UPS (uninterruptible power supply) · BACnet points list

Vertiv Liebert APM 160 UPS BACnet points list

Updated 6 November 2026

Short answer

The Liebert APM 160 UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.

This page lists 440 BACnet objects for the Vertiv Liebert APM 160 UPS — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert APM 160 UPS
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
440 (1 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
APM 160, Liebert APM160, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 440 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert APM 160 UPS

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 3454123_1Normal, warning or alarm stateRead
MV 3444872_1Load on inverter, bypass or batteryRead
AV 584150_1Estimated battery runtime, minRead
AV 1954208_1Output power, kWRead
AV 14097_1Input voltage, VRead
AV 1684385_1Output voltage, VRead
AV 1714204_1Output current, ARead
BV 394168_1Load is on batteryRead
BV 6424300_1Internal communication lostRead

Network setup

Watch out for

Vertiv Liebert APM 160 UPS BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

440 of 440 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert APM 160 UPS BACnet Points List
DescriptionStates
BV15155_1Mains Input Neutral LostReadActive = alarm
BV24146_1System Input Phs Rotation ErrorReadActive = alarm
BV34122_1System Input Power ProblemReadActive = alarm
BV46061_1Input Source BackfeedReadActive = alarm
BV154135_1Bypass Not AvailableReadActive = alarm
BV164143_1Bypass Static Switch UnavailableReadActive = alarm
BV174139_1Bypass - Excess Auto RetransfersReadActive = alarm
BV184298_1UPS Output on BypassReadActive = alarm
BV194299_1Output Load on Maint. BypassReadActive = alarm
BV204216_1Bypass Backfeed DetectedReadActive = alarm
BV218199_1Load on Bypass UnionReadActive = alarm
BV228200_1Bypass Control Module Not AvailableReadActive = alarm
BV238201_1Bypass Module Not AvailableReadActive = alarm
BV248096_1Bypass controlling the SCR autonomouslyReadActive = alarm
BV258283_1Bypass Unable to TraceReadActive = alarm
BV367485_1Battery Circuit Breaker OpenReadActive = alarm
BV374741_1Battery Self TestReadActive = alarm
BV384200_1Battery Charging InhibitedReadActive = alarm
BVmin394168_1Battery DischargingReadActive = alarm
BV404171_1Battery Manual Test In ProgressReadActive = alarm
BV414172_1Battery Auto Test In ProgressReadActive = alarm
BV424322_1Battery Test PassedReadActive = alarm
BV434323_1Battery Test FailedReadActive = alarm
BV444219_1Battery Over TemperatureReadActive = alarm
BV454162_1Battery LowReadActive = alarm
BV464222_1Battery Ground FaultReadActive = alarm
BV475149_1Battery Not QualifiedReadActive = alarm
BV485150_1Battery Terminals ReversedReadActive = alarm
BV494166_1Battery Capacity LowReadActive = alarm
BV506063_1Battery Converter Current LimitReadActive = alarm
BV516065_1Battery Charge Equalization TimeoutReadActive = alarm
BV526068_1Battery Room AlarmReadActive = alarm
BV537461_1Battery Breaker Open FailureReadActive = alarm
BV544170_1Battery EqualizeReadActive = alarm
BV555874_1Battery Over VoltageReadActive = alarm
BV568288_1Battery Terminal AbnormalReadActive = alarm
BV578194_1Battery Management System Rack is Offline WarningReadActive = alarm
BV588195_1Battery Management System General WarningReadActive = alarm
BV598196_1Battery Management System FaultReadActive = alarm
BV706062_1Loss of SynchronizationReadActive = alarm
BV815806_1Output OverloadReadActive = alarm
BV824389_1System Output FaultReadActive = alarm
BV838284_1Output Breaker OpenReadActive = alarm
BV946438_1Power Module Input Current Abnormal (Power Modules 1)ReadActive = alarm
BV958285_1Power Module Input Current High (Power Modules 1)ReadActive = alarm
BV964295_1Rectifier Failure (Power Modules 1)ReadActive = alarm
BV974233_1Inverter Failure (Power Modules 1)ReadActive = alarm
BV985154_1DC Bus Abnormal (Power Modules 1)ReadActive = alarm
BV995153_1Load Sharing Fault (Power Modules 1)ReadActive = alarm
BV1006059_1Inverter Relay Fault (Power Modules 1)ReadActive = alarm
BV1014164_1Battery Charging Error (Power Modules 1)ReadActive = alarm
BV1025151_1Battery Converter Failure (Power Modules 1)ReadActive = alarm
BV1036439_1Power Module Balancer of DC Bus Failure (Power Modules 1)ReadActive = alarm
BV1044290_1Inverter Shutdown - Overload (Power Modules 1)ReadActive = alarm
BV1056440_1Power Module Fuse Failure (Power Modules 1)ReadActive = alarm
BV1066441_1Power Module Power Supply Failure (Power Modules 1)ReadActive = alarm
BV1075838_1Power Module Fan Fault (Power Modules 1)ReadActive = alarm
BV1085839_1Power Module Over Temperature (Power Modules 1)ReadActive = alarm
BV1098098_1Power Module Communication status (Power Modules 1)ReadActive = alarm
BV1106528_1Power Module Lever Unlocked (Power Modules 1)ReadActive = alarm
BV1216438_2Power Module Input Current Abnormal (Power Modules 2)ReadActive = alarm
BV1228285_2Power Module Input Current High (Power Modules 2)ReadActive = alarm
BV1234295_2Rectifier Failure (Power Modules 2)ReadActive = alarm
BV1244233_2Inverter Failure (Power Modules 2)ReadActive = alarm
BV1255154_2DC Bus Abnormal (Power Modules 2)ReadActive = alarm
BV1265153_2Load Sharing Fault (Power Modules 2)ReadActive = alarm
BV1276059_2Inverter Relay Fault (Power Modules 2)ReadActive = alarm
BV1284164_2Battery Charging Error (Power Modules 2)ReadActive = alarm
BV1295151_2Battery Converter Failure (Power Modules 2)ReadActive = alarm
BV1306439_2Power Module Balancer of DC Bus Failure (Power Modules 2)ReadActive = alarm
BV1314290_2Inverter Shutdown - Overload (Power Modules 2)ReadActive = alarm
BV1326440_2Power Module Fuse Failure (Power Modules 2)ReadActive = alarm
BV1336441_2Power Module Power Supply Failure (Power Modules 2)ReadActive = alarm
BV1345838_2Power Module Fan Fault (Power Modules 2)ReadActive = alarm
BV1355839_2Power Module Over Temperature (Power Modules 2)ReadActive = alarm
BV1368098_2Power Module Communication status (Power Modules 2)ReadActive = alarm
BV1376528_2Power Module Lever Unlocked (Power Modules 2)ReadActive = alarm
BV6076438_20Power Module Input Current Abnormal (Power Modules 20)ReadActive = alarm
BV6088285_20Power Module Input Current High (Power Modules 20)ReadActive = alarm
BV6094295_20Rectifier Failure (Power Modules 20)ReadActive = alarm
BV6104233_20Inverter Failure (Power Modules 20)ReadActive = alarm
BV6115154_20DC Bus Abnormal (Power Modules 20)ReadActive = alarm
BV6125153_20Load Sharing Fault (Power Modules 20)ReadActive = alarm
BV6136059_20Inverter Relay Fault (Power Modules 20)ReadActive = alarm
BV6144164_20Battery Charging Error (Power Modules 20)ReadActive = alarm
BV6155151_20Battery Converter Failure (Power Modules 20)ReadActive = alarm
BV6166439_20Power Module Balancer of DC Bus Failure (Power Modules 20)ReadActive = alarm
BV6174290_20Inverter Shutdown - Overload (Power Modules 20)ReadActive = alarm
BV6186440_20Power Module Fuse Failure (Power Modules 20)ReadActive = alarm
BV6196441_20Power Module Power Supply Failure (Power Modules 20)ReadActive = alarm
BV6205838_20Power Module Fan Fault (Power Modules 20)ReadActive = alarm
BV6215839_20Power Module Over Temperature (Power Modules 20)ReadActive = alarm
BV6228098_20Power Module Communication status (Power Modules 20)ReadActive = alarm
BV6236528_20Power Module Lever Unlocked (Power Modules 20)ReadActive = alarm
BV6345817_1Loss of RedundancyReadActive = alarm
BV6356529_1Hardware MismatchReadActive = alarm
BV6366066_1Parallel Cable FailureReadActive = alarm
BV6376064_1LBS Cable FailureReadActive = alarm
BV6386060_1Transfer to Bypass - System OverloadReadActive = alarm
BV6395458_1Excess ECO SuspendsReadActive = alarm
BV6405157_1User Operation InvalidReadActive = alarm
BV6415156_1Load Impact TransferReadActive = alarm
BVmin6424300_1Internal Communications FailureReadActive = alarm
BV6434823_1Parallel Comm WarningReadActive = alarm
BV6444310_1Equipment Over TemperatureReadActive = alarm
BV6454758_1LBS InhibitedReadActive = alarm
BV6464315_1On GeneratorReadActive = alarm
BV6474757_1LBS ActiveReadActive = alarm
BV6484213_1System Shutdown - EPOReadActive = alarm
BV6496536_1MMS Capacity ExceededReadActive = alarm
BV6504440_1Fuse FailureReadActive = alarm
BV6515970_1Ground FaultReadActive = alarm
BV6524311_1System Fan FailureReadActive = alarm
BV6538286_1Parameter Configuration FailedReadActive = alarm
BV6544215_1System Output OffReadActive = alarm
BV6658227_1SPM Internal Comm FailureReadActive = alarm
BV6668228_1SPM CRC Check ErrorReadActive = alarm
BV6778229_1_1SPM Board Not Ready (SPM Board Not Ready 1)ReadActive = alarm
BV6888229_1_2SPM Board Not Ready (SPM Board Not Ready 2)ReadActive = alarm
BV7988229_1_12SPM Board Not Ready (SPM Board Not Ready 12)ReadActive = alarm
BV8098208_1_1Branch Over Current (Branch Group 1 Branch 1)ReadActive = alarm
BV8108209_1_1Branch Current Over HL (Branch Group 1 Branch 1)ReadActive = alarm
BV8118210_1_1Branch Current Over LL (Branch Group 1 Branch 1)ReadActive = alarm
BV8128212_1_1Branch Breaker Fail (Branch Group 1 Branch 1)ReadActive = alarm
BV8238208_1_2Branch Over Current (Branch Group 1 Branch 2)ReadActive = alarm
BV8248209_1_2Branch Current Over HL (Branch Group 1 Branch 2)ReadActive = alarm
BV8258210_1_2Branch Current Over LL (Branch Group 1 Branch 2)ReadActive = alarm
BV8268212_1_2Branch Breaker Fail (Branch Group 1 Branch 2)ReadActive = alarm
BV11318208_1_24Branch Over Current (Branch Group 1 Branch 24)ReadActive = alarm
BV11328209_1_24Branch Current Over HL (Branch Group 1 Branch 24)ReadActive = alarm
BV11338210_1_24Branch Current Over LL (Branch Group 1 Branch 24)ReadActive = alarm
BV11348212_1_24Branch Breaker Fail (Branch Group 1 Branch 24)ReadActive = alarm
BV11458208_2_1Branch Over Current (Branch Group 2 Branch 1)ReadActive = alarm
BV11468209_2_1Branch Current Over HL (Branch Group 2 Branch 1)ReadActive = alarm
BV11478210_2_1Branch Current Over LL (Branch Group 2 Branch 1)ReadActive = alarm
BV11488212_2_1Branch Breaker Fail (Branch Group 2 Branch 1)ReadActive = alarm
BV11598208_2_2Branch Over Current (Branch Group 2 Branch 2)ReadActive = alarm
BV11608209_2_2Branch Current Over HL (Branch Group 2 Branch 2)ReadActive = alarm
BV11618210_2_2Branch Current Over LL (Branch Group 2 Branch 2)ReadActive = alarm
BV11628212_2_2Branch Breaker Fail (Branch Group 2 Branch 2)ReadActive = alarm
BV14678208_2_24Branch Over Current (Branch Group 2 Branch 24)ReadActive = alarm
BV14688209_2_24Branch Current Over HL (Branch Group 2 Branch 24)ReadActive = alarm
BV14698210_2_24Branch Current Over LL (Branch Group 2 Branch 24)ReadActive = alarm
BV14708212_2_24Branch Breaker Fail (Branch Group 2 Branch 24)ReadActive = alarm
BV14818208_3_1Branch Over Current (Branch Group 3 Branch 1)ReadActive = alarm
BV14828209_3_1Branch Current Over HL (Branch Group 3 Branch 1)ReadActive = alarm
BV14838210_3_1Branch Current Over LL (Branch Group 3 Branch 1)ReadActive = alarm
BV14848212_3_1Branch Breaker Fail (Branch Group 3 Branch 1)ReadActive = alarm
BV14958208_3_2Branch Over Current (Branch Group 3 Branch 2)ReadActive = alarm
BV14968209_3_2Branch Current Over HL (Branch Group 3 Branch 2)ReadActive = alarm
BV14978210_3_2Branch Current Over LL (Branch Group 3 Branch 2)ReadActive = alarm
BV14988212_3_2Branch Breaker Fail (Branch Group 3 Branch 2)ReadActive = alarm
BV18038208_3_24Branch Over Current (Branch Group 3 Branch 24)ReadActive = alarm
BV18048209_3_24Branch Current Over HL (Branch Group 3 Branch 24)ReadActive = alarm
BV18058210_3_24Branch Current Over LL (Branch Group 3 Branch 24)ReadActive = alarm
BV18068212_3_24Branch Breaker Fail (Branch Group 3 Branch 24)ReadActive = alarm
AVmin14097_1System Input RMS A-BVRead
AV24099_1System Input RMS B-CVRead
AV34101_1System Input RMS C-AVRead
AV44113_1System Input RMS Current Phase AARead
AV54114_1System Input RMS Current Phase BARead
AV64115_1System Input RMS Current Phase CARead
AV74105_1System Input FrequencyHzRead
AV84096_1System Input RMS A-NVRead
AV94098_1System Input RMS B-NVRead
AV104100_1System Input RMS C-NVRead
AV114116_1System Input Power Factor Phs ARead
AV124117_1System Input Power Factor Phs BRead
AV134118_1System Input Power Factor Phs CRead
AV146318_1System Input Power Phase AkWRead
AV156319_1System Input Power Phase BkWRead
AV166320_1System Input Power Phase CkWRead
AV178093_1System Input Apparent Power Phs AkVARead
AV188094_1System Input Apparent Power Phs BkVARead
AV198095_1System Input Apparent Power Phs CkVARead
AV204102_1System Input Nominal VoltageVRead
AV214104_1System Input Nominal CurrentARead
AV224119_1System Input Brown Out CountRead
AV234120_1System Input Black Out CountRead
AV344128_1Bypass Input Voltage RMS A-NVRead
AV354129_1Bypass Input Voltage RMS B-NVRead
AV364130_1Bypass Input Voltage RMS C-NVRead
AV374131_1Bypass Input FrequencyHzRead
AV384125_1Bypass Input Voltage RMS A-BVRead
AV394126_1Bypass Input Voltage RMS B-CVRead
AV404127_1Bypass Input Voltage RMS C-AVRead
AV416325_1Bypass Power Phase AkWRead
AV426326_1Bypass Power Phase BkWRead
AV436327_1Bypass Power Phase CkWRead
AV446328_1Bypass Apparent Power Phase AkVARead
AV456329_1Bypass Apparent Power Phase BkVARead
AV466330_1Bypass Apparent Power Phase CkVARead
AV474259_1Bypass Nominal VoltageVRead
AVmin584150_1Battery Time RemainingminRead
AV594149_1DC Bus CurrentA DCRead
AV605804_1Time Until Next Auto Battery TestminRead
AV614153_1Battery Percentage Charge%Read
AV625845_1Number of Discharge CyclesRead
AV635846_1Accumulated Discharge TimehRead
AV645802_1Low Battery Warning TimeminRead
AV655991_1Battery Self Test Cycle TimedayRead
AV664148_1DC Bus VoltageVDCRead
AV675853_1Battery Temperature°CRead
AV100675853_1_deg_FBattery Temperature°FRead
AV688281_1Positive DC Bus VoltageVDCRead
AV698282_1Negative DC Bus VoltageVDCRead
AV804156_1_1Battery Temperature for Cabinet (Battery Cabinets 1)°CRead
AV100804156_1_1_deg_FBattery Temperature for Cabinet (Battery Cabinets 1)°FRead
AV914156_1_2Battery Temperature for Cabinet (Battery Cabinets 2)°CRead
AV100914156_1_2_deg_FBattery Temperature for Cabinet (Battery Cabinets 2)°FRead
AV1574156_1_8Battery Temperature for Cabinet (Battery Cabinets 8)°CRead
AV101574156_1_8_deg_FBattery Temperature for Cabinet (Battery Cabinets 8)°FRead
AVmin1684385_1System Output Voltage RMS A-NVRead
AV1694386_1System Output Voltage RMS B-NVRead
AV1704387_1System Output Voltage RMS C-NVRead
AVmin1714204_1System Output RMS Current Phs AARead
AV1724205_1System Output RMS Current Phs BARead
AV1734206_1System Output RMS Current Phs CARead
AV1744207_1System Output FrequencyHzRead
AV1754201_1System Output Voltage RMS A-BVRead
AV1764202_1System Output Voltage RMS B-CVRead
AV1774203_1System Output Voltage RMS C-AVRead
AV1784210_1System Output Power Factor Phs ARead
AV1794211_1System Output Power Factor Phs BRead
AV1804212_1System Output Power Factor Phs CRead
AV1814223_1System Output Pct Power Phase A%Read
AV1824224_1System Output Pct Power Phase B%Read
AV1834225_1System Output Pct Power Phase C%Read
AV1844812_1MMS Output Apparent PowerkVARead
AV1854811_1MMS Output PowerkWRead
AV1865159_1Output Current Crest Factor Phs ARead
AV1875160_1Output Current Crest Factor Phs BRead
AV1885161_1Output Current Crest Factor Phs CRead
AV1895859_1System Output Power Phase AkWRead
AV1905860_1System Output Power Phase BkWRead
AV1915959_1System Output Power Phase CkWRead
AV1925868_1System Output Apparent Power Phs AkVARead
AV1935869_1System Output Apparent Power Phs BkVARead
AV1945870_1System Output Apparent Power Phs CkVARead
AVmin1954208_1System Output PowerkWRead
AV1964209_1System Output Apparent PowerkVARead
AV1974226_1System Output Pct Pwr (VA) Phs A%Read
AV1984227_1System Output Pct Pwr (VA) Phs B%Read
AV1994228_1System Output Pct Pwr (VA) Phs C%Read
AV2008097_1ECO Suspended Time RemainingsRead
AV2014260_1System Output Nominal VoltageVRead
AV2024261_1System Output Nominal FrequencyHzRead
AV2136442_1Power Module Bypass Input FrequencyHzRead
AV2146443_1Power Module Bypass Input Voltage RMS A-NVRead
AV2156444_1Power Module Bypass Input Voltage RMS B-NVRead
AV2166445_1Power Module Bypass Input Voltage RMS C-NVRead
AV2176446_1Power Module Bypass Input Voltage RMS A-BVRead
AV2186447_1Power Module Bypass Input Voltage RMS B-CVRead
AV2196448_1Power Module Bypass Input Voltage RMS C-AVRead
AV2305824_1Number Of Active Power ModulesRead
AV2315823_1Number of Installed Power ModulesRead
AV2324291_1Inlet Air Temperature°CRead
AV102324291_1_deg_FInlet Air Temperature°FRead
AV2336069_1Average system efficiency%Read
AV2444293_1System Date and TimeSecs since Epoch(UTC)Write
AV2454292_1Total System Operating TimehRead
AV2465821_1System CapacitykVARead
AV2578215_1_1Total Input RMS Current Phase A (Total Input Source 1)ARead
AV2588216_1_1Total Input RMS Current Phase B (Total Input Source 1)ARead
AV2598217_1_1Total Input RMS Current Phase C (Total Input Source 1)ARead
AV2608232_1_1Total Input Energy Phase A (Total Input Source 1)kWhRead
AV2618233_1_1Total Input Energy Phase B (Total Input Source 1)kWhRead
AV2628234_1_1Total Input Energy Phase C (Total Input Source 1)kWhRead
AV2638235_1_1Total Input Active Power Phase A (Total Input Source 1)kWRead
AV2648236_1_1Total Input Active Power Phase B (Total Input Source 1)kWRead
AV2658237_1_1Total Input Active Power Phase C (Total Input Source 1)kWRead
AV2668218_1_1Total Input Apparent Power Phase A (Total Input Source 1)kVARead
AV2678219_1_1Total Input Apparent Power Phase B (Total Input Source 1)kVARead
AV2688220_1_1Total Input Apparent Power Phase C (Total Input Source 1)kVARead
AV2698221_1_1Total Input THDI Phase A (Total Input Source 1)%Read
AV2708222_1_1Total Input THDI Phase B (Total Input Source 1)%Read
AV2718223_1_1Total Input THDI Phase C (Total Input Source 1)%Read
AV2728238_1_1Input Current Rating (Total Input Source 1)ARead
AV2738239_1_1Total Input Current Load Phase A (Total Input Source 1)%Read
AV2748240_1_1Total Input Current Load Phase B (Total Input Source 1)%Read
AV2758241_1_1Total Input Current Load Phase C (Total Input Source 1)%Read
AV2768242_1_1Total Input Power Factor Phase A (Total Input Source 1)Read
AV2778243_1_1Total Input Power Factor Phase B (Total Input Source 1)Read
AV2788244_1_1Total Input Power Factor Phase C (Total Input Source 1)Read
AV2798245_1_1Total Input Voltage Phase A (Total Input Source 1)VRead
AV2808246_1_1Total Input Voltage Phase B (Total Input Source 1)VRead
AV2818247_1_1Total Input Voltage Phase C (Total Input Source 1)VRead
AV2828248_1_1Total Input Frequency (Total Input Source 1)HzRead
AV2838249_1_1Total Input THDU Phase A (Total Input Source 1)%Read
AV2848250_1_1Total Input THDU Phase B (Total Input Source 1)%Read
AV2858251_1_1Total Input THDU Phase C (Total Input Source 1)%Read
AV2968215_1_2Total Input RMS Current Phase A (Total Input Source 2)ARead
AV2978216_1_2Total Input RMS Current Phase B (Total Input Source 2)ARead
AV2988217_1_2Total Input RMS Current Phase C (Total Input Source 2)ARead
AV2998232_1_2Total Input Energy Phase A (Total Input Source 2)kWhRead
AV3008233_1_2Total Input Energy Phase B (Total Input Source 2)kWhRead
AV3018234_1_2Total Input Energy Phase C (Total Input Source 2)kWhRead
AV3028235_1_2Total Input Active Power Phase A (Total Input Source 2)kWRead
AV3038236_1_2Total Input Active Power Phase B (Total Input Source 2)kWRead
AV3048237_1_2Total Input Active Power Phase C (Total Input Source 2)kWRead
AV3058218_1_2Total Input Apparent Power Phase A (Total Input Source 2)kVARead
AV3068219_1_2Total Input Apparent Power Phase B (Total Input Source 2)kVARead
AV3078220_1_2Total Input Apparent Power Phase C (Total Input Source 2)kVARead
AV3088221_1_2Total Input THDI Phase A (Total Input Source 2)%Read
AV3098222_1_2Total Input THDI Phase B (Total Input Source 2)%Read
AV3108223_1_2Total Input THDI Phase C (Total Input Source 2)%Read
AV3118238_1_2Input Current Rating (Total Input Source 2)ARead
AV3128239_1_2Total Input Current Load Phase A (Total Input Source 2)%Read
AV3138240_1_2Total Input Current Load Phase B (Total Input Source 2)%Read
AV3148241_1_2Total Input Current Load Phase C (Total Input Source 2)%Read
AV3158242_1_2Total Input Power Factor Phase A (Total Input Source 2)Read
AV3168243_1_2Total Input Power Factor Phase B (Total Input Source 2)Read
AV3178244_1_2Total Input Power Factor Phase C (Total Input Source 2)Read
AV3188245_1_2Total Input Voltage Phase A (Total Input Source 2)VRead
AV3198246_1_2Total Input Voltage Phase B (Total Input Source 2)VRead
AV3208247_1_2Total Input Voltage Phase C (Total Input Source 2)VRead
AV3218248_1_2Total Input Frequency (Total Input Source 2)HzRead
AV3228249_1_2Total Input THDU Phase A (Total Input Source 2)%Read
AV3238250_1_2Total Input THDU Phase B (Total Input Source 2)%Read
AV3248251_1_2Total Input THDU Phase C (Total Input Source 2)%Read
AV3358202_1_1Branch Current (Branch Group 1 Branch 1)ARead
AV3365223_1_1Branch Energy (Branch Group 1 Branch 1)kWhRead
AV3375222_1_1Branch Active Power (Branch Group 1 Branch 1)kWRead
AV3388204_1_1Branch Apparent Power (Branch Group 1 Branch 1)kVARead
AV3398205_1_1Branch THDI (Branch Group 1 Branch 1)%Read
AV3405225_1_1Branch Phase Current Load (Branch Group 1 Branch 1)%Read
AV3418206_1_1Branch Current Rating (Branch Group 1 Branch 1)ARead
AV3425224_1_1Branch Power Factor (Branch Group 1 Branch 1)Read
AV3438207_1_1Branch Voltage (Branch Group 1 Branch 1)VRead
AV3548202_1_2Branch Current (Branch Group 1 Branch 2)ARead
AV3555223_1_2Branch Energy (Branch Group 1 Branch 2)kWhRead
AV3565222_1_2Branch Active Power (Branch Group 1 Branch 2)kWRead
AV3578204_1_2Branch Apparent Power (Branch Group 1 Branch 2)kVARead
AV3588205_1_2Branch THDI (Branch Group 1 Branch 2)%Read
AV3595225_1_2Branch Phase Current Load (Branch Group 1 Branch 2)%Read
AV3608206_1_2Branch Current Rating (Branch Group 1 Branch 2)ARead
AV3615224_1_2Branch Power Factor (Branch Group 1 Branch 2)Read
AV3628207_1_2Branch Voltage (Branch Group 1 Branch 2)VRead
AV7728202_1_24Branch Current (Branch Group 1 Branch 24)ARead
AV7735223_1_24Branch Energy (Branch Group 1 Branch 24)kWhRead
AV7745222_1_24Branch Active Power (Branch Group 1 Branch 24)kWRead
AV7758204_1_24Branch Apparent Power (Branch Group 1 Branch 24)kVARead
AV7768205_1_24Branch THDI (Branch Group 1 Branch 24)%Read
AV7775225_1_24Branch Phase Current Load (Branch Group 1 Branch 24)%Read
AV7788206_1_24Branch Current Rating (Branch Group 1 Branch 24)ARead
AV7795224_1_24Branch Power Factor (Branch Group 1 Branch 24)Read
AV7808207_1_24Branch Voltage (Branch Group 1 Branch 24)VRead
AV7918202_2_1Branch Current (Branch Group 2 Branch 1)ARead
AV7925223_2_1Branch Energy (Branch Group 2 Branch 1)kWhRead
AV7935222_2_1Branch Active Power (Branch Group 2 Branch 1)kWRead
AV7948204_2_1Branch Apparent Power (Branch Group 2 Branch 1)kVARead
AV7958205_2_1Branch THDI (Branch Group 2 Branch 1)%Read
AV7965225_2_1Branch Phase Current Load (Branch Group 2 Branch 1)%Read
AV7978206_2_1Branch Current Rating (Branch Group 2 Branch 1)ARead
AV7985224_2_1Branch Power Factor (Branch Group 2 Branch 1)Read
AV7998207_2_1Branch Voltage (Branch Group 2 Branch 1)VRead
AV8108202_2_2Branch Current (Branch Group 2 Branch 2)ARead
AV8115223_2_2Branch Energy (Branch Group 2 Branch 2)kWhRead
AV8125222_2_2Branch Active Power (Branch Group 2 Branch 2)kWRead
AV8138204_2_2Branch Apparent Power (Branch Group 2 Branch 2)kVARead
AV8148205_2_2Branch THDI (Branch Group 2 Branch 2)%Read
AV8155225_2_2Branch Phase Current Load (Branch Group 2 Branch 2)%Read
AV8168206_2_2Branch Current Rating (Branch Group 2 Branch 2)ARead
AV8175224_2_2Branch Power Factor (Branch Group 2 Branch 2)Read
AV8188207_2_2Branch Voltage (Branch Group 2 Branch 2)VRead
AV12288202_2_24Branch Current (Branch Group 2 Branch 24)ARead
AV12295223_2_24Branch Energy (Branch Group 2 Branch 24)kWhRead
AV12305222_2_24Branch Active Power (Branch Group 2 Branch 24)kWRead
AV12318204_2_24Branch Apparent Power (Branch Group 2 Branch 24)kVARead
AV12328205_2_24Branch THDI (Branch Group 2 Branch 24)%Read
AV12335225_2_24Branch Phase Current Load (Branch Group 2 Branch 24)%Read
AV12348206_2_24Branch Current Rating (Branch Group 2 Branch 24)ARead
AV12355224_2_24Branch Power Factor (Branch Group 2 Branch 24)Read
AV12368207_2_24Branch Voltage (Branch Group 2 Branch 24)VRead
AV12478202_3_1Branch Current (Branch Group 3 Branch 1)ARead
AV12485223_3_1Branch Energy (Branch Group 3 Branch 1)kWhRead
AV12495222_3_1Branch Active Power (Branch Group 3 Branch 1)kWRead
AV12508204_3_1Branch Apparent Power (Branch Group 3 Branch 1)kVARead
AV12518205_3_1Branch THDI (Branch Group 3 Branch 1)%Read
AV12525225_3_1Branch Phase Current Load (Branch Group 3 Branch 1)%Read
AV12538206_3_1Branch Current Rating (Branch Group 3 Branch 1)ARead
AV12545224_3_1Branch Power Factor (Branch Group 3 Branch 1)Read
AV12558207_3_1Branch Voltage (Branch Group 3 Branch 1)VRead
AV12668202_3_2Branch Current (Branch Group 3 Branch 2)ARead
AV12675223_3_2Branch Energy (Branch Group 3 Branch 2)kWhRead
AV12685222_3_2Branch Active Power (Branch Group 3 Branch 2)kWRead
AV12698204_3_2Branch Apparent Power (Branch Group 3 Branch 2)kVARead
AV12708205_3_2Branch THDI (Branch Group 3 Branch 2)%Read
AV12715225_3_2Branch Phase Current Load (Branch Group 3 Branch 2)%Read
AV12728206_3_2Branch Current Rating (Branch Group 3 Branch 2)ARead
AV12735224_3_2Branch Power Factor (Branch Group 3 Branch 2)Read
AV12748207_3_2Branch Voltage (Branch Group 3 Branch 2)VRead
AV16848202_3_24Branch Current (Branch Group 3 Branch 24)ARead
AV16855223_3_24Branch Energy (Branch Group 3 Branch 24)kWhRead
AV16865222_3_24Branch Active Power (Branch Group 3 Branch 24)kWRead
AV16878204_3_24Branch Apparent Power (Branch Group 3 Branch 24)kVARead
AV16888205_3_24Branch THDI (Branch Group 3 Branch 24)%Read
AV16895225_3_24Branch Phase Current Load (Branch Group 3 Branch 24)%Read
AV16908206_3_24Branch Current Rating (Branch Group 3 Branch 24)ARead
AV16915224_3_24Branch Power Factor (Branch Group 3 Branch 24)Read
AV16928207_3_24Branch Voltage (Branch Group 3 Branch 24)VRead
MV14766_1Input BreakerRead1=Open, 2=Close, 3=Not Installed
MV26056_1External Input BreakerRead1=Open, 2=Close, 3=Not Installed
MV136057_1External Bypass BreakerRead1=Open, 2=Close, 3=Not Installed
MV144769_1Internal Bypass BreakerRead1=Open, 2=Close, 3=Not Installed
MV255803_1Automatic Battery TestRead1=disabled, 2=enabled
MV264871_1UPS Battery StatusRead1=Unknown, 2=Normal, 3=Low, 4=Depleted
MV275799_1Battery Charge StatusRead1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off)
MV384768_1Output BreakerRead1=Open, 2=Close, 3=Not Installed
MV394746_1Inverter On/Off StateRead1=off, 2=on
MV506437_1Power Module Sleep Status (Power Modules 1)Read1=Sleeping, 2=Not Sleeping
MV518099_1Power Module Ready Status (Power Modules 1)Read1=Not ready, 2=Ready
MV525833_1Module Operating Status (Power Modules 1)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV535864_1Inverter Status (Power Modules 1)Read1=Inverter Inactive, 2=Inverter Active
MV646437_2Power Module Sleep Status (Power Modules 2)Read1=Sleeping, 2=Not Sleeping
MV658099_2Power Module Ready Status (Power Modules 2)Read1=Not ready, 2=Ready
MV665833_2Module Operating Status (Power Modules 2)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV675864_2Inverter Status (Power Modules 2)Read1=Inverter Inactive, 2=Inverter Active
MV3166437_20Power Module Sleep Status (Power Modules 20)Read1=Sleeping, 2=Not Sleeping
MV3178099_20Power Module Ready Status (Power Modules 20)Read1=Not ready, 2=Ready
MV3185833_20Module Operating Status (Power Modules 20)Read1=Normal, 2=Warning, 3=Alarm, 4=Fault
MV3195864_20Inverter Status (Power Modules 20)Read1=Inverter Inactive, 2=Inverter Active
MV3308275_1Application Mode For UPSRead1=UPS Mode, 2=Frequency Converter Mode, 3=Intelligent Paralleling Mode, 4=Intelligent Paralleling Mode Demo, 5=ECO Mode, 6=Intelligent ECO Mode, 7=Intelligent ECO Mode Demo, 8=Testing Mode, 9=Regen Mode, 10=Power Conditioner Mode, 11=Frequency Converter Mode without Battery, 12=Dynamic Online Model
MV3315820_1System Set To Operate WithRead1=No Redundancy, 2=Redundancy
MV3324772_1Maintenance Bypass BreakerRead1=Open, 2=Close, 3=Not Installed
MV3334874_1MMS UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MVmin3444872_1UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MVmin3454123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MV3568224_1Input Source SwitchRead1=None, 2=ATS, 3=Breaker
MV3578225_1ATS StatusRead1=Not Installed, 2=Channel 1, 3=Channel 2, 4=Unknown
MV3588226_1Total Input Breaker StatusRead1=Open, 2=Closed, 3=Not Installed, 4=Unknown
MV3698203_1_1Branch Breaker (Branch Group 1 Branch 1)Read1=Open, 2=Closed, 3=Not Installed, 4=Unknown
MV3808203_1_2Branch Breaker (Branch Group 1 Branch 2)Read1=Open, 2=Closed, 3=Not Installed, 4=Unknown
MV6228203_1_24Branch Breaker (Branch Group 1 Branch 24)Read1=Open, 2=Closed, 3=Not Installed, 4=Unknown
MV6338203_2_1Branch Breaker (Branch Group 2 Branch 1)Read1=Open, 2=Closed, 3=Not Installed, 4=Unknown
MV6448203_2_2Branch Breaker (Branch Group 2 Branch 2)Read1=Open, 2=Closed, 3=Not Installed, 4=Unknown
MV8868203_2_24Branch Breaker (Branch Group 2 Branch 24)Read1=Open, 2=Closed, 3=Not Installed, 4=Unknown
MV8978203_3_1Branch Breaker (Branch Group 3 Branch 1)Read1=Open, 2=Closed, 3=Not Installed, 4=Unknown
MV9088203_3_2Branch Breaker (Branch Group 3 Branch 2)Read1=Open, 2=Closed, 3=Not Installed, 4=Unknown
MV11508203_3_24Branch Breaker (Branch Group 3 Branch 24)Read1=Open, 2=Closed, 3=Not Installed, 4=Unknown
Object ID lookup: Vertiv Liebert APM 160 UPS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert APM 160 UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert APM 160 UPS

How many BACnet points does the Vertiv Liebert APM 160 UPS have?

This list has 440 BACnet objects: 245 analog values, 156 binary values, 39 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert APM 160 UPS BACnet points are writable?

1 of the 440 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert APM 160 UPS BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert APM 160 UPS?

Start with MV 345 4123_1 (Normal, warning or alarm state); MV 344 4872_1 (Load on inverter, bypass or battery); AV 58 4150_1 (Estimated battery runtime, min); AV 195 4208_1 (Output power, kW); AV 1 4097_1 (Input voltage, V); AV 168 4385_1 (Output voltage, V); AV 171 4204_1 (Output current, A); BV 39 4168_1 (Load is on battery); BV 642 4300_1 (Internal communication lost).

How do I check these points on the real Liebert APM 160 UPS?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.