 "manufacturer": "Vertiv",
 "manufacturer_slug": "vertiv",
 "model": "Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)",
 "model_slug": "icom-v4-precision-cooling",
 "aliases": [
  "Liebert CW",
  "Liebert CWA",
  "Liebert DS",
  "Liebert DSE",
  "Liebert PeX",
  "Liebert HPM",
  "Liebert Challenger 3000",
  "Liebert Challenger ITR",
  "Liebert Deluxe System/3",
  "Liebert PDX",
  "Liebert PCW",
  "iCOM v4",
  "SL-28170"
 ],
 "equipment_type": "Precision cooling unit (computer room air handler)",
 "applies_to": "Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.",
 "summary": "The Liebert iCOM v4 precision cooling reports to a BMS through a Liebert IntelliSlot card (IS-UNITY-DP for BACnet IP or BACnet MS/TP; some units also IS-IPBML). The object list has Binary Values for events, Analog Values for temperatures, humidity, setpoints and run hours, and Multi-state Values for states and control modes. Objects are created on the card when it discovers the unit, so only options fitted to the unit appear.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Tables 5.1, 5.2, 5.3, pdf pages 1231-1343 of the 2024 guide (printed page numbers are 4 lower).",
  "Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.",
  "Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.",
  "The guide prints the same instance twice for: MV 70 (5581_1 and 5357_1); only the first is listed.",
  "A column in the guide ties each point to the iCOM firmware versions that support it; check your controller version."
 ],
 "source": {
  "title": "Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP)",
  "doc_number": "SL-28170",
  "revision_date": "2024-04 (Rev 29)",
  "url": "https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf"
 },
 "integration": {
  "summary": "Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.",
  "minimum_points": [
   {
    "ref": "MV 115",
    "name": "5143_1",
    "why": "On/off command (1=off, 2=on)"
   },
   {
    "ref": "AV 1",
    "name": "5008_1",
    "why": "Air temperature setpoint, °C"
   },
   {
    "ref": "AV 20",
    "name": "5331_1_1",
    "why": "Supply air temperature setpoint, °C"
   },
   {
    "ref": "MV 292",
    "name": "4717_1",
    "why": "Acknowledge / reset events"
   },
   {
    "ref": "MV 94",
    "name": "4706_1",
    "why": "Run / standby / off state"
   },
   {
    "ref": "MV 93",
    "name": "4123_1",
    "why": "Normal, warning or alarm state"
   },
   {
    "ref": "AV 19",
    "name": "5002_1_1",
    "why": "Supply air temperature, °C"
   },
   {
    "ref": "AV 31",
    "name": "4291_1",
    "why": "Return air temperature, °C"
   },
   {
    "ref": "AV 2584",
    "name": "4643_1",
    "why": "Supply fluid temperature, °C"
   },
   {
    "ref": "AV 60",
    "name": "5028_1",
    "why": "Return air humidity, %RH"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The card needs a unique Device Instance Number; the device object represents the card, not the unit.",
   "The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).",
   "IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports."
  ],
  "gotchas": [
   "Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.",
   "No segmented responses: large ReadPropertyMultiple requests can fail, so split them.",
   "Only data the managed unit actually has is created on the card, so object counts vary by model and options."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 1245,
   "name": "6538_1",
   "description": "TSA Control Input Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "5015_1_1",
   "description": "Supply Air Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "5019_1_1",
   "description": "Supply Air Under Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "5026_1_1",
   "description": "Supply Air Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "6530_1_1",
   "description": "Supply NTC Air Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "5023_1_1",
   "description": "Return Air Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "5335_1_1",
   "description": "Return Air Under Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "5147_1_1",
   "description": "Return Air Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "4601_1_1",
   "description": "Ext Air Sensor A Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "4608_1_1",
   "description": "Ext Air Sensor A Under Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "4618_1_1",
   "description": "Ext Air Sensor A Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "5573_1_1",
   "description": "Ambient Air Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "4621_1_1",
   "description": "External Air Sensor B Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "6531_1_1",
   "description": "External Air Sensor C Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "6532_1_1",
   "description": "External Air Sensor D Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "6533_1_1",
   "description": "External Air Sensor E Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1050,
   "name": "5966_1_1",
   "description": "Aux Air Temp Device Communication Lost",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "5034_1",
   "description": "High Return Humidity",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "5036_1",
   "description": "Low Return Humidity",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "5578_1",
   "description": "Dew Point Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "5579_1",
   "description": "Dew Point Under Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "5902_1",
   "description": "Return Humidity Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "5349_1_1",
   "description": "Ext Air Sensor A High Humidity",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "5351_1_1",
   "description": "Ext Air Sensor A Low Humidity",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "4615_1_1",
   "description": "Ext Dew Point Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "5577_1_1",
   "description": "Ext Dew Point Under Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 65,
   "name": "5067_1",
   "description": "Ext Compressor Lockout",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 66,
   "name": "5513_1",
   "description": "Compressor Capacity Reduced",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 77,
   "name": "5269_1_1",
   "description": "Compressor Hours Exceeded (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 78,
   "name": "5270_1_1",
   "description": "Compressor High Head Pressure (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 79,
   "name": "5271_1_1",
   "description": "Compressor Low Suction Pressure (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 80,
   "name": "5352_1_1",
   "description": "Compressor Short Cycle (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 81,
   "name": "5146_1_1",
   "description": "Compressor Pump Down Issue (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 82,
   "name": "5272_1_1",
   "description": "Compressor Thermal Overload (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 83,
   "name": "5354_1_1",
   "description": "Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 84,
   "name": "5355_1_1",
   "description": "Dig Scroll Comp Over Temp (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 85,
   "name": "5514_1_1",
   "description": "Compressor Low Pressure Transducer Issue (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 86,
   "name": "5148_1_1",
   "description": "Compressor High Pressure Transducer Issue (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "5604_1_1",
   "description": "Compressor Superheat Over Threshold (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "5903_1_1",
   "description": "Compressor Low Differential Pressure Lockout (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "6758_1_1",
   "description": "Compressor Freeze Protection (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 97,
   "name": "5269_1_2",
   "description": "Compressor Hours Exceeded (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 98,
   "name": "5270_1_2",
   "description": "Compressor High Head Pressure (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 99,
   "name": "5271_1_2",
   "description": "Compressor Low Suction Pressure (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 100,
   "name": "5352_1_2",
   "description": "Compressor Short Cycle (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 101,
   "name": "5146_1_2",
   "description": "Compressor Pump Down Issue (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 102,
   "name": "5272_1_2",
   "description": "Compressor Thermal Overload (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 103,
   "name": "5354_1_2",
   "description": "Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 104,
   "name": "5355_1_2",
   "description": "Dig Scroll Comp Over Temp (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 105,
   "name": "5514_1_2",
   "description": "Compressor Low Pressure Transducer Issue (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 106,
   "name": "5148_1_2",
   "description": "Compressor High Pressure Transducer Issue (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 107,
   "name": "5604_1_2",
   "description": "Compressor Superheat Over Threshold (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 108,
   "name": "5903_1_2",
   "description": "Compressor Low Differential Pressure Lockout (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 109,
   "name": "6758_1_2",
   "description": "Compressor Freeze Protection (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1265,
   "name": "5269_1_3",
   "description": "Compressor Hours Exceeded (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1266,
   "name": "5270_1_3",
   "description": "Compressor High Head Pressure (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1267,
   "name": "5271_1_3",
   "description": "Compressor Low Suction Pressure (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1268,
   "name": "5352_1_3",
   "description": "Compressor Short Cycle (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1269,
   "name": "5146_1_3",
   "description": "Compressor Pump Down Issue (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1270,
   "name": "5272_1_3",
   "description": "Compressor Thermal Overload (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1271,
   "name": "5354_1_3",
   "description": "Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1272,
   "name": "5355_1_3",
   "description": "Dig Scroll Comp Over Temp (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1273,
   "name": "5514_1_3",
   "description": "Compressor Low Pressure Transducer Issue (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1274,
   "name": "5148_1_3",
   "description": "Compressor High Pressure Transducer Issue (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1275,
   "name": "5604_1_3",
   "description": "Compressor Superheat Over Threshold (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1276,
   "name": "5903_1_3",
   "description": "Compressor Low Differential Pressure Lockout (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1277,
   "name": "6758_1_3",
   "description": "Compressor Freeze Protection (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1287,
   "name": "5269_1_4",
   "description": "Compressor Hours Exceeded (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1288,
   "name": "5270_1_4",
   "description": "Compressor High Head Pressure (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1289,
   "name": "5271_1_4",
   "description": "Compressor Low Suction Pressure (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1290,
   "name": "5352_1_4",
   "description": "Compressor Short Cycle (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1291,
   "name": "5146_1_4",
   "description": "Compressor Pump Down Issue (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1292,
   "name": "5272_1_4",
   "description": "Compressor Thermal Overload (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1293,
   "name": "5354_1_4",
   "description": "Dig Scroll Comp Discharge Temp Sensor Issue (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1294,
   "name": "5355_1_4",
   "description": "Dig Scroll Comp Over Temp (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1295,
   "name": "5514_1_4",
   "description": "Compressor Low Pressure Transducer Issue (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1296,
   "name": "5148_1_4",
   "description": "Compressor High Pressure Transducer Issue (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1297,
   "name": "5604_1_4",
   "description": "Compressor Superheat Over Threshold (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1298,
   "name": "5903_1_4",
   "description": "Compressor Low Differential Pressure Lockout (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1299,
   "name": "6758_1_4",
   "description": "Compressor Freeze Protection (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 117,
   "name": "5306_1",
   "description": "Free Cooling Valve Hours Exceeded",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 118,
   "name": "5361_1",
   "description": "Ext Free Cooling Lockout",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 119,
   "name": "5362_1",
   "description": "Free Cooling Temp Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 120,
   "name": "6539_1",
   "description": "Chilled Water Valve Hours Exceeded",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 130,
   "name": "5365_1",
   "description": "Hot Water / Hot Gas Valve Hours Exceeded",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 131,
   "name": "5068_1",
   "description": "Reheater Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 132,
   "name": "5070_1",
   "description": "Ext Reheat Lockout",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 143,
   "name": "5368_1_1",
   "description": "Electric Reheater Hours Exceeded (Electric Reheater 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 154,
   "name": "5368_1_2",
   "description": "Electric Reheater Hours Exceeded (Electric Reheater 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 165,
   "name": "5368_1_3",
   "description": "Electric Reheater Hours Exceeded (Electric Reheater 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 176,
   "name": "5037_1",
   "description": "Humidifier Hours Exceeded",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 177,
   "name": "5044_1",
   "description": "Ext Humidifier Lockout",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 178,
   "name": "5045_1",
   "description": "Humidifier Control Board Not Detected",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 179,
   "name": "5042_1",
   "description": "Humidifier Cylinder Worn",
   "units": "",
   "access": "R",
   "states": "Active on Alarm Active on Alarm"
  },
  {
   "type": "BV",
   "instance": 180,
   "name": "5043_1",
   "description": "Humidifier Issue",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 181,
   "name": "5041_1",
   "description": "Humidifier Low Water",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 182,
   "name": "5040_1",
   "description": "Humidifier Over Current",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 183,
   "name": "5039_1",
   "description": "Humidifier Under Current",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 194,
   "name": "5038_1",
   "description": "Dehumidifier Hours Exceeded",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 205,
   "name": "5054_1",
   "description": "Fan Hours Exceeded",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 206,
   "name": "5376_1",
   "description": "Main Fan Overload",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 207,
   "name": "4729_1",
   "description": "Fan Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 208,
   "name": "6540_1",
   "description": "FSA Control Input Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1648,
   "name": "8105_1_1",
   "description": "Supply Fan Communication Lost (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1659,
   "name": "8105_1_2",
   "description": "Supply Fan Communication Lost (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1670,
   "name": "8105_1_3",
   "description": "Supply Fan Communication Lost (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1681,
   "name": "8105_1_4",
   "description": "Supply Fan Communication Lost (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1692,
   "name": "8105_1_5",
   "description": "Supply Fan Communication Lost (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1703,
   "name": "8105_1_6",
   "description": "Supply Fan Communication Lost (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1714,
   "name": "8105_1_7",
   "description": "Supply Fan Communication Lost (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1725,
   "name": "8105_1_8",
   "description": "Supply Fan Communication Lost (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1736,
   "name": "8105_1_9",
   "description": "Supply Fan Communication Lost (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1747,
   "name": "8105_1_10",
   "description": "Supply Fan Communication Lost (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1758,
   "name": "8105_1_11",
   "description": "Supply Fan Communication Lost (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1769,
   "name": "8105_1_12",
   "description": "Supply Fan Communication Lost (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1780,
   "name": "8105_1_13",
   "description": "Supply Fan Communication Lost (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1791,
   "name": "8105_1_14",
   "description": "Supply Fan Communication Lost (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1802,
   "name": "8105_1_15",
   "description": "Supply Fan Communication Lost (Supply Fan Status 15)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1813,
   "name": "8105_1_16",
   "description": "Supply Fan Communication Lost (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 219,
   "name": "5072_1",
   "description": "Condenser VFD Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 220,
   "name": "5106_1",
   "description": "Ext Condenser Pump High Water",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1060,
   "name": "6105_1",
   "description": "External Condenser TVSS Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1061,
   "name": "6106_1",
   "description": "External Condenser VFD Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 231,
   "name": "5377_1_1",
   "description": "Condenser Issue (Condenser 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 242,
   "name": "5377_1_2",
   "description": "Condenser Issue (Condenser 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 253,
   "name": "4270_1",
   "description": "Customer Input 1",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 254,
   "name": "4271_1",
   "description": "Customer Input 2",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 255,
   "name": "4272_1",
   "description": "Customer Input 3",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 256,
   "name": "4273_1",
   "description": "Customer Input 4",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 257,
   "name": "5415_1",
   "description": "Ext Loss of Air Blower",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 258,
   "name": "5105_1",
   "description": "Ext Loss of Flow",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 259,
   "name": "5107_1",
   "description": "Ext Standby Glycol Pump On",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 260,
   "name": "5115_1",
   "description": "BMS Communications Timeout",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 261,
   "name": "5416_1",
   "description": "Ext Standby Unit On",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 262,
   "name": "5118_1",
   "description": "Clogged Air Filter",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 263,
   "name": "5053_1",
   "description": "Loss of Air Flow",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 264,
   "name": "4726_1",
   "description": "Service Required",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 265,
   "name": "5120_1",
   "description": "Master Unit Communication Lost",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 266,
   "name": "5119_1",
   "description": "RAM Battery Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 267,
   "name": "4714_1",
   "description": "Shutdown - Loss Of Power",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 268,
   "name": "5121_1",
   "description": "High Power Shutdown",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 269,
   "name": "4720_1",
   "description": "Smoke Detected",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 270,
   "name": "4980_1",
   "description": "Supply Chilled Water Loss of Flow",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 271,
   "name": "4626_1",
   "description": "Supply Chilled Water Over Temp",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 272,
   "name": "5418_1",
   "description": "Unit Code Missing",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 273,
   "name": "5419_1",
   "description": "Unit Communication Lost",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 274,
   "name": "5114_1",
   "description": "Water Leakage Detector Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 275,
   "name": "4723_1",
   "description": "Water Under Floor",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 276,
   "name": "5104_1",
   "description": "Ext Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 277,
   "name": "5108_1",
   "description": "External Fire Detected",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 278,
   "name": "5588_1",
   "description": "Unspecified General Event",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 279,
   "name": "5617_1",
   "description": "Temperature Control Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 280,
   "name": "5906_1",
   "description": "Airflow Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 281,
   "name": "5907_1",
   "description": "Ext Air Damper Position Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 282,
   "name": "5908_1",
   "description": "Ext Power Source A Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 283,
   "name": "5909_1",
   "description": "Ext Power Source B Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 284,
   "name": "5924_1",
   "description": "Mixed Mode Lockout",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 350,
   "name": "6541_1",
   "description": "Auto Tune License Expiring",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 351,
   "name": "6542_1",
   "description": "Auto Tune License Expired",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 352,
   "name": "6543_1",
   "description": "Unit In Standby Due To Cooling Loss",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 353,
   "name": "6544_1",
   "description": "Control Units Remote Shutdown Mismatch",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 354,
   "name": "6545_1",
   "description": "Slave Control Unit Communication Lost",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 355,
   "name": "6546_1",
   "description": "Control Units Unit Code Mismatch",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 356,
   "name": "5471_1",
   "description": "Door Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 357,
   "name": "8192_1",
   "description": "Water Leakage",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 358,
   "name": "8231_1",
   "description": "PHE Sup Tem Snsr Fail",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 288,
   "name": "4703_1_1",
   "description": "Chilled Water Control Valve Failure (Chilled Water Valve 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 299,
   "name": "4703_1_2",
   "description": "Chilled Water Control Valve Failure (Chilled Water Valve 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 310,
   "name": "5110_1_1",
   "description": "Unit Off",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 311,
   "name": "5109_1_1",
   "description": "Unit On",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 312,
   "name": "5112_1_1",
   "description": "Unit Partial Shutdown",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 313,
   "name": "5113_1_1",
   "description": "Unit Shutdown",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 314,
   "name": "5111_1_1",
   "description": "Unit Standby",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 315,
   "name": "5116_1_1",
   "description": "Maintenance Due",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 316,
   "name": "5117_1_1",
   "description": "Maintenance Completed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 327,
   "name": "5417_1_1",
   "description": "Digital Output Board Not Detected (iCOM DO Board 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 338,
   "name": "5417_1_2",
   "description": "Digital Output Board Not Detected (iCOM DO Board 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 349,
   "name": "5417_1_3",
   "description": "Digital Output Board Not Detected (iCOM DO Board 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 361,
   "name": "5593_1",
   "description": "Remote Sensor Average Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 362,
   "name": "5594_1",
   "description": "Remote Sensor Average Under Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 363,
   "name": "5595_1",
   "description": "Remote Sensor System Average Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 364,
   "name": "5596_1",
   "description": "Remote Sensor System Average Under Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 376,
   "name": "5597_1_1",
   "description": "Remote Sensor Over Temperature (Remote Sensor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 377,
   "name": "5598_1_1",
   "description": "Remote Sensor Under Temperature (Remote Sensor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 378,
   "name": "5060_1_1",
   "description": "Remote Sensor Issue (Remote Sensor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 390,
   "name": "5597_1_2",
   "description": "Remote Sensor Over Temperature (Remote Sensor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 391,
   "name": "5598_1_2",
   "description": "Remote Sensor Under Temperature (Remote Sensor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 392,
   "name": "5060_1_2",
   "description": "Remote Sensor Issue (Remote Sensor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 404,
   "name": "5597_1_3",
   "description": "Remote Sensor Over Temperature (Remote Sensor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 405,
   "name": "5598_1_3",
   "description": "Remote Sensor Under Temperature (Remote Sensor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 406,
   "name": "5060_1_3",
   "description": "Remote Sensor Issue (Remote Sensor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 418,
   "name": "5597_1_4",
   "description": "Remote Sensor Over Temperature (Remote Sensor 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 419,
   "name": "5598_1_4",
   "description": "Remote Sensor Under Temperature (Remote Sensor 4)",
   "units": "",
   "access": "R",
   "states": "Active on Alarm Active on Alarm"
  },
  {
   "type": "BV",
   "instance": 420,
   "name": "5060_1_4",
   "description": "Remote Sensor Issue (Remote Sensor 4)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 432,
   "name": "5597_1_5",
   "description": "Remote Sensor Over Temperature (Remote Sensor 5)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 433,
   "name": "5598_1_5",
   "description": "Remote Sensor Under Temperature (Remote Sensor 5)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 434,
   "name": "5060_1_5",
   "description": "Remote Sensor Issue (Remote Sensor 5)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 446,
   "name": "5597_1_6",
   "description": "Remote Sensor Over Temperature (Remote Sensor 6)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 447,
   "name": "5598_1_6",
   "description": "Remote Sensor Under Temperature (Remote Sensor 6)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 448,
   "name": "5060_1_6",
   "description": "Remote Sensor Issue (Remote Sensor 6)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 460,
   "name": "5597_1_7",
   "description": "Remote Sensor Over Temperature (Remote Sensor 7)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 461,
   "name": "5598_1_7",
   "description": "Remote Sensor Under Temperature (Remote Sensor 7)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 462,
   "name": "5060_1_7",
   "description": "Remote Sensor Issue (Remote Sensor 7)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 474,
   "name": "5597_1_8",
   "description": "Remote Sensor Over Temperature (Remote Sensor 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 475,
   "name": "5598_1_8",
   "description": "Remote Sensor Under Temperature (Remote Sensor 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 476,
   "name": "5060_1_8",
   "description": "Remote Sensor Issue (Remote Sensor 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 488,
   "name": "5597_1_9",
   "description": "Remote Sensor Over Temperature (Remote Sensor 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 489,
   "name": "5598_1_9",
   "description": "Remote Sensor Under Temperature (Remote Sensor 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 490,
   "name": "5060_1_9",
   "description": "Remote Sensor Issue (Remote Sensor 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 502,
   "name": "5597_1_10",
   "description": "Remote Sensor Over Temperature (Remote Sensor 10)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 503,
   "name": "5598_1_10",
   "description": "Remote Sensor Under Temperature (Remote Sensor 10)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 504,
   "name": "5060_1_10",
   "description": "Remote Sensor Issue (Remote Sensor 10)",
   "units": "",
   "access": "R",
   "states": "Active on Alarm Active on Alarm"
  },
  {
   "type": "BV",
   "instance": 516,
   "name": "5600_1",
   "description": "Air Economizer Emergency Override",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 517,
   "name": "5601_1",
   "description": "Air Economizer Reduced Airflow",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 540,
   "name": "5625_1",
   "description": "EEV Unspecified General Event",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 563,
   "name": "5629_1",
   "description": "Static Pressure Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 564,
   "name": "5630_1",
   "description": "High Static Pressure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 565,
   "name": "5631_1",
   "description": "Low Static Pressure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 566,
   "name": "5910_1",
   "description": "Static Pressure Sensor Out of Range",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 567,
   "name": "6547_1",
   "description": "SSA Control Input Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 623,
   "name": "5636_1",
   "description": "Pump Unspecified General Event",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1001,
   "name": "5568_1",
   "description": "Input Undervoltage (Power Measurement 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1040,
   "name": "5967_1",
   "description": "Modbus Power Meter Communication Lost (Power Measurement 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1002,
   "name": "5568_2",
   "description": "Input Undervoltage (Power Measurement 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1041,
   "name": "5967_2",
   "description": "Modbus Power Meter Communication Lost (Power Measurement 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1003,
   "name": "5568_3",
   "description": "Input Undervoltage (Power Measurement 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1042,
   "name": "5967_3",
   "description": "Modbus Power Meter Communication Lost (Power Measurement 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1004,
   "name": "5568_4",
   "description": "Input Undervoltage (Power Measurement 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1043,
   "name": "5967_4",
   "description": "Modbus Power Meter Communication Lost (Power Measurement 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1005,
   "name": "5568_5",
   "description": "Input Undervoltage (Power Measurement 5)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1044,
   "name": "5967_5",
   "description": "Modbus Power Meter Communication Lost (Power Measurement 5)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1006,
   "name": "5568_6",
   "description": "Input Undervoltage (Power Measurement 6)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1045,
   "name": "5967_6",
   "description": "Modbus Power Meter Communication Lost (Power Measurement 6)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1021,
   "name": "5911_1",
   "description": "Fluid Temperature Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1022,
   "name": "5912_1",
   "description": "Fluid Flow Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1031,
   "name": "5911_2",
   "description": "Fluid Temperature Sensor Issue (Fluid 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1032,
   "name": "5912_2",
   "description": "Fluid Flow Sensor Issue (Fluid 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 643,
   "name": "5637_1",
   "description": "Condenser Unit Unspecified General Event",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1082,
   "name": "5536_1_1",
   "description": "Condenser Outside Air Temp Out of Operating Range (Condenser 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1084,
   "name": "5537_1_1",
   "description": "Condenser Control Board Issue (Condenser 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1086,
   "name": "5535_1_1",
   "description": "Condenser Outside Air Temp Sensor Issue (Condenser 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1088,
   "name": "5531_1_1",
   "description": "Condenser Communication Lost (Condenser 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1090,
   "name": "6100_1_1",
   "description": "Condenser Remote Shutdown (Condenser 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 218,
   "name": "5073_1_1",
   "description": "Condenser TVSS Issue (Condenser 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1083,
   "name": "5536_1_2",
   "description": "Condenser Outside Air Temp Out of Operating Range (Condenser 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1085,
   "name": "5537_1_2",
   "description": "Condenser Control Board Issue (Condenser 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1087,
   "name": "5535_1_2",
   "description": "Condenser Outside Air Temp Sensor Issue (Condenser 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1089,
   "name": "5531_1_2",
   "description": "Condenser Communication Lost (Condenser 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1091,
   "name": "6100_1_2",
   "description": "Condenser Remote Shutdown (Condenser 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1092,
   "name": "5073_1_2",
   "description": "Condenser TVSS Issue (Condenser 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1350,
   "name": "5073_1_3",
   "description": "Condenser TVSS Issue (Condenser 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1319,
   "name": "5536_1_3",
   "description": "Condenser Outside Air Temp Out of Operating Range (Condenser 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1320,
   "name": "5537_1_3",
   "description": "Condenser Control Board Issue (Condenser 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1321,
   "name": "5535_1_3",
   "description": "Condenser Outside Air Temp Sensor Issue (Condenser 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1322,
   "name": "5531_1_3",
   "description": "Condenser Communication Lost (Condenser 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1323,
   "name": "6100_1_3",
   "description": "Condenser Remote Shutdown (Condenser 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1366,
   "name": "5073_1_4",
   "description": "Condenser TVSS Issue (Condenser 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1335,
   "name": "5536_1_4",
   "description": "Condenser Outside Air Temp Out of Operating Range (Condenser 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1336,
   "name": "5537_1_4",
   "description": "Condenser Control Board Issue (Condenser 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1337,
   "name": "5535_1_4",
   "description": "Condenser Outside Air Temp Sensor Issue (Condenser 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1338,
   "name": "5531_1_4",
   "description": "Condenser Communication Lost (Condenser 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1339,
   "name": "6100_1_4",
   "description": "Condenser Remote Shutdown (Condenser 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 644,
   "name": "5638_1_1",
   "description": "Condenser Circuit Unspecified General Event (Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1104,
   "name": "5541_1_1",
   "description": "Condenser Refrigerant Pressure Sensor Issue (Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1106,
   "name": "5540_1_1",
   "description": "Condenser Refrigerant Pressure Under Threshold (Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1108,
   "name": "5539_1_1",
   "description": "Condenser Refrigerant Pressure Over Threshold (Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1110,
   "name": "5544_1_1",
   "description": "Condenser Supply Refrigerant Temp Sensor Issue (Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1112,
   "name": "5543_1_1",
   "description": "Condenser Supply Refrigerant Under Temp (Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1114,
   "name": "5542_1_1",
   "description": "Condenser Supply Refrigerant Over Temp (Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1116,
   "name": "5545_1_1",
   "description": "Condenser Max Fan Speed Override (Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 896,
   "name": "5638_1_2",
   "description": "Condenser Circuit Unspecified General Event (Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1105,
   "name": "5541_1_2",
   "description": "Condenser Refrigerant Pressure Sensor Issue (Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1107,
   "name": "5540_1_2",
   "description": "Condenser Refrigerant Pressure Under Threshold (Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1109,
   "name": "5539_1_2",
   "description": "Condenser Refrigerant Pressure Over Threshold (Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1111,
   "name": "5544_1_2",
   "description": "Condenser Supply Refrigerant Temp Sensor Issue (Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1113,
   "name": "5543_1_2",
   "description": "Condenser Supply Refrigerant Under Temp (Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1115,
   "name": "5542_1_2",
   "description": "Condenser Supply Refrigerant Over Temp (Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1117,
   "name": "5545_1_2",
   "description": "Condenser Max Fan Speed Override (Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1359,
   "name": "5541_1_3",
   "description": "Condenser Refrigerant Pressure Sensor Issue (Circuit 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1360,
   "name": "5540_1_3",
   "description": "Condenser Refrigerant Pressure Under Threshold (Circuit 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1361,
   "name": "5539_1_3",
   "description": "Condenser Refrigerant Pressure Over Threshold (Circuit 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1362,
   "name": "5544_1_3",
   "description": "Condenser Supply Refrigerant Temp Sensor Issue (Circuit 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1363,
   "name": "5543_1_3",
   "description": "Condenser Supply Refrigerant Under Temp (Circuit 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1364,
   "name": "5542_1_3",
   "description": "Condenser Supply Refrigerant Over Temp (Circuit 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1365,
   "name": "5545_1_3",
   "description": "Condenser Max Fan Speed Override (Circuit 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1376,
   "name": "5541_1_4",
   "description": "Condenser Refrigerant Pressure Sensor Issue (Circuit 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1377,
   "name": "5540_1_4",
   "description": "Condenser Refrigerant Pressure Under Threshold (Circuit 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1378,
   "name": "5539_1_4",
   "description": "Condenser Refrigerant Pressure Over Threshold (Circuit 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1379,
   "name": "5544_1_4",
   "description": "Condenser Supply Refrigerant Temp Sensor Issue (Circuit 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1380,
   "name": "5543_1_4",
   "description": "Condenser Supply Refrigerant Under Temp (Circuit 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1381,
   "name": "5542_1_4",
   "description": "Condenser Supply Refrigerant Over Temp (Circuit 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1382,
   "name": "5545_1_4",
   "description": "Condenser Max Fan Speed Override (Circuit 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1128,
   "name": "5277_1_1_1",
   "description": "Condenser Fan Issue (Condenser 1 Fan 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1129,
   "name": "5277_1_1_2",
   "description": "Condenser Fan Issue (Condenser 1 Fan 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1130,
   "name": "5277_1_1_3",
   "description": "Condenser Fan Issue (Condenser 1 Fan 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1131,
   "name": "5277_1_1_4",
   "description": "Condenser Fan Issue (Condenser 1 Fan 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1132,
   "name": "5277_1_2_1",
   "description": "Condenser Fan Issue (Condenser 2 Fan 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1133,
   "name": "5277_1_2_2",
   "description": "Condenser Fan Issue (Condenser 2 Fan 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1134,
   "name": "5277_1_2_3",
   "description": "Condenser Fan Issue (Condenser 2 Fan 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1135,
   "name": "5277_1_2_4",
   "description": "Condenser Fan Issue (Condenser 2 Fan 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1402,
   "name": "5277_1_3_1",
   "description": "Condenser Fan Issue (Condenser 3 Fan 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1422,
   "name": "5277_1_3_2",
   "description": "Condenser Fan Issue (Condenser 3 Fan 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1442,
   "name": "5277_1_3_3",
   "description": "Condenser Fan Issue (Condenser 3 Fan 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1462,
   "name": "5277_1_3_4",
   "description": "Condenser Fan Issue (Condenser 3 Fan 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1482,
   "name": "5277_1_4_1",
   "description": "Condenser Fan Issue (Condenser 4 Fan 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1502,
   "name": "5277_1_4_2",
   "description": "Condenser Fan Issue (Condenser 4 Fan 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1522,
   "name": "5277_1_4_3",
   "description": "Condenser Fan Issue (Condenser 4 Fan 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1542,
   "name": "5277_1_4_4",
   "description": "Condenser Fan Issue (Condenser 4 Fan 4)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1146,
   "name": "6092_1",
   "description": "Compressor 1B Thermal Overload",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1147,
   "name": "6093_1",
   "description": "Compressor 2B Thermal Overload",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1148,
   "name": "6094_1",
   "description": "Compressor 1B Hours Exceeded",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1149,
   "name": "6095_1",
   "description": "Compressor 2B Hours Exceeded",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1150,
   "name": "6303_1",
   "description": "Team Static Pressure Sensor Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1151,
   "name": "6304_1",
   "description": "Heating Lockout",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1152,
   "name": "6305_1",
   "description": "Free Cooling Stopped - High Room Temp",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1163,
   "name": "6306_1_1",
   "description": "Cold Aisle Temperature/Humidity Team Sensor Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1174,
   "name": "6309_1_1",
   "description": "Cold Aisle Air Sensor Failure (Cold Aisle Sensor 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1185,
   "name": "6309_1_2",
   "description": "Cold Aisle Air Sensor Failure (Cold Aisle Sensor 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1196,
   "name": "6309_1_3",
   "description": "Cold Aisle Air Sensor Failure (Cold Aisle Sensor 3)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1207,
   "name": "6310_1",
   "description": "Chilled Water Inlet Temperature Control Active",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1218,
   "name": "6313_1_1",
   "description": "Chilled Water Inlet Temperature Sensor Failure (Chilled Water Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1219,
   "name": "6314_1_1",
   "description": "Chilled Water Outlet Temperature Sensor Failure (Chilled Water Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1220,
   "name": "6315_1_1",
   "description": "Chilled Water Flow Meter Sensor Failure (Chilled Water Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1231,
   "name": "6313_1_2",
   "description": "Chilled Water Inlet Temperature Sensor Failure (Chilled Water Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1232,
   "name": "6314_1_2",
   "description": "Chilled Water Outlet Temperature Sensor Failure (Chilled Water Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1233,
   "name": "6315_1_2",
   "description": "Chilled Water Flow Meter Sensor Failure (Chilled Water Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1554,
   "name": "6691_1_1",
   "description": "Group Independent On",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1555,
   "name": "6692_1_1",
   "description": "Group Independent Off",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1567,
   "name": "6818_1",
   "description": "External Supply Fluid High Temperature (Fluid Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1568,
   "name": "6819_1",
   "description": "External Supply Fluid Temp Sensor Issue (Fluid Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1569,
   "name": "6824_1",
   "description": "External Supply Fluid Flow Issue (Fluid Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1570,
   "name": "8075_1",
   "description": "Valve Communications Failure (Fluid Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1571,
   "name": "8076_1",
   "description": "Valve Issue (Fluid Circuit 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1581,
   "name": "6818_2",
   "description": "External Supply Fluid High Temperature (Fluid Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1582,
   "name": "6819_2",
   "description": "External Supply Fluid Temp Sensor Issue (Fluid Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1583,
   "name": "6824_2",
   "description": "External Supply Fluid Flow Issue (Fluid Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1584,
   "name": "8075_2",
   "description": "Valve Communications Failure (Fluid Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1585,
   "name": "8076_2",
   "description": "Valve Issue (Fluid Circuit 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1595,
   "name": "6822_1",
   "description": "Audit Log Update",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1606,
   "name": "7163_1",
   "description": "Modbus Automatic Transfer Switch Communication Lost",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1617,
   "name": "4651_1",
   "description": "Supply Fluid Temp Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1618,
   "name": "5295_1",
   "description": "Return Fluid Temp Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1619,
   "name": "7474_1",
   "description": "Flow Sensor Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1620,
   "name": "7475_1",
   "description": "Check Water System",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1621,
   "name": "4645_1",
   "description": "Supply Fluid Over Temp",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1622,
   "name": "5293_1",
   "description": "Return Fluid Over Temp",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1623,
   "name": "7476_1",
   "description": "Pump Operating Without Flow",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1824,
   "name": "8180_1",
   "description": "Supply Fluid Low Temp",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1825,
   "name": "8181_1",
   "description": "Return Fluid Low Temp",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1826,
   "name": "8182_1",
   "description": "Fluid High Differential Pressure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1827,
   "name": "8183_1",
   "description": "Fluid Low Differential Pressure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1828,
   "name": "8184_1",
   "description": "Fluid Flow Low Inlet Pressure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1829,
   "name": "8185_1",
   "description": "Fluid Flow High Supply Pressure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1830,
   "name": "8186_1",
   "description": "Fluid Low System Flow",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1831,
   "name": "8187_1",
   "description": "Fluid Flow Blocked",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1832,
   "name": "8188_1",
   "description": "Fluid Dewpoint Margin Control",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1833,
   "name": "8189_1",
   "description": "Fluid Supply Pressure Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1834,
   "name": "8190_1",
   "description": "Fluid Return Pressure Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1835,
   "name": "8191_1",
   "description": "Fluid Inlet Pressure Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1634,
   "name": "7483_1_1",
   "description": "Pump Inverter Failure (Fluid Pump 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1635,
   "name": "7484_1_1",
   "description": "Pump Flow Failure (Fluid Pump 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1636,
   "name": "7483_1_2",
   "description": "Pump Inverter Failure (Fluid Pump 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1637,
   "name": "7484_1_2",
   "description": "Pump Flow Failure (Fluid Pump 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1846,
   "name": "8170_1_1",
   "description": "XD Pump Communication Lost (Fluid Pump Status 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1857,
   "name": "8170_1_2",
   "description": "XD Pump Communication Lost (Fluid Pump Status 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "5008_1",
   "description": "Air Temperature Set Point",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10001,
   "name": "5008_1_deg_F",
   "description": "Air Temperature Set Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "5325_1",
   "description": "Air Temperature Proportional Band",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10002,
   "name": "5325_1_deg_F",
   "description": "Air Temperature Proportional Band",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "5011_1",
   "description": "Air Temperature Dead Band",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10003,
   "name": "5011_1_deg_F",
   "description": "Air Temperature Dead Band",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "5326_1",
   "description": "Air Temperature Control Integration Time",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "5327_1",
   "description": "Today's High Air Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10005,
   "name": "5327_1_deg_F",
   "description": "Today's High Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "5328_1",
   "description": "Today's High Air Temperature Time",
   "units": "Seconds since Midnight",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "5329_1",
   "description": "Today's Low Air Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10007,
   "name": "5329_1_deg_F",
   "description": "Today's Low Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "5330_1",
   "description": "Today's Low Air Temperature Time",
   "units": "Seconds since Midnight",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "5002_1_1",
   "description": "Supply Air Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10019,
   "name": "5002_1_1_deg_F",
   "description": "Supply Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "5331_1_1",
   "description": "Supply Air Temperature Set Point",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10020,
   "name": "5331_1_1_deg_F",
   "description": "Supply Air Temperature Set Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "5014_1_1",
   "description": "High Supply Air Temperature Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10021,
   "name": "5014_1_1_deg_F",
   "description": "High Supply Air Temperature Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "5018_1_1",
   "description": "Low Supply Air Temperature Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10022,
   "name": "5018_1_1_deg_F",
   "description": "Low Supply Air Temperature Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "6756_1_1",
   "description": "Supply Sensor Events Initial Delay",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "5022_1_1",
   "description": "High Return Air Temperature Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10033,
   "name": "5022_1_1_deg_F",
   "description": "High Return Air Temperature Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "5334_1_1",
   "description": "Low Return Air Temperature Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10034,
   "name": "5334_1_1_deg_F",
   "description": "Low Return Air Temperature Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "6757_1_1",
   "description": "Return Sensor Events Initial Delay",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "4594_1_1",
   "description": "Ext Air Sensor A Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10045,
   "name": "4594_1_1_deg_F",
   "description": "Ext Air Sensor A Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "4597_1_1",
   "description": "Ext Air Sensor B Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10046,
   "name": "4597_1_1_deg_F",
   "description": "Ext Air Sensor B Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "5336_1_1",
   "description": "Ext Air Sensor C Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10047,
   "name": "5336_1_1_deg_F",
   "description": "Ext Air Sensor C Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "5337_1_1",
   "description": "Ext Air Sensor A Over Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10048,
   "name": "5337_1_1_deg_F",
   "description": "Ext Air Sensor A Over Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "5338_1_1",
   "description": "Ext Air Sensor A Under Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10049,
   "name": "5338_1_1_deg_F",
   "description": "Ext Air Sensor A Under Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "5574_1_1",
   "description": "Outside Air Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10050,
   "name": "5574_1_1_deg_F",
   "description": "Outside Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "5028_1",
   "description": "Return Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "5029_1",
   "description": "Humidity Set Point",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "5339_1",
   "description": "Return Humidity Set Point",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "5341_1",
   "description": "Humidity Proportional Band",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "5032_1",
   "description": "Humidity Dead Band",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "5342_1",
   "description": "Humidity Control Integration Time",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "5033_1",
   "description": "High Return Humidity Threshold",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "5035_1",
   "description": "Low Return Humidity Threshold",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "5343_1",
   "description": "Today's High Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "5344_1",
   "description": "Today's High Humidity Time",
   "units": "Seconds since Midnight",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "5345_1",
   "description": "Today's Low Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "5346_1",
   "description": "Today's Low Humidity Time",
   "units": "Seconds since Midnight",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "6258_1",
   "description": "Dew Point Proportional Band",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10072,
   "name": "6258_1_deg_F",
   "description": "Dew Point Proportional Band",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "6259_1",
   "description": "Dew Point Dead Band",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10073,
   "name": "6259_1_deg_F",
   "description": "Dew Point Dead Band",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "6575_1",
   "description": "Dew Point Over Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10074,
   "name": "6575_1_deg_F",
   "description": "Dew Point Over Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "6576_1",
   "description": "Dew Point Under Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10075,
   "name": "6576_1_deg_F",
   "description": "Dew Point Under Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "4595_1_1",
   "description": "Ext Air Sensor A Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "4598_1_1",
   "description": "Ext Air Sensor B Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "5347_1_1",
   "description": "Ext Air Sensor C Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "5348_1_1",
   "description": "Ext Air Sensor A High Humidity Threshold",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "5350_1_1",
   "description": "Ext Air Sensor A Low Humidity Threshold",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "4596_1_1",
   "description": "Ext Air Sensor A Dew Point Temp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10087,
   "name": "4596_1_1_deg_F",
   "description": "Ext Air Sensor A Dew Point Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "4614_1_1",
   "description": "Ext Dew Point Over Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10088,
   "name": "4614_1_1_deg_F",
   "description": "Ext Dew Point Over Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "5576_1_1",
   "description": "Ext Dew Point Under Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10089,
   "name": "5576_1_1_deg_F",
   "description": "Ext Dew Point Under Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "5267_1_1",
   "description": "Compressor Hours (Compressor 1)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "5268_1_1",
   "description": "Compressor Hours Threshold (Compressor 1)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "5353_1_1",
   "description": "Dig Scroll Comp Discharge Temp (Compressor 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10099,
   "name": "5353_1_1_deg_F",
   "description": "Dig Scroll Comp Discharge Temp (Compressor 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "5619_1_1",
   "description": "Digital Scroll Compressor Loading (Compressor 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "6241_1_1",
   "description": "Tandem 'B' Compressor Hours (Compressor 1)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "6688_1_1",
   "description": "Compressor Suction Pressure (Compressor 1)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "5267_1_2",
   "description": "Compressor Hours (Compressor 2)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "5268_1_2",
   "description": "Compressor Hours Threshold (Compressor 2)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "5353_1_2",
   "description": "Dig Scroll Comp Discharge Temp (Compressor 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10112,
   "name": "5353_1_2_deg_F",
   "description": "Dig Scroll Comp Discharge Temp (Compressor 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "5619_1_2",
   "description": "Digital Scroll Compressor Loading (Compressor 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "6241_1_2",
   "description": "Tandem 'B' Compressor Hours (Compressor 2)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "6688_1_2",
   "description": "Compressor Suction Pressure (Compressor 2)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2235,
   "name": "5353_1_3",
   "description": "Dig Scroll Comp Discharge Temp (Compressor 3)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12235,
   "name": "5353_1_3_deg_F",
   "description": "Dig Scroll Comp Discharge Temp (Compressor 3)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2236,
   "name": "5619_1_3",
   "description": "Digital Scroll Compressor Loading (Compressor 3)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2237,
   "name": "5267_1_3",
   "description": "Compressor Hours (Compressor 3)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2238,
   "name": "6241_1_3",
   "description": "Tandem 'B' Compressor Hours (Compressor 3)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2239,
   "name": "5268_1_3",
   "description": "Compressor Hours Threshold (Compressor 3)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2240,
   "name": "6688_1_3",
   "description": "Compressor Suction Pressure (Compressor 3)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2250,
   "name": "5353_1_4",
   "description": "Dig Scroll Comp Discharge Temp (Compressor 4)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12250,
   "name": "5353_1_4_deg_F",
   "description": "Dig Scroll Comp Discharge Temp (Compressor 4)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2251,
   "name": "5619_1_4",
   "description": "Digital Scroll Compressor Loading (Compressor 4)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2252,
   "name": "5267_1_4",
   "description": "Compressor Hours (Compressor 4)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2253,
   "name": "6241_1_4",
   "description": "Tandem 'B' Compressor Hours (Compressor 4)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2254,
   "name": "5268_1_4",
   "description": "Compressor Hours Threshold (Compressor 4)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2255,
   "name": "6688_1_4",
   "description": "Compressor Suction Pressure (Compressor 4)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "5356_1",
   "description": "Free Cooling Internal Temperature Delta",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10123,
   "name": "5356_1_deg_F",
   "description": "Free Cooling Internal Temperature Delta",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "5358_1",
   "description": "Free Cooling Fluid Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10124,
   "name": "5358_1_deg_F",
   "description": "Free Cooling Fluid Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "5360_1",
   "description": "Minimum Chilled Water Temp Set Point",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10125,
   "name": "5360_1_deg_F",
   "description": "Minimum Chilled Water Temp Set Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "5304_1",
   "description": "Free Cooling Valve Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "5305_1",
   "description": "Free Cooling Valve Hours Threshold",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "5614_1",
   "description": "Chilled Water Valve Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "6452_1",
   "description": "Chilled Water Valve Operating Hours Threshold",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "6759_1",
   "description": "Fluid Free Cooling Lockout Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10130,
   "name": "6759_1_deg_F",
   "description": "Fluid Free Cooling Lockout Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "5363_1",
   "description": "Hot Water / Hot Gas Valve Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "5364_1",
   "description": "Hot Water / Hot Gas Valve Hours Threshold",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 140,
   "name": "6761_1",
   "description": "Dehum Reheat Low Limit Set Point",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10140,
   "name": "6761_1_deg_F",
   "description": "Dehum Reheat Low Limit Set Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 141,
   "name": "6762_1",
   "description": "Dehum Reheat Low Limit 1",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10141,
   "name": "6762_1_deg_F",
   "description": "Dehum Reheat Low Limit 1",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 142,
   "name": "6763_1",
   "description": "Dehum Reheat Low Limit 2",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10142,
   "name": "6763_1_deg_F",
   "description": "Dehum Reheat Low Limit 2",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "6764_1",
   "description": "Dehum Reheat Proportional Band",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10143,
   "name": "6764_1_deg_F",
   "description": "Dehum Reheat Proportional Band",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "5366_1_1",
   "description": "Electric Reheater Hours (Electric Reheater 1)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "5367_1_1",
   "description": "Electric Reheater Hours Threshold (Electric Reheater 1)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 162,
   "name": "5366_1_2",
   "description": "Electric Reheater Hours (Electric Reheater 2)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 163,
   "name": "5367_1_2",
   "description": "Electric Reheater Hours Threshold (Electric Reheater 2)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 174,
   "name": "5366_1_3",
   "description": "Electric Reheater Hours (Electric Reheater 3)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 175,
   "name": "5367_1_3",
   "description": "Electric Reheater Hours Threshold (Electric Reheater 3)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 186,
   "name": "5369_1",
   "description": "Humidifier Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 187,
   "name": "5370_1",
   "description": "Humidifier Hours Threshold",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 188,
   "name": "5445_1",
   "description": "Infrared Humidifier Flush Rate",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 189,
   "name": "6765_1",
   "description": "Return Temp Threshold for Humidifier Disable",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10189,
   "name": "6765_1_deg_F",
   "description": "Return Temp Threshold for Humidifier Disable",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 190,
   "name": "6766_1",
   "description": "Return Temp Hysteresis for Humidifier Disable",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10190,
   "name": "6766_1_deg_F",
   "description": "Return Temp Hysteresis for Humidifier Disable",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 199,
   "name": "5371_1",
   "description": "Dehumidifier Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "5372_1",
   "description": "Dehumidifier Hours Threshold",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 211,
   "name": "5050_1",
   "description": "Fan Speed Maximum Set Point",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 212,
   "name": "5374_1",
   "description": "Fan Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 213,
   "name": "5375_1",
   "description": "Fan Hours Threshold",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 214,
   "name": "5051_1",
   "description": "Fan Speed Minimum Set Point",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 215,
   "name": "5585_1",
   "description": "Fan Speed Temperature Set Point",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10215,
   "name": "5585_1_deg_F",
   "description": "Fan Speed Temperature Set Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 216,
   "name": "6772_1",
   "description": "Fan Back Draft Speed Set Point",
   "units": "VDC",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 217,
   "name": "6768_1",
   "description": "Fan Speed Temp Control Proportional Band",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10217,
   "name": "6768_1_deg_F",
   "description": "Fan Speed Temp Control Proportional Band",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 218,
   "name": "6769_1",
   "description": "Fan Speed Temp Control Integration Time",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 219,
   "name": "6770_1",
   "description": "Fan Speed Temperature Dead Band",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10219,
   "name": "6770_1_deg_F",
   "description": "Fan Speed Temperature Dead Band",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 220,
   "name": "8252_1",
   "description": "Fan Speed Min Dehum",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2631,
   "name": "8103_1_1",
   "description": "Fan Power (Supply Fan Status 1)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2632,
   "name": "8104_1_1",
   "description": "Fan Current (Supply Fan Status 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2633,
   "name": "8487_1_1",
   "description": "Supply Fan Measured Speed (Supply Fan Status 1)",
   "units": "RPM",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2643,
   "name": "8103_1_2",
   "description": "Fan Power (Supply Fan Status 2)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2644,
   "name": "8104_1_2",
   "description": "Fan Current (Supply Fan Status 2)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2645,
   "name": "8487_1_2",
   "description": "Supply Fan Measured Speed (Supply Fan Status 2)",
   "units": "RPM",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2655,
   "name": "8103_1_3",
   "description": "Fan Power (Supply Fan Status 3)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2656,
   "name": "8104_1_3",
   "description": "Fan Current (Supply Fan Status 3)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2667,
   "name": "8103_1_4",
   "description": "Fan Power (Supply Fan Status 4)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2668,
   "name": "8104_1_4",
   "description": "Fan Current (Supply Fan Status 4)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2679,
   "name": "8103_1_5",
   "description": "Fan Power (Supply Fan Status 5)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2680,
   "name": "8104_1_5",
   "description": "Fan Current (Supply Fan Status 5)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2691,
   "name": "8103_1_6",
   "description": "Fan Power (Supply Fan Status 6)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2692,
   "name": "8104_1_6",
   "description": "Fan Current (Supply Fan Status 6)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2703,
   "name": "8103_1_7",
   "description": "Fan Power (Supply Fan Status 7)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2704,
   "name": "8104_1_7",
   "description": "Fan Current (Supply Fan Status 7)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2715,
   "name": "8103_1_8",
   "description": "Fan Power (Supply Fan Status 8)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2716,
   "name": "8104_1_8",
   "description": "Fan Current (Supply Fan Status 8)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2727,
   "name": "8103_1_9",
   "description": "Fan Power (Supply Fan Status 9)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2728,
   "name": "8104_1_9",
   "description": "Fan Current (Supply Fan Status 9)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2739,
   "name": "8103_1_10",
   "description": "Fan Power (Supply Fan Status 10)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2740,
   "name": "8104_1_10",
   "description": "Fan Current (Supply Fan Status 10)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2751,
   "name": "8103_1_11",
   "description": "Fan Power (Supply Fan Status 11)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2752,
   "name": "8104_1_11",
   "description": "Fan Current (Supply Fan Status 11)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2763,
   "name": "8103_1_12",
   "description": "Fan Power (Supply Fan Status 12)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2764,
   "name": "8104_1_12",
   "description": "Fan Current (Supply Fan Status 12)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2775,
   "name": "8103_1_13",
   "description": "Fan Power (Supply Fan Status 13)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2776,
   "name": "8104_1_13",
   "description": "Fan Current (Supply Fan Status 13)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2787,
   "name": "8103_1_14",
   "description": "Fan Power (Supply Fan Status 14)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2788,
   "name": "8104_1_14",
   "description": "Fan Current (Supply Fan Status 14)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2799,
   "name": "8103_1_15",
   "description": "Fan Power (Supply Fan Status 15, 16)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2800,
   "name": "8104_1_15",
   "description": "Fan Current (Supply Fan Status 15, 16)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2811,
   "name": "8103_1_16",
   "description": "Fan Power (Supply Fan Status 16)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2812,
   "name": "8104_1_16",
   "description": "Fan Current (Supply Fan Status 16)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2813,
   "name": "8487_1_16",
   "description": "Supply Fan Measured Speed (Supply Fan Status 16)",
   "units": "RPM",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 224,
   "name": "5378_1",
   "description": "Analog Input Reading (Analog Inputs 1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 235,
   "name": "5378_2",
   "description": "Analog Input Reading (Analog Inputs 2)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 246,
   "name": "5378_3",
   "description": "Analog Input Reading (Analog Inputs 3)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 257,
   "name": "5378_4",
   "description": "Analog Input Reading (Analog Inputs 4)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2930,
   "name": "5378_5",
   "description": "Analog Input Reading (Analog Inputs 5)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2941,
   "name": "5378_6",
   "description": "Analog Input Reading (Analog Inputs 6)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2952,
   "name": "5378_7",
   "description": "Analog Input Reading (Analog Inputs 7)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2963,
   "name": "5378_8",
   "description": "Analog Input Reading (Analog Inputs 8)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2974,
   "name": "5378_9",
   "description": "Analog Input Reading (Analog Inputs 9)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2985,
   "name": "5378_10",
   "description": "Analog Input Reading (Analog Inputs 10)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2996,
   "name": "5378_11",
   "description": "Analog Input Reading (Analog Inputs 11)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3007,
   "name": "5378_12",
   "description": "Analog Input Reading (Analog Inputs 12)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3018,
   "name": "8473_1",
   "description": "Analog Output (Analog Outputs 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3029,
   "name": "8473_2",
   "description": "Analog Output (Analog Outputs 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3073,
   "name": "8473_6",
   "description": "Analog Output (Analog Outputs 6)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 268,
   "name": "5075_1",
   "description": "BMS Timeout Period",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 269,
   "name": "4710_1",
   "description": "Auto Restart Delay",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 270,
   "name": "5314_1",
   "description": "Standby Units (Unit Information)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 271,
   "name": "6121_1",
   "description": "Unit to Unit Group",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 272,
   "name": "6120_1",
   "description": "Unit to Unit Address",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "5333_1",
   "description": "Return Air Temperature Set Point",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10032,
   "name": "5333_1_deg_F",
   "description": "Return Air Temperature Set Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "4291_1",
   "description": "Return Air Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10031,
   "name": "4291_1_deg_F",
   "description": "Return Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 280,
   "name": "5077_1",
   "description": "Fan Speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 281,
   "name": "5078_1",
   "description": "Compressor Utilization",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 282,
   "name": "5379_1",
   "description": "Free Cooling Valve Open Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 283,
   "name": "4870_1",
   "description": "Maintenance Ramp",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 284,
   "name": "4868_1",
   "description": "Calculated Next Maintenance Month",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 285,
   "name": "4869_1",
   "description": "Calculated Next Maintenance Year",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 286,
   "name": "5380_1",
   "description": "Hot Water / Hot Gas Valve Open Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 287,
   "name": "5080_1",
   "description": "Reheat Utilization",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 288,
   "name": "5081_1",
   "description": "Humidifier Utilization",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 289,
   "name": "5079_1",
   "description": "Dehumidifier Utilization",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 290,
   "name": "5490_1",
   "description": "Cooling Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 291,
   "name": "5606_1",
   "description": "Adjusted Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 292,
   "name": "5004_1",
   "description": "Return Dew Point",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10292,
   "name": "5004_1_deg_F",
   "description": "Return Dew Point",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 293,
   "name": "5607_1",
   "description": "Actual Air Temperature Set Point",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10293,
   "name": "5607_1_deg_F",
   "description": "Actual Air Temperature Set Point",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 294,
   "name": "5608_1",
   "description": "Actual Humidity Set Point",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 295,
   "name": "5575_1",
   "description": "Dew Point Set Point",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10295,
   "name": "5575_1_deg_F",
   "description": "Dew Point Set Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 296,
   "name": "5615_1",
   "description": "Cooling Control Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10296,
   "name": "5615_1_deg_F",
   "description": "Cooling Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 297,
   "name": "5616_1",
   "description": "Fan Speed Control Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10297,
   "name": "5616_1_deg_F",
   "description": "Fan Speed Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 298,
   "name": "5904_1",
   "description": "Unit Cooling Load",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 299,
   "name": "6134_1",
   "description": "Unit Calculated Airflow",
   "units": "m3/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 300,
   "name": "4293_1",
   "description": "System Date and Time",
   "units": "Secs since Epoch (UTC)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 312,
   "name": "5589_1",
   "description": "Remote Sensor Over Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10312,
   "name": "5589_1_deg_F",
   "description": "Remote Sensor Over Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 313,
   "name": "5590_1",
   "description": "Remote Sensor Under Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10313,
   "name": "5590_1_deg_F",
   "description": "Remote Sensor Under Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 314,
   "name": "5007_1",
   "description": "Remote Sensor Average Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10314,
   "name": "5007_1_deg_F",
   "description": "Remote Sensor Average Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 315,
   "name": "5006_1",
   "description": "Remote Sensor Maximum Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10315,
   "name": "5006_1_deg_F",
   "description": "Remote Sensor Maximum Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 316,
   "name": "5591_1",
   "description": "Remote Sensor System Average Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10316,
   "name": "5591_1_deg_F",
   "description": "Remote Sensor System Average Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 317,
   "name": "5592_1",
   "description": "Remote Sensor System Maximum Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10317,
   "name": "5592_1_deg_F",
   "description": "Remote Sensor System Maximum Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 329,
   "name": "5059_1_1",
   "description": "Remote Sensor Temperature (Remote Sensor 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10329,
   "name": "5059_1_1_deg_F",
   "description": "Remote Sensor Temperature (Remote Sensor 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 341,
   "name": "5059_1_2",
   "description": "Remote Sensor Temperature (Remote Sensor 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10341,
   "name": "5059_1_2_deg_F",
   "description": "Remote Sensor Temperature (Remote Sensor 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 353,
   "name": "5059_1_3",
   "description": "Remote Sensor Temperature (Remote Sensor 3)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10353,
   "name": "5059_1_3_deg_F",
   "description": "Remote Sensor Temperature (Remote Sensor 3)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 365,
   "name": "5059_1_4",
   "description": "Remote Sensor Temperature (Remote Sensor 4)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10365,
   "name": "5059_1_4_deg_F",
   "description": "Remote Sensor Temperature (Remote Sensor 4)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377,
   "name": "5059_1_5",
   "description": "Remote Sensor Temperature (Remote Sensor 5)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10377,
   "name": "5059_1_5_deg_F",
   "description": "Remote Sensor Temperature (Remote Sensor 5)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 389,
   "name": "5059_1_6",
   "description": "Remote Sensor Temperature (Remote Sensor 6)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10389,
   "name": "5059_1_6_deg_F",
   "description": "Remote Sensor Temperature (Remote Sensor 6)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 401,
   "name": "5059_1_7",
   "description": "Remote Sensor Temperature (Remote Sensor 7)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10401,
   "name": "5059_1_7_deg_F",
   "description": "Remote Sensor Temperature (Remote Sensor 7)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 413,
   "name": "5059_1_8",
   "description": "Remote Sensor Temperature (Remote Sensor 8)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10413,
   "name": "5059_1_8_deg_F",
   "description": "Remote Sensor Temperature (Remote Sensor 8)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 425,
   "name": "5059_1_9",
   "description": "Remote Sensor Temperature (Remote Sensor 9)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10425,
   "name": "5059_1_9_deg_F",
   "description": "Remote Sensor Temperature (Remote Sensor 9)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 437,
   "name": "5059_1_10",
   "description": "Remote Sensor Temperature (Remote Sensor 10)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10437,
   "name": "5059_1_10_deg_F",
   "description": "Remote Sensor Temperature (Remote Sensor 10)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 461,
   "name": "5626_1",
   "description": "Static Pressure Set Point",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2121,
   "name": "5626_1",
   "description": "Static Pressure Set Point",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 462,
   "name": "5627_1",
   "description": "Unit Static Pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2122,
   "name": "5627_1",
   "description": "Unit Static Pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 463,
   "name": "5628_1",
   "description": "System Static Pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2123,
   "name": "5628_1",
   "description": "System Static Pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 505,
   "name": "5299_1",
   "description": "Pump Hours Threshold",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 523,
   "name": "5298_1_1",
   "description": "Pump Hours (Pump 1)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 522,
   "name": "5634_1_1",
   "description": "Pump Speed (Pump 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 535,
   "name": "5635_1_1",
   "description": "Pump Inlet Refrigerant Temperature (Pump 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10535,
   "name": "5635_1_1_deg_F",
   "description": "Pump Inlet Refrigerant Temperature (Pump 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 537,
   "name": "5639_1_1",
   "description": "Pump Outlet Refrigerant Temperature (Pump 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10537,
   "name": "5639_1_1_deg_F",
   "description": "Pump Outlet Refrigerant Temperature (Pump 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 526,
   "name": "5298_1_2",
   "description": "Pump Hours (Pump 2)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 525,
   "name": "5634_1_2",
   "description": "Pump Speed (Pump 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 538,
   "name": "5635_1_2",
   "description": "Pump Inlet Refrigerant Temperature (Pump 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10538,
   "name": "5635_1_2_deg_F",
   "description": "Pump Inlet Refrigerant Temperature (Pump 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 540,
   "name": "5639_1_2",
   "description": "Pump Outlet Refrigerant Temperature (Pump 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10540,
   "name": "5639_1_2_deg_F",
   "description": "Pump Outlet Refrigerant Temperature (Pump 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2274,
   "name": "5298_1_3",
   "description": "Pump Hours (Pump 3)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2275,
   "name": "5634_1_3",
   "description": "Pump Speed (Pump 3)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2276,
   "name": "5635_1_3",
   "description": "Pump Inlet Refrigerant Temperature (Pump 3)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12276,
   "name": "5635_1_3_deg_F",
   "description": "Pump Inlet Refrigerant Temperature (Pump 3)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2277,
   "name": "5639_1_3",
   "description": "Pump Outlet Refrigerant Temperature (Pump 3)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12277,
   "name": "5639_1_3_deg_F",
   "description": "Pump Outlet Refrigerant Temperature (Pump 3)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2288,
   "name": "5298_1_4",
   "description": "Pump Hours (Pump 4)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2289,
   "name": "5634_1_4",
   "description": "Pump Speed (Pump 4)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2290,
   "name": "5635_1_4",
   "description": "Pump Inlet Refrigerant Temperature (Pump 4)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12290,
   "name": "5635_1_4_deg_F",
   "description": "Pump Inlet Refrigerant Temperature (Pump 4)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2291,
   "name": "5639_1_4",
   "description": "Pump Outlet Refrigerant Temperature (Pump 4)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12291,
   "name": "5639_1_4_deg_F",
   "description": "Pump Outlet Refrigerant Temperature (Pump 4)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 810,
   "name": "4096_1",
   "description": "System Input RMS A-N (Power Measurement 1)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 811,
   "name": "4098_1",
   "description": "System Input RMS B-N (Power Measurement 1)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 812,
   "name": "4100_1",
   "description": "System Input RMS C-N (Power Measurement 1)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 813,
   "name": "4113_1",
   "description": "System Input RMS Current Phase A (Power Measurement 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 814,
   "name": "4114_1",
   "description": "System Input RMS Current Phase B (Power Measurement 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 815,
   "name": "4115_1",
   "description": "System Input RMS Current Phase C (Power Measurement 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 816,
   "name": "5901_1",
   "description": "Instantaneous Power (Power Measurement 1)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 817,
   "name": "5900_1",
   "description": "Energy Consumption (Power Measurement 1)",
   "units": "kWh",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1900,
   "name": "4097_1",
   "description": "System Input RMS A-B (Power Measurement 1)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1901,
   "name": "4099_1",
   "description": "System Input RMS B-C (Power Measurement 1)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1902,
   "name": "4101_1",
   "description": "System Input RMS C-A (Power Measurement 1)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 820,
   "name": "4096_2",
   "description": "System Input RMS A-N (Power Measurement 2)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 821,
   "name": "4098_2",
   "description": "System Input RMS B-N (Power Measurement 2)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 822,
   "name": "4100_2",
   "description": "System Input RMS C-N (Power Measurement 2)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 823,
   "name": "4113_2",
   "description": "System Input RMS Current Phase A (Power Measurement 2)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 824,
   "name": "4114_2",
   "description": "System Input RMS Current Phase B (Power Measurement 2)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 825,
   "name": "4115_2",
   "description": "System Input RMS Current Phase C (Power Measurement 2)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 826,
   "name": "5901_2",
   "description": "Instantaneous Power (Power Measurement 2)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 827,
   "name": "5900_2",
   "description": "Energy Consumption (Power Measurement 2)",
   "units": "kWh",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1910,
   "name": "4097_2",
   "description": "System Input RMS A-B (Power Measurement 2)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1911,
   "name": "4099_2",
   "description": "System Input RMS B-C (Power Measurement 2)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1912,
   "name": "4101_2",
   "description": "System Input RMS C-A (Power Measurement 2)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 830,
   "name": "4096_3",
   "description": "System Input RMS A-N (Power Measurement 3)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 831,
   "name": "4098_3",
   "description": "System Input RMS B-N (Power Measurement 3)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 832,
   "name": "4100_3",
   "description": "System Input RMS C-N (Power Measurement 3)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 833,
   "name": "4113_3",
   "description": "System Input RMS Current Phase A (Power Measurement 3)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 834,
   "name": "4114_3",
   "description": "System Input RMS Current Phase B (Power Measurement 3)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 835,
   "name": "4115_3",
   "description": "System Input RMS Current Phase C (Power Measurement 3)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 836,
   "name": "5901_3",
   "description": "Instantaneous Power (Power Measurement 3)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 837,
   "name": "5900_3",
   "description": "Energy Consumption (Power Measurement 3)",
   "units": "kWh",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1920,
   "name": "4097_3",
   "description": "System Input RMS A-B (Power Measurement 3)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1921,
   "name": "4099_3",
   "description": "System Input RMS B-C (Power Measurement 3)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1922,
   "name": "4101_3",
   "description": "System Input RMS C-A (Power Measurement 3)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 840,
   "name": "4096_4",
   "description": "System Input RMS A-N (Power Measurement 4)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 841,
   "name": "4098_4",
   "description": "System Input RMS B-N (Power Measurement 4)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 842,
   "name": "4100_4",
   "description": "System Input RMS C-N (Power Measurement 4)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 843,
   "name": "4113_4",
   "description": "System Input RMS Current Phase A (Power Measurement 4)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 844,
   "name": "4114_4",
   "description": "System Input RMS Current Phase B (Power Measurement 4)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 845,
   "name": "4115_4",
   "description": "System Input RMS Current Phase C (Power Measurement 4)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 846,
   "name": "5901_4",
   "description": "Instantaneous Power (Power Measurement 4)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 847,
   "name": "5900_4",
   "description": "Energy Consumption (Power Measurement 4)",
   "units": "kWh",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1930,
   "name": "4097_4",
   "description": "System Input RMS A-B (Power Measurement 4)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1931,
   "name": "4099_4",
   "description": "System Input RMS B-C (Power Measurement 4)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1932,
   "name": "4101_4",
   "description": "System Input RMS C-A (Power Measurement 4)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 850,
   "name": "4096_5",
   "description": "System Input RMS A-N (Power Measurement 5)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 851,
   "name": "4098_5",
   "description": "System Input RMS B-N (Power Measurement 5)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 852,
   "name": "4100_5",
   "description": "System Input RMS C-N (Power Measurement 5)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 853,
   "name": "4113_5",
   "description": "System Input RMS Current Phase A (Power Measurement 5)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 854,
   "name": "4114_5",
   "description": "System Input RMS Current Phase B (Power Measurement 5)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 855,
   "name": "4115_5",
   "description": "System Input RMS Current Phase C (Power Measurement 5)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 856,
   "name": "5901_5",
   "description": "Instantaneous Power (Power Measurement 5)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 857,
   "name": "5900_5",
   "description": "Energy Consumption (Power Measurement 5)",
   "units": "kWh",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1940,
   "name": "4097_5",
   "description": "System Input RMS A-B (Power Measurement 5)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1941,
   "name": "4099_5",
   "description": "System Input RMS B-C (Power Measurement 5)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1942,
   "name": "4101_5",
   "description": "System Input RMS C-A (Power Measurement 5)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 860,
   "name": "4096_6",
   "description": "System Input RMS A-N (Power Measurement 6)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 861,
   "name": "4098_6",
   "description": "System Input RMS B-N (Power Measurement 6)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 862,
   "name": "4100_6",
   "description": "System Input RMS C-N (Power Measurement 6)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 863,
   "name": "4113_6",
   "description": "System Input RMS Current Phase A (Power Measurement 6)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 864,
   "name": "4114_6",
   "description": "System Input RMS Current Phase B (Power Measurement 6)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 865,
   "name": "4115_6",
   "description": "System Input RMS Current Phase C (Power Measurement 6)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 866,
   "name": "5901_6",
   "description": "Instantaneous Power (Power Measurement 6)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 867,
   "name": "5900_6",
   "description": "Energy Consumption (Power Measurement 6)",
   "units": "kWh",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1950,
   "name": "4097_6",
   "description": "System Input RMS A-B (Power Measurement 6)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1951,
   "name": "4099_6",
   "description": "System Input RMS B-C (Power Measurement 6)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1952,
   "name": "4101_6",
   "description": "System Input RMS C-A (Power Measurement 6)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 871,
   "name": "5897_1",
   "description": "Fluid Input Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10871,
   "name": "5897_1_deg_F",
   "description": "Fluid Input Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 872,
   "name": "5898_1",
   "description": "Fluid Output Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10872,
   "name": "5898_1_deg_F",
   "description": "Fluid Output Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1871,
   "name": "5897_2",
   "description": "Fluid Input Temperature (Fluid 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11871,
   "name": "5897_2_deg_F",
   "description": "Fluid Input Temperature (Fluid 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1872,
   "name": "5898_2",
   "description": "Fluid Output Temperature (Fluid 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11872,
   "name": "5898_2_deg_F",
   "description": "Fluid Output Temperature (Fluid 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 881,
   "name": "5899_1",
   "description": "Fluid Flow Rate (Circuit)",
   "units": "l/min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 882,
   "name": "8488_1",
   "description": "Fluid Control Valve Position (Circuit)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 891,
   "name": "5899_2",
   "description": "Fluid Flow Rate (Circuit 2)",
   "units": "l/min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 892,
   "name": "8488_2",
   "description": "Fluid Control Valve Position (Circuit 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 901,
   "name": "5905_1_1",
   "description": "Circuit Cooling Load (Cooling Load 1)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 911,
   "name": "5905_1_2",
   "description": "Circuit Cooling Load (Cooling Load 2)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1960,
   "name": "5964_1_1",
   "description": "Raw Auxiliary Air Temperature",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11960,
   "name": "5964_1_1_deg_F",
   "description": "Raw Auxiliary Air Temperature",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1961,
   "name": "5965_1_1",
   "description": "Actual Auxiliary Air Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11961,
   "name": "5965_1_1_deg_F",
   "description": "Actual Auxiliary Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1981,
   "name": "6101_1",
   "description": "Expected Condenser Unit Count",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 529,
   "name": "5548_1_1",
   "description": "Condenser Low Noise Mode Max Fan Speed",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 530,
   "name": "5549_1_1",
   "description": "Condenser Normal Mode Max Fan Speed",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 531,
   "name": "5552_1_1",
   "description": "Condenser Low Noise Mode Start Time",
   "units": "Seconds since Midnight",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 532,
   "name": "5553_1_1",
   "description": "Condenser Low Noise Mode Stop Time",
   "units": "Seconds since Midnight",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 533,
   "name": "5550_1_1",
   "description": "Condenser Low Noise Mode - Interval Days",
   "units": "",
   "access": "W",
   "states": "1=Monday, 2=Tuesday, 4=Wednesday, 8=Thursday, 16=Friday, 32=Saturday, 64=Sunday"
  },
  {
   "type": "AV",
   "instance": 534,
   "name": "5551_1_1",
   "description": "Condenser Low Noise Mode - Full Days",
   "units": "",
   "access": "W",
   "states": "1=Monday, 2=Tuesday, 4=Wednesday, 8=Thursday, 16=Friday, 32=Saturday, 64=Sunday"
  },
  {
   "type": "AV",
   "instance": 1992,
   "name": "5534_1_1",
   "description": "Condenser Outside Air Temperature (Condenser 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11992,
   "name": "5534_1_1_deg_F",
   "description": "Condenser Outside Air Temperature (Condenser 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1993,
   "name": "5534_1_2",
   "description": "Condenser Outside Air Temperature (Condenser 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11993,
   "name": "5534_1_2_deg_F",
   "description": "Condenser Outside Air Temperature (Condenser 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2307,
   "name": "5534_1_3",
   "description": "Condenser Outside Air Temperature (Condenser 3)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12307,
   "name": "5534_1_3_deg_F",
   "description": "Condenser Outside Air Temperature (Condenser 3)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2318,
   "name": "5534_1_4",
   "description": "Condenser Outside Air Temperature (Condenser 4)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12318,
   "name": "5534_1_4_deg_F",
   "description": "Condenser Outside Air Temperature (Condenser 4)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2004,
   "name": "6103_1_1",
   "description": "Condenser Refrigerant Pressure (Circuit 1)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2006,
   "name": "6102_1_1",
   "description": "Condenser Supply Refrigerant Temperature (Circuit 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12006,
   "name": "6102_1_1_deg_F",
   "description": "Condenser Supply Refrigerant Temperature (Circuit 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2005,
   "name": "6103_1_2",
   "description": "Condenser Refrigerant Pressure (Circuit 2)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2007,
   "name": "6102_1_2",
   "description": "Condenser Supply Refrigerant Temperature (Circuit 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12007,
   "name": "6102_1_2_deg_F",
   "description": "Condenser Supply Refrigerant Temperature (Circuit 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2338,
   "name": "6103_1_3",
   "description": "Condenser Refrigerant Pressure (Circuit 3)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2339,
   "name": "6102_1_3",
   "description": "Condenser Supply Refrigerant Temperature (Circuit 3)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12339,
   "name": "6102_1_3_deg_F",
   "description": "Condenser Supply Refrigerant Temperature (Circuit 3)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2350,
   "name": "6103_1_4",
   "description": "Condenser Refrigerant Pressure (Circuit 4)",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2351,
   "name": "6102_1_4",
   "description": "Condenser Supply Refrigerant Temperature (Circuit 4)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12351,
   "name": "6102_1_4_deg_F",
   "description": "Condenser Supply Refrigerant Temperature (Circuit 4)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2018,
   "name": "5276_1_1_1",
   "description": "Condenser Fan Speed (Condenser 1 Fan 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2026,
   "name": "5538_1_1_1",
   "description": "Condenser Fan Power (Condenser 1 Fan 1)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2034,
   "name": "6244_1_1_1",
   "description": "Condenser Fan Current (Condenser 1 Fan 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2019,
   "name": "5276_1_1_2",
   "description": "Condenser Fan Speed (Condenser 1 Fan 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2027,
   "name": "5538_1_1_2",
   "description": "Condenser Fan Power (Condenser 1 Fan 2)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2035,
   "name": "6244_1_1_2",
   "description": "Condenser Fan Current (Condenser 1 Fan 2)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2020,
   "name": "5276_1_1_3",
   "description": "Condenser Fan Speed (Condenser 1 Fan 3)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2028,
   "name": "5538_1_1_3",
   "description": "Condenser Fan Power (Condenser 1 Fan 3)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2036,
   "name": "6244_1_1_3",
   "description": "Condenser Fan Current (Condenser 1 Fan 3)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2021,
   "name": "5276_1_1_4",
   "description": "Condenser Fan Speed (Condenser 1 Fan 4)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2029,
   "name": "5538_1_1_4",
   "description": "Condenser Fan Power (Condenser 1 Fan 4)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2037,
   "name": "6244_1_1_4",
   "description": "Condenser Fan Current (Condenser 1 Fan 4)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2022,
   "name": "5276_1_2_1",
   "description": "Condenser Fan Speed (Condenser 2 Fan 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2030,
   "name": "5538_1_2_1",
   "description": "Condenser Fan Power (Condenser 2 Fan 1)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2038,
   "name": "6244_1_2_1",
   "description": "Condenser Fan Current (Condenser 2 Fan 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2023,
   "name": "5276_1_2_2",
   "description": "Condenser Fan Speed (Condenser 2 Fan 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2031,
   "name": "5538_1_2_2",
   "description": "Condenser Fan Power (Condenser 2 Fan 2)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2039,
   "name": "6244_1_2_2",
   "description": "Condenser Fan Current (Condenser 2 Fan 2)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2024,
   "name": "5276_1_2_3",
   "description": "Condenser Fan Speed (Condenser 2 Fan 3)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2032,
   "name": "5538_1_2_3",
   "description": "Condenser Fan Power (Condenser 2 Fan 3)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2040,
   "name": "6244_1_2_3",
   "description": "Condenser Fan Current (Condenser 2 Fan 3)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2025,
   "name": "5276_1_2_4",
   "description": "Condenser Fan Speed (Condenser 2 Fan 4)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2033,
   "name": "5538_1_2_4",
   "description": "Condenser Fan Power (Condenser 2 Fan 4)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2041,
   "name": "6244_1_2_4",
   "description": "Condenser Fan Current (Condenser 2 Fan 4)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2371,
   "name": "5276_1_3_1",
   "description": "Condenser Fan Speed (Condenser 3 Fan 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2372,
   "name": "5538_1_3_1",
   "description": "Condenser Fan Power (Condenser 3 Fan 1)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2373,
   "name": "6244_1_3_1",
   "description": "Condenser Fan Current (Condenser 3 Fan 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2384,
   "name": "5276_1_3_2",
   "description": "Condenser Fan Speed (Condenser 3 Fan 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2385,
   "name": "5538_1_3_2",
   "description": "Condenser Fan Power (Condenser 3 Fan 2)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2386,
   "name": "6244_1_3_2",
   "description": "Condenser Fan Current (Condenser 3 Fan 2)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2397,
   "name": "5276_1_3_3",
   "description": "Condenser Fan Speed (Condenser 3 Fan 3)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2398,
   "name": "5538_1_3_3",
   "description": "Condenser Fan Power (Condenser 3 Fan 3)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2399,
   "name": "6244_1_3_3",
   "description": "Condenser Fan Current (Condenser 3 Fan 3)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2410,
   "name": "5276_1_3_4",
   "description": "Condenser Fan Speed (Condenser 3 Fan 4)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2411,
   "name": "5538_1_3_4",
   "description": "Condenser Fan Power (Condenser 3 Fan 4)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2412,
   "name": "6244_1_3_4",
   "description": "Condenser Fan Current (Condenser 3 Fan 4)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2423,
   "name": "5276_1_4_1",
   "description": "Condenser Fan Speed (Condenser 4 Fan 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2424,
   "name": "5538_1_4_1",
   "description": "Condenser Fan Power (Condenser 4 Fan 1)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2425,
   "name": "6244_1_4_1",
   "description": "Condenser Fan Current (Condenser 4 Fan 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2436,
   "name": "5276_1_4_2",
   "description": "Condenser Fan Speed (Condenser 4 Fan 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2437,
   "name": "5538_1_4_2",
   "description": "Condenser Fan Power (Condenser 4 Fan 2)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2438,
   "name": "6244_1_4_2",
   "description": "Condenser Fan Current (Condenser 4 Fan 2)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2449,
   "name": "5276_1_4_3",
   "description": "Condenser Fan Speed (Condenser 4 Fan 3)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2450,
   "name": "5538_1_4_3",
   "description": "Condenser Fan Power (Condenser 4 Fan 3)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2451,
   "name": "6244_1_4_3",
   "description": "Condenser Fan Current (Condenser 4 Fan 3)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2462,
   "name": "5276_1_4_4",
   "description": "Condenser Fan Speed (Condenser 4 Fan 4)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2463,
   "name": "5538_1_4_4",
   "description": "Condenser Fan Power (Condenser 4 Fan 4)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2464,
   "name": "6244_1_4_4",
   "description": "Condenser Fan Current (Condenser 4 Fan 4)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2044,
   "name": "6085_1",
   "description": "Actual Cold Aisle Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2045,
   "name": "6086_1",
   "description": "Actual Cold Aisle Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12045,
   "name": "6086_1_deg_F",
   "description": "Actual Cold Aisle Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2046,
   "name": "6087_1",
   "description": "Cold Aisle Cascade Fan Speed Max Set Point",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2047,
   "name": "6088_1",
   "description": "Cold Aisle Fan Speed Min Set Point",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2048,
   "name": "6089_1",
   "description": "Cold Aisle Fan Speed Max Set Point",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2049,
   "name": "6096_1",
   "description": "Humidification Fan Speed Min Set Point",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2050,
   "name": "6097_1",
   "description": "Heating Fan Speed Min Set Point",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2051,
   "name": "6098_1",
   "description": "Dehumidification Fan Speed Min Set Point",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2052,
   "name": "6099_1",
   "description": "Back Draft Control Fan Speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2053,
   "name": "6302_1",
   "description": "Air Filter Differential Pressure (PCW-PDX)",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2213,
   "name": "6302_1",
   "description": "Air Filter Differential Pressure (PCW-PDX)",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2147,
   "name": "6307_1_1",
   "description": "Cold Aisle Sensor Air Temperature (Cold Aisle Sensor 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12147,
   "name": "6307_1_1_deg_F",
   "description": "Cold Aisle Sensor Air Temperature (Cold Aisle Sensor 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2148,
   "name": "6308_1_1",
   "description": "Cold Aisle Sensor Humidity (Cold Aisle Sensor 1)",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2159,
   "name": "6307_1_2",
   "description": "Cold Aisle Sensor Air Temperature (Cold Aisle Sensor 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12159,
   "name": "6307_1_2_deg_F",
   "description": "Cold Aisle Sensor Air Temperature (Cold Aisle Sensor 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2160,
   "name": "6308_1_2",
   "description": "Cold Aisle Sensor Humidity (Cold Aisle Sensor 2)",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2171,
   "name": "6307_1_3",
   "description": "Cold Aisle Sensor Air Temperature (Cold Aisle Sensor 3)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12171,
   "name": "6307_1_3_deg_F",
   "description": "Cold Aisle Sensor Air Temperature (Cold Aisle Sensor 3)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2172,
   "name": "6308_1_3",
   "description": "Cold Aisle Sensor Humidity (Cold Aisle Sensor 3)",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2488,
   "name": "6825_1_1",
   "description": "Cooling Fluid Source Temperature (Fluid Source 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12488,
   "name": "6825_1_1_deg_F",
   "description": "Cooling Fluid Source Temperature (Fluid Source 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2489,
   "name": "6825_1_2",
   "description": "Cooling Fluid Source Temperature (Fluid Source 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12489,
   "name": "6825_1_2_deg_F",
   "description": "Cooling Fluid Source Temperature (Fluid Source 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2100,
   "name": "6234_1",
   "description": "Super Saver Call For Cooling",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2135,
   "name": "6263_1",
   "description": "Thermal Control Override - Temperature Call",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2136,
   "name": "6265_1",
   "description": "Thermal Control Override - Humidity Call",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2189,
   "name": "6311_1_1",
   "description": "Chilled Water Inlet Temperature (Chilled Water Circuit 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12189,
   "name": "6311_1_1_deg_F",
   "description": "Chilled Water Inlet Temperature (Chilled Water Circuit 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2190,
   "name": "6312_1_1",
   "description": "Chilled Water Outlet Temperature (Chilled Water Circuit 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12190,
   "name": "6312_1_1_deg_F",
   "description": "Chilled Water Outlet Temperature (Chilled Water Circuit 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2201,
   "name": "6311_1_2",
   "description": "Chilled Water Inlet Temperature (Chilled Water Circuit 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12201,
   "name": "6311_1_2_deg_F",
   "description": "Chilled Water Inlet Temperature (Chilled Water Circuit 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2202,
   "name": "6312_1_2",
   "description": "Chilled Water Outlet Temperature (Chilled Water Circuit 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12202,
   "name": "6312_1_2_deg_F",
   "description": "Chilled Water Outlet Temperature (Chilled Water Circuit 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2476,
   "name": "6797_1",
   "description": "EconoPhase Proportional Band Switchover",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2501,
   "name": "6820_1",
   "description": "Event Log Record Counter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2502,
   "name": "6821_1",
   "description": "Audit Log Record Counter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2526,
   "name": "6780_1_1",
   "description": "Unit Cascade On Delay",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2527,
   "name": "6781_1_1",
   "description": "Quick Start Unit Cascade On Delay",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2528,
   "name": "6779_1_1",
   "description": "Unit Cascade Control Delay",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2529,
   "name": "6783_1_1",
   "description": "Teamwork Average Calculation Unit Count",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2541,
   "name": "5314_1_1",
   "description": "Standby Units (Standby/Rotation)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2542,
   "name": "6122_1_1",
   "description": "Networked Unit Rotation Time",
   "units": "Seconds since Midnight",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2543,
   "name": "6123_1_1",
   "description": "Networked Unit Rotation Count",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2554,
   "name": "7130_1_1",
   "description": "Power Source: L1- L2 voltage (Power Source 1)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2555,
   "name": "7131_1_1",
   "description": "Power Source: L2- L3 voltage (Power Source 1)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2556,
   "name": "7132_1_1",
   "description": "Power Source: L3- L1 voltage (Power Source 1)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2557,
   "name": "7133_1_1",
   "description": "Power Source: Line Frequency (Power Source 1)",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2558,
   "name": "7134_1_1",
   "description": "Power Source: Breaker Operation Count (Power Source 1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2569,
   "name": "7130_1_2",
   "description": "Power Source: L1- L2 voltage (Power Source 2)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2570,
   "name": "7131_1_2",
   "description": "Power Source: L2- L3 voltage (Power Source 2)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2571,
   "name": "7132_1_2",
   "description": "Power Source: L3- L1 voltage (Power Source 2)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2572,
   "name": "7133_1_2",
   "description": "Power Source: Line Frequency (Power Source 2)",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2573,
   "name": "7134_1_2",
   "description": "Power Source: Breaker Operation Count (Power Source 2)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2584,
   "name": "4643_1",
   "description": "Supply Fluid Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12584,
   "name": "4643_1_deg_F",
   "description": "Supply Fluid Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2585,
   "name": "5288_1",
   "description": "Return Fluid Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12585,
   "name": "5288_1_deg_F",
   "description": "Return Fluid Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2586,
   "name": "7468_1",
   "description": "Flow Rate",
   "units": "l/min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2587,
   "name": "5491_1",
   "description": "Cooling Capacity",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2588,
   "name": "7469_1",
   "description": "Pump Speed (Fluid Loop)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2589,
   "name": "7470_1",
   "description": "Flow Set Point",
   "units": "l/min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2590,
   "name": "7471_1",
   "description": "Flow Proportional Band",
   "units": "l/min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2591,
   "name": "7472_1",
   "description": "Flow Dead Band",
   "units": "l/min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2592,
   "name": "7473_1",
   "description": "Flow Integration Time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2593,
   "name": "4644_1",
   "description": "Supply Fluid Over Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12593,
   "name": "4644_1_deg_F",
   "description": "Supply Fluid Over Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2594,
   "name": "5289_1",
   "description": "Return Fluid Over Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12594,
   "name": "5289_1_deg_F",
   "description": "Return Fluid Over Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2605,
   "name": "7480_1_1",
   "description": "Pump Speed (Fluid Pump 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2606,
   "name": "7481_1_1",
   "description": "Pump Expected Speed (Fluid Pump 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2607,
   "name": "7482_1_1",
   "description": "Pump Run Time (Fluid Pump 1)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2618,
   "name": "7480_1_2",
   "description": "Pump Speed (Fluid Pump 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2619,
   "name": "7481_1_2",
   "description": "Pump Expected Speed (Fluid Pump 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2620,
   "name": "7482_1_2",
   "description": "Pump Run Time (Fluid Pump 2)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2904,
   "name": "8167_1_1",
   "description": "Pump Motor Power (Fluid Pump Status 1)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2905,
   "name": "8168_1_1",
   "description": "Pump Motor Amps (Fluid Pump Status 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2906,
   "name": "8169_1_1",
   "description": "Inverter Temperature (Fluid Pump Status 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12906,
   "name": "8169_1_1_deg_F",
   "description": "Inverter Temperature (Fluid Pump Status 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2917,
   "name": "8167_1_2",
   "description": "Pump Motor Power (Fluid Pump Status 2)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2918,
   "name": "8168_1_2",
   "description": "Pump Motor Amps (Fluid Pump Status 2)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2919,
   "name": "8169_1_2",
   "description": "Inverter Temperature (Fluid Pump Status 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12919,
   "name": "8169_1_2_deg_F",
   "description": "Inverter Temperature (Fluid Pump Status 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2823,
   "name": "8132_1",
   "description": "Unit Fluid Supply Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12823,
   "name": "8132_1_deg_F",
   "description": "Unit Fluid Supply Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2824,
   "name": "8133_1",
   "description": "Unit Fluid Return Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12824,
   "name": "8133_1_deg_F",
   "description": "Unit Fluid Return Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2825,
   "name": "8134_1",
   "description": "Unit Fluid Supply Pressure",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2826,
   "name": "8135_1",
   "description": "Unit Fluid Return Pressure",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2827,
   "name": "8136_1",
   "description": "Unit Fluid Pump Speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2828,
   "name": "8137_1",
   "description": "Unit Fluid Flow",
   "units": "l/min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2829,
   "name": "8138_1",
   "description": "Unit Fluid Diff Pressure",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2830,
   "name": "8139_1",
   "description": "Unit Fluid Cooling Capacity",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2831,
   "name": "8140_1",
   "description": "System Fluid Flow",
   "units": "l/min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2832,
   "name": "8141_1",
   "description": "System Fluid Diff Pressure",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2833,
   "name": "8142_1",
   "description": "System Fluid Cooling Capacity",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2844,
   "name": "8143_1_1",
   "description": "Fluid Temperature Set Point",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12844,
   "name": "8143_1_1_deg_F",
   "description": "Fluid Temperature Set Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2845,
   "name": "8145_1_1",
   "description": "Fluid Temperature Proportional Band",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12845,
   "name": "8145_1_1_deg_F",
   "description": "Fluid Temperature Proportional Band",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2846,
   "name": "8146_1_1",
   "description": "Fluid Temperature Dead Band",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12846,
   "name": "8146_1_1_deg_F",
   "description": "Fluid Temperature Dead Band",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2847,
   "name": "8147_1_1",
   "description": "Fluid Temperature Control Integration Time",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2858,
   "name": "8149_1_1",
   "description": "Fluid Flow Set Point",
   "units": "l/min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2859,
   "name": "8150_1_1",
   "description": "Fluid Flow Proportional Band",
   "units": "l/min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2860,
   "name": "8151_1_1",
   "description": "Fluid Flow Dead Band",
   "units": "l/min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2861,
   "name": "8152_1_1",
   "description": "Fluid Flow Control Integration Time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2862,
   "name": "8153_1_1",
   "description": "Fluid Diff Prs Set Point",
   "units": "bar",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2863,
   "name": "8154_1_1",
   "description": "Fluid Diff Prs Prop Band",
   "units": "bar",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2864,
   "name": "8155_1_1",
   "description": "Flow Diff Prs Dead Band",
   "units": "bar",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2865,
   "name": "8156_1_1",
   "description": "Fluid Diff Prs Control Integration Time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2866,
   "name": "8157_1_1",
   "description": "Flow Manual Pump Speed",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2867,
   "name": "8158_1_1",
   "description": "Pump Operation Period",
   "units": "day",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2868,
   "name": "8159_1_1",
   "description": "Pump Operation Duration",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2869,
   "name": "8160_1_1",
   "description": "Pump Operation Speed",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2880,
   "name": "8163_1_1",
   "description": "Dew Point Max Adjust",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12880,
   "name": "8163_1_1_deg_F",
   "description": "Dew Point Max Adjust",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2881,
   "name": "8164_1_1",
   "description": "System Dew Point",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12881,
   "name": "8164_1_1_deg_F",
   "description": "System Dew Point",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2882,
   "name": "8165_1_1",
   "description": "Unit Dew Point",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12882,
   "name": "8165_1_1_deg_F",
   "description": "Unit Dew Point",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2893,
   "name": "8230_1_1",
   "description": "PHE Fluid Supply Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12893,
   "name": "8230_1_1_deg_F",
   "description": "PHE Fluid Supply Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "4553_1",
   "description": "Server Class",
   "units": "",
   "access": "R",
   "states": "1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "5324_1",
   "description": "Air Temperature Control Type",
   "units": "",
   "access": "W",
   "states": "1=Proportional, 2=Prop+Integral, 3=Adaptive PID, 4=Intelligent"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "5012_1",
   "description": "Air Temperature Control Sensor",
   "units": "",
   "access": "W",
   "states": "1=Supply, 2=Remote, 3=Return"
  },
  {
   "type": "MV",
   "instance": 23,
   "name": "5332_1_1",
   "description": "Supply Air Temperature Sensor Control",
   "units": "",
   "access": "W",
   "states": "1=Disabled, 2=Limit, 3=Control, 4=Temp Only"
  },
  {
   "type": "MV",
   "instance": 34,
   "name": "5340_1",
   "description": "Humidity Control Type",
   "units": "",
   "access": "W",
   "states": "1=Relative, 2=Compensated, 3=Predictive"
  },
  {
   "type": "MV",
   "instance": 35,
   "name": "5603_1",
   "description": "Humidity Control Type",
   "units": "",
   "access": "W",
   "states": "1=Relative, 2=Compensated, 3=Predictive, 4=Dew Point"
  },
  {
   "type": "MV",
   "instance": 36,
   "name": "5618_1",
   "description": "Humidity Control Sensor",
   "units": "",
   "access": "W",
   "states": "1=Supply, 2=Remote, 3=Return"
  },
  {
   "type": "MV",
   "instance": 45,
   "name": "5264_1_1",
   "description": "Compressor State (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 46,
   "name": "5265_1_1",
   "description": "Compressor Capacity Control State (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 47,
   "name": "6243_1_1",
   "description": "Tandem 'B' Compressor State (Compressor 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 57,
   "name": "5264_1_2",
   "description": "Compressor State (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 58,
   "name": "5265_1_2",
   "description": "Compressor Capacity Control State (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 59,
   "name": "6243_1_2",
   "description": "Tandem 'B' Compressor State (Compressor 2)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 543,
   "name": "5264_1_3",
   "description": "Compressor State (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on n"
  },
  {
   "type": "MV",
   "instance": 544,
   "name": "5265_1_3",
   "description": "Compressor Capacity Control State (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 545,
   "name": "6243_1_3",
   "description": "Tandem 'B' Compressor State (Compressor 3)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 556,
   "name": "5264_1_4",
   "description": "Compressor State (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 557,
   "name": "5265_1_4",
   "description": "Compressor Capacity Control State (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 558,
   "name": "6243_1_4",
   "description": "Tandem 'B' Compressor State (Compressor 4)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 69,
   "name": "5302_1",
   "description": "Free Cooling Status",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on, 3=No Support"
  },
  {
   "type": "MV",
   "instance": 70,
   "name": "5581_1",
   "description": "Free Cooling Internal Control Mode",
   "units": "",
   "access": "W",
   "states": "1=Disabled, 2=Contact, 3=Temperature, 4=Set Point"
  },
  {
   "type": "MV",
   "instance": 71,
   "name": "5359_1",
   "description": "Minimum Chilled Water Temp Set Point Enable",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 72,
   "name": "5605_1",
   "description": "Main Chilled Water Valve",
   "units": "",
   "access": "W",
   "states": "1=Valve 1, 2=Valve 2"
  },
  {
   "type": "MV",
   "instance": 82,
   "name": "5373_1",
   "description": "Fan Control Mode",
   "units": "",
   "access": "W",
   "states": "1=Auto, 2=Manual, 3=Economy, 4=Delta"
  },
  {
   "type": "MV",
   "instance": 83,
   "name": "5586_1",
   "description": "Fan Control Sensor",
   "units": "",
   "access": "W",
   "states": "1=Supply, 2=Remote, 3=Return, 4=Manual"
  },
  {
   "type": "MV",
   "instance": 84,
   "name": "6736_1",
   "description": "Fan Back Draft Operation",
   "units": "",
   "access": "W",
   "states": "1=Disabled, 2=Standby, 3=Outdoor Temp"
  },
  {
   "type": "MV",
   "instance": 85,
   "name": "6771_1",
   "description": "Fan Back Draft Control Enable",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 86,
   "name": "6767_1",
   "description": "Fan Speed Temp Control Type",
   "units": "",
   "access": "W",
   "states": "1=Proportional, 2=Prop+Integral, 3=Adaptive PID"
  },
  {
   "type": "MV",
   "instance": 93,
   "name": "4123_1",
   "description": "System Status",
   "units": "",
   "access": "R",
   "states": "1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation"
  },
  {
   "type": "MV",
   "instance": 94,
   "name": "4706_1",
   "description": "Unit Operating State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on, 3=standby"
  },
  {
   "type": "MV",
   "instance": 95,
   "name": "4707_1",
   "description": "Unit Control Mode",
   "units": "",
   "access": "R",
   "states": "1=Internal (Auto), 2=External (Manual)"
  },
  {
   "type": "MV",
   "instance": 96,
   "name": "5074_1",
   "description": "Unit Off Reason",
   "units": "",
   "access": "R",
   "states": "1=None, 2=User, 3=Alarm, 4=Timer, 5=Monitoring, 6=Remote Off, 7=HCS12 Off"
  },
  {
   "type": "MV",
   "instance": 107,
   "name": "5381_1",
   "description": "Fan State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 108,
   "name": "5382_1",
   "description": "Cooling State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 109,
   "name": "5383_1",
   "description": "Free Cooling State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 110,
   "name": "5384_1",
   "description": "Maintenance Tracking State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 111,
   "name": "5385_1",
   "description": "Hot Water / Hot Gas State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 112,
   "name": "5386_1",
   "description": "Electric Reheat State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 113,
   "name": "5387_1",
   "description": "Dehumidifier State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 114,
   "name": "5388_1",
   "description": "Humidifier State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 115,
   "name": "5143_1",
   "description": "System On/Off Control",
   "units": "",
   "access": "W",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 500,
   "name": "6175_1",
   "description": "Local Fan Override",
   "units": "",
   "access": "R",
   "states": "1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection"
  },
  {
   "type": "MV",
   "instance": 501,
   "name": "6176_1",
   "description": "Local Cooling Override",
   "units": "",
   "access": "R",
   "states": "1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection"
  },
  {
   "type": "MV",
   "instance": 502,
   "name": "6177_1",
   "description": "Local Electric Heat Override",
   "units": "",
   "access": "R",
   "states": "1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection, 1=Normal operation"
  },
  {
   "type": "MV",
   "instance": 503,
   "name": "6178_1",
   "description": "Local Humidifier Override",
   "units": "",
   "access": "R",
   "states": "2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection"
  },
  {
   "type": "MV",
   "instance": 504,
   "name": "6179_1",
   "description": "Local Dehumidifier Override",
   "units": "",
   "access": "R",
   "states": "1=Normal operation, 2=Increased for internal protection, 3=Decreased for internal protection, 4=Disabled for internal protection, 5=Limited or disabled for low limit protection"
  },
  {
   "type": "MV",
   "instance": 505,
   "name": "6553_1",
   "description": "Master Cooling Fluid Source",
   "units": "",
   "access": "W",
   "states": "1=Supply 1, 2=Supply 2"
  },
  {
   "type": "MV",
   "instance": 506,
   "name": "6524_1",
   "description": "Automatic Transfer Switch - Active Power Supply",
   "units": "",
   "access": "R",
   "states": "1=Power Supply 1, 2=Power Supply 2"
  },
  {
   "type": "MV",
   "instance": 507,
   "name": "6525_1",
   "description": "Automatic Transfer Switch - Power Supply 1 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 508,
   "name": "6526_1",
   "description": "Automatic Transfer Switch - Power Supply 2 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 126,
   "name": "4718_1",
   "description": "Customer Input 1 - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 127,
   "name": "4719_1",
   "description": "Customer Input 1 - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 128,
   "name": "5098_1",
   "description": "Customer Input 2 - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 129,
   "name": "5099_1",
   "description": "Customer Input 2 - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 130,
   "name": "5100_1",
   "description": "Customer Input 3 - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 131,
   "name": "5101_1",
   "description": "Customer Input 3 - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 132,
   "name": "5102_1",
   "description": "Customer Input 4 - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 133,
   "name": "5103_1",
   "description": "Customer Input 4 - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 134,
   "name": "5389_1",
   "description": "Ext Free Cooling Lockout - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 135,
   "name": "5390_1",
   "description": "Ext Free Cooling Lockout - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 136,
   "name": "5122_1",
   "description": "Ext Condenser Pump High Water - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 137,
   "name": "5123_1",
   "description": "Ext Condenser Pump High Water - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 138,
   "name": "5129_1",
   "description": "Ext Standby Glycol Pump On - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 139,
   "name": "5130_1",
   "description": "Ext Standby Glycol Pump On - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 140,
   "name": "5391_1",
   "description": "Ext Standby Unit On - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 141,
   "name": "5392_1",
   "description": "Ext Standby Unit On - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 142,
   "name": "5086_1",
   "description": "Ext Humidifier Lockout - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 143,
   "name": "5087_1",
   "description": "Ext Humidifier Lockout - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 144,
   "name": "5082_1",
   "description": "Ext Loss of Flow - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 145,
   "name": "5083_1",
   "description": "Ext Loss of Flow - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 146,
   "name": "5090_1",
   "description": "Ext Over Temperature - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 147,
   "name": "5091_1",
   "description": "Ext Over Temperature - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 148,
   "name": "5084_1",
   "description": "Ext Reheat Lockout - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 149,
   "name": "5085_1",
   "description": "Ext Reheat Lockout - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 150,
   "name": "5141_1",
   "description": "High Power Shutdown - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 151,
   "name": "5142_1",
   "description": "High Power Shutdown - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 152,
   "name": "5131_1",
   "description": "Humidifier Issue - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 153,
   "name": "5132_1",
   "description": "Humidifier Issue - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 154,
   "name": "5133_1",
   "description": "Master Unit Communication Lost - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 155,
   "name": "5134_1",
   "description": "Master Unit Communication Lost - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 156,
   "name": "4727_1",
   "description": "Service Required - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 157,
   "name": "4728_1",
   "description": "Service Required - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 158,
   "name": "4715_1",
   "description": "Shutdown - Loss Of Power - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 159,
   "name": "4716_1",
   "description": "Shutdown - Loss Of Power - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 160,
   "name": "4721_1",
   "description": "Smoke Detected - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 161,
   "name": "4722_1",
   "description": "Smoke Detected - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 162,
   "name": "4724_1",
   "description": "Water Under Floor - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 163,
   "name": "4725_1",
   "description": "Water Under Floor - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 164,
   "name": "5088_1",
   "description": "Ext Compressor Lockout - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 165,
   "name": "5089_1",
   "description": "Ext Compressor Lockout - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 166,
   "name": "5135_1",
   "description": "Clogged Air Filter - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 167,
   "name": "5136_1",
   "description": "Clogged Air Filter - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 168,
   "name": "5393_1",
   "description": "Ext Loss of Air Blower - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 169,
   "name": "5394_1",
   "description": "Ext Loss of Air Blower - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 180,
   "name": "5316_1_1",
   "description": "Compressor High Head Pressure - Event Control (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 181,
   "name": "5317_1_1",
   "description": "Compressor High Head Pressure - Event Type (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 182,
   "name": "5318_1_1",
   "description": "Compressor Low Suction Pressure - Event Control (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 183,
   "name": "5319_1_1",
   "description": "Compressor Low Suction Pressure - Event Type (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 184,
   "name": "5395_1_1",
   "description": "Compressor Pump Down Issue - Event Control (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 185,
   "name": "5396_1_1",
   "description": "Compressor Pump Down Issue - Event Type (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 186,
   "name": "5397_1_1",
   "description": "Compressor Short Cycle - Event Control (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 187,
   "name": "5398_1_1",
   "description": "Compressor Short Cycle - Event Type (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 188,
   "name": "5320_1_1",
   "description": "Compressor Thermal Overload - Event Control (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 189,
   "name": "5321_1_1",
   "description": "Compressor Thermal Overload - Event Type (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 190,
   "name": "5399_1_1",
   "description": "Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 191,
   "name": "5400_1_1",
   "description": "Dig Scroll Comp Discharge Over Temp - Event Type (Compressor 1)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 202,
   "name": "5316_1_2",
   "description": "Compressor High Head Pressure - Event Control (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 203,
   "name": "5317_1_2",
   "description": "Compressor High Head Pressure - Event Type (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 204,
   "name": "5318_1_2",
   "description": "Compressor Low Suction Pressure - Event Control (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 205,
   "name": "5319_1_2",
   "description": "Compressor Low Suction Pressure - Event Type (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 206,
   "name": "5395_1_2",
   "description": "Compressor Pump Down Issue - Event Control (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 207,
   "name": "5396_1_2",
   "description": "Compressor Pump Down Issue - Event Type (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 208,
   "name": "5397_1_2",
   "description": "Compressor Short Cycle - Event Control (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 209,
   "name": "5398_1_2",
   "description": "Compressor Short Cycle - Event Type (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 210,
   "name": "5320_1_2",
   "description": "Compressor Thermal Overload - Event Control (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 211,
   "name": "5321_1_2",
   "description": "Compressor Thermal Overload - Event Type (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 212,
   "name": "5399_1_2",
   "description": "Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 213,
   "name": "5400_1_2",
   "description": "Dig Scroll Comp Discharge Over Temp - Event Type (Compressor 2)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 224,
   "name": "5401_1_1",
   "description": "Ext Air Sensor A Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 225,
   "name": "5402_1_1",
   "description": "Return Air Sensor Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 226,
   "name": "5403_1_1",
   "description": "Ext Air Sensor A High Humidity - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 227,
   "name": "5404_1_1",
   "description": "Ext Air Sensor A High Humidity - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 228,
   "name": "5405_1_1",
   "description": "Ext Air Sensor A Low Humidity - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 229,
   "name": "5406_1_1",
   "description": "Ext Air Sensor A Low Humidity - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 230,
   "name": "4602_1_1",
   "description": "Ext Air Sensor A Over Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 231,
   "name": "4603_1_1",
   "description": "Ext Air Sensor A Over Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 232,
   "name": "4609_1_1",
   "description": "Ext Air Sensor A Under Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 233,
   "name": "4610_1_1",
   "description": "Ext Air Sensor A Under Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 234,
   "name": "5137_1_1",
   "description": "High Return Humidity - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 235,
   "name": "5138_1_1",
   "description": "High Return Humidity - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 236,
   "name": "5139_1_1",
   "description": "Low Return Humidity - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 237,
   "name": "5140_1_1",
   "description": "Low Return Humidity - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 238,
   "name": "5024_1_1",
   "description": "Return Air Over Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 239,
   "name": "5025_1_1",
   "description": "Return Air Over Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 240,
   "name": "5407_1_1",
   "description": "Return Air Under Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 241,
   "name": "5408_1_1",
   "description": "Return Air Under Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 242,
   "name": "5587_1_1",
   "description": "Supply Air Over/Under Temperature - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 252,
   "name": "5409_1_1",
   "description": "Fan Hours Exceeded - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 253,
   "name": "5410_1_1",
   "description": "Fan Hours Exceeded - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 254,
   "name": "4730_1_1",
   "description": "Fan Issue - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 255,
   "name": "4731_1_1",
   "description": "Fan Issue - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 256,
   "name": "5411_1_1",
   "description": "Main Fan Overload - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 257,
   "name": "5412_1_1",
   "description": "Main Fan Overload - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 268,
   "name": "5413_1_1",
   "description": "Condenser Issue - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 269,
   "name": "5414_1_1",
   "description": "Condenser Issue - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 280,
   "name": "5413_1_2",
   "description": "Condenser Issue - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 281,
   "name": "5414_1_2",
   "description": "Condenser Issue - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 292,
   "name": "4717_1",
   "description": "System Event Acknowledge/Reset",
   "units": "",
   "access": "W",
   "states": "1=Reset, 2=Acknowledge"
  },
  {
   "type": "MV",
   "instance": 304,
   "name": "5580_1",
   "description": "Compressor Lockout",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 316,
   "name": "5582_1",
   "description": "Reheater Lockout",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 317,
   "name": "6760_1",
   "description": "Dehum Reheat Low Limit Sensor",
   "units": "",
   "access": "W",
   "states": "1=Supply, 2=Remote, 3=Return"
  },
  {
   "type": "MV",
   "instance": 328,
   "name": "5583_1",
   "description": "Humidifier Lockout",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 340,
   "name": "5599_1",
   "description": "Air Economizer Availability",
   "units": "",
   "access": "R",
   "states": "1=Not Available, 2=Available"
  },
  {
   "type": "MV",
   "instance": 341,
   "name": "5602_1",
   "description": "Air Economizer Control Source",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=internal, 3=external"
  },
  {
   "type": "MV",
   "instance": 363,
   "name": "5632_1_1",
   "description": "PRE Operational Mode (Pump 1)",
   "units": "",
   "access": "R",
   "states": "1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test"
  },
  {
   "type": "MV",
   "instance": 364,
   "name": "5633_1_1",
   "description": "Pump State (Pump 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 368,
   "name": "5632_1_2",
   "description": "PRE Operational Mode (Pump 2)",
   "units": "",
   "access": "R",
   "states": "1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test"
  },
  {
   "type": "MV",
   "instance": 369,
   "name": "5633_1_2",
   "description": "Pump State (Pump 2)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 577,
   "name": "5633_1_3",
   "description": "Pump State (Pump 3)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 578,
   "name": "5632_1_3",
   "description": "PRE Operational Mode (Pump 3)",
   "units": "",
   "access": "R",
   "states": "1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test"
  },
  {
   "type": "MV",
   "instance": 589,
   "name": "5633_1_4",
   "description": "Pump State (Pump 4)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 590,
   "name": "5632_1_4",
   "description": "PRE Operational Mode (Pump 4)",
   "units": "",
   "access": "R",
   "states": "1=Bootup, 2=Idle, 3=Manual, 4=Pump Automatic, 5=Test"
  },
  {
   "type": "MV",
   "instance": 395,
   "name": "5533_1",
   "description": "Condenser Refrigerant Type",
   "units": "",
   "access": "R",
   "states": "1=R22, 2=R407C, 3=R410A"
  },
  {
   "type": "MV",
   "instance": 374,
   "name": "5546_1_1",
   "description": "Condenser Low Noise Mode State",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active (Interval), 3=Active (Full Day)"
  },
  {
   "type": "MV",
   "instance": 375,
   "name": "5547_1_1",
   "description": "Condenser Low Noise Mode Schedule Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 406,
   "name": "6104_1_1",
   "description": "Condenser Fan Reversal Requested (Condenser 1)",
   "units": "",
   "access": "W",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 407,
   "name": "6104_1_2",
   "description": "Condenser Fan Reversal Requested (Condenser 2)",
   "units": "",
   "access": "W",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 612,
   "name": "6104_1_3",
   "description": "Condenser Fan Reversal Requested (Condenser 3)",
   "units": "",
   "access": "W",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 623,
   "name": "6104_1_4",
   "description": "Condenser Fan Reversal Requested (Condenser 4)",
   "units": "",
   "access": "W",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 438,
   "name": "6081_1",
   "description": "Cold Aisle Humidity Calculation Method",
   "units": "",
   "access": "R",
   "states": "1=Highest, 2=Average"
  },
  {
   "type": "MV",
   "instance": 439,
   "name": "6082_1",
   "description": "Cold Aisle Temperature Calculation Method",
   "units": "",
   "access": "R",
   "states": "1=Highest, 2=Average"
  },
  {
   "type": "MV",
   "instance": 440,
   "name": "6083_1",
   "description": "Cold Aisle Control Enable",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 441,
   "name": "6084_1",
   "description": "Cold Aisle Force Max Fan/Cooling - Ext Control",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 442,
   "name": "6090_1",
   "description": "Static Pressure Control Enable",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 443,
   "name": "6091_1",
   "description": "Chilled Water Valve Reset Enable",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 529,
   "name": "6300_1",
   "description": "Underfloor Static Pressure Control Enable",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled, 3=visualization only"
  },
  {
   "type": "MV",
   "instance": 531,
   "name": "6301_1",
   "description": "Return Damper Status",
   "units": "",
   "access": "R",
   "states": "1=closed, 2=open"
  },
  {
   "type": "MV",
   "instance": 516,
   "name": "6261_1",
   "description": "Thermal Control Override",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 517,
   "name": "6262_1",
   "description": "Thermal Control Override - Temperature Control Type",
   "units": "",
   "access": "W",
   "states": "1=Cooling, 2=Heating"
  },
  {
   "type": "MV",
   "instance": 518,
   "name": "6264_1",
   "description": "Thermal Control Override - Humidity Control Type",
   "units": "",
   "access": "W",
   "states": "1=Dehumidification, 2=Humidification"
  },
  {
   "type": "MV",
   "instance": 635,
   "name": "6695_1_1",
   "description": "Group Independent Operation Enable",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 636,
   "name": "6690_1_1",
   "description": "Group Independent Operation",
   "units": "",
   "access": "W",
   "states": "1=No override (default), 2=Override, forced on, 3=Override, forced off"
  },
  {
   "type": "MV",
   "instance": 648,
   "name": "6775_1",
   "description": "Auto Restart Enable",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 649,
   "name": "6777_1",
   "description": "Virtual Master Enable",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 661,
   "name": "6784_1_1",
   "description": "Teamwork Mode",
   "units": "",
   "access": "W",
   "states": "1=No Teamwork Mode, 2=Mode 1 (parallel), 3=Mode 2 (independent), 4=Mode 3 (optimized aisle)"
  },
  {
   "type": "MV",
   "instance": 662,
   "name": "6778_1_1",
   "description": "Unit Cascade Type",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Temp/Humidity, 3=Cool/Heat, 4=Cooling, 5=Fan PI, 6=Fan Speed"
  },
  {
   "type": "MV",
   "instance": 663,
   "name": "6782_1_1",
   "description": "Teamwork Temperature Calculation Method",
   "units": "",
   "access": "W",
   "states": "1=Average, 2=Maximum"
  },
  {
   "type": "MV",
   "instance": 675,
   "name": "6130_1_1",
   "description": "Networked Unit Daily Rotation Frequency",
   "units": "",
   "access": "W",
   "states": "1=Every 24 hours, 2=Every 12 hours"
  },
  {
   "type": "MV",
   "instance": 676,
   "name": "6131_1_1",
   "description": "Force Networked Unit Rotation",
   "units": "",
   "access": "W",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 677,
   "name": "6129_1_1",
   "description": "Networked Unit Rotation Frequency",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Daily, 3=Weekly Monday, 4=Weekly Tuesday, 5=Weekly Wednesday, 6=Weekly Thursday, 7=Weekly Friday, 8=Weekly Saturday, 9=Weekly Sunday, 10=Monthly Monday, 11=Monthly Tuesday, 12=Monthly Wednesday, 13=Monthly Thursday, 14=Monthly Friday, 15=Monthly Saturday, 16=Monthly Sunday"
  },
  {
   "type": "MV",
   "instance": 678,
   "name": "6823_1_1",
   "description": "Start Standby Units on High Temperature",
   "units": "",
   "access": "W",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 689,
   "name": "7564_1",
   "description": "Static Pressure Fan Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=Limit, 3=Control, 4=BMS Backup SP Ctrl"
  },
  {
   "type": "MV",
   "instance": 700,
   "name": "7127_1",
   "description": "ATS Switch Mode",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Manual, 3=Automatic, 4=Test"
  },
  {
   "type": "MV",
   "instance": 701,
   "name": "7128_1",
   "description": "ATS Load Not Powered Timeout",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 702,
   "name": "7129_1",
   "description": "ATS Non Priority Load Breaker Timeout",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 713,
   "name": "7135_1_1",
   "description": "Power Source: All status are okay (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 714,
   "name": "7136_1_1",
   "description": "Power Source: Voltage Is Too Low (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 715,
   "name": "7137_1_1",
   "description": "Power Source: Voltage Is Too High (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 716,
   "name": "7138_1_1",
   "description": "Power Source: Voltages Are Asymmetric (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 717,
   "name": "7139_1_1",
   "description": "Power Source: Voltage Phase Loss (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 718,
   "name": "7140_1_1",
   "description": "Power Source: Phase Sequence Issue (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 719,
   "name": "7141_1_1",
   "description": "Power Source: Frequency Is Too Low (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 720,
   "name": "7142_1_1",
   "description": "Power Source: Frequency Is Too High (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 721,
   "name": "7143_1_1",
   "description": "Power Source: Breaker is closed (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 722,
   "name": "7144_1_1",
   "description": "Power Source: Breaker command status closed (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 723,
   "name": "7145_1_1",
   "description": "Power Source: Breaker withdrawn issue (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 724,
   "name": "7146_1_1",
   "description": "Power Source: Breaker Timeout Issue (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 725,
   "name": "7147_1_1",
   "description": "Power Source: Line Operating Hour Exceeded (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 726,
   "name": "7148_1_1",
   "description": "Power Source: Breaker Operating Hour Exceeded (Power Source 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 737,
   "name": "7135_1_2",
   "description": "Power Source: All status are okay (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 738,
   "name": "7136_1_2",
   "description": "Power Source: Voltage Is Too Low (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 739,
   "name": "7137_1_2",
   "description": "Power Source: Voltage Is Too High (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 740,
   "name": "7138_1_2",
   "description": "Power Source: Voltages Are Asymmetric (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 741,
   "name": "7139_1_2",
   "description": "Power Source: Voltage Phase Loss (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 742,
   "name": "7140_1_2",
   "description": "Power Source: Phase Sequence Issue (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 743,
   "name": "7141_1_2",
   "description": "Power Source: Frequency Is Too Low (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 744,
   "name": "7142_1_2",
   "description": "Power Source: Frequency Is Too High (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 745,
   "name": "7143_1_2",
   "description": "Power Source: Breaker is closed (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 746,
   "name": "7144_1_2",
   "description": "Power Source: Breaker command status closed (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 747,
   "name": "7145_1_2",
   "description": "Power Source: Breaker withdrawn issue (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 748,
   "name": "7146_1_2",
   "description": "Power Source: Breaker Timeout Issue (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 749,
   "name": "7147_1_2",
   "description": "Power Source: Line Operating Hour Exceeded (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 750,
   "name": "7148_1_2",
   "description": "Power Source: Breaker Operating Hour Exceeded (Power Source 2)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 761,
   "name": "7477_1",
   "description": "Force Pump Rotate",
   "units": "",
   "access": "W",
   "states": "1=Rotate"
  },
  {
   "type": "MV",
   "instance": 762,
   "name": "7478_1",
   "description": "Reset Pump Speed Calibration",
   "units": "",
   "access": "W",
   "states": "1=Reset"
  },
  {
   "type": "MV",
   "instance": 773,
   "name": "7479_1_1",
   "description": "Pump Operating State (Fluid Pump 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 784,
   "name": "7479_1_2",
   "description": "Pump Operating State (Fluid Pump 2)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 1175,
   "name": "8171_1_1",
   "description": "Pump Drive Overload (Fluid Pump Status 1)",
   "units": "",
   "access": "R",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 1176,
   "name": "8172_1_1",
   "description": "Pump Drive Over Temperature (Fluid Pump Status 1)",
   "units": "",
   "access": "R",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 1177,
   "name": "8173_1_1",
   "description": "Pump Drive Warning (Fluid Pump Status 1)",
   "units": "",
   "access": "R",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 1178,
   "name": "8174_1_1",
   "description": "Pump Drive Low AC Alarm (Fluid Pump Status 1)",
   "units": "",
   "access": "R",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 1179,
   "name": "8175_1_1",
   "description": "Pump Drive Phase Loss Active (Fluid Pump Status 1)",
   "units": "",
   "access": "R",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 1180,
   "name": "8176_1_1",
   "description": "Pump Drive Product Identification (Fluid Pump Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1181,
   "name": "8177_1_1",
   "description": "Pump Drive Communications (Fluid Pump Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1192,
   "name": "8171_1_2",
   "description": "Pump Drive Overload (Fluid Pump Status 2)",
   "units": "",
   "access": "R",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 1193,
   "name": "8172_1_2",
   "description": "Pump Drive Over Temperature (Fluid Pump Status 2)",
   "units": "",
   "access": "R",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 1194,
   "name": "8173_1_2",
   "description": "Pump Drive Warning (Fluid Pump Status 2)",
   "units": "",
   "access": "R",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 1195,
   "name": "8174_1_2",
   "description": "Pump Drive Low AC Alarm (Fluid Pump Status 2)",
   "units": "",
   "access": "R",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 1196,
   "name": "8175_1_2",
   "description": "Pump Drive Phase Loss Active (Fluid Pump Status 2)",
   "units": "",
   "access": "R",
   "states": "1=no, 2=yes"
  },
  {
   "type": "MV",
   "instance": 1197,
   "name": "8176_1_2",
   "description": "Pump Drive Product Identification (Fluid Pump Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1198,
   "name": "8177_1_2",
   "description": "Pump Drive Communications (Fluid Pump Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 795,
   "name": "8101_1_1",
   "description": "Communicate At Fan Power Off",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 796,
   "name": "8102_1_1",
   "description": "Supply Fan Emergency Op",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 807,
   "name": "8106_1_1",
   "description": "Fan Error: Phase Failure (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 808,
   "name": "8107_1_1",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 809,
   "name": "8108_1_1",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 810,
   "name": "8109_1_1",
   "description": "Fan Error: General Failure (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 811,
   "name": "8110_1_1",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 812,
   "name": "8111_1_1",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 813,
   "name": "8112_1_1",
   "description": "Fan Error: Locked Motor (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 814,
   "name": "8113_1_1",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 815,
   "name": "8114_1_1",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 816,
   "name": "8115_1_1",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 817,
   "name": "8116_1_1",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 818,
   "name": "8117_1_1",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 819,
   "name": "8118_1_1",
   "description": "Fan Warning: Identification (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 820,
   "name": "8193_1_1",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 1)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 830,
   "name": "8106_1_2",
   "description": "Fan Error: Phase Failure (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 831,
   "name": "8107_1_2",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 832,
   "name": "8108_1_2",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 833,
   "name": "8109_1_2",
   "description": "Fan Error: General Failure (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 834,
   "name": "8110_1_2",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 835,
   "name": "8111_1_2",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 836,
   "name": "8112_1_2",
   "description": "Fan Error: Locked Motor (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 837,
   "name": "8113_1_2",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 838,
   "name": "8114_1_2",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 839,
   "name": "8115_1_2",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 840,
   "name": "8116_1_2",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 841,
   "name": "8117_1_2",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 842,
   "name": "8118_1_2",
   "description": "Fan Warning: Identification (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 843,
   "name": "8193_1_2",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 2)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 853,
   "name": "8106_1_3",
   "description": "Fan Error: Phase Failure (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 854,
   "name": "8107_1_3",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 855,
   "name": "8108_1_3",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 856,
   "name": "8109_1_3",
   "description": "Fan Error: General Failure (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 857,
   "name": "8110_1_3",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 858,
   "name": "8111_1_3",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 859,
   "name": "8112_1_3",
   "description": "Fan Error: Locked Motor (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 860,
   "name": "8113_1_3",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 861,
   "name": "8114_1_3",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 862,
   "name": "8115_1_3",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 863,
   "name": "8116_1_3",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 864,
   "name": "8117_1_3",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 865,
   "name": "8118_1_3",
   "description": "Fan Warning: Identification (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 866,
   "name": "8193_1_3",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 3)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 876,
   "name": "8106_1_4",
   "description": "Fan Error: Phase Failure (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 877,
   "name": "8107_1_4",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 878,
   "name": "8108_1_4",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 879,
   "name": "8109_1_4",
   "description": "Fan Error: General Failure (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 880,
   "name": "8110_1_4",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 881,
   "name": "8111_1_4",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 882,
   "name": "8112_1_4",
   "description": "Fan Error: Locked Motor (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 883,
   "name": "8113_1_4",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 884,
   "name": "8114_1_4",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 885,
   "name": "8115_1_4",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 886,
   "name": "8116_1_4",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 887,
   "name": "8117_1_4",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 888,
   "name": "8118_1_4",
   "description": "Fan Warning: Identification (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 889,
   "name": "8193_1_4",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 4)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 899,
   "name": "8106_1_5",
   "description": "Fan Error: Phase Failure (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 900,
   "name": "8107_1_5",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 901,
   "name": "8108_1_5",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 902,
   "name": "8109_1_5",
   "description": "Fan Error: General Failure (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 903,
   "name": "8110_1_5",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 904,
   "name": "8111_1_5",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 905,
   "name": "8112_1_5",
   "description": "Fan Error: Locked Motor (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 906,
   "name": "8113_1_5",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 907,
   "name": "8114_1_5",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 908,
   "name": "8115_1_5",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 909,
   "name": "8116_1_5",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 910,
   "name": "8117_1_5",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 911,
   "name": "8118_1_5",
   "description": "Fan Warning: Identification (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 912,
   "name": "8193_1_5",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 5)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 922,
   "name": "8106_1_6",
   "description": "Fan Error: Phase Failure (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 923,
   "name": "8107_1_6",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 924,
   "name": "8108_1_6",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 925,
   "name": "8109_1_6",
   "description": "Fan Error: General Failure (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 926,
   "name": "8110_1_6",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 927,
   "name": "8111_1_6",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 928,
   "name": "8112_1_6",
   "description": "Fan Error: Locked Motor (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 929,
   "name": "8113_1_6",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 930,
   "name": "8114_1_6",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 931,
   "name": "8115_1_6",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 932,
   "name": "8116_1_6",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 933,
   "name": "8117_1_6",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 934,
   "name": "8118_1_6",
   "description": "Fan Warning: Identification (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 935,
   "name": "8193_1_6",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 6)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 945,
   "name": "8106_1_7",
   "description": "Fan Error: Phase Failure (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 946,
   "name": "8107_1_7",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 947,
   "name": "8108_1_7",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 948,
   "name": "8109_1_7",
   "description": "Fan Error: General Failure (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 949,
   "name": "8110_1_7",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 950,
   "name": "8111_1_7",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 951,
   "name": "8112_1_7",
   "description": "Fan Error: Locked Motor (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 952,
   "name": "8113_1_7",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 953,
   "name": "8114_1_7",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 954,
   "name": "8115_1_7",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 955,
   "name": "8116_1_7",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 956,
   "name": "8117_1_7",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 957,
   "name": "8118_1_7",
   "description": "Fan Warning: Identification (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 958,
   "name": "8193_1_7",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 7)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 968,
   "name": "8106_1_8",
   "description": "Fan Error: Phase Failure (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 969,
   "name": "8107_1_8",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 970,
   "name": "8108_1_8",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 971,
   "name": "8109_1_8",
   "description": "Fan Error: General Failure (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 972,
   "name": "8110_1_8",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 973,
   "name": "8111_1_8",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 974,
   "name": "8112_1_8",
   "description": "Fan Error: Locked Motor (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 975,
   "name": "8113_1_8",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 976,
   "name": "8114_1_8",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 977,
   "name": "8115_1_8",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 978,
   "name": "8116_1_8",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 979,
   "name": "8117_1_8",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 980,
   "name": "8118_1_8",
   "description": "Fan Warning: Identification (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 981,
   "name": "8193_1_8",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 8)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 991,
   "name": "8106_1_9",
   "description": "Fan Error: Phase Failure (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 992,
   "name": "8107_1_9",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 993,
   "name": "8108_1_9",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 994,
   "name": "8109_1_9",
   "description": "Fan Error: General Failure (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 995,
   "name": "8110_1_9",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 996,
   "name": "8111_1_9",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 997,
   "name": "8112_1_9",
   "description": "Fan Error: Locked Motor (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 998,
   "name": "8113_1_9",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 999,
   "name": "8114_1_9",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1000,
   "name": "8115_1_9",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1001,
   "name": "8116_1_9",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1002,
   "name": "8117_1_9",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1003,
   "name": "8118_1_9",
   "description": "Fan Warning: Identification (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1004,
   "name": "8193_1_9",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 9)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1014,
   "name": "8106_1_10",
   "description": "Fan Error: Phase Failure (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1015,
   "name": "8107_1_10",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1016,
   "name": "8108_1_10",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1017,
   "name": "8109_1_10",
   "description": "Fan Error: General Failure (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1018,
   "name": "8110_1_10",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1019,
   "name": "8111_1_10",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1020,
   "name": "8112_1_10",
   "description": "Fan Error: Locked Motor (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1021,
   "name": "8113_1_10",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1022,
   "name": "8114_1_10",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1023,
   "name": "8115_1_10",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1024,
   "name": "8116_1_10",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1025,
   "name": "8117_1_10",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1026,
   "name": "8118_1_10",
   "description": "Fan Warning: Identification (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1027,
   "name": "8193_1_10",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 10)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1037,
   "name": "8106_1_11",
   "description": "Fan Error: Phase Failure (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1038,
   "name": "8107_1_11",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1039,
   "name": "8108_1_11",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1040,
   "name": "8109_1_11",
   "description": "Fan Error: General Failure (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1041,
   "name": "8110_1_11",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1042,
   "name": "8111_1_11",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1043,
   "name": "8112_1_11",
   "description": "Fan Error: Locked Motor (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1044,
   "name": "8113_1_11",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1045,
   "name": "8114_1_11",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1046,
   "name": "8115_1_11",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1047,
   "name": "8116_1_11",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1048,
   "name": "8117_1_11",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1049,
   "name": "8118_1_11",
   "description": "Fan Warning: Identification (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1050,
   "name": "8193_1_11",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 11)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1060,
   "name": "8106_1_12",
   "description": "Fan Error: Phase Failure (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1061,
   "name": "8107_1_12",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1062,
   "name": "8108_1_12",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1063,
   "name": "8109_1_12",
   "description": "Fan Error: General Failure (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1064,
   "name": "8110_1_12",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1065,
   "name": "8111_1_12",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1066,
   "name": "8112_1_12",
   "description": "Fan Error: Locked Motor (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1067,
   "name": "8113_1_12",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1068,
   "name": "8114_1_12",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1069,
   "name": "8115_1_12",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1070,
   "name": "8116_1_12",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1071,
   "name": "8117_1_12",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1072,
   "name": "8118_1_12",
   "description": "Fan Warning: Identification (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1073,
   "name": "8193_1_12",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 12)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1083,
   "name": "8106_1_13",
   "description": "Fan Error: Phase Failure (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1084,
   "name": "8107_1_13",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1085,
   "name": "8108_1_13",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1086,
   "name": "8109_1_13",
   "description": "Fan Error: General Failure (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1087,
   "name": "8110_1_13",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1088,
   "name": "8111_1_13",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1089,
   "name": "8112_1_13",
   "description": "Fan Error: Locked Motor (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1090,
   "name": "8113_1_13",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1091,
   "name": "8114_1_13",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1092,
   "name": "8115_1_13",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1093,
   "name": "8116_1_13",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1094,
   "name": "8117_1_13",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1095,
   "name": "8118_1_13",
   "description": "Fan Warning: Identification (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1096,
   "name": "8193_1_13",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 13)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1106,
   "name": "8106_1_14",
   "description": "Fan Error: Phase Failure (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1107,
   "name": "8107_1_14",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1108,
   "name": "8108_1_14",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1109,
   "name": "8109_1_14",
   "description": "Fan Error: General Failure (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1110,
   "name": "8110_1_14",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1111,
   "name": "8111_1_14",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1112,
   "name": "8112_1_14",
   "description": "Fan Error: Locked Motor (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1113,
   "name": "8113_1_14",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1114,
   "name": "8114_1_14",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1115,
   "name": "8115_1_14",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1116,
   "name": "8116_1_14",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1117,
   "name": "8117_1_14",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1118,
   "name": "8118_1_14",
   "description": "Fan Warning: Identification (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1119,
   "name": "8193_1_14",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 14)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1129,
   "name": "8106_1_15",
   "description": "Fan Error: Phase Failure (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1130,
   "name": "8107_1_15",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1131,
   "name": "8108_1_15",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1132,
   "name": "8109_1_15",
   "description": "Fan Error: General Failure (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1133,
   "name": "8110_1_15",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1134,
   "name": "8111_1_15",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1135,
   "name": "8112_1_15",
   "description": "Fan Error: Locked Motor (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1136,
   "name": "8113_1_15",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1137,
   "name": "8114_1_15",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1138,
   "name": "8115_1_15",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1139,
   "name": "8116_1_15",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1140,
   "name": "8117_1_15",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1141,
   "name": "8118_1_15",
   "description": "Fan Warning: Identification (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1142,
   "name": "8193_1_15",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 15, 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1152,
   "name": "8106_1_16",
   "description": "Fan Error: Phase Failure (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1153,
   "name": "8107_1_16",
   "description": "Fan Error: Pwr Mod Overheated (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1154,
   "name": "8108_1_16",
   "description": "Fan Error: Internal Comms Error (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1155,
   "name": "8109_1_16",
   "description": "Fan Error: General Failure (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1156,
   "name": "8110_1_16",
   "description": "Fan Error: Motor Overheated (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1157,
   "name": "8111_1_16",
   "description": "Fan Error: Hall Sensor Error (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1158,
   "name": "8112_1_16",
   "description": "Fan Error: Locked Motor (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1159,
   "name": "8113_1_16",
   "description": "Fan Warning: High Supply Voltage (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1160,
   "name": "8114_1_16",
   "description": "Fan Warning: DC-link voltage high (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1161,
   "name": "8115_1_16",
   "description": "Fan Warning: High Interior Temperature (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1162,
   "name": "8116_1_16",
   "description": "Fan Warning: High Motor Temperature (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1163,
   "name": "8117_1_16",
   "description": "Fan Error: DC-link undervoltage (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1164,
   "name": "8118_1_16",
   "description": "Fan Warning: Identification (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1165,
   "name": "8193_1_16",
   "description": "Fan Error: Speed Limit or Rotor Sens Calib (Supply Fan Status 16)",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=Not OK"
  },
  {
   "type": "MV",
   "instance": 1209,
   "name": "8144_1_1",
   "description": "Fluid Temperature Control Type",
   "units": "",
   "access": "W",
   "states": "1=Proportional, 2=Prop+Integral, 3=Adaptive PID, 4=Intelligent"
  },
  {
   "type": "MV",
   "instance": 1220,
   "name": "8148_1_1",
   "description": "Fluid Control Type",
   "units": "",
   "access": "W",
   "states": "1=Flow Rate, 2=Differential Pressure, 3=Flow Rate with DP Limit, 4=Diff Prs with Flo Limit, 5=Manual"
  },
  {
   "type": "MV",
   "instance": 1231,
   "name": "8161_1_1",
   "description": "Pump Operation Type",
   "units": "",
   "access": "W",
   "states": "1=Unit On or Standby, 2=Unit On, Off, or Standby"
  },
  {
   "type": "MV",
   "instance": 1242,
   "name": "8162_1_1",
   "description": "Fluid Dew Pnt Margin",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/vertiv/icom-v4-precision-cooling",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}