Easy BACnet
  1. Home
  2. BACnet points lists
  3. Vertiv
  4. Liebert GXT5 UPS

UPS (uninterruptible power supply) · BACnet points list

Vertiv Liebert GXT5 UPS BACnet points list

Updated 6 November 2026

Short answer

The Liebert GXT5 UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.

This page lists 272 BACnet objects for the Vertiv Liebert GXT5 UPS — 58 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.

Manufacturer
Vertiv
Model
Liebert GXT5 UPS
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
272 (58 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
GXT5, Liebert GXT5, SL-28170
Source document
Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29)
Download CSV 272 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.

BMS integration notes: Vertiv Liebert GXT5 UPS

Integration in brief

Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 964123_1Normal, warning or alarm stateRead
MV 294872_1Load on inverter, bypass or batteryRead
AV 504150_1Estimated battery runtime, minRead
AV 834208_1Output power, WRead
AV 14096_1Input voltage, VRead
AV 774385_1Output voltage, VRead
AV 804204_1Output current, ARead
BV 404168_1Load is on batteryRead
BV 754300_1Internal communication lostRead

Network setup

Watch out for

Vertiv Liebert GXT5 UPS BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

272 of 272 shown
Type
AnalogBinaryMulti-state
Access
Show
Vertiv Liebert GXT5 UPS BACnet Points List
DescriptionStates
BV14135_1Bypass Not AvailableReadActive = alarm
BV24216_1Bypass Backfeed DetectedReadActive = alarm
BV38309_1Bypass disabledReadActive = alarm
BV124741_1Battery Self TestReadActive = alarm
BV134162_1Battery LowReadActive = alarm
BV144323_1Battery Test FailedReadActive = alarm
BV156182_1Replace BatteryReadActive = alarm
BV165149_1Battery Not QualifiedReadActive = alarm
BV178120_1External Battery Cabinet RemovedReadActive = alarm
BV185150_1Battery Terminals ReversedReadActive = alarm
BV194219_1Battery Over TemperatureReadActive = alarm
BV208307_1Battery cabinet connection abnormalReadActive = alarm
BV217164_1Battery Deep DischargeReadActive = alarm
BV1158344_1_1Battery Voltage Abnormal (Lithium Battery Group 1)ReadActive = alarm
BV1168345_1_1Battery Temperature Abnormal (Lithium Battery Group 1)ReadActive = alarm
BV1178346_1_1Battery Current Abnormal (Lithium Battery Group 1)ReadActive = alarm
BV1188347_1_1Battery Cabinet Address Fault (Lithium Battery Group 1)ReadActive = alarm
BV1198348_1_1Battery Cabinet Connect Fault (Lithium Battery Group 1)ReadActive = alarm
BV1208349_1_1Battery Cabinet Communication Fail (Lithium Battery Group 1)ReadActive = alarm
BV1218336_1_1Lithium Battery Cabinet Wait Charge (Lithium Battery Group 1)ReadActive = alarm
BV1227464_1_1Lithium-Ion Battery System Abnormal (Lithium Battery Group 1)ReadActive = alarm
BV1238439_1_1Battery Cabinet SOH Low (Lithium Battery Group 1)ReadActive = alarm
BV1248438_1_1Battery Cabinet Parallel Failure (Lithium Battery Group 1)ReadActive = alarm
BV1318344_1_2Battery Voltage Abnormal (Lithium Battery Group 2)ReadActive = alarm
BV1328345_1_2Battery Temperature Abnormal (Lithium Battery Group 2)ReadActive = alarm
BV1338346_1_2Battery Current Abnormal (Lithium Battery Group 2)ReadActive = alarm
BV1348347_1_2Battery Cabinet Address Fault (Lithium Battery Group 2)ReadActive = alarm
BV1358348_1_2Battery Cabinet Connect Fault (Lithium Battery Group 2)ReadActive = alarm
BV1368349_1_2Battery Cabinet Communication Fail (Lithium Battery Group 2)ReadActive = alarm
BV1378336_1_2Lithium Battery Cabinet Wait Charge (Lithium Battery Group 2)ReadActive = alarm
BV1387464_1_2Lithium-Ion Battery System Abnormal (Lithium Battery Group 2)ReadActive = alarm
BV1398439_1_2Battery Cabinet SOH Low (Lithium Battery Group 2)ReadActive = alarm
BV1408438_1_2Battery Cabinet Parallel Failure (Lithium Battery Group 2)ReadActive = alarm
BV3558344_1_16Battery Voltage Abnormal (Lithium Battery Group 16)ReadActive = alarm
BV3568345_1_16Battery Temperature Abnormal (Lithium Battery Group 16)ReadActive = alarm
BV3578346_1_16Battery Current Abnormal (Lithium Battery Group 16)ReadActive = alarm
BV3588347_1_16Battery Cabinet Address Fault (Lithium Battery Group 16)ReadActive = alarm
BV3598348_1_16Battery Cabinet Connect Fault (Lithium Battery Group 16)ReadActive = alarm
BV3608349_1_16Battery Cabinet Communication Fail (Lithium Battery Group 16)ReadActive = alarm
BV3618336_1_16Lithium Battery Cabinet Wait Charge (Lithium Battery Group 16)ReadActive = alarm
BV3627464_1_16Lithium-Ion Battery System Abnormal (Lithium Battery Group 16)ReadActive = alarm
BV3638439_1_16Battery Cabinet SOH Low (Lithium Battery Group 16)ReadActive = alarm
BV3648438_1_16Battery Cabinet Parallel Failure (Lithium Battery Group 16)ReadActive = alarm
BV3728331_1_1Battery Cabinet Serial Number Illegal ErrorReadActive = alarm
BV3738332_1_1Lithium Battery Cabinet Online Number ErrorReadActive = alarm
BV3748333_1_1Lithium Battery Cabinet Communication FailureReadActive = alarm
BV3758334_1_1Lithium Battery Cabinet mismatch the unitReadActive = alarm
BV3768335_1_1Lithium Battery Cabinet Address Set ErrorReadActive = alarm
BV3778337_1_1Number of Lithium Battery Cabinets Over LimitReadActive = alarm
BV3788339_1_1Manual lithium battery wake up occurredReadActive = alarm
BV3798338_1_1Lithium Battery Cabinet CheckReadActive = alarm
BV265806_1Output OverloadReadActive = alarm
BV274215_1System Output OffReadActive = alarm
BV284389_1System Output FaultReadActive = alarm
BV298308_1Insufficient capacity to startReadActive = alarm
BV308362_1Turn on failedReadActive = alarm
BV394298_1UPS Output on BypassReadActive = alarm
BVmin404168_1Battery DischargingReadActive = alarm
BV414122_1System Input Power ProblemReadActive = alarm
BV424310_1Equipment Over TemperatureReadActive = alarm
BV436187_1Shutdown PendingReadActive = alarm
BV445588_1Unspecified General EventReadActive = alarm
BV476254_1Charger FailureReadActive = alarm
BV484295_1Rectifier FailureReadActive = alarm
BV494233_1Inverter FailureReadActive = alarm
BV505976_1Maintenance Bypass Breaker ClosedReadActive = alarm
BV514311_1System Fan FailureReadActive = alarm
BV524229_1Emergency Power Off - LatchedReadActive = alarm
BV546454_1DC to DC Converter FaultReadActive = alarm
BV565433_1Transformer OvertemperatureReadActive = alarm
BV575840_1Power Module Shutdown - Over TemperatureReadActive = alarm
BV585850_1System Shutdown - Transformer Over TemperatureReadActive = alarm
BV595155_1Mains Input Neutral LostReadActive = alarm
BV605808_1System Shutdown - Output ShortReadActive = alarm
BV614297_1UPS Output on InverterReadActive = alarm
BV625810_1System Shutdown - Remote ShutdownReadActive = alarm
BV638310_1Auxiliary power faultReadActive = alarm
BV648311_1Output off due to abnormal bypassReadActive = alarm
BV658312_1Local output is disconnectedReadActive = alarm
BV668313_1Output off voltage is not zeroReadActive = alarm
BV678315_1Manual Power OnReadActive = alarm
BV688316_1Remote Power OnReadActive = alarm
BV698317_1Battery to utility transitionReadActive = alarm
BV708318_1UPS was reset to factory defaultsReadActive = alarm
BV718319_1Device Faults were cleared, as requestedReadActive = alarm
BV728320_1Scheduled power on occurredReadActive = alarm
BV738321_1Scheduled power off occurredReadActive = alarm
BV746059_1Inverter Relay FaultReadActive = alarm
BVmin754300_1Internal Communications FailureReadActive = alarm
BV766350_1General FaultReadActive = alarm
BV778368_1System output Inhibit - ExtReadActive = alarm
BV454823_1_1Parallel Comm WarningReadActive = alarm
BV464825_1_1Loss of RedundancyReadActive = alarm
BV3935153_1_1Load Sharing FaultReadActive = alarm
BV3948314_1_1Parallel output frequency abnormalReadActive = alarm
BV3956066_1_1Parallel Cable FailureReadActive = alarm
BV536453_1_1Input Wiring FaultReadActive = alarm
BV1004382_1System Input Current ImbalanceReadActive = alarm
BV1014147_1System Input Current LimitReadActive = alarm
BV1025154_1DC Bus AbnormalReadActive = alarm
BV1038306_1Rectifier soft start failureReadActive = alarm
BV1046061_1Input Source BackfeedReadActive = alarm
AVmin14096_1System Input RMS L1-NVRead
AV24098_1System Input RMS L2-NVRead
AV34100_1System Input RMS L3-NVRead
AV44097_1System Input RMS L1-L2VRead
AV54099_1System Input RMS L2-L3VRead
AV64101_1System Input RMS L3-L1VRead
AV74113_1System Input RMS Current L1ARead
AV84114_1System Input RMS Current L2ARead
AV94115_1System Input RMS Current L3ARead
AV104105_1System Input FrequencyHzRead
AV114116_1System Input Power Factor L1Read
AV124117_1System Input Power Factor L2Read
AV134118_1System Input Power Factor L3Read
AV144106_1System Input Max Voltage L1-NVRead
AV154107_1System Input Min Voltage L1-NVRead
AV164108_1System Input Max Voltage L2-NVRead
AV174109_1System Input Min Voltage L2-NVRead
AV184110_1System Input Max Voltage L3-NVRead
AV194111_1System Input Min Voltage L3-NVRead
AV204102_1System Input Nominal VoltageVRead
AV214104_1System Input Nominal CurrentARead
AV224103_1System Input Nominal FrequencyHzRead
AV234112_1System Input Phase CountRead
AV245900_1Input EnergykWhRead
AV354128_1Bypass Input Voltage RMS L1-NVRead
AV364129_1Bypass Input Voltage RMS L2-NVRead
AV374125_1Bypass Input Voltage RMS L1-L2VRead
AV384131_1Bypass Input FrequencyHzRead
AV394259_1Bypass Nominal VoltageVRead
AVmin504150_1Battery Time RemainingminRead
AV514153_1Battery Percentage Charge%Read
AV524149_1Battery CurrentA DCRead
AV534148_1DC Bus VoltageVDCRead
AV546189_1DC Bus Nominal VoltageVDCRead
AV554156_1Battery Temperature°CRead
AV100554156_1_deg_FBattery Temperature°FRead
AV565853_1The Highest Battery Temperature°CRead
AV100565853_1_deg_FThe Highest Battery Temperature°FRead
AV574898_1Battery RatingAHRead
AV595800_1Number of EBC InstalledRead
AV606195_1Nominal Battery CapacityminRead
AV614151_1Battery Discharge TimeminRead
AV624152_1Battery Total Discharge TimehRead
AV635767_1Total Number of Battery DischargesRead
AV654160_1Battery last replaced timeSecs since Epoch(UTC)Read
AV667462_1Battery State of Health%Read
AV675988_1Battery Float VoltageVDCRead
AV688327_1Battery expiration dateSecs since Epoch(UTC)Read
AV698400_1Battery average temperature°CRead
AV100698400_1_deg_FBattery average temperature°FRead
AV708401_1Battery lowest temperature°CRead
AV100708401_1_deg_FBattery lowest temperature°FRead
AV1798340_1_1Lithium Battery Cabinet State of Charge (Lithium Battery Group 1)%Read
AV1808341_1_1Battery State of Health (Lithium Battery Group 1)%Read
AV1918340_1_2Lithium Battery Cabinet State of Charge (Lithium Battery Group 2)%Read
AV1928341_1_2Battery State of Health (Lithium Battery Group 2)%Read
AV3598340_1_16Lithium Battery Cabinet State of Charge (Lithium Battery Group 16)%Read
AV3608341_1_16Battery State of Health (Lithium Battery Group 16)%Read
AV3718352_1_1Battery periodic test time (hour)Write
AV3728353_1_1Battery periodic test time (minute)Write
AV585802_1_1Low Battery Warning TimeminWrite
AV3748354_1_1Battery reminder (months)Write
AV3758355_1_1Discharge protect timeminWrite
AV3778360_1_1External Battery Cabinets AhWrite
AV646252_1_1Max Charge CurrentA DCWrite
AV3898328_1_1Maximum Cell VoltagemV DCRead
AV3908329_1_1Minimum Cell VoltagemV DCRead
AVmin774385_1System Output Voltage RMS L1-NVRead
AV784386_1System Output Voltage RMS L2-NVRead
AV794201_1System Output Voltage RMS L1-L2VRead
AVmin804204_1System Output RMS Current L1ARead
AV814205_1System Output RMS Current L2ARead
AV824207_1System Output FrequencyHzRead
AVmin834208_1System Output PowerWRead
AV845859_1System Output Power L1WRead
AV855860_1System Output Power L2WRead
AV865861_1System Output Pct Power%Read
AV874223_1System Output Pct Power L1%Read
AV884224_1System Output Pct Power L2%Read
AV894209_1System Output Apparent PowerVARead
AV905868_1System Output Apparent Power L1VARead
AV915869_1System Output Apparent Power L2VARead
AV924210_1System Output Power Factor L1Read
AV934211_1System Output Power Factor L2Read
AV944260_1System Output Nominal VoltageVRead
AV955166_1Output EnergykWhWrite
AV964264_1Output Apparent Power RatingVARead
AV974261_1System Output Nominal FrequencyHzRead
AV985816_1Output On DelaysWrite
AV995815_1Reboot With DelaysWrite
AV1005814_1Shutdown After DelaysWrite
AV1015812_1Nominal Power FactorRead
AV1024811_1Parallel Output PowerWRead
AV1034812_1Parallel Output Apparent PowerVARead
AV1044829_1Parallel IDRead
AV1054833_1Number of parallel unitsRead
AV1164510_1Outlet Group Identifier (Outlet Group 1)Read
AV1274510_2Outlet Group Identifier (Outlet Group 2)Read
AV1494510_4Outlet Group Identifier (Outlet Group 4)Read
AV1604120_1System Input Black Out CountRead
AV1614119_1System Input Brown Out CountRead
AV1634291_1Inlet Air Temperature°CRead
AV101634291_1_deg_FInlet Air Temperature°FRead
AV1656069_1Average system efficiency%Read
AV1644293_1System Date and TimeSecs since Epoch(UTC)Write
AV1624710_1Auto Restart DelaysWrite
AV4138386_1_1Sleep mode power on time HourWrite
AV4148387_1_1Sleep mode power on time MinuteWrite
AV4158389_1_1Sleep mode power off time HourWrite
AV4168390_1_1Sleep mode power off time MinuteWrite
MV14553_1Server ClassRead1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR
MV124871_1UPS Battery StatusRead1=Unknown, 2=Normal, 3=Low, 4=Depleted
MV135799_1Battery Charge StatusRead1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off)
MV176181_1Battery Test ResultRead1=Unknown, 2=Passed, 3=Failed, 4=In Progress, 5=System Failure, 6=Inhibited
MV186183_1Battery Cabinet TypeRead1=Internal, 2=External, 3=LRT
MV206192_1Battery Charger StateRead1=off, 2=on
MV218330_1Battery typeRead1=VRLA, 2=Lithium Battery
MV2288350_1_1Lithium Battery Status (Lithium Battery Group 1)Read1=Idle, 2=charging, 3=discharging, 4=Balance
MV2398350_1_2Lithium Battery Status (Lithium Battery Group 2)Read1=Idle, 2=charging, 3=discharging, 4=Balance
MV3938350_1_16Lithium Battery Status (Lithium Battery Group 16)Read1=Idle, 2=charging, 3=discharging, 4=Balance
MV145803_1_1Automatic Battery TestWrite1=disabled, 2=enabled
MV155805_1_1Auto Battery Test IntervalWrite1=8 weeks, 2=12 weeks, 3=16 weeks, 4=20 weeks, 5=26 weeks
MV4068351_1_1Battery periodic test weekdayWrite1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday
MV165858_1_1Manual Battery TestWrite1=Start Test
MV198121_1_1Acknowledge External Battery Cabinet RemovedWrite1=Acknowledge
MV4098356_1_1Equal chargeWrite1=disabled, 2=enabled
MV4108357_1_1Temperature compensationWrite1=disabled, 2=enabled
MV4118440_1_1Set External Battery Cabinet QuantityWrite1=AutoDetect, 2=0 Cabinets, 3=1 Cabinet, 4=2 Cabinets, 5=3 Cabinets, 6=4 Cabinets, 7=5 Cabinets, 8=6 Cabinets, 9=7 Cabinets, 10=8 Cabinets, 11=9 Cabinets, 12=10 Cabinets
MV4228361_1_1Lithium Battery Manual Wake-upWrite1=Wake up the lithium battery manually
MVmin294872_1UPS Output SourceRead1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer
MV404365_1Outlet Group Power Control (Outlet Group 1)Write1=Off, 2=On, 3=Cycle Power
MV514365_2Outlet Group Power Control (Outlet Group 2)Write1=Off, 2=On, 3=Cycle Power
MV734365_4Outlet Group Power Control (Outlet Group 4)Write1=Off, 2=On, 3=Cycle Power
MV846198_1ECO Mode StatusRead1=off, 2=on
MV855454_1ECO Mode Operation StateWrite1=disabled, 2=enabled
MV868363_1ECO voltage rangeWrite1=+/- 5%, 2=+/- 10%, 3=+/- 15%
MV878364_1ECO frequency rangeWrite1=+/- 1Hz, 2=+/- 2Hz, 3=+/- 3Hz
MV888365_1ECO requalification timeWrite1=1 min, 2=5 min, 3=15 min, 4=30 min
MVmin964123_1System StatusRead1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation
MV984746_1Inverter On/Off StateRead1=off, 2=on
MV996197_1Shutdown ReasonRead1=None, 2=Over Temperature, 3=Overload, 4=DC Bus Overload, 5=Output Short, 6=Line Swap, 7=Low Battery, 8=Remote Command, 9=Input Under Voltage, 10=Power Factor Correction Fail, 11=External Signal Command
MV1006199_1UPS TopologyRead1=unknown, 2=Offline, 3=Line Interactive, 4=Online
MV1148367_1_1Master or slaveRead1=Master, 2=Slave
MV1026188_1Audible Alarm ControlWrite1=off, 2=on
MV1036257_1Silence Audible AlarmWrite1=Silence Alarm
MV975831_1Auto RestartWrite1=disabled, 2=enabled
MV1016191_1Reset Power StatisticsWrite1=Reset
MV1258369_1Clear UPS faultsWrite1=Clear UPS faults
MV1268372_1Guaranteed shutdownWrite1=disabled, 2=enabled
MV1278374_1Start with no batteryWrite1=disabled, 2=enabled
MV1288375_1Any mode shutdown auto restartWrite1=disabled, 2=enabled
MV1298376_1IT system compatibilityWrite1=disabled, 2=enabled
MV1308377_1Model supports Transformer Distribution UnitWrite1=disabled, 2=enabled
MV1318378_1Turn to bypassWrite1=Turn To Bypass
MV1328379_1Startup on bypassWrite1=disabled, 2=enabled
MV1338380_1Frequency selectionRead1=Auto, Bypass enable, 2=Auto, Bypass disable, 3=50Hz, Bypass disable, 4=60Hz, Bypass disable
MV1348381_1Bypass voltage upper limitWrite1=+10%, 2=+15%, 3=+20%
MV1358382_1Bypass voltage lower limitWrite1=-10%, 2=-15%, 3=-20%
MV1368383_1Output Voltage SettingRead1=AutoDetect, 2=100 VAC, 3=110 VAC, 4=115 VAC, 5=120 VAC, 6=125 VAC, 7=200 VAC, 8=208 VAC, 9=220 VAC, 10=230 VAC, 11=240 VAC, 12=100/173 VAC, 13=100/173rvs VAC, 14=100/200 VAC, 15=110/190.5 VAC, 16=110/190.5rvs VAC, 17=110/220 VAC, 18=115/199 VAC, 19=115/199rvs VAC, 20=115/230 VAC, 21=120/208 VAC, 22=120/208rvs VAC, 23=120/240 VAC, 24=125/216.5 VAC, 25=125/216.5rvs VAC, 26=125/250 VAC
MV1478384_1_1Sleep modeWrite1=disabled, 2=enabled
MV1488385_1_1Sleep mode power on day of weekWrite1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday
MV1498388_1_1Sleep mode power off day of weekWrite1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday
MV1608391_1_1Output dry contactWrite1=NO, 2=NC
MV1618393_1_1Dry contact 5 outputWrite1=Low battery, 2=On bypass, 3=On battery, 4=UPS fault
MV1628394_1_1Dry contact 6 outputWrite1=Low battery, 2=On bypass, 3=On battery, 4=UPS fault
MV1738392_1_1Input dry contactWrite1=NO, 2=NC
MV1748395_1_1Dry contact 1 inputWrite1=disabled, 2=Battery mode shutdown, 3=Any mode shutdown, 4=Maintenance mode
MV1758396_1_1Dry contact 2 inputWrite1=disabled, 2=Battery mode shutdown, 3=Any mode shutdown, 4=Maintenance mode
MV1868402_1_1Input Dry contact action setting (Input DryContact for GXT5 work with Transformer Distribution Unit 1)Write1=disabled, 2=Battery mode shutdown, 3=Any mode shutdown, 4=TDU Over temp signal
MV1978402_1_2Input Dry contact action setting (Input DryContact for GXT5 work with Transformer Distribution Unit 2)Write1=disabled, 2=Battery mode shutdown, 3=Any mode shutdown, 4=TDU Over temp signal
Object ID lookup: Vertiv Liebert GXT5 UPS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert GXT5 UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vertiv Liebert GXT5 UPS

How many BACnet points does the Vertiv Liebert GXT5 UPS have?

This list has 272 BACnet objects: 110 analog values, 102 binary values, 60 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vertiv Liebert GXT5 UPS BACnet points are writable?

58 of the 272 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vertiv Liebert GXT5 UPS BACnet documentation?

The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.

What are the minimum BACnet points to integrate the Vertiv Liebert GXT5 UPS?

Start with MV 96 4123_1 (Normal, warning or alarm state); MV 29 4872_1 (Load on inverter, bypass or battery); AV 50 4150_1 (Estimated battery runtime, min); AV 83 4208_1 (Output power, W); AV 1 4096_1 (Input voltage, V); AV 77 4385_1 (Output voltage, V); AV 80 4204_1 (Output current, A); BV 40 4168_1 (Load is on battery); BV 75 4300_1 (Internal communication lost).

How do I check these points on the real Liebert GXT5 UPS?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vertiv BACnet points lists

Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.