- Home
- BACnet points lists
- Vertiv
- Liebert GXT5 UPS
UPS (uninterruptible power supply) · BACnet points list
Vertiv Liebert GXT5 UPS BACnet points list
Updated 6 November 2026
The Liebert GXT5 UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.
This page lists 272 BACnet objects for the Vertiv Liebert GXT5 UPS — 58 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vertiv’s own free documentation, linked below.
- Manufacturer
- Vertiv
- Model
- Liebert GXT5 UPS
- Equipment
- UPS (uninterruptible power supply)
- Equipment type
- Other equipment
- BACnet objects
- 272 (58 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- GXT5, Liebert GXT5, SL-28170
Reference only, provided as-is: verify against Vertiv’s current documentation and the live device before use. Not official Vertiv information. Terms of use.
BMS integration notes: Vertiv Liebert GXT5 UPS
Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 96 | 4123_1 | Normal, warning or alarm state | Read |
| MV 29 | 4872_1 | Load on inverter, bypass or battery | Read |
| AV 50 | 4150_1 | Estimated battery runtime, min | Read |
| AV 83 | 4208_1 | Output power, W | Read |
| AV 1 | 4096_1 | Input voltage, V | Read |
| AV 77 | 4385_1 | Output voltage, V | Read |
| AV 80 | 4204_1 | Output current, A | Read |
| BV 40 | 4168_1 | Load is on battery | Read |
| BV 75 | 4300_1 | Internal communication lost | Read |
Network setup
- The card needs a unique Device Instance Number; the device object represents the card, not the unit.
- The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).
- IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports.
Watch out for
- Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.
- No segmented responses: large ReadPropertyMultiple requests can fail, so split them.
- Only data the managed unit actually has is created on the card, so object counts vary by model and options.
Vertiv Liebert GXT5 UPS BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 1 | 4135_1 | Bypass Not Available | Read | Active = alarm | |
| BV | 2 | 4216_1 | Bypass Backfeed Detected | Read | Active = alarm | |
| BV | 3 | 8309_1 | Bypass disabled | Read | Active = alarm | |
| BV | 12 | 4741_1 | Battery Self Test | Read | Active = alarm | |
| BV | 13 | 4162_1 | Battery Low | Read | Active = alarm | |
| BV | 14 | 4323_1 | Battery Test Failed | Read | Active = alarm | |
| BV | 15 | 6182_1 | Replace Battery | Read | Active = alarm | |
| BV | 16 | 5149_1 | Battery Not Qualified | Read | Active = alarm | |
| BV | 17 | 8120_1 | External Battery Cabinet Removed | Read | Active = alarm | |
| BV | 18 | 5150_1 | Battery Terminals Reversed | Read | Active = alarm | |
| BV | 19 | 4219_1 | Battery Over Temperature | Read | Active = alarm | |
| BV | 20 | 8307_1 | Battery cabinet connection abnormal | Read | Active = alarm | |
| BV | 21 | 7164_1 | Battery Deep Discharge | Read | Active = alarm | |
| BV | 115 | 8344_1_1 | Battery Voltage Abnormal (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 116 | 8345_1_1 | Battery Temperature Abnormal (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 117 | 8346_1_1 | Battery Current Abnormal (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 118 | 8347_1_1 | Battery Cabinet Address Fault (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 119 | 8348_1_1 | Battery Cabinet Connect Fault (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 120 | 8349_1_1 | Battery Cabinet Communication Fail (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 121 | 8336_1_1 | Lithium Battery Cabinet Wait Charge (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 122 | 7464_1_1 | Lithium-Ion Battery System Abnormal (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 123 | 8439_1_1 | Battery Cabinet SOH Low (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 124 | 8438_1_1 | Battery Cabinet Parallel Failure (Lithium Battery Group 1) | Read | Active = alarm | |
| BV | 131 | 8344_1_2 | Battery Voltage Abnormal (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 132 | 8345_1_2 | Battery Temperature Abnormal (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 133 | 8346_1_2 | Battery Current Abnormal (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 134 | 8347_1_2 | Battery Cabinet Address Fault (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 135 | 8348_1_2 | Battery Cabinet Connect Fault (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 136 | 8349_1_2 | Battery Cabinet Communication Fail (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 137 | 8336_1_2 | Lithium Battery Cabinet Wait Charge (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 138 | 7464_1_2 | Lithium-Ion Battery System Abnormal (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 139 | 8439_1_2 | Battery Cabinet SOH Low (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 140 | 8438_1_2 | Battery Cabinet Parallel Failure (Lithium Battery Group 2) | Read | Active = alarm | |
| BV | 355 | 8344_1_16 | Battery Voltage Abnormal (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 356 | 8345_1_16 | Battery Temperature Abnormal (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 357 | 8346_1_16 | Battery Current Abnormal (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 358 | 8347_1_16 | Battery Cabinet Address Fault (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 359 | 8348_1_16 | Battery Cabinet Connect Fault (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 360 | 8349_1_16 | Battery Cabinet Communication Fail (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 361 | 8336_1_16 | Lithium Battery Cabinet Wait Charge (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 362 | 7464_1_16 | Lithium-Ion Battery System Abnormal (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 363 | 8439_1_16 | Battery Cabinet SOH Low (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 364 | 8438_1_16 | Battery Cabinet Parallel Failure (Lithium Battery Group 16) | Read | Active = alarm | |
| BV | 372 | 8331_1_1 | Battery Cabinet Serial Number Illegal Error | Read | Active = alarm | |
| BV | 373 | 8332_1_1 | Lithium Battery Cabinet Online Number Error | Read | Active = alarm | |
| BV | 374 | 8333_1_1 | Lithium Battery Cabinet Communication Failure | Read | Active = alarm | |
| BV | 375 | 8334_1_1 | Lithium Battery Cabinet mismatch the unit | Read | Active = alarm | |
| BV | 376 | 8335_1_1 | Lithium Battery Cabinet Address Set Error | Read | Active = alarm | |
| BV | 377 | 8337_1_1 | Number of Lithium Battery Cabinets Over Limit | Read | Active = alarm | |
| BV | 378 | 8339_1_1 | Manual lithium battery wake up occurred | Read | Active = alarm | |
| BV | 379 | 8338_1_1 | Lithium Battery Cabinet Check | Read | Active = alarm | |
| BV | 26 | 5806_1 | Output Overload | Read | Active = alarm | |
| BV | 27 | 4215_1 | System Output Off | Read | Active = alarm | |
| BV | 28 | 4389_1 | System Output Fault | Read | Active = alarm | |
| BV | 29 | 8308_1 | Insufficient capacity to start | Read | Active = alarm | |
| BV | 30 | 8362_1 | Turn on failed | Read | Active = alarm | |
| BV | 39 | 4298_1 | UPS Output on Bypass | Read | Active = alarm | |
| BVmin | 40 | 4168_1 | Battery Discharging | Read | Active = alarm | |
| BV | 41 | 4122_1 | System Input Power Problem | Read | Active = alarm | |
| BV | 42 | 4310_1 | Equipment Over Temperature | Read | Active = alarm | |
| BV | 43 | 6187_1 | Shutdown Pending | Read | Active = alarm | |
| BV | 44 | 5588_1 | Unspecified General Event | Read | Active = alarm | |
| BV | 47 | 6254_1 | Charger Failure | Read | Active = alarm | |
| BV | 48 | 4295_1 | Rectifier Failure | Read | Active = alarm | |
| BV | 49 | 4233_1 | Inverter Failure | Read | Active = alarm | |
| BV | 50 | 5976_1 | Maintenance Bypass Breaker Closed | Read | Active = alarm | |
| BV | 51 | 4311_1 | System Fan Failure | Read | Active = alarm | |
| BV | 52 | 4229_1 | Emergency Power Off - Latched | Read | Active = alarm | |
| BV | 54 | 6454_1 | DC to DC Converter Fault | Read | Active = alarm | |
| BV | 56 | 5433_1 | Transformer Overtemperature | Read | Active = alarm | |
| BV | 57 | 5840_1 | Power Module Shutdown - Over Temperature | Read | Active = alarm | |
| BV | 58 | 5850_1 | System Shutdown - Transformer Over Temperature | Read | Active = alarm | |
| BV | 59 | 5155_1 | Mains Input Neutral Lost | Read | Active = alarm | |
| BV | 60 | 5808_1 | System Shutdown - Output Short | Read | Active = alarm | |
| BV | 61 | 4297_1 | UPS Output on Inverter | Read | Active = alarm | |
| BV | 62 | 5810_1 | System Shutdown - Remote Shutdown | Read | Active = alarm | |
| BV | 63 | 8310_1 | Auxiliary power fault | Read | Active = alarm | |
| BV | 64 | 8311_1 | Output off due to abnormal bypass | Read | Active = alarm | |
| BV | 65 | 8312_1 | Local output is disconnected | Read | Active = alarm | |
| BV | 66 | 8313_1 | Output off voltage is not zero | Read | Active = alarm | |
| BV | 67 | 8315_1 | Manual Power On | Read | Active = alarm | |
| BV | 68 | 8316_1 | Remote Power On | Read | Active = alarm | |
| BV | 69 | 8317_1 | Battery to utility transition | Read | Active = alarm | |
| BV | 70 | 8318_1 | UPS was reset to factory defaults | Read | Active = alarm | |
| BV | 71 | 8319_1 | Device Faults were cleared, as requested | Read | Active = alarm | |
| BV | 72 | 8320_1 | Scheduled power on occurred | Read | Active = alarm | |
| BV | 73 | 8321_1 | Scheduled power off occurred | Read | Active = alarm | |
| BV | 74 | 6059_1 | Inverter Relay Fault | Read | Active = alarm | |
| BVmin | 75 | 4300_1 | Internal Communications Failure | Read | Active = alarm | |
| BV | 76 | 6350_1 | General Fault | Read | Active = alarm | |
| BV | 77 | 8368_1 | System output Inhibit - Ext | Read | Active = alarm | |
| BV | 45 | 4823_1_1 | Parallel Comm Warning | Read | Active = alarm | |
| BV | 46 | 4825_1_1 | Loss of Redundancy | Read | Active = alarm | |
| BV | 393 | 5153_1_1 | Load Sharing Fault | Read | Active = alarm | |
| BV | 394 | 8314_1_1 | Parallel output frequency abnormal | Read | Active = alarm | |
| BV | 395 | 6066_1_1 | Parallel Cable Failure | Read | Active = alarm | |
| BV | 53 | 6453_1_1 | Input Wiring Fault | Read | Active = alarm | |
| BV | 100 | 4382_1 | System Input Current Imbalance | Read | Active = alarm | |
| BV | 101 | 4147_1 | System Input Current Limit | Read | Active = alarm | |
| BV | 102 | 5154_1 | DC Bus Abnormal | Read | Active = alarm | |
| BV | 103 | 8306_1 | Rectifier soft start failure | Read | Active = alarm | |
| BV | 104 | 6061_1 | Input Source Backfeed | Read | Active = alarm | |
| AVmin | 1 | 4096_1 | System Input RMS L1-N | V | Read | |
| AV | 2 | 4098_1 | System Input RMS L2-N | V | Read | |
| AV | 3 | 4100_1 | System Input RMS L3-N | V | Read | |
| AV | 4 | 4097_1 | System Input RMS L1-L2 | V | Read | |
| AV | 5 | 4099_1 | System Input RMS L2-L3 | V | Read | |
| AV | 6 | 4101_1 | System Input RMS L3-L1 | V | Read | |
| AV | 7 | 4113_1 | System Input RMS Current L1 | A | Read | |
| AV | 8 | 4114_1 | System Input RMS Current L2 | A | Read | |
| AV | 9 | 4115_1 | System Input RMS Current L3 | A | Read | |
| AV | 10 | 4105_1 | System Input Frequency | Hz | Read | |
| AV | 11 | 4116_1 | System Input Power Factor L1 | Read | ||
| AV | 12 | 4117_1 | System Input Power Factor L2 | Read | ||
| AV | 13 | 4118_1 | System Input Power Factor L3 | Read | ||
| AV | 14 | 4106_1 | System Input Max Voltage L1-N | V | Read | |
| AV | 15 | 4107_1 | System Input Min Voltage L1-N | V | Read | |
| AV | 16 | 4108_1 | System Input Max Voltage L2-N | V | Read | |
| AV | 17 | 4109_1 | System Input Min Voltage L2-N | V | Read | |
| AV | 18 | 4110_1 | System Input Max Voltage L3-N | V | Read | |
| AV | 19 | 4111_1 | System Input Min Voltage L3-N | V | Read | |
| AV | 20 | 4102_1 | System Input Nominal Voltage | V | Read | |
| AV | 21 | 4104_1 | System Input Nominal Current | A | Read | |
| AV | 22 | 4103_1 | System Input Nominal Frequency | Hz | Read | |
| AV | 23 | 4112_1 | System Input Phase Count | Read | ||
| AV | 24 | 5900_1 | Input Energy | kWh | Read | |
| AV | 35 | 4128_1 | Bypass Input Voltage RMS L1-N | V | Read | |
| AV | 36 | 4129_1 | Bypass Input Voltage RMS L2-N | V | Read | |
| AV | 37 | 4125_1 | Bypass Input Voltage RMS L1-L2 | V | Read | |
| AV | 38 | 4131_1 | Bypass Input Frequency | Hz | Read | |
| AV | 39 | 4259_1 | Bypass Nominal Voltage | V | Read | |
| AVmin | 50 | 4150_1 | Battery Time Remaining | min | Read | |
| AV | 51 | 4153_1 | Battery Percentage Charge | % | Read | |
| AV | 52 | 4149_1 | Battery Current | A DC | Read | |
| AV | 53 | 4148_1 | DC Bus Voltage | VDC | Read | |
| AV | 54 | 6189_1 | DC Bus Nominal Voltage | VDC | Read | |
| AV | 55 | 4156_1 | Battery Temperature | °C | Read | |
| AV | 10055 | 4156_1_deg_F | Battery Temperature | °F | Read | |
| AV | 56 | 5853_1 | The Highest Battery Temperature | °C | Read | |
| AV | 10056 | 5853_1_deg_F | The Highest Battery Temperature | °F | Read | |
| AV | 57 | 4898_1 | Battery Rating | AH | Read | |
| AV | 59 | 5800_1 | Number of EBC Installed | Read | ||
| AV | 60 | 6195_1 | Nominal Battery Capacity | min | Read | |
| AV | 61 | 4151_1 | Battery Discharge Time | min | Read | |
| AV | 62 | 4152_1 | Battery Total Discharge Time | h | Read | |
| AV | 63 | 5767_1 | Total Number of Battery Discharges | Read | ||
| AV | 65 | 4160_1 | Battery last replaced time | Secs since Epoch(UTC) | Read | |
| AV | 66 | 7462_1 | Battery State of Health | % | Read | |
| AV | 67 | 5988_1 | Battery Float Voltage | VDC | Read | |
| AV | 68 | 8327_1 | Battery expiration date | Secs since Epoch(UTC) | Read | |
| AV | 69 | 8400_1 | Battery average temperature | °C | Read | |
| AV | 10069 | 8400_1_deg_F | Battery average temperature | °F | Read | |
| AV | 70 | 8401_1 | Battery lowest temperature | °C | Read | |
| AV | 10070 | 8401_1_deg_F | Battery lowest temperature | °F | Read | |
| AV | 179 | 8340_1_1 | Lithium Battery Cabinet State of Charge (Lithium Battery Group 1) | % | Read | |
| AV | 180 | 8341_1_1 | Battery State of Health (Lithium Battery Group 1) | % | Read | |
| AV | 191 | 8340_1_2 | Lithium Battery Cabinet State of Charge (Lithium Battery Group 2) | % | Read | |
| AV | 192 | 8341_1_2 | Battery State of Health (Lithium Battery Group 2) | % | Read | |
| AV | 359 | 8340_1_16 | Lithium Battery Cabinet State of Charge (Lithium Battery Group 16) | % | Read | |
| AV | 360 | 8341_1_16 | Battery State of Health (Lithium Battery Group 16) | % | Read | |
| AV | 371 | 8352_1_1 | Battery periodic test time (hour) | Write | ||
| AV | 372 | 8353_1_1 | Battery periodic test time (minute) | Write | ||
| AV | 58 | 5802_1_1 | Low Battery Warning Time | min | Write | |
| AV | 374 | 8354_1_1 | Battery reminder (months) | Write | ||
| AV | 375 | 8355_1_1 | Discharge protect time | min | Write | |
| AV | 377 | 8360_1_1 | External Battery Cabinets Ah | Write | ||
| AV | 64 | 6252_1_1 | Max Charge Current | A DC | Write | |
| AV | 389 | 8328_1_1 | Maximum Cell Voltage | mV DC | Read | |
| AV | 390 | 8329_1_1 | Minimum Cell Voltage | mV DC | Read | |
| AVmin | 77 | 4385_1 | System Output Voltage RMS L1-N | V | Read | |
| AV | 78 | 4386_1 | System Output Voltage RMS L2-N | V | Read | |
| AV | 79 | 4201_1 | System Output Voltage RMS L1-L2 | V | Read | |
| AVmin | 80 | 4204_1 | System Output RMS Current L1 | A | Read | |
| AV | 81 | 4205_1 | System Output RMS Current L2 | A | Read | |
| AV | 82 | 4207_1 | System Output Frequency | Hz | Read | |
| AVmin | 83 | 4208_1 | System Output Power | W | Read | |
| AV | 84 | 5859_1 | System Output Power L1 | W | Read | |
| AV | 85 | 5860_1 | System Output Power L2 | W | Read | |
| AV | 86 | 5861_1 | System Output Pct Power | % | Read | |
| AV | 87 | 4223_1 | System Output Pct Power L1 | % | Read | |
| AV | 88 | 4224_1 | System Output Pct Power L2 | % | Read | |
| AV | 89 | 4209_1 | System Output Apparent Power | VA | Read | |
| AV | 90 | 5868_1 | System Output Apparent Power L1 | VA | Read | |
| AV | 91 | 5869_1 | System Output Apparent Power L2 | VA | Read | |
| AV | 92 | 4210_1 | System Output Power Factor L1 | Read | ||
| AV | 93 | 4211_1 | System Output Power Factor L2 | Read | ||
| AV | 94 | 4260_1 | System Output Nominal Voltage | V | Read | |
| AV | 95 | 5166_1 | Output Energy | kWh | Write | |
| AV | 96 | 4264_1 | Output Apparent Power Rating | VA | Read | |
| AV | 97 | 4261_1 | System Output Nominal Frequency | Hz | Read | |
| AV | 98 | 5816_1 | Output On Delay | s | Write | |
| AV | 99 | 5815_1 | Reboot With Delay | s | Write | |
| AV | 100 | 5814_1 | Shutdown After Delay | s | Write | |
| AV | 101 | 5812_1 | Nominal Power Factor | Read | ||
| AV | 102 | 4811_1 | Parallel Output Power | W | Read | |
| AV | 103 | 4812_1 | Parallel Output Apparent Power | VA | Read | |
| AV | 104 | 4829_1 | Parallel ID | Read | ||
| AV | 105 | 4833_1 | Number of parallel units | Read | ||
| AV | 116 | 4510_1 | Outlet Group Identifier (Outlet Group 1) | Read | ||
| AV | 127 | 4510_2 | Outlet Group Identifier (Outlet Group 2) | Read | ||
| AV | 149 | 4510_4 | Outlet Group Identifier (Outlet Group 4) | Read | ||
| AV | 160 | 4120_1 | System Input Black Out Count | Read | ||
| AV | 161 | 4119_1 | System Input Brown Out Count | Read | ||
| AV | 163 | 4291_1 | Inlet Air Temperature | °C | Read | |
| AV | 10163 | 4291_1_deg_F | Inlet Air Temperature | °F | Read | |
| AV | 165 | 6069_1 | Average system efficiency | % | Read | |
| AV | 164 | 4293_1 | System Date and Time | Secs since Epoch(UTC) | Write | |
| AV | 162 | 4710_1 | Auto Restart Delay | s | Write | |
| AV | 413 | 8386_1_1 | Sleep mode power on time Hour | Write | ||
| AV | 414 | 8387_1_1 | Sleep mode power on time Minute | Write | ||
| AV | 415 | 8389_1_1 | Sleep mode power off time Hour | Write | ||
| AV | 416 | 8390_1_1 | Sleep mode power off time Minute | Write | ||
| MV | 1 | 4553_1 | Server Class | Read | 1=UPS, 2=AIR, 3=PMP, 4=PDU, 5=MONITOR | |
| MV | 12 | 4871_1 | UPS Battery Status | Read | 1=Unknown, 2=Normal, 3=Low, 4=Depleted | |
| MV | 13 | 5799_1 | Battery Charge Status | Read | 1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off) | |
| MV | 17 | 6181_1 | Battery Test Result | Read | 1=Unknown, 2=Passed, 3=Failed, 4=In Progress, 5=System Failure, 6=Inhibited | |
| MV | 18 | 6183_1 | Battery Cabinet Type | Read | 1=Internal, 2=External, 3=LRT | |
| MV | 20 | 6192_1 | Battery Charger State | Read | 1=off, 2=on | |
| MV | 21 | 8330_1 | Battery type | Read | 1=VRLA, 2=Lithium Battery | |
| MV | 228 | 8350_1_1 | Lithium Battery Status (Lithium Battery Group 1) | Read | 1=Idle, 2=charging, 3=discharging, 4=Balance | |
| MV | 239 | 8350_1_2 | Lithium Battery Status (Lithium Battery Group 2) | Read | 1=Idle, 2=charging, 3=discharging, 4=Balance | |
| MV | 393 | 8350_1_16 | Lithium Battery Status (Lithium Battery Group 16) | Read | 1=Idle, 2=charging, 3=discharging, 4=Balance | |
| MV | 14 | 5803_1_1 | Automatic Battery Test | Write | 1=disabled, 2=enabled | |
| MV | 15 | 5805_1_1 | Auto Battery Test Interval | Write | 1=8 weeks, 2=12 weeks, 3=16 weeks, 4=20 weeks, 5=26 weeks | |
| MV | 406 | 8351_1_1 | Battery periodic test weekday | Write | 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday | |
| MV | 16 | 5858_1_1 | Manual Battery Test | Write | 1=Start Test | |
| MV | 19 | 8121_1_1 | Acknowledge External Battery Cabinet Removed | Write | 1=Acknowledge | |
| MV | 409 | 8356_1_1 | Equal charge | Write | 1=disabled, 2=enabled | |
| MV | 410 | 8357_1_1 | Temperature compensation | Write | 1=disabled, 2=enabled | |
| MV | 411 | 8440_1_1 | Set External Battery Cabinet Quantity | Write | 1=AutoDetect, 2=0 Cabinets, 3=1 Cabinet, 4=2 Cabinets, 5=3 Cabinets, 6=4 Cabinets, 7=5 Cabinets, 8=6 Cabinets, 9=7 Cabinets, 10=8 Cabinets, 11=9 Cabinets, 12=10 Cabinets | |
| MV | 422 | 8361_1_1 | Lithium Battery Manual Wake-up | Write | 1=Wake up the lithium battery manually | |
| MVmin | 29 | 4872_1 | UPS Output Source | Read | 1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer | |
| MV | 40 | 4365_1 | Outlet Group Power Control (Outlet Group 1) | Write | 1=Off, 2=On, 3=Cycle Power | |
| MV | 51 | 4365_2 | Outlet Group Power Control (Outlet Group 2) | Write | 1=Off, 2=On, 3=Cycle Power | |
| MV | 73 | 4365_4 | Outlet Group Power Control (Outlet Group 4) | Write | 1=Off, 2=On, 3=Cycle Power | |
| MV | 84 | 6198_1 | ECO Mode Status | Read | 1=off, 2=on | |
| MV | 85 | 5454_1 | ECO Mode Operation State | Write | 1=disabled, 2=enabled | |
| MV | 86 | 8363_1 | ECO voltage range | Write | 1=+/- 5%, 2=+/- 10%, 3=+/- 15% | |
| MV | 87 | 8364_1 | ECO frequency range | Write | 1=+/- 1Hz, 2=+/- 2Hz, 3=+/- 3Hz | |
| MV | 88 | 8365_1 | ECO requalification time | Write | 1=1 min, 2=5 min, 3=15 min, 4=30 min | |
| MVmin | 96 | 4123_1 | System Status | Read | 1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation | |
| MV | 98 | 4746_1 | Inverter On/Off State | Read | 1=off, 2=on | |
| MV | 99 | 6197_1 | Shutdown Reason | Read | 1=None, 2=Over Temperature, 3=Overload, 4=DC Bus Overload, 5=Output Short, 6=Line Swap, 7=Low Battery, 8=Remote Command, 9=Input Under Voltage, 10=Power Factor Correction Fail, 11=External Signal Command | |
| MV | 100 | 6199_1 | UPS Topology | Read | 1=unknown, 2=Offline, 3=Line Interactive, 4=Online | |
| MV | 114 | 8367_1_1 | Master or slave | Read | 1=Master, 2=Slave | |
| MV | 102 | 6188_1 | Audible Alarm Control | Write | 1=off, 2=on | |
| MV | 103 | 6257_1 | Silence Audible Alarm | Write | 1=Silence Alarm | |
| MV | 97 | 5831_1 | Auto Restart | Write | 1=disabled, 2=enabled | |
| MV | 101 | 6191_1 | Reset Power Statistics | Write | 1=Reset | |
| MV | 125 | 8369_1 | Clear UPS faults | Write | 1=Clear UPS faults | |
| MV | 126 | 8372_1 | Guaranteed shutdown | Write | 1=disabled, 2=enabled | |
| MV | 127 | 8374_1 | Start with no battery | Write | 1=disabled, 2=enabled | |
| MV | 128 | 8375_1 | Any mode shutdown auto restart | Write | 1=disabled, 2=enabled | |
| MV | 129 | 8376_1 | IT system compatibility | Write | 1=disabled, 2=enabled | |
| MV | 130 | 8377_1 | Model supports Transformer Distribution Unit | Write | 1=disabled, 2=enabled | |
| MV | 131 | 8378_1 | Turn to bypass | Write | 1=Turn To Bypass | |
| MV | 132 | 8379_1 | Startup on bypass | Write | 1=disabled, 2=enabled | |
| MV | 133 | 8380_1 | Frequency selection | Read | 1=Auto, Bypass enable, 2=Auto, Bypass disable, 3=50Hz, Bypass disable, 4=60Hz, Bypass disable | |
| MV | 134 | 8381_1 | Bypass voltage upper limit | Write | 1=+10%, 2=+15%, 3=+20% | |
| MV | 135 | 8382_1 | Bypass voltage lower limit | Write | 1=-10%, 2=-15%, 3=-20% | |
| MV | 136 | 8383_1 | Output Voltage Setting | Read | 1=AutoDetect, 2=100 VAC, 3=110 VAC, 4=115 VAC, 5=120 VAC, 6=125 VAC, 7=200 VAC, 8=208 VAC, 9=220 VAC, 10=230 VAC, 11=240 VAC, 12=100/173 VAC, 13=100/173rvs VAC, 14=100/200 VAC, 15=110/190.5 VAC, 16=110/190.5rvs VAC, 17=110/220 VAC, 18=115/199 VAC, 19=115/199rvs VAC, 20=115/230 VAC, 21=120/208 VAC, 22=120/208rvs VAC, 23=120/240 VAC, 24=125/216.5 VAC, 25=125/216.5rvs VAC, 26=125/250 VAC | |
| MV | 147 | 8384_1_1 | Sleep mode | Write | 1=disabled, 2=enabled | |
| MV | 148 | 8385_1_1 | Sleep mode power on day of week | Write | 1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday | |
| MV | 149 | 8388_1_1 | Sleep mode power off day of week | Write | 1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday | |
| MV | 160 | 8391_1_1 | Output dry contact | Write | 1=NO, 2=NC | |
| MV | 161 | 8393_1_1 | Dry contact 5 output | Write | 1=Low battery, 2=On bypass, 3=On battery, 4=UPS fault | |
| MV | 162 | 8394_1_1 | Dry contact 6 output | Write | 1=Low battery, 2=On bypass, 3=On battery, 4=UPS fault | |
| MV | 173 | 8392_1_1 | Input dry contact | Write | 1=NO, 2=NC | |
| MV | 174 | 8395_1_1 | Dry contact 1 input | Write | 1=disabled, 2=Battery mode shutdown, 3=Any mode shutdown, 4=Maintenance mode | |
| MV | 175 | 8396_1_1 | Dry contact 2 input | Write | 1=disabled, 2=Battery mode shutdown, 3=Any mode shutdown, 4=Maintenance mode | |
| MV | 186 | 8402_1_1 | Input Dry contact action setting (Input DryContact for GXT5 work with Transformer Distribution Unit 1) | Write | 1=disabled, 2=Battery mode shutdown, 3=Any mode shutdown, 4=TDU Over temp signal | |
| MV | 197 | 8402_1_2 | Input Dry contact action setting (Input DryContact for GXT5 work with Transformer Distribution Unit 2) | Write | 1=disabled, 2=Battery mode shutdown, 3=Any mode shutdown, 4=TDU Over temp signal |
No points match these filters.
Object ID lookup: Vertiv Liebert GXT5 UPS point IDs by name
BV14135_1BV24216_1BV38309_1BV124741_1BV134162_1BV144323_1BV156182_1BV165149_1BV178120_1BV185150_1BV194219_1BV208307_1BV217164_1BV1158344_1_1BV1168345_1_1BV1178346_1_1BV1188347_1_1BV1198348_1_1BV1208349_1_1BV1218336_1_1BV1227464_1_1BV1238439_1_1BV1248438_1_1BV1318344_1_2BV1328345_1_2BV1338346_1_2BV1348347_1_2BV1358348_1_2BV1368349_1_2BV1378336_1_2BV1387464_1_2BV1398439_1_2BV1408438_1_2BV3558344_1_16BV3568345_1_16BV3578346_1_16BV3588347_1_16BV3598348_1_16BV3608349_1_16BV3618336_1_16BV3627464_1_16BV3638439_1_16BV3648438_1_16BV3728331_1_1BV3738332_1_1BV3748333_1_1BV3758334_1_1BV3768335_1_1BV3778337_1_1BV3788339_1_1BV3798338_1_1BV265806_1BV274215_1BV284389_1BV298308_1BV308362_1BV394298_1BV404168_1BV414122_1BV424310_1BV436187_1BV445588_1BV476254_1BV484295_1BV494233_1BV505976_1BV514311_1BV524229_1BV546454_1BV565433_1BV575840_1BV585850_1BV595155_1BV605808_1BV614297_1BV625810_1BV638310_1BV648311_1BV658312_1BV668313_1BV678315_1BV688316_1BV698317_1BV708318_1BV718319_1BV728320_1BV738321_1BV746059_1BV754300_1BV766350_1BV778368_1BV454823_1_1BV464825_1_1BV3935153_1_1BV3948314_1_1BV3956066_1_1BV536453_1_1BV1004382_1BV1014147_1BV1025154_1BV1038306_1BV1046061_1AV14096_1AV24098_1AV34100_1AV44097_1AV54099_1AV64101_1AV74113_1AV84114_1AV94115_1AV104105_1AV114116_1AV124117_1AV134118_1AV144106_1AV154107_1AV164108_1AV174109_1AV184110_1AV194111_1AV204102_1AV214104_1AV224103_1AV234112_1AV245900_1AV354128_1AV364129_1AV374125_1AV384131_1AV394259_1AV504150_1AV514153_1AV524149_1AV534148_1AV546189_1AV554156_1AV100554156_1_deg_FAV565853_1AV100565853_1_deg_FAV574898_1AV595800_1AV606195_1AV614151_1AV624152_1AV635767_1AV654160_1AV667462_1AV675988_1AV688327_1AV698400_1AV100698400_1_deg_FAV708401_1AV100708401_1_deg_FAV1798340_1_1AV1808341_1_1AV1918340_1_2AV1928341_1_2AV3598340_1_16AV3608341_1_16AV3718352_1_1AV3728353_1_1AV585802_1_1AV3748354_1_1AV3758355_1_1AV3778360_1_1AV646252_1_1AV3898328_1_1AV3908329_1_1AV774385_1AV784386_1AV794201_1AV804204_1AV814205_1AV824207_1AV834208_1AV845859_1AV855860_1AV865861_1AV874223_1AV884224_1AV894209_1AV905868_1AV915869_1AV924210_1AV934211_1AV944260_1AV955166_1AV964264_1AV974261_1AV985816_1AV995815_1AV1005814_1AV1015812_1AV1024811_1AV1034812_1AV1044829_1AV1054833_1AV1164510_1AV1274510_2AV1494510_4AV1604120_1AV1614119_1AV1634291_1AV101634291_1_deg_FAV1656069_1AV1644293_1AV1624710_1AV4138386_1_1AV4148387_1_1AV4158389_1_1AV4168390_1_1MV14553_1MV124871_1MV135799_1MV176181_1MV186183_1MV206192_1MV218330_1MV2288350_1_1MV2398350_1_2MV3938350_1_16MV145803_1_1MV155805_1_1MV4068351_1_1MV165858_1_1MV198121_1_1MV4098356_1_1MV4108357_1_1MV4118440_1_1MV4228361_1_1MV294872_1MV404365_1MV514365_2MV734365_4MV846198_1MV855454_1MV868363_1MV878364_1MV888365_1MV964123_1MV984746_1MV996197_1MV1006199_1MV1148367_1_1MV1026188_1MV1036257_1MV975831_1MV1016191_1MV1258369_1MV1268372_1MV1278374_1MV1288375_1MV1298376_1MV1308377_1MV1318378_1MV1328379_1MV1338380_1MV1348381_1MV1358382_1MV1368383_1MV1478384_1_1MV1488385_1_1MV1498388_1_1MV1608391_1_1MV1618393_1_1MV1628394_1_1MV1738392_1_1MV1748395_1_1MV1758396_1_1MV1868402_1_1MV1978402_1_2
Integration notes
- Tables 5.170, 5.171, 5.172, pdf pages 2181-2195 of the 2024 guide (printed page numbers are 4 lower).
- Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.
- Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert GXT5 UPS and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Vertiv Liebert GXT5 UPS
How many BACnet points does the Vertiv Liebert GXT5 UPS have?
This list has 272 BACnet objects: 110 analog values, 102 binary values, 60 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Vertiv Liebert GXT5 UPS BACnet points are writable?
58 of the 272 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Vertiv Liebert GXT5 UPS BACnet documentation?
The source is Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) (SL-28170), revision 2024-04 (Rev 29), published free by Vertiv at https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf.
What are the minimum BACnet points to integrate the Vertiv Liebert GXT5 UPS?
Start with MV 96 4123_1 (Normal, warning or alarm state); MV 29 4872_1 (Load on inverter, bypass or battery); AV 50 4150_1 (Estimated battery runtime, min); AV 83 4208_1 (Output power, W); AV 1 4096_1 (Input voltage, V); AV 77 4385_1 (Output voltage, V); AV 80 4204_1 (Output current, A); BV 40 4168_1 (Load is on battery); BV 75 4300_1 (Internal communication lost).
How do I check these points on the real Liebert GXT5 UPS?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Vertiv BACnet points lists
- Battery monitoring system
Vertiv Alber BDSU battery monitoring
Alber BDSU battery monitoring systems (strings and cells).
Also known as: Alber BDSU, BDSU, Vertiv Alber, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM / NXC / NXR UPS
Liebert APM, NXC and NXR UPS systems.
Also known as: Liebert APM, Liebert NXC, Liebert NXR, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 160 UPS
Liebert APM 160 UPS systems.
Also known as: APM 160, Liebert APM160, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM 600 UPS with GHMI
Liebert APM 600 UPS systems with the GHMI display.
Also known as: APM 600, Liebert APM600, GHMI, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APM2 UPS
Liebert APM2 UPS systems.
Also known as: APM2, Liebert APM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert APS UPS
Liebert APS modular UPS systems.
Also known as: Liebert APS, APS, SL-28170 - Computer room air handling unit
Vertiv Liebert CAHU computer room air handler
Liebert CAHU computer room air handling units (iCOM Edge controller).
Also known as: CAHU, Liebert CAHU, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR012 in-row cooling
Liebert CRV CR012 in-row cooling units (iCOM Edge controller).
Also known as: CR012, Liebert CRV CR012, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR025 / CRD25 / CRD35 in-row cooling
Liebert CRV in-row units CR025, CRD25 and CRD35 (iCOM Edge controller).
Also known as: CR025, CRD25, CRD35, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CR030 / CRC30 / CRC60 in-row cooling
Liebert CRV in-row units CR030, CRC30 and CRC60 (iCOM Edge controller).
Also known as: CR030, CRC30, CRC60, Liebert CRV, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV CRD10 in-row cooling
Liebert CRV CRD10 in-row cooling units (iCOM Edge controller).
Also known as: CRD10, Liebert CRV CRD10, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV in-row cooling (iCOM v4)
Liebert CRV in-row cooling units with the iCOM v4 controller.
Also known as: Liebert CRV, CR019, CR020, CR035, CR040, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4 in-row cooling
Vertiv Liebert CRV4 in-row cooling units (iCOM Edge controller).
Also known as: CRV4, Liebert CRV4, SL-28170 - In-row precision cooling unit (computer room air handler)
Vertiv Liebert CRV4-12 in-row cooling
Vertiv Liebert CRV4-12 in-row cooling units (iCOM Edge controller).
Also known as: CRV4-12, Liebert CRV4 12, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, iCOM CMS card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the iCOM CMS card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert DataMate / Mini-Mate2 (MM2 controller, IS-WEBADPT card)
Liebert DataMate and Mini-Mate2 units with the MM2 controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Liebert Mini-Mate2, Liebert DataMate, MM2, IS-WEBADPT, SL-28170 - XD refrigerant cooling system unit
Vertiv Liebert DCP (Liebert XD system unit)
Liebert DCP units of a Liebert XD pumped-refrigerant cooling system (iCOM v4 controller).
Also known as: Liebert DCP, DCP, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert DME2 precision cooling
Vertiv Liebert DME2 cooling units (iCOM Edge controller).
Also known as: DME2, Liebert DME2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EPM UPS
Liebert EPM UPS systems.
Also known as: Liebert EPM, EPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert EXC / FDC / FPC / PPC / RDC / RX power distribution (LDMF controller)
Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units with the LDMF controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert EXC, LDMF, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL S1 UPS
Liebert EXL S1 UPS systems.
Also known as: EXL S1, Liebert EXL S1, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXL UPS
Liebert EXL UPS systems.
Also known as: Liebert EXL, EXL, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with LCD HMI
Liebert EXM UPS systems whose controller has the LCD HMI.
Also known as: Liebert EXM, EXM LCD, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM UPS, controller with touchscreen HMI
Liebert EXM UPS systems whose controller has the touchscreen HMI.
Also known as: Liebert EXM, EXM touchscreen, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXM2 / APM Plus UPS
Liebert EXM2 and APM Plus UPS systems.
Also known as: EXM2, APM Plus, Liebert EXM2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS / ITA2 UPS
Liebert EXS and ITA2 UPS systems.
Also known as: Liebert EXS, Liebert ITA2, ITA2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert EXS 15-30 kVA 208 V / 30-80 kVA 400 V UPS
Liebert EXS UPS systems, 15-30 kVA at 208 V and 30-80 kVA at 400 V.
Also known as: Liebert EXS, EXS 15-30 kVA, EXS 30-80 kVA, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FDC / FPC / PPC / RDC power distribution (CPM controller)
Liebert FDC, FPC, PPC and RDC power distribution units with the CPM controller.
Also known as: Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, CPM, SL-28170 - Power distribution unit (PDU) monitoring
Vertiv Liebert FPC / PPC power distribution (VPMP controller)
Liebert FPC and PPC power distribution units with the VPMP controller.
Also known as: Liebert FPC, Liebert PPC, VPMP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXE3 UPS
Vertiv Liebert GXE3 UPS systems.
Also known as: GXE3, Liebert GXE3, Vertiv GXE3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert GXT3 / GXT4 UPS
Liebert GXT3 and GXT4 UPS systems.
Also known as: GXT3, GXT4, Liebert GXT4, SL-28170 - Free-cooling chiller
Vertiv Liebert HPC chiller
Liebert HPC chillers with the iCOM v4 controller.
Also known as: Liebert HPC, HPC chiller, SL-28170 - Chilled water precision cooling unit (computer room air handler)
Vertiv Liebert iCOM DCL chilled water cooling
Liebert DCL chilled-water cooling units with the iCOM controller.
Also known as: Liebert DCL, iCOM DCL, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM v4 precision cooling (CW, DS, DSE, PeX, HPM, Challenger 3000, PDX/PCW)
Liebert room cooling units with the iCOM v4 controller: Challenger 3000, Challenger ITR, CW, CWA, Deluxe System/3, DS, DSE, HPM, PeX and PDX/PCW.
Also known as: Liebert CW, Liebert CWA, Liebert DS, Liebert DSE, Liebert PeX, Liebert HPM, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert PDX, Liebert PCW, iCOM v4, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert iCOM XDM precision cooling
Liebert XDM cooling units with the iCOM controller.
Also known as: Liebert XDM, iCOM XDM, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP3000 leak detection
Liebert Liqui-tect LP3000 leak detection panels.
Also known as: LP3000, Liqui-tect LP3000, SL-28170 - Leak detection controller (water sensor cable)
Vertiv Liebert Liqui-tect LP6000 leak detection
Liebert Liqui-tect LP6000 leak detection panels.
Also known as: LP6000, Liqui-tect LP6000, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)
Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.
Also known as: Liebert Mini-Mate2, Mini-Mate2 8 ton, IS-UNITY-DP, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, iCOM CMS card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the iCOM CMS card.
Also known as: Mini-Mate2 8 ton, L8T, ICOM-CMS, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate2 8 ton (L8T controller, IS-WEBADPT card)
Liebert Mini-Mate2 8-ton units with the L8T controller, read through the IS-WEBADPT / OC485-ADPT card.
Also known as: Mini-Mate2 8 ton, L8T, IS-WEBADPT, SL-28170 - Ceiling-mounted precision split cooling unit
Vertiv Liebert Mini-Mate3
Liebert Mini-Mate3 ceiling-mounted cooling units.
Also known as: Mini-Mate3, Liebert MM3, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert MTP UPS
Liebert MTP UPS systems.
Also known as: Liebert MTP, MTP, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NX 225-600 kVA UPS
Liebert NX 225-600 kVA UPS systems upgraded with the MUND control board (IS-UNITY-DP card).
Also known as: Liebert NX, NX 225-600 kVA, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 50 Hz UPS (CE, models 48 and 49)
Liebert NXL UPS, 50 Hz CE version (models 48 and 49).
Also known as: Liebert NXL, NXL model 48, NXL model 49, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert NXL 60 Hz UPS (UL, model 40)
Liebert NXL UPS, 60 Hz UL version (model 40).
Also known as: Liebert NXL, NXL model 40, SL-28170 - Precision cooling unit (computer room air handler)
Vertiv Liebert PEX4 precision cooling
Liebert PEX4 room cooling units (iCOM Edge controller).
Also known as: PEX4, Liebert PeX4, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert PSI5 / Vertiv Edge UPS
Liebert PSI5 line-interactive UPS units.
Also known as: PSI5, Liebert PSI5, Vertiv Edge, SL-28170 - Power distribution panel / transformer monitoring
Vertiv Liebert RXA / TFX power panel
Liebert RXA and TFX power distribution panels.
Also known as: Liebert RXA, Liebert TFX, SL-28170 - Cooling unit group (Liebert SRC)
Vertiv Liebert SRC (iCOM CMS card)
Liebert SRC units read through the iCOM CMS card; the map repeats one block per unit for units 1-8.
Also known as: Liebert SRC, SL-28170 - Static transfer switch
Vertiv Liebert STS2 static transfer switch
Liebert STS2 static transfer switches.
Also known as: STS2, Liebert STS2, SL-28170 - UPS (uninterruptible power supply)
Vertiv Liebert Trinergy Cube UPS
Liebert Trinergy Cube UPS systems.
Also known as: Trinergy Cube, Liebert Trinergy, SL-28170 - Refrigerant chiller for Liebert XD systems
Vertiv Liebert XDC refrigerant chiller
Liebert XDC chillers of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDC, XDC, SL-28170 - Refrigerant pumping unit for Liebert XD systems
Vertiv Liebert XDP refrigerant pumping unit
Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).
Also known as: Liebert XDP, XDP, SL-28170 - Coolant distribution unit (liquid cooling)
Vertiv Liebert XDU coolant distribution unit
Vertiv Liebert XDU coolant distribution units.
Also known as: Liebert XDU, XDU, Vertiv XDU, SL-28170
Source: Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP) · SL-28170 · rev. 2024-04 (Rev 29). Object names, instances and units are reproduced as published; descriptions are our own.