_1_4Fan Warning: High Interior Temperature (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8868116_1_4Fan Warning: High Motor Temperature (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8878117_1_4Fan Error: DC-link undervoltage (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8888118_1_4Fan Warning: Identification (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8898193_1_4Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 4)Read1=OK, 2=Not OK
MV8998106_1_5Fan Error: Phase Failure (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9008107_1_5Fan Error: Pwr Mod Overheated (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9018108_1_5Fan Error: Internal Comms Error (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9028109_1_5Fan Error: General Failure (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9038110_1_5Fan Error: Motor Overheated (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9048111_1_5Fan Error: Hall Sensor Error (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9058112_1_5Fan Error: Locked Motor (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9068113_1_5Fan Warning: High Supply Voltage (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9078114_1_5Fan Warning: DC-link voltage high (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9088115_1_5Fan Warning: High Interior Temperature (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9098116_1_5Fan Warning: High Motor Temperature (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9108117_1_5Fan Error: DC-link undervoltage (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9118118_1_5Fan Warning: Identification (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9128193_1_5Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 5)Read1=OK, 2=Not OK
MV9228106_1_6Fan Error: Phase Failure (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9238107_1_6Fan Error: Pwr Mod Overheated (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9248108_1_6Fan Error: Internal Comms Error (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9258109_1_6Fan Error: General Failure (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9268110_1_6Fan Error: Motor Overheated (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9278111_1_6Fan Error: Hall Sensor Error (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9288112_1_6Fan Error: Locked Motor (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9298113_1_6Fan Warning: High Supply Voltage (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9308114_1_6Fan Warning: DC-link voltage high (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9318115_1_6Fan Warning: High Interior Temperature (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9328116_1_6Fan Warning: High Motor Temperature (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9338117_1_6Fan Error: DC-link undervoltage (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9348118_1_6Fan Warning: Identification (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9358193_1_6Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 6)Read1=OK, 2=Not OK
MV9458106_1_7Fan Error: Phase Failure (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9468107_1_7Fan Error: Pwr Mod Overheated (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9478108_1_7Fan Error: Internal Comms Error (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9488109_1_7Fan Error: General Failure (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9498110_1_7Fan Error: Motor Overheated (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9508111_1_7Fan Error: Hall Sensor Error (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9518112_1_7Fan Error: Locked Motor (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9528113_1_7Fan Warning: High Supply Voltage (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9538114_1_7Fan Warning: DC-link voltage high (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9548115_1_7Fan Warning: High Interior Temperature (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9558116_1_7Fan Warning: High Motor Temperature (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9568117_1_7Fan Error: DC-link undervoltage (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9578118_1_7Fan Warning: Identification (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9588193_1_7Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 7)Read1=OK, 2=Not OK
MV9688106_1_8Fan Error: Phase Failure (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9698107_1_8Fan Error: Pwr Mod Overheated (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9708108_1_8Fan Error: Internal Comms Error (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9718109_1_8Fan Error: General Failure (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9728110_1_8Fan Error: Motor Overheated (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9738111_1_8Fan Error: Hall Sensor Error (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9748112_1_8Fan Error: Locked Motor (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9758113_1_8Fan Warning: High Supply Voltage (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9768114_1_8Fan Warning: DC-link voltage high (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9778115_1_8Fan Warning: High Interior Temperature (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9788116_1_8Fan Warning: High Motor Temperature (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9798117_1_8Fan Error: DC-link undervoltage (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9808118_1_8Fan Warning: Identification (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9818193_1_8Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 8)Read1=OK, 2=Not OK
MV9918106_1_9Fan Error: Phase Failure (Supply Fan Status 9)Read1=OK, 2=Not OK
MV9928107_1_9Fan Error: Pwr Mod Overheated (Supply Fan Status 9)Read1=OK, 2=Not OK
MV9938108_1_9Fan Error: Internal Comms Error (Supply Fan Status 9)Read1=OK, 2=Not OK
MV9948109_1_9Fan Error: General Failure (Supply Fan Status 9)Read1=OK, 2=Not OK
MV9958110_1_9Fan Error: Motor Overheated (Supply Fan Status 9)Read1=OK, 2=Not OK
MV9968111_1_9Fan Error: Hall Sensor Error (Supply Fan Status 9)Read1=OK, 2=Not OK
MV9978112_1_9Fan Error: Locked Motor (Supply Fan Status 9)Read1=OK, 2=Not OK
MV9988113_1_9Fan Warning: High Supply Voltage (Supply Fan Status 9)Read1=OK, 2=Not OK
MV9998114_1_9Fan Warning: DC-link voltage high (Supply Fan Status 9)Read1=OK, 2=Not OK
MV10008115_1_9Fan Warning: High Interior Temperature (Supply Fan Status 9)Read1=OK, 2=Not OK
MV10018116_1_9Fan Warning: High Motor Temperature (Supply Fan Status 9)Read1=OK, 2=Not OK
MV10028117_1_9Fan Error: DC-link undervoltage (Supply Fan Status 9)Read1=OK, 2=Not OK
MV10038118_1_9Fan Warning: Identification (Supply Fan Status 9)Read1=OK, 2=Not OK
MV10048193_1_9Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 9)Read1=OK, 2=Not OK
MV10148106_1_10Fan Error: Phase Failure (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10158107_1_10Fan Error: Pwr Mod Overheated (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10168108_1_10Fan Error: Internal Comms Error (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10178109_1_10Fan Error: General Failure (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10188110_1_10Fan Error: Motor Overheated (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10198111_1_10Fan Error: Hall Sensor Error (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10208112_1_10Fan Error: Locked Motor (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10218113_1_10Fan Warning: High Supply Voltage (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10228114_1_10Fan Warning: DC-link voltage high (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10238115_1_10Fan Warning: High Interior Temperature (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10248116_1_10Fan Warning: High Motor Temperature (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10258117_1_10Fan Error: DC-link undervoltage (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10268118_1_10Fan Warning: Identification (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10278193_1_10Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 10)Read1=OK, 2=Not OK
MV10378106_1_11Fan Error: Phase Failure (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10388107_1_11Fan Error: Pwr Mod Overheated (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10398108_1_11Fan Error: Internal Comms Error (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10408109_1_11Fan Error: General Failure (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10418110_1_11Fan Error: Motor Overheated (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10428111_1_11Fan Error: Hall Sensor Error (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10438112_1_11Fan Error: Locked Motor (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10448113_1_11Fan Warning: High Supply Voltage (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10458114_1_11Fan Warning: DC-link voltage high (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10468115_1_11Fan Warning: High Interior Temperature (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10478116_1_11Fan Warning: High Motor Temperature (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10488117_1_11Fan Error: DC-link undervoltage (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10498118_1_11Fan Warning: Identification (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10508193_1_11Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 11)Read1=OK, 2=Not OK
MV10608106_1_12Fan Error: Phase Failure (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10618107_1_12Fan Error: Pwr Mod Overheated (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10628108_1_12Fan Error: Internal Comms Error (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10638109_1_12Fan Error: General Failure (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10648110_1_12Fan Error: Motor Overheated (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10658111_1_12Fan Error: Hall Sensor Error (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10668112_1_12Fan Error: Locked Motor (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10678113_1_12Fan Warning: High Supply Voltage (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10688114_1_12Fan Warning: DC-link voltage high (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10698115_1_12Fan Warning: High Interior Temperature (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10708116_1_12Fan Warning: High Motor Temperature (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10718117_1_12Fan Error: DC-link undervoltage (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10728118_1_12Fan Warning: Identification (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10738193_1_12Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 12)Read1=OK, 2=Not OK
MV10838106_1_13Fan Error: Phase Failure (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10848107_1_13Fan Error: Pwr Mod Overheated (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10858108_1_13Fan Error: Internal Comms Error (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10868109_1_13Fan Error: General Failure (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10878110_1_13Fan Error: Motor Overheated (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10888111_1_13Fan Error: Hall Sensor Error (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10898112_1_13Fan Error: Locked Motor (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10908113_1_13Fan Warning: High Supply Voltage (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10918114_1_13Fan Warning: DC-link voltage high (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10928115_1_13Fan Warning: High Interior Temperature (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10938116_1_13Fan Warning: High Motor Temperature (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10948117_1_13Fan Error: DC-link undervoltage (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10958118_1_13Fan Warning: Identification (Supply Fan Status 13)Read1=OK, 2=Not OK
MV10968193_1_13Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 13)Read1=OK, 2=Not OK
MV11068106_1_14Fan Error: Phase Failure (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11078107_1_14Fan Error: Pwr Mod Overheated (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11088108_1_14Fan Error: Internal Comms Error (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11098109_1_14Fan Error: General Failure (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11108110_1_14Fan Error: Motor Overheated (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11118111_1_14Fan Error: Hall Sensor Error (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11128112_1_14Fan Error: Locked Motor (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11138113_1_14Fan Warning: High Supply Voltage (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11148114_1_14Fan Warning: DC-link voltage high (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11158115_1_14Fan Warning: High Interior Temperature (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11168116_1_14Fan Warning: High Motor Temperature (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11178117_1_14Fan Error: DC-link undervoltage (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11188118_1_14Fan Warning: Identification (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11198193_1_14Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 14)Read1=OK, 2=Not OK
MV11298106_1_15Fan Error: Phase Failure (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11308107_1_15Fan Error: Pwr Mod Overheated (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11318108_1_15Fan Error: Internal Comms Error (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11328109_1_15Fan Error: General Failure (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11338110_1_15Fan Error: Motor Overheated (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11348111_1_15Fan Error: Hall Sensor Error (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11358112_1_15Fan Error: Locked Motor (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11368113_1_15Fan Warning: High Supply Voltage (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11378114_1_15Fan Warning: DC-link voltage high (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11388115_1_15Fan Warning: High Interior Temperature (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11398116_1_15Fan Warning: High Motor Temperature (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11408117_1_15Fan Error: DC-link undervoltage (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11418118_1_15Fan Warning: Identification (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11428193_1_15Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 15, 16)Read1=OK, 2=Not OK
MV11528106_1_16Fan Error: Phase Failure (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11538107_1_16Fan Error: Pwr Mod Overheated (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11548108_1_16Fan Error: Internal Comms Error (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11558109_1_16Fan Error: General Failure (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11568110_1_16Fan Error: Motor Overheated (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11578111_1_16Fan Error: Hall Sensor Error (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11588112_1_16Fan Error: Locked Motor (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11598113_1_16Fan Warning: High Supply Voltage (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11608114_1_16Fan Warning: DC-link voltage high (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11618115_1_16Fan Warning: High Interior Temperature (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11628116_1_16Fan Warning: High Motor Temperature (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11638117_1_16Fan Error: DC-link undervoltage (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11648118_1_16Fan Warning: Identification (Supply Fan Status 16)Read1=OK, 2=Not OK
MV11658193_1_16Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 16)Read1=OK, 2=Not OK
MV12098144_1_1Fluid Temperature Control TypeWrite1=Proportional, 2=Prop+Integral, 3=Adaptive PID, 4=Intelligent
MV12208148_1_1Fluid Control TypeWrite1=Flow Rate, 2=Differential Pressure, 3=Flow Rate with DP Limit, 4=Diff Prs with Flo Limit, 5=Manual
MV12318161_1_1Pump Operation TypeWrite1=Unit On or Standby, 2=Unit On, Off, or Standby
MV12428162_1_1Fluid Dew Pnt MarginWrite
Object ID lookup: Vertiv Liebert iCOM v4 precision cooling point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)

How many BACnet points does the Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW) have?

This list has 1416 BACnet objects: 580 analog values, 365 binary values, 471 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW) BACnet points are writable?

323 of the 1416 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW) BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)?

Start with MV 115 5143_1 (On/off command (1=off, 2=on)); AV 1 5008_1 (Air temperature setpoint, °C); AV 20 5331_1_1 (Supply air temperature setpoint, °C); MV 292 4717_1 (Acknowledge / reset events); MV 94 4706_1 (Run / standby / off state); MV 93 4123_1 (Normal, warning or alarm state); AV 19 5002_1_1 (Supply air temperature, °C); AV 31 4291_1 (Return air temperature, °C); AV 2584 4643_1 (Supply fluid temperature, °C); AV 60 5028_1 (Return air humidity, %RH).

How do I check these points on the real Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.