 "manufacturer": "Vertiv",
 "manufacturer_slug": "vertiv",
 "model": "Liebert APM2 UPS",
 "model_slug": "apm2",
 "aliases": [
  "APM2",
  "Liebert APM2",
  "SL-28170"
 ],
 "equipment_type": "UPS (uninterruptible power supply)",
 "applies_to": "Liebert APM2 UPS systems.",
 "summary": "The Liebert APM2 UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Tables 5.118, 5.119, 5.120, pdf pages 1933-1970 of the 2024 guide (printed page numbers are 4 lower).",
  "Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.",
  "Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000."
 ],
 "source": {
  "title": "Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP)",
  "doc_number": "SL-28170",
  "revision_date": "2024-04 (Rev 29)",
  "url": "https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf"
 },
 "integration": {
  "summary": "Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.",
  "minimum_points": [
   {
    "ref": "MV 643",
    "name": "4123_1",
    "why": "Normal, warning or alarm state"
   },
   {
    "ref": "AV 267",
    "name": "4150_1",
    "why": "Estimated battery runtime, min"
   },
   {
    "ref": "AV 77",
    "name": "4208_1",
    "why": "Output power, kW"
   },
   {
    "ref": "AV 1",
    "name": "4097_1",
    "why": "Input voltage, V"
   },
   {
    "ref": "AV 55",
    "name": "4201_1",
    "why": "Output voltage, V"
   },
   {
    "ref": "AV 61",
    "name": "4204_1",
    "why": "Output current, A"
   },
   {
    "ref": "BV 939",
    "name": "4168_1",
    "why": "Load is on battery"
   },
   {
    "ref": "BV 909",
    "name": "4300_1",
    "why": "Internal communication lost"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The card needs a unique Device Instance Number; the device object represents the card, not the unit.",
   "The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).",
   "IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports."
  ],
  "gotchas": [
   "Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.",
   "No segmented responses: large ReadPropertyMultiple requests can fail, so split them.",
   "Only data the managed unit actually has is created on the card, so object counts vary by model and options."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 1,
   "name": "5155_1",
   "description": "Mains Input Neutral Lost",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "4146_1",
   "description": "System Input Phs Rotation Error",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "4122_1",
   "description": "System Input Power Problem",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "6630_1",
   "description": "Input Under Voltage",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "6061_1",
   "description": "Input Source Backfeed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "6333_1",
   "description": "Bypass out of sync",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "5957_1",
   "description": "Bypass Input Voltage Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "4325_1",
   "description": "Backfeed Breaker Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "5976_1",
   "description": "Maintenance Bypass Breaker Closed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "8489_1",
   "description": "System Bypass Phase Rotation Error",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "5806_1",
   "description": "Output Overload",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "4389_1",
   "description": "System Output Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "6220_1",
   "description": "Module Output Breaker Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "8494_1",
   "description": "System Control Card Not Ready (System Control Card 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "8495_1",
   "description": "System Control Card Power Supply Failure (System Control Card 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "8496_1",
   "description": "System Control Card Communication Fail (System Control Card 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "8494_2",
   "description": "System Control Card Not Ready (System Control Card 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "8495_2",
   "description": "System Control Card Power Supply Failure (System Control Card 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "8496_2",
   "description": "System Control Card Communication Fail (System Control Card 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "8501_1",
   "description": "Bypass Module Not Ready",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "8502_1",
   "description": "Bypass Module Power Supply Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 72,
   "name": "8503_1",
   "description": "Bypass Module Communication Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 73,
   "name": "4143_1",
   "description": "Bypass Static Switch Unavailable",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 74,
   "name": "4216_1",
   "description": "Bypass Backfeed Detected",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "8096_1",
   "description": "Bypass controlling the SCR autonomously",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 76,
   "name": "4139_1",
   "description": "Bypass - Excess Auto Retransfers",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 77,
   "name": "8504_1",
   "description": "Bypass Module Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 78,
   "name": "8505_1",
   "description": "Bypass Module Fan Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "8512_1",
   "description": "Power Module Not Ready (Power Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "6441_1",
   "description": "Power Module Power Supply Failure (Power Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "8098_1",
   "description": "Power Module Communication status (Power Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 92,
   "name": "6440_1",
   "description": "Power Module Fuse Failure (Power Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "5838_1",
   "description": "Power Module Fan Fault (Power Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 94,
   "name": "5839_1",
   "description": "Power Module Over Temperature (Power Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 105,
   "name": "6438_1_1",
   "description": "Power Module Input Current Abnormal (Power Module 1 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 106,
   "name": "8285_1_1",
   "description": "Power Module Input Current High (Power Module 1 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 107,
   "name": "4295_1_1",
   "description": "Rectifier Failure (Power Module 1 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 118,
   "name": "5154_1_1",
   "description": "DC Bus Abnormal (Power Module 1 DC Bus 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 119,
   "name": "6439_1_1",
   "description": "Power Module Balancer of DC Bus Failure (Power Module 1 DC Bus 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 130,
   "name": "5153_1_1",
   "description": "Load Sharing Fault (Power Module 1 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 131,
   "name": "6059_1_1",
   "description": "Inverter Relay Fault (Power Module 1 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 132,
   "name": "4290_1_1",
   "description": "Inverter Shutdown - Overload (Power Module 1 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 133,
   "name": "6062_1_1",
   "description": "Loss of Synchronization (Power Module 1 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 134,
   "name": "4233_1_1",
   "description": "Inverter Failure (Power Module 1 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 145,
   "name": "6254_1_1",
   "description": "Charger Failure (Power Module 1 Charger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 156,
   "name": "8510_1_1",
   "description": "Discharger Failure (Power Module 1 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 157,
   "name": "8274_1_1",
   "description": "Discharger Shutdown (Power Module 1 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 158,
   "name": "6063_1_1",
   "description": "Battery Converter Current Limit (Power Module 1 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 169,
   "name": "8512_2",
   "description": "Power Module Not Ready (Power Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 170,
   "name": "6441_2",
   "description": "Power Module Power Supply Failure (Power Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 171,
   "name": "8098_2",
   "description": "Power Module Communication status (Power Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 172,
   "name": "6440_2",
   "description": "Power Module Fuse Failure (Power Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 173,
   "name": "5838_2",
   "description": "Power Module Fan Fault (Power Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 174,
   "name": "5839_2",
   "description": "Power Module Over Temperature (Power Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 185,
   "name": "6438_2_1",
   "description": "Power Module Input Current Abnormal (Power Module 2 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 186,
   "name": "8285_2_1",
   "description": "Power Module Input Current High (Power Module 2 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 187,
   "name": "4295_2_1",
   "description": "Rectifier Failure (Power Module 2 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 198,
   "name": "5154_2_1",
   "description": "DC Bus Abnormal (Power Module 2 DC Bus 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 199,
   "name": "6439_2_1",
   "description": "Power Module Balancer of DC Bus Failure (Power Module 2 DC Bus 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 210,
   "name": "5153_2_1",
   "description": "Load Sharing Fault (Power Module 2 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 211,
   "name": "6059_2_1",
   "description": "Inverter Relay Fault (Power Module 2 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 212,
   "name": "4290_2_1",
   "description": "Inverter Shutdown - Overload (Power Module 2 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 213,
   "name": "6062_2_1",
   "description": "Loss of Synchronization (Power Module 2 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 214,
   "name": "4233_2_1",
   "description": "Inverter Failure (Power Module 2 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 225,
   "name": "6254_2_1",
   "description": "Charger Failure (Power Module 2 Charger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 236,
   "name": "8510_2_1",
   "description": "Discharger Failure (Power Module 2 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 237,
   "name": "8274_2_1",
   "description": "Discharger Shutdown (Power Module 2 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 238,
   "name": "6063_2_1",
   "description": "Battery Converter Current Limit (Power Module 2 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 809,
   "name": "8512_10",
   "description": "Power Module Not Ready (Power Module 10)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 810,
   "name": "6441_10",
   "description": "Power Module Power Supply Failure (Power Module 10)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 811,
   "name": "8098_10",
   "description": "Power Module Communication status (Power Module 10)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 812,
   "name": "6440_10",
   "description": "Power Module Fuse Failure (Power Module 10)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 813,
   "name": "5838_10",
   "description": "Power Module Fan Fault (Power Module 10)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 814,
   "name": "5839_10",
   "description": "Power Module Over Temperature (Power Module 10)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 825,
   "name": "6438_10_1",
   "description": "Power Module Input Current Abnormal (Power Module 10 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 826,
   "name": "8285_10_1",
   "description": "Power Module Input Current High (Power Module 10 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 827,
   "name": "4295_10_1",
   "description": "Rectifier Failure (Power Module 10 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 838,
   "name": "5154_10_1",
   "description": "DC Bus Abnormal (Power Module 10 DC Bus 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 839,
   "name": "6439_10_1",
   "description": "Power Module Balancer of DC Bus Failure (Power Module 10 DC Bus 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 850,
   "name": "5153_10_1",
   "description": "Load Sharing Fault (Power Module 10 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 851,
   "name": "6059_10_1",
   "description": "Inverter Relay Fault (Power Module 10 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 852,
   "name": "4290_10_1",
   "description": "Inverter Shutdown - Overload (Power Module 10 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 853,
   "name": "6062_10_1",
   "description": "Loss of Synchronization (Power Module 10 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 854,
   "name": "4233_10_1",
   "description": "Inverter Failure (Power Module 10 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 865,
   "name": "6254_10_1",
   "description": "Charger Failure (Power Module 10 Charger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 876,
   "name": "8510_10_1",
   "description": "Discharger Failure (Power Module 10 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 877,
   "name": "8274_10_1",
   "description": "Discharger Shutdown (Power Module 10 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 878,
   "name": "6063_10_1",
   "description": "Battery Converter Current Limit (Power Module 10 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 889,
   "name": "6066_1",
   "description": "Parallel Cable Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 890,
   "name": "4823_1",
   "description": "Parallel Comm Warning",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 891,
   "name": "6536_1",
   "description": "MMS Capacity Exceeded",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 892,
   "name": "5817_1",
   "description": "Loss of Redundancy",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 903,
   "name": "6529_1",
   "description": "Hardware Mismatch",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 904,
   "name": "6064_1",
   "description": "LBS Cable Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 905,
   "name": "6060_1",
   "description": "Transfer to Bypass - System Overload",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 906,
   "name": "5458_1",
   "description": "Excess ECO Suspends",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 907,
   "name": "5157_1",
   "description": "User Operation Invalid",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 908,
   "name": "5156_1",
   "description": "Load Impact Transfer",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 909,
   "name": "4300_1",
   "description": "Internal Communications Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 910,
   "name": "4310_1",
   "description": "Equipment Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 911,
   "name": "4758_1",
   "description": "LBS Inhibited",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 912,
   "name": "4315_1",
   "description": "On Generator",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 913,
   "name": "4757_1",
   "description": "LBS Active",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 914,
   "name": "4213_1",
   "description": "System Shutdown - EPO",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 915,
   "name": "4440_1",
   "description": "Fuse Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 916,
   "name": "5970_1",
   "description": "Ground Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 917,
   "name": "4311_1",
   "description": "System Fan Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 918,
   "name": "8286_1",
   "description": "Parameter Configuration Failed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 919,
   "name": "4215_1",
   "description": "System Output Off",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 920,
   "name": "8287_1",
   "description": "Output Disabled",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 921,
   "name": "5770_1",
   "description": "Top Outlet Fan Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 922,
   "name": "8100_1",
   "description": "ECO mode Inhibited",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 923,
   "name": "4289_1",
   "description": "Inverter Transfer Inhibit - Ext",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 924,
   "name": "4298_1",
   "description": "UPS Output on Bypass",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 925,
   "name": "4299_1",
   "description": "Output Load on Maint. Bypass",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 926,
   "name": "5185_1",
   "description": "Transformer Overtemperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 937,
   "name": "4741_1",
   "description": "Battery Self Test",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 938,
   "name": "4200_1",
   "description": "Battery Charging Inhibited",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 939,
   "name": "4168_1",
   "description": "Battery Discharging",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 940,
   "name": "4171_1",
   "description": "Battery Manual Test In Progress",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 941,
   "name": "4172_1",
   "description": "Battery Auto Test In Progress",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 942,
   "name": "4323_1",
   "description": "Battery Test Failed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 943,
   "name": "4162_1",
   "description": "Battery Low",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 944,
   "name": "4222_1",
   "description": "Battery Ground Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 945,
   "name": "5149_1",
   "description": "Battery Not Qualified",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 946,
   "name": "5150_1",
   "description": "Battery Terminals Reversed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 947,
   "name": "6182_1",
   "description": "Replace Battery",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 948,
   "name": "6065_1",
   "description": "Battery Charge Equalization Timeout",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 949,
   "name": "6068_1",
   "description": "Battery Room Alarm",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 950,
   "name": "4170_1",
   "description": "Battery Equalize",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 951,
   "name": "8288_1",
   "description": "Battery Terminal Abnormal",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 952,
   "name": "8429_1",
   "description": "Battery System Communication Abnormal",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 953,
   "name": "8430_1",
   "description": "Battery System Warning",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 954,
   "name": "8431_1",
   "description": "Battery System Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 955,
   "name": "4176_1",
   "description": "Battery Circuit Breaker 1 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 956,
   "name": "4179_1",
   "description": "Battery Circuit Breaker 2 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 957,
   "name": "4182_1",
   "description": "Battery Circuit Breaker 3 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 958,
   "name": "4185_1",
   "description": "Battery Circuit Breaker 4 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 959,
   "name": "4188_1",
   "description": "Battery Circuit Breaker 5 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 960,
   "name": "4191_1",
   "description": "Battery Circuit Breaker 6 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 961,
   "name": "4194_1",
   "description": "Battery Circuit Breaker 7 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 962,
   "name": "4197_1",
   "description": "Battery Circuit Breaker 8 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 963,
   "name": "8517_1",
   "description": "Battery Circuit Breaker 9 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 964,
   "name": "8518_1",
   "description": "Battery Circuit Breaker 10 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 965,
   "name": "8519_1",
   "description": "Battery Circuit Breaker 11 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 966,
   "name": "8520_1",
   "description": "Battery Circuit Breaker 12 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 967,
   "name": "4178_1",
   "description": "Battery Breaker 1 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 968,
   "name": "4180_1",
   "description": "Battery Breaker 2 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 969,
   "name": "4183_1",
   "description": "Battery Breaker 3 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 970,
   "name": "4186_1",
   "description": "Battery Breaker 4 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 971,
   "name": "4190_1",
   "description": "Battery Breaker 5 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 972,
   "name": "4192_1",
   "description": "Battery Breaker 6 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 973,
   "name": "4195_1",
   "description": "Battery Breaker 7 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 974,
   "name": "4198_1",
   "description": "Battery Breaker 8 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 975,
   "name": "8521_1",
   "description": "Battery Breaker 9 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 976,
   "name": "8522_1",
   "description": "Battery Breaker 10 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 977,
   "name": "8523_1",
   "description": "Battery Breaker 11 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 978,
   "name": "8524_1",
   "description": "Battery Breaker 12 Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 989,
   "name": "8537_1",
   "description": "Battery Cabinet High Overall Voltage (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 990,
   "name": "8538_1",
   "description": "Battery Cabinet Low Overall Voltage (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 991,
   "name": "8539_1",
   "description": "Battery Cabinet High Cell Voltage (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 992,
   "name": "8540_1",
   "description": "Battery Cabinet Low Cell Voltage (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 993,
   "name": "8541_1",
   "description": "Battery Cabinet Over Overall Voltage (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 994,
   "name": "8542_1",
   "description": "Battery Cabinet Under Overall Voltage (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 995,
   "name": "8543_1",
   "description": "Battery Cabinet Over Cell Voltage (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 996,
   "name": "8544_1",
   "description": "Battery Cabinet Under Cell Voltage (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 997,
   "name": "8545_1",
   "description": "Battery Cabinet Charge Over Current (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 998,
   "name": "8546_1",
   "description": "Battery Cabinet Discharge Over Current (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 999,
   "name": "8547_1",
   "description": "Battery Cabinet Over Temperature (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1000,
   "name": "8548_1",
   "description": "Battery Cabinet Under Temperature (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1001,
   "name": "4174_1",
   "description": "Battery Temperature Sensor Fault (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1012,
   "name": "8587_1_1",
   "description": "Battery Module Disconnected (Battery Cabinet 1 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1013,
   "name": "8590_1_1",
   "description": "Battery Module Over Temperature (Battery Cabinet 1 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1024,
   "name": "8579_1_1_1",
   "description": "Battery Module High Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1025,
   "name": "8580_1_1_1",
   "description": "Battery Module Low Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1026,
   "name": "8581_1_1_1",
   "description": "Battery Module High Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1027,
   "name": "8582_1_1_1",
   "description": "Battery Module Low Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1028,
   "name": "8583_1_1_1",
   "description": "Battery Module Over Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1029,
   "name": "8584_1_1_1",
   "description": "Battery Module Under Overall Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1030,
   "name": "8585_1_1_1",
   "description": "Battery Module Over Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1031,
   "name": "8586_1_1_1",
   "description": "Battery Module Under Cell Voltage (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1032,
   "name": "8588_1_1_1",
   "description": "Battery Module Charge Over Current (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1033,
   "name": "8589_1_1_1",
   "description": "Battery Module Discharge Over Current (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1034,
   "name": "8591_1_1_1",
   "description": "Battery Module Under Temperature (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1035,
   "name": "8592_1_1_1",
   "description": "Battery Module Fault (Battery Cabinet 1 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1046,
   "name": "8587_1_2",
   "description": "Battery Module Disconnected (Battery Cabinet 1 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1047,
   "name": "8590_1_2",
   "description": "Battery Module Over Temperature (Battery Cabinet 1 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1058,
   "name": "8579_1_2_1",
   "description": "Battery Module High Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1059,
   "name": "8580_1_2_1",
   "description": "Battery Module Low Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1060,
   "name": "8581_1_2_1",
   "description": "Battery Module High Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1061,
   "name": "8582_1_2_1",
   "description": "Battery Module Low Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1062,
   "name": "8583_1_2_1",
   "description": "Battery Module Over Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1063,
   "name": "8584_1_2_1",
   "description": "Battery Module Under Overall Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1064,
   "name": "8585_1_2_1",
   "description": "Battery Module Over Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1065,
   "name": "8586_1_2_1",
   "description": "Battery Module Under Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1066,
   "name": "8588_1_2_1",
   "description": "Battery Module Charge Over Current (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1067,
   "name": "8589_1_2_1",
   "description": "Battery Module Discharge Over Current (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1068,
   "name": "8591_1_2_1",
   "description": "Battery Module Under Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1069,
   "name": "8592_1_2_1",
   "description": "Battery Module Fault (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2066,
   "name": "8587_1_32",
   "description": "Battery Module Disconnected (Battery Cabinet 1 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2067,
   "name": "8590_1_32",
   "description": "Battery Module Over Temperature (Battery Cabinet 1 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2078,
   "name": "8579_1_32_1",
   "description": "Battery Module High Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2079,
   "name": "8580_1_32_1",
   "description": "Battery Module Low Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2080,
   "name": "8581_1_32_1",
   "description": "Battery Module High Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2081,
   "name": "8582_1_32_1",
   "description": "Battery Module Low Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2082,
   "name": "8583_1_32_1",
   "description": "Battery Module Over Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2083,
   "name": "8584_1_32_1",
   "description": "Battery Module Under Overall Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2084,
   "name": "8585_1_32_1",
   "description": "Battery Module Over Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2085,
   "name": "8586_1_32_1",
   "description": "Battery Module Under Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2086,
   "name": "8588_1_32_1",
   "description": "Battery Module Charge Over Current (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2087,
   "name": "8589_1_32_1",
   "description": "Battery Module Discharge Over Current (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2088,
   "name": "8591_1_32_1",
   "description": "Battery Module Under Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2089,
   "name": "8592_1_32_1",
   "description": "Battery Module Fault (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2100,
   "name": "8537_2",
   "description": "Battery Cabinet High Overall Voltage (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2101,
   "name": "8538_2",
   "description": "Battery Cabinet Low Overall Voltage (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2102,
   "name": "8539_2",
   "description": "Battery Cabinet High Cell Voltage (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2103,
   "name": "8540_2",
   "description": "Battery Cabinet Low Cell Voltage (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2104,
   "name": "8541_2",
   "description": "Battery Cabinet Over Overall Voltage (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2105,
   "name": "8542_2",
   "description": "Battery Cabinet Under Overall Voltage (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2106,
   "name": "8543_2",
   "description": "Battery Cabinet Over Cell Voltage (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2107,
   "name": "8544_2",
   "description": "Battery Cabinet Under Cell Voltage (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2108,
   "name": "8545_2",
   "description": "Battery Cabinet Charge Over Current (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2109,
   "name": "8546_2",
   "description": "Battery Cabinet Discharge Over Current (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2110,
   "name": "8547_2",
   "description": "Battery Cabinet Over Temperature (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2111,
   "name": "8548_2",
   "description": "Battery Cabinet Under Temperature (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2112,
   "name": "4174_2",
   "description": "Battery Temperature Sensor Fault (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2123,
   "name": "8587_2_1",
   "description": "Battery Module Disconnected (Battery Cabinet 2 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2124,
   "name": "8590_2_1",
   "description": "Battery Module Over Temperature (Battery Cabinet 2 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2135,
   "name": "8579_2_1_1",
   "description": "Battery Module High Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2136,
   "name": "8580_2_1_1",
   "description": "Battery Module Low Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2137,
   "name": "8581_2_1_1",
   "description": "Battery Module High Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2138,
   "name": "8582_2_1_1",
   "description": "Battery Module Low Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2139,
   "name": "8583_2_1_1",
   "description": "Battery Module Over Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2140,
   "name": "8584_2_1_1",
   "description": "Battery Module Under Overall Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2141,
   "name": "8585_2_1_1",
   "description": "Battery Module Over Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2142,
   "name": "8586_2_1_1",
   "description": "Battery Module Under Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2143,
   "name": "8588_2_1_1",
   "description": "Battery Module Charge Over Current (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2144,
   "name": "8589_2_1_1",
   "description": "Battery Module Discharge Over Current (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2145,
   "name": "8591_2_1_1",
   "description": "Battery Module Under Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2146,
   "name": "8592_2_1_1",
   "description": "Battery Module Fault (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2157,
   "name": "8587_2_2",
   "description": "Battery Module Disconnected (Battery Cabinet 2 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2158,
   "name": "8590_2_2",
   "description": "Battery Module Over Temperature (Battery Cabinet 2 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2169,
   "name": "8579_2_2_1",
   "description": "Battery Module High Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2170,
   "name": "8580_2_2_1",
   "description": "Battery Module Low Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2171,
   "name": "8581_2_2_1",
   "description": "Battery Module High Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2172,
   "name": "8582_2_2_1",
   "description": "Battery Module Low Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2173,
   "name": "8583_2_2_1",
   "description": "Battery Module Over Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2174,
   "name": "8584_2_2_1",
   "description": "Battery Module Under Overall Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2175,
   "name": "8585_2_2_1",
   "description": "Battery Module Over Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2176,
   "name": "8586_2_2_1",
   "description": "Battery Module Under Cell Voltage (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2177,
   "name": "8588_2_2_1",
   "description": "Battery Module Charge Over Current (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2178,
   "name": "8589_2_2_1",
   "description": "Battery Module Discharge Over Current (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2179,
   "name": "8591_2_2_1",
   "description": "Battery Module Under Temperature (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2180,
   "name": "8592_2_2_1",
   "description": "Battery Module Fault (Battery Cabinet 2 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3177,
   "name": "8587_2_32",
   "description": "Battery Module Disconnected (Battery Cabinet 2 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3178,
   "name": "8590_2_32",
   "description": "Battery Module Over Temperature (Battery Cabinet 2 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3189,
   "name": "8579_2_32_1",
   "description": "Battery Module High Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3190,
   "name": "8580_2_32_1",
   "description": "Battery Module Low Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3191,
   "name": "8581_2_32_1",
   "description": "Battery Module High Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3192,
   "name": "8582_2_32_1",
   "description": "Battery Module Low Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3193,
   "name": "8583_2_32_1",
   "description": "Battery Module Over Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3194,
   "name": "8584_2_32_1",
   "description": "Battery Module Under Overall Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3195,
   "name": "8585_2_32_1",
   "description": "Battery Module Over Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3196,
   "name": "8586_2_32_1",
   "description": "Battery Module Under Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3197,
   "name": "8588_2_32_1",
   "description": "Battery Module Charge Over Current (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3198,
   "name": "8589_2_32_1",
   "description": "Battery Module Discharge Over Current (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3199,
   "name": "8591_2_32_1",
   "description": "Battery Module Under Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3200,
   "name": "8592_2_32_1",
   "description": "Battery Module Fault (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9877,
   "name": "8537_9",
   "description": "Battery Cabinet High Overall Voltage (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9878,
   "name": "8538_9",
   "description": "Battery Cabinet Low Overall Voltage (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9879,
   "name": "8539_9",
   "description": "Battery Cabinet High Cell Voltage (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9880,
   "name": "8540_9",
   "description": "Battery Cabinet Low Cell Voltage (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9881,
   "name": "8541_9",
   "description": "Battery Cabinet Over Overall Voltage (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9882,
   "name": "8542_9",
   "description": "Battery Cabinet Under Overall Voltage (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9883,
   "name": "8543_9",
   "description": "Battery Cabinet Over Cell Voltage (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9884,
   "name": "8544_9",
   "description": "Battery Cabinet Under Cell Voltage (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9885,
   "name": "8545_9",
   "description": "Battery Cabinet Charge Over Current (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9886,
   "name": "8546_9",
   "description": "Battery Cabinet Discharge Over Current (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9887,
   "name": "8547_9",
   "description": "Battery Cabinet Over Temperature (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9888,
   "name": "8548_9",
   "description": "Battery Cabinet Under Temperature (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9889,
   "name": "4174_9",
   "description": "Battery Temperature Sensor Fault (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9900,
   "name": "8587_9_1",
   "description": "Battery Module Disconnected (Battery Cabinet 9 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9901,
   "name": "8590_9_1",
   "description": "Battery Module Over Temperature (Battery Cabinet 9 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9912,
   "name": "8579_9_1_1",
   "description": "Battery Module High Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9913,
   "name": "8580_9_1_1",
   "description": "Battery Module Low Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9914,
   "name": "8581_9_1_1",
   "description": "Battery Module High Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9915,
   "name": "8582_9_1_1",
   "description": "Battery Module Low Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9916,
   "name": "8583_9_1_1",
   "description": "Battery Module Over Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9917,
   "name": "8584_9_1_1",
   "description": "Battery Module Under Overall Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9918,
   "name": "8585_9_1_1",
   "description": "Battery Module Over Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9919,
   "name": "8586_9_1_1",
   "description": "Battery Module Under Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9920,
   "name": "8588_9_1_1",
   "description": "Battery Module Charge Over Current (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9921,
   "name": "8589_9_1_1",
   "description": "Battery Module Discharge Over Current (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9922,
   "name": "8591_9_1_1",
   "description": "Battery Module Under Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9923,
   "name": "8592_9_1_1",
   "description": "Battery Module Fault (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9934,
   "name": "8587_9_2",
   "description": "Battery Module Disconnected (Battery Cabinet 9 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9935,
   "name": "8590_9_2",
   "description": "Battery Module Over Temperature (Battery Cabinet 9 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9946,
   "name": "8579_9_2_1",
   "description": "Battery Module High Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9947,
   "name": "8580_9_2_1",
   "description": "Battery Module Low Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9948,
   "name": "8581_9_2_1",
   "description": "Battery Module High Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9949,
   "name": "8582_9_2_1",
   "description": "Battery Module Low Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9950,
   "name": "8583_9_2_1",
   "description": "Battery Module Over Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9951,
   "name": "8584_9_2_1",
   "description": "Battery Module Under Overall Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9952,
   "name": "8585_9_2_1",
   "description": "Battery Module Over Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9953,
   "name": "8586_9_2_1",
   "description": "Battery Module Under Cell Voltage (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9954,
   "name": "8588_9_2_1",
   "description": "Battery Module Charge Over Current (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9955,
   "name": "8589_9_2_1",
   "description": "Battery Module Discharge Over Current (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9956,
   "name": "8591_9_2_1",
   "description": "Battery Module Under Temperature (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9957,
   "name": "8592_9_2_1",
   "description": "Battery Module Fault (Battery Cabinet 9 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10954,
   "name": "8587_9_32",
   "description": "Battery Module Disconnected (Battery Cabinet 9 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10955,
   "name": "8590_9_32",
   "description": "Battery Module Over Temperature (Battery Cabinet 9 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10966,
   "name": "8579_9_32_1",
   "description": "Battery Module High Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10967,
   "name": "8580_9_32_1",
   "description": "Battery Module Low Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10968,
   "name": "8581_9_32_1",
   "description": "Battery Module High Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10969,
   "name": "8582_9_32_1",
   "description": "Battery Module Low Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10970,
   "name": "8583_9_32_1",
   "description": "Battery Module Over Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10971,
   "name": "8584_9_32_1",
   "description": "Battery Module Under Overall Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10972,
   "name": "8585_9_32_1",
   "description": "Battery Module Over Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10973,
   "name": "8586_9_32_1",
   "description": "Battery Module Under Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10974,
   "name": "8588_9_32_1",
   "description": "Battery Module Charge Over Current (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10975,
   "name": "8589_9_32_1",
   "description": "Battery Module Discharge Over Current (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10976,
   "name": "8591_9_32_1",
   "description": "Battery Module Under Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10977,
   "name": "8592_9_32_1",
   "description": "Battery Module Fault (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10988,
   "name": "8605_1",
   "description": "Battery String High Overall Voltage (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10989,
   "name": "8606_1",
   "description": "Battery String Low Overall Voltage (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10990,
   "name": "8558_1",
   "description": "Battery String High Cell Voltage (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10991,
   "name": "8559_1",
   "description": "Battery String Low Cell Voltage (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10992,
   "name": "8560_1",
   "description": "Battery String Over Overall Voltage (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10993,
   "name": "8561_1",
   "description": "Battery String Under Overall Voltage (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10994,
   "name": "8562_1",
   "description": "Battery String Over Cell Voltage (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10995,
   "name": "8563_1",
   "description": "Battery String Under Cell Voltage (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10996,
   "name": "8564_1",
   "description": "Battery String Charge Over Current (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10997,
   "name": "8565_1",
   "description": "Battery String Discharge Over Current (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10998,
   "name": "8566_1",
   "description": "Battery String Over Temperature (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10999,
   "name": "8567_1",
   "description": "Battery String Under Temperature (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11010,
   "name": "8605_2",
   "description": "Battery String High Overall Voltage (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11011,
   "name": "8606_2",
   "description": "Battery String Low Overall Voltage (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11012,
   "name": "8558_2",
   "description": "Battery String High Cell Voltage (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11013,
   "name": "8559_2",
   "description": "Battery String Low Cell Voltage (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11014,
   "name": "8560_2",
   "description": "Battery String Over Overall Voltage (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11015,
   "name": "8561_2",
   "description": "Battery String Under Overall Voltage (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11016,
   "name": "8562_2",
   "description": "Battery String Over Cell Voltage (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11017,
   "name": "8563_2",
   "description": "Battery String Under Cell Voltage (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11018,
   "name": "8564_2",
   "description": "Battery String Charge Over Current (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11019,
   "name": "8565_2",
   "description": "Battery String Discharge Over Current (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11020,
   "name": "8566_2",
   "description": "Battery String Over Temperature (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11021,
   "name": "8567_2",
   "description": "Battery String Under Temperature (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11142,
   "name": "8605_8",
   "description": "Battery String High Overall Voltage (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11143,
   "name": "8606_8",
   "description": "Battery String Low Overall Voltage (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11144,
   "name": "8558_8",
   "description": "Battery String High Cell Voltage (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11145,
   "name": "8559_8",
   "description": "Battery String Low Cell Voltage (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11146,
   "name": "8560_8",
   "description": "Battery String Over Overall Voltage (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11147,
   "name": "8561_8",
   "description": "Battery String Under Overall Voltage (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11148,
   "name": "8562_8",
   "description": "Battery String Over Cell Voltage (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11149,
   "name": "8563_8",
   "description": "Battery String Under Cell Voltage (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11150,
   "name": "8564_8",
   "description": "Battery String Charge Over Current (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11151,
   "name": "8565_8",
   "description": "Battery String Discharge Over Current (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11152,
   "name": "8566_8",
   "description": "Battery String Over Temperature (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11153,
   "name": "8567_8",
   "description": "Battery String Under Temperature (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "4097_1",
   "description": "System Input RMS A-B",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "4099_1",
   "description": "System Input RMS B-C",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "4101_1",
   "description": "System Input RMS C-A",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "4096_1",
   "description": "System Input RMS A-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "4098_1",
   "description": "System Input RMS B-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "4100_1",
   "description": "System Input RMS C-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "4113_1",
   "description": "System Input RMS Current Phase A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "4114_1",
   "description": "System Input RMS Current Phase B",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "4115_1",
   "description": "System Input RMS Current Phase C",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "4105_1",
   "description": "System Input Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "4116_1",
   "description": "System Input Power Factor Phs A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "4117_1",
   "description": "System Input Power Factor Phs B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "4118_1",
   "description": "System Input Power Factor Phs C",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "6318_1",
   "description": "System Input Power Phase A",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "6319_1",
   "description": "System Input Power Phase B",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "6320_1",
   "description": "System Input Power Phase C",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "8093_1",
   "description": "System Input Apparent Power Phs A",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "8094_1",
   "description": "System Input Apparent Power Phs B",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "8095_1",
   "description": "System Input Apparent Power Phs C",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "4119_1",
   "description": "System Input Brown Out Count",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "4120_1",
   "description": "System Input Black Out Count",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "4125_1",
   "description": "Bypass Input Voltage RMS A-B",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "4126_1",
   "description": "Bypass Input Voltage RMS B-C",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "4127_1",
   "description": "Bypass Input Voltage RMS C-A",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "4128_1",
   "description": "Bypass Input Voltage RMS A-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "4129_1",
   "description": "Bypass Input Voltage RMS B-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "4130_1",
   "description": "Bypass Input Voltage RMS C-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "4131_1",
   "description": "Bypass Input Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "6325_1",
   "description": "Bypass Power Phase A",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "6326_1",
   "description": "Bypass Power Phase B",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "6327_1",
   "description": "Bypass Power Phase C",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "6328_1",
   "description": "Bypass Apparent Power Phase A",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "6329_1",
   "description": "Bypass Apparent Power Phase B",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "6330_1",
   "description": "Bypass Apparent Power Phase C",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "4201_1",
   "description": "System Output Voltage RMS A-B",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "4202_1",
   "description": "System Output Voltage RMS B-C",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "4203_1",
   "description": "System Output Voltage RMS C-A",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "4385_1",
   "description": "System Output Voltage RMS A-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "4386_1",
   "description": "System Output Voltage RMS B-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "4387_1",
   "description": "System Output Voltage RMS C-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "4204_1",
   "description": "System Output RMS Current Phs A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "4205_1",
   "description": "System Output RMS Current Phs B",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "4206_1",
   "description": "System Output RMS Current Phs C",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "5159_1",
   "description": "Output Current Crest Factor Phs A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "5160_1",
   "description": "Output Current Crest Factor Phs B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "5161_1",
   "description": "Output Current Crest Factor Phs C",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "4207_1",
   "description": "System Output Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "4210_1",
   "description": "System Output Power Factor Phs A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "4211_1",
   "description": "System Output Power Factor Phs B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "4212_1",
   "description": "System Output Power Factor Phs C",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "5859_1",
   "description": "System Output Power Phase A",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "5860_1",
   "description": "System Output Power Phase B",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "5959_1",
   "description": "System Output Power Phase C",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "5868_1",
   "description": "System Output Apparent Power Phs A",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "5869_1",
   "description": "System Output Apparent Power Phs B",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "5870_1",
   "description": "System Output Apparent Power Phs C",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "4208_1",
   "description": "System Output Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "4209_1",
   "description": "System Output Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "4226_1",
   "description": "System Output Pct Pwr (VA) Phs A",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "4227_1",
   "description": "System Output Pct Pwr (VA) Phs B",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "4228_1",
   "description": "System Output Pct Pwr (VA) Phs C",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "4223_1",
   "description": "System Output Pct Power Phase A",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "4224_1",
   "description": "System Output Pct Power Phase B",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "4225_1",
   "description": "System Output Pct Power Phase C",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "8281_1_1",
   "description": "Positive DC Bus Voltage (Power Module 1 DC Bus 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "8282_1_1",
   "description": "Negative DC Bus Voltage (Power Module 1 DC Bus 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "8281_2_1",
   "description": "Positive DC Bus Voltage (Power Module 2 DC Bus 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "8282_2_1",
   "description": "Negative DC Bus Voltage (Power Module 2 DC Bus 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 203,
   "name": "8281_10_1",
   "description": "Positive DC Bus Voltage (Power Module 10 DC Bus 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 204,
   "name": "8282_10_1",
   "description": "Negative DC Bus Voltage (Power Module 10 DC Bus 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 215,
   "name": "4811_1",
   "description": "MMS Output Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 216,
   "name": "4812_1",
   "description": "MMS Output Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 227,
   "name": "5824_1",
   "description": "Number Of Active Power Modules",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 228,
   "name": "5823_1",
   "description": "Number of Installed Power Modules",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 229,
   "name": "8513_1",
   "description": "Redundant Count of Power Module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 230,
   "name": "4291_1",
   "description": "Inlet Air Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 500230,
   "name": "4291_1_deg_F",
   "description": "Inlet Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 231,
   "name": "6069_1",
   "description": "Average system efficiency",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 232,
   "name": "8097_1",
   "description": "ECO Suspended Time Remaining",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 233,
   "name": "4292_1",
   "description": "Total System Operating Time",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 244,
   "name": "4293_1",
   "description": "System Date and Time",
   "units": "Secs since Epoch(UTC)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 245,
   "name": "5821_1",
   "description": "System Capacity",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 246,
   "name": "4102_1",
   "description": "System Input Nominal Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 247,
   "name": "4104_1",
   "description": "System Input Nominal Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 248,
   "name": "4259_1",
   "description": "Bypass Nominal Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 249,
   "name": "4260_1",
   "description": "System Output Nominal Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 250,
   "name": "4261_1",
   "description": "System Output Nominal Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 261,
   "name": "8514_1",
   "description": "External Battery Cabinet Count",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 262,
   "name": "8515_1",
   "description": "Battery String Count",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 263,
   "name": "4148_1",
   "description": "DC Bus Voltage",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 264,
   "name": "4149_1",
   "description": "DC Bus Current",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 265,
   "name": "8516_1",
   "description": "Battery Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 500265,
   "name": "8516_1_deg_F",
   "description": "Battery Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 266,
   "name": "4153_1",
   "description": "Battery Percentage Charge",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 267,
   "name": "4150_1",
   "description": "Battery Time Remaining",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 268,
   "name": "5845_1",
   "description": "Number of Discharge Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 269,
   "name": "5846_1",
   "description": "Accumulated Discharge Time",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 270,
   "name": "5991_1",
   "description": "Battery Self Test Cycle Time",
   "units": "day",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 271,
   "name": "5804_1",
   "description": "Time Until Next Auto Battery Test",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 272,
   "name": "5802_1",
   "description": "Low Battery Warning Time",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 283,
   "name": "4155_1",
   "description": "Battery Volts for Cabinet (Battery Cabinet 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 284,
   "name": "8527_1",
   "description": "Battery Current for Cabinet (Battery Cabinet 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 285,
   "name": "4156_1",
   "description": "Battery Temperature for Cabinet (Battery Cabinet 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 500285,
   "name": "4156_1_deg_F",
   "description": "Battery Temperature for Cabinet (Battery Cabinet 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 286,
   "name": "8528_1",
   "description": "Battery Cabinet Capacity (Battery Cabinet 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 287,
   "name": "8529_1",
   "description": "Battery Cabinet Max Cell Voltage (Battery Cabinet 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 288,
   "name": "8530_1",
   "description": "Battery Cabinet Min Cell Voltage (Battery Cabinet 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 289,
   "name": "8531_1",
   "description": "Battery Cabinet Highest Cell Temperature (Battery Cabinet 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 500289,
   "name": "8531_1_deg_F",
   "description": "Battery Cabinet Highest Cell Temperature (Battery Cabinet 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 290,
   "name": "8532_1",
   "description": "Battery Cabinet Lowest Cell Temperature (Battery Cabinet 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 500290,
   "name": "8532_1_deg_F",
   "description": "Battery Cabinet Lowest Cell Temperature (Battery Cabinet 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 301,
   "name": "4962_1_1",
   "description": "Cell Voltage (Battery Cabinet 1 Battery Cell In Cabinet 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 302,
   "name": "4963_1_1",
   "description": "Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 500302,
   "name": "4963_1_1_deg_F",
   "description": "Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 303,
   "name": "5443_1_1",
   "description": "Internal Resistance Value (Battery Cabinet 1 Battery Cell In Cabinet 1)",
   "units": "milliOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 314,
   "name": "4962_1_2",
   "description": "Cell Voltage (Battery Cabinet 1 Battery Cell In Cabinet 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 315,
   "name": "4963_1_2",
   "description": "Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 500315,
   "name": "4963_1_2_deg_F",
   "description": "Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 316,
   "name": "5443_1_2",
   "description": "Internal Resistance Value (Battery Cabinet 1 Battery Cell In Cabinet 2)",
   "units": "milliOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2888,
   "name": "4962_1_200",
   "description": "Cell Voltage (Battery Cabinet 1 Battery Cell In Cabinet 200)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2889,
   "name": "4963_1_200",
   "description": "Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 200)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 502889,
   "name": "4963_1_200_deg_F",
   "description": "Cell Temperature (Battery Cabinet 1 Battery Cell In Cabinet 200)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2890,
   "name": "5443_1_200",
   "description": "Internal Resistance Value (Battery Cabinet 1 Battery Cell In Cabinet 200)",
   "units": "milliOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2901,
   "name": "5844_1_1",
   "description": "Battery Module Temperature (Battery Cabinet 1 Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 502901,
   "name": "5844_1_1_deg_F",
   "description": "Battery Module Temperature (Battery Cabinet 1 Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2912,
   "name": "8571_1_1_1",
   "description": "Battery Module Voltage (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2913,
   "name": "8572_1_1_1",
   "description": "Battery Module Current (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2914,
   "name": "8573_1_1_1",
   "description": "Battery Module State Of Charge (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2915,
   "name": "8574_1_1_1",
   "description": "Battery Module Max Cell Voltage (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2916,
   "name": "8575_1_1_1",
   "description": "Battery Module Min Cell Voltage (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2917,
   "name": "8576_1_1_1",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 502917,
   "name": "8576_1_1_1_deg_F",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2918,
   "name": "8577_1_1_1",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 502918,
   "name": "8577_1_1_1_deg_F",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2930,
   "name": "8593_1_1_1",
   "description": "Battery Cell Voltage (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2931,
   "name": "8570_1_1_1",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 502931,
   "name": "8570_1_1_1_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2942,
   "name": "8593_1_1_2",
   "description": "Battery Cell Voltage (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2943,
   "name": "8570_1_1_2",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 502943,
   "name": "8570_1_1_2_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4118,
   "name": "8593_1_1_100",
   "description": "Battery Cell Voltage (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4119,
   "name": "8570_1_1_100",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 504119,
   "name": "8570_1_1_100_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 1 Battery Cell In Module 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4129,
   "name": "5844_1_2",
   "description": "Battery Module Temperature (Battery Cabinet 1 Battery Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 504129,
   "name": "5844_1_2_deg_F",
   "description": "Battery Module Temperature (Battery Cabinet 1 Battery Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4140,
   "name": "8571_1_2_1",
   "description": "Battery Module Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4141,
   "name": "8572_1_2_1",
   "description": "Battery Module Current (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4142,
   "name": "8573_1_2_1",
   "description": "Battery Module State Of Charge (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4143,
   "name": "8574_1_2_1",
   "description": "Battery Module Max Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4144,
   "name": "8575_1_2_1",
   "description": "Battery Module Min Cell Voltage (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4145,
   "name": "8576_1_2_1",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 504145,
   "name": "8576_1_2_1_deg_F",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4146,
   "name": "8577_1_2_1",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 504146,
   "name": "8577_1_2_1_deg_F",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4158,
   "name": "8593_1_2_1",
   "description": "Battery Cell Voltage (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4159,
   "name": "8570_1_2_1",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 504159,
   "name": "8570_1_2_1_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4170,
   "name": "8593_1_2_2",
   "description": "Battery Cell Voltage (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4171,
   "name": "8570_1_2_2",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 504171,
   "name": "8570_1_2_2_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5346,
   "name": "8593_1_2_100",
   "description": "Battery Cell Voltage (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5347,
   "name": "8570_1_2_100",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 505347,
   "name": "8570_1_2_100_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 2 Battery Cell In Module 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40969,
   "name": "5844_1_32",
   "description": "Battery Module Temperature (Battery Cabinet 1 Battery Module 32)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 540969,
   "name": "5844_1_32_deg_F",
   "description": "Battery Module Temperature (Battery Cabinet 1 Battery Module 32)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40980,
   "name": "8571_1_32_1",
   "description": "Battery Module Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40981,
   "name": "8572_1_32_1",
   "description": "Battery Module Current (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40982,
   "name": "8573_1_32_1",
   "description": "Battery Module State Of Charge (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40983,
   "name": "8574_1_32_1",
   "description": "Battery Module Max Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40984,
   "name": "8575_1_32_1",
   "description": "Battery Module Min Cell Voltage (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40985,
   "name": "8576_1_32_1",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 540985,
   "name": "8576_1_32_1_deg_F",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40986,
   "name": "8577_1_32_1",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 540986,
   "name": "8577_1_32_1_deg_F",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 1 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40998,
   "name": "8593_1_32_1",
   "description": "Battery Cell Voltage (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40999,
   "name": "8570_1_32_1",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 540999,
   "name": "8570_1_32_1_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41010,
   "name": "8593_1_32_2",
   "description": "Battery Cell Voltage (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41011,
   "name": "8570_1_32_2",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 541011,
   "name": "8570_1_32_2_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42186,
   "name": "8593_1_32_100",
   "description": "Battery Cell Voltage (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42187,
   "name": "8570_1_32_100",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 542187,
   "name": "8570_1_32_100_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 1 Battery Module 32 Battery Cell In Module 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42197,
   "name": "4155_2",
   "description": "Battery Volts for Cabinet (Battery Cabinet 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42198,
   "name": "8527_2",
   "description": "Battery Current for Cabinet (Battery Cabinet 2)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42199,
   "name": "4156_2",
   "description": "Battery Temperature for Cabinet (Battery Cabinet 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 542199,
   "name": "4156_2_deg_F",
   "description": "Battery Temperature for Cabinet (Battery Cabinet 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42200,
   "name": "8528_2",
   "description": "Battery Cabinet Capacity (Battery Cabinet 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42201,
   "name": "8529_2",
   "description": "Battery Cabinet Max Cell Voltage (Battery Cabinet 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42202,
   "name": "8530_2",
   "description": "Battery Cabinet Min Cell Voltage (Battery Cabinet 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42203,
   "name": "8531_2",
   "description": "Battery Cabinet Highest Cell Temperature (Battery Cabinet 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 542203,
   "name": "8531_2_deg_F",
   "description": "Battery Cabinet Highest Cell Temperature (Battery Cabinet 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42204,
   "name": "8532_2",
   "description": "Battery Cabinet Lowest Cell Temperature (Battery Cabinet 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 542204,
   "name": "8532_2_deg_F",
   "description": "Battery Cabinet Lowest Cell Temperature (Battery Cabinet 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42215,
   "name": "4962_2_1",
   "description": "Cell Voltage (Battery Cabinet 2 Battery Cell In Cabinet 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42216,
   "name": "4963_2_1",
   "description": "Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 542216,
   "name": "4963_2_1_deg_F",
   "description": "Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42217,
   "name": "5443_2_1",
   "description": "Internal Resistance Value (Battery Cabinet 2 Battery Cell In Cabinet 1)",
   "units": "milliOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42228,
   "name": "4962_2_2",
   "description": "Cell Voltage (Battery Cabinet 2 Battery Cell In Cabinet 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42229,
   "name": "4963_2_2",
   "description": "Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 542229,
   "name": "4963_2_2_deg_F",
   "description": "Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42230,
   "name": "5443_2_2",
   "description": "Internal Resistance Value (Battery Cabinet 2 Battery Cell In Cabinet 2)",
   "units": "milliOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44802,
   "name": "4962_2_200",
   "description": "Cell Voltage (Battery Cabinet 2 Battery Cell In Cabinet 200)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44803,
   "name": "4963_2_200",
   "description": "Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 200)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 544803,
   "name": "4963_2_200_deg_F",
   "description": "Cell Temperature (Battery Cabinet 2 Battery Cell In Cabinet 200)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44804,
   "name": "5443_2_200",
   "description": "Internal Resistance Value (Battery Cabinet 2 Battery Cell In Cabinet 200)",
   "units": "milliOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44815,
   "name": "5844_2_1",
   "description": "Battery Module Temperature (Battery Cabinet 2 Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 544815,
   "name": "5844_2_1_deg_F",
   "description": "Battery Module Temperature (Battery Cabinet 2 Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44826,
   "name": "8571_2_1_1",
   "description": "Battery Module Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44827,
   "name": "8572_2_1_1",
   "description": "Battery Module Current (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44828,
   "name": "8573_2_1_1",
   "description": "Battery Module State Of Charge (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44829,
   "name": "8574_2_1_1",
   "description": "Battery Module Max Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44830,
   "name": "8575_2_1_1",
   "description": "Battery Module Min Cell Voltage (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44831,
   "name": "8576_2_1_1",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 544831,
   "name": "8576_2_1_1_deg_F",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44832,
   "name": "8577_2_1_1",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 544832,
   "name": "8577_2_1_1_deg_F",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 1 LithiumIon Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44844,
   "name": "8593_2_1_1",
   "description": "Battery Cell Voltage (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44845,
   "name": "8570_2_1_1",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 544845,
   "name": "8570_2_1_1_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44856,
   "name": "8593_2_1_2",
   "description": "Battery Cell Voltage (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44857,
   "name": "8570_2_1_2",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 544857,
   "name": "8570_2_1_2_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46032,
   "name": "8593_2_1_100",
   "description": "Battery Cell Voltage (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46033,
   "name": "8570_2_1_100",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 546033,
   "name": "8570_2_1_100_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 1 Battery Cell In Module 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46043,
   "name": "5844_2_2",
   "description": "Battery Module Temperature (Battery Cabinet 2 Battery Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 546043,
   "name": "5844_2_2_deg_F",
   "description": "Battery Module Temperature (Battery Cabinet 2 Battery Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46054,
   "name": "8571_2_2_1",
   "description": "Battery Module Voltage (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46055,
   "name": "8572_2_2_1",
   "description": "Battery Module Current (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46056,
   "name": "8573_2_2_1",
   "description": "Battery Module State Of Charge (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46057,
   "name": "8574_2_2_1",
   "description": "Battery Module Max Cell Voltage (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46058,
   "name": "8575_2_2_1",
   "description": "Battery Module Min Cell Voltage (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46059,
   "name": "8576_2_2_1",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 546059,
   "name": "8576_2_2_1_deg_F",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46060,
   "name": "8577_2_2_1",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 546060,
   "name": "8577_2_2_1_deg_F",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 2 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46072,
   "name": "8593_2_2_1",
   "description": "Battery Cell Voltage (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46073,
   "name": "8570_2_2_1",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 546073,
   "name": "8570_2_2_1_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46084,
   "name": "8593_2_2_2",
   "description": "Battery Cell Voltage (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46085,
   "name": "8570_2_2_2",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 546085,
   "name": "8570_2_2_2_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47260,
   "name": "8593_2_2_100",
   "description": "Battery Cell Voltage (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47261,
   "name": "8570_2_2_100",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 547261,
   "name": "8570_2_2_100_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 2 Battery Cell In Module 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82883,
   "name": "5844_2_32",
   "description": "Battery Module Temperature (Battery Cabinet 2 Battery Module 32)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 582883,
   "name": "5844_2_32_deg_F",
   "description": "Battery Module Temperature (Battery Cabinet 2 Battery Module 32)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82894,
   "name": "8571_2_32_1",
   "description": "Battery Module Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82895,
   "name": "8572_2_32_1",
   "description": "Battery Module Current (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82896,
   "name": "8573_2_32_1",
   "description": "Battery Module State Of Charge (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82897,
   "name": "8574_2_32_1",
   "description": "Battery Module Max Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82898,
   "name": "8575_2_32_1",
   "description": "Battery Module Min Cell Voltage (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82899,
   "name": "8576_2_32_1",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 582899,
   "name": "8576_2_32_1_deg_F",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82900,
   "name": "8577_2_32_1",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 582900,
   "name": "8577_2_32_1_deg_F",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 2 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82912,
   "name": "8593_2_32_1",
   "description": "Battery Cell Voltage (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82913,
   "name": "8570_2_32_1",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 582913,
   "name": "8570_2_32_1_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82924,
   "name": "8593_2_32_2",
   "description": "Battery Cell Voltage (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82925,
   "name": "8570_2_32_2",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 582925,
   "name": "8570_2_32_2_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84100,
   "name": "8593_2_32_100",
   "description": "Battery Cell Voltage (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84101,
   "name": "8570_2_32_100",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 584101,
   "name": "8570_2_32_100_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 2 Battery Module 32 Battery Cell In Module 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335595,
   "name": "4155_9",
   "description": "Battery Volts for Cabinet (Battery Cabinet 9)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335596,
   "name": "8527_9",
   "description": "Battery Current for Cabinet (Battery Cabinet 9)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335597,
   "name": "4156_9",
   "description": "Battery Temperature for Cabinet (Battery Cabinet 9)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 835597,
   "name": "4156_9_deg_F",
   "description": "Battery Temperature for Cabinet (Battery Cabinet 9)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335598,
   "name": "8528_9",
   "description": "Battery Cabinet Capacity (Battery Cabinet 9)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335599,
   "name": "8529_9",
   "description": "Battery Cabinet Max Cell Voltage (Battery Cabinet 9)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335600,
   "name": "8530_9",
   "description": "Battery Cabinet Min Cell Voltage (Battery Cabinet 9)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335601,
   "name": "8531_9",
   "description": "Battery Cabinet Highest Cell Temperature (Battery Cabinet 9)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 835601,
   "name": "8531_9_deg_F",
   "description": "Battery Cabinet Highest Cell Temperature (Battery Cabinet 9)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335602,
   "name": "8532_9",
   "description": "Battery Cabinet Lowest Cell Temperature (Battery Cabinet 9)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 835602,
   "name": "8532_9_deg_F",
   "description": "Battery Cabinet Lowest Cell Temperature (Battery Cabinet 9)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335613,
   "name": "4962_9_1",
   "description": "Cell Voltage (Battery Cabinet 9 Battery Cell In Cabinet 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335614,
   "name": "4963_9_1",
   "description": "Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 835614,
   "name": "4963_9_1_deg_F",
   "description": "Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335615,
   "name": "5443_9_1",
   "description": "Internal Resistance Value (Battery Cabinet 9 Battery Cell In Cabinet 1)",
   "units": "milliOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335626,
   "name": "4962_9_2",
   "description": "Cell Voltage (Battery Cabinet 9 Battery Cell In Cabinet 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335627,
   "name": "4963_9_2",
   "description": "Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 835627,
   "name": "4963_9_2_deg_F",
   "description": "Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 335628,
   "name": "5443_9_2",
   "description": "Internal Resistance Value (Battery Cabinet 9 Battery Cell In Cabinet 2)",
   "units": "milliOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338200,
   "name": "4962_9_200",
   "description": "Cell Voltage (Battery Cabinet 9 Battery Cell In Cabinet 200)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338201,
   "name": "4963_9_200",
   "description": "Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 200)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 838201,
   "name": "4963_9_200_deg_F",
   "description": "Cell Temperature (Battery Cabinet 9 Battery Cell In Cabinet 200)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338202,
   "name": "5443_9_200",
   "description": "Internal Resistance Value (Battery Cabinet 9 Battery Cell In Cabinet 200)",
   "units": "milliOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338213,
   "name": "5844_9_1",
   "description": "Battery Module Temperature (Battery Cabinet 9 Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 838213,
   "name": "5844_9_1_deg_F",
   "description": "Battery Module Temperature (Battery Cabinet 9 Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338224,
   "name": "8571_9_1_1",
   "description": "Battery Module Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338225,
   "name": "8572_9_1_1",
   "description": "Battery Module Current (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338226,
   "name": "8573_9_1_1",
   "description": "Battery Module State Of Charge (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338227,
   "name": "8574_9_1_1",
   "description": "Battery Module Max Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338228,
   "name": "8575_9_1_1",
   "description": "Battery Module Min Cell Voltage (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338229,
   "name": "8576_9_1_1",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 838229,
   "name": "8576_9_1_1_deg_F",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338230,
   "name": "8577_9_1_1",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 838230,
   "name": "8577_9_1_1_deg_F",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 1 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338242,
   "name": "8593_9_1_1",
   "description": "Battery Cell Voltage (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338243,
   "name": "8570_9_1_1",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 838243,
   "name": "8570_9_1_1_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338254,
   "name": "8593_9_1_2",
   "description": "Battery Cell Voltage (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338255,
   "name": "8570_9_1_2",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 838255,
   "name": "8570_9_1_2_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339430,
   "name": "8593_9_1_100",
   "description": "Battery Cell Voltage (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339431,
   "name": "8570_9_1_100",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 839431,
   "name": "8570_9_1_100_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 1 Battery Cell In Module 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339441,
   "name": "5844_9_2",
   "description": "Battery Module Temperature (Battery Cabinet 9 Battery Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 839441,
   "name": "5844_9_2_deg_F",
   "description": "Battery Module Temperature (Battery Cabinet 9 Battery Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339452,
   "name": "8571_9_2_1",
   "description": "Battery Module Voltage (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339453,
   "name": "8572_9_2_1",
   "description": "Battery Module Current (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339454,
   "name": "8573_9_2_1",
   "description": "Battery Module State Of Charge (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339455,
   "name": "8574_9_2_1",
   "description": "Battery Module Max Cell Voltage (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339456,
   "name": "8575_9_2_1",
   "description": "Battery Module Min Cell Voltage (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339457,
   "name": "8576_9_2_1",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 839457,
   "name": "8576_9_2_1_deg_F",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339458,
   "name": "8577_9_2_1",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 839458,
   "name": "8577_9_2_1_deg_F",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 2 LithiumIon Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339470,
   "name": "8593_9_2_1",
   "description": "Battery Cell Voltage (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339471,
   "name": "8570_9_2_1",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 839471,
   "name": "8570_9_2_1_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339482,
   "name": "8593_9_2_2",
   "description": "Battery Cell Voltage (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339483,
   "name": "8570_9_2_2",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 839483,
   "name": "8570_9_2_2_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 340658,
   "name": "8593_9_2_100",
   "description": "Battery Cell Voltage (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 340659,
   "name": "8570_9_2_100",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 840659,
   "name": "8570_9_2_100_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 2 Battery Cell In Module 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376281,
   "name": "5844_9_32",
   "description": "Battery Module Temperature (Battery Cabinet 9 Battery Module 32)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 876281,
   "name": "5844_9_32_deg_F",
   "description": "Battery Module Temperature (Battery Cabinet 9 Battery Module 32)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376292,
   "name": "8571_9_32_1",
   "description": "Battery Module Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376293,
   "name": "8572_9_32_1",
   "description": "Battery Module Current (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376294,
   "name": "8573_9_32_1",
   "description": "Battery Module State Of Charge (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376295,
   "name": "8574_9_32_1",
   "description": "Battery Module Max Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376296,
   "name": "8575_9_32_1",
   "description": "Battery Module Min Cell Voltage (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376297,
   "name": "8576_9_32_1",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 876297,
   "name": "8576_9_32_1_deg_F",
   "description": "Battery Module Highest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376298,
   "name": "8577_9_32_1",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 876298,
   "name": "8577_9_32_1_deg_F",
   "description": "Battery Module Lowest Cell Temperature (Battery Cabinet 9 Battery Module 32 Lithium-Ion Battery Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376310,
   "name": "8593_9_32_1",
   "description": "Battery Cell Voltage (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376311,
   "name": "8570_9_32_1",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 876311,
   "name": "8570_9_32_1_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376322,
   "name": "8593_9_32_2",
   "description": "Battery Cell Voltage (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376323,
   "name": "8570_9_32_2",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 876323,
   "name": "8570_9_32_2_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377498,
   "name": "8593_9_32_100",
   "description": "Battery Cell Voltage (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377499,
   "name": "8570_9_32_100",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 877499,
   "name": "8570_9_32_100_deg_F",
   "description": "Battery Cell Temperature (Battery Cabinet 9 Battery Module 32 Battery Cell In Module 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377509,
   "name": "4900_1",
   "description": "String Overall Voltage (Battery String 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377510,
   "name": "4901_1",
   "description": "String Current (Battery String 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377511,
   "name": "8549_1",
   "description": "Battery String Temperature (Battery String 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 877511,
   "name": "8549_1_deg_F",
   "description": "Battery String Temperature (Battery String 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377512,
   "name": "8550_1",
   "description": "Battery String State Of Charge (Battery String 1)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377513,
   "name": "8551_1",
   "description": "Battery String Max Cell Voltage (Battery String 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377514,
   "name": "8552_1",
   "description": "Battery String Min Cell Voltage (Battery String 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377515,
   "name": "8553_1",
   "description": "Battery String Highest Cell Temperature (Battery String 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 877515,
   "name": "8553_1_deg_F",
   "description": "Battery String Highest Cell Temperature (Battery String 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377516,
   "name": "8554_1",
   "description": "Battery String Lowest Cell Temperature (Battery String 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 877516,
   "name": "8554_1_deg_F",
   "description": "Battery String Lowest Cell Temperature (Battery String 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377527,
   "name": "8568_1_1",
   "description": "Battery Cell Voltage (Battery String 1 Battery Cell In String 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377528,
   "name": "8569_1_1",
   "description": "Battery Cell Temperature (Battery String 1 Battery Cell In String 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 877528,
   "name": "8569_1_1_deg_F",
   "description": "Battery Cell Temperature (Battery String 1 Battery Cell In String 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377539,
   "name": "8568_1_2",
   "description": "Battery Cell Voltage (Battery String 1 Battery Cell In String 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377540,
   "name": "8569_1_2",
   "description": "Battery Cell Temperature (Battery String 1 Battery Cell In String 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 877540,
   "name": "8569_1_2_deg_F",
   "description": "Battery Cell Temperature (Battery String 1 Battery Cell In String 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378715,
   "name": "8568_1_100",
   "description": "Battery Cell Voltage (Battery String 1 Battery Cell In String 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378716,
   "name": "8569_1_100",
   "description": "Battery Cell Temperature (Battery String 1 Battery Cell In String 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 878716,
   "name": "8569_1_100_deg_F",
   "description": "Battery Cell Temperature (Battery String 1 Battery Cell In String 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378727,
   "name": "4900_2",
   "description": "String Overall Voltage (Battery String 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378728,
   "name": "4901_2",
   "description": "String Current (Battery String 2)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378729,
   "name": "8549_2",
   "description": "Battery String Temperature (Battery String 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 878729,
   "name": "8549_2_deg_F",
   "description": "Battery String Temperature (Battery String 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378730,
   "name": "8550_2",
   "description": "Battery String State Of Charge (Battery String 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378731,
   "name": "8551_2",
   "description": "Battery String Max Cell Voltage (Battery String 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378732,
   "name": "8552_2",
   "description": "Battery String Min Cell Voltage (Battery String 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378733,
   "name": "8553_2",
   "description": "Battery String Highest Cell Temperature (Battery String 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 878733,
   "name": "8553_2_deg_F",
   "description": "Battery String Highest Cell Temperature (Battery String 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378734,
   "name": "8554_2",
   "description": "Battery String Lowest Cell Temperature (Battery String 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 878734,
   "name": "8554_2_deg_F",
   "description": "Battery String Lowest Cell Temperature (Battery String 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378745,
   "name": "8568_2_1",
   "description": "Battery Cell Voltage (Battery String 2 Battery Cell In String 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378746,
   "name": "8569_2_1",
   "description": "Battery Cell Temperature (Battery String 2 Battery Cell In String 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 878746,
   "name": "8569_2_1_deg_F",
   "description": "Battery Cell Temperature (Battery String 2 Battery Cell In String 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378757,
   "name": "8568_2_2",
   "description": "Battery Cell Voltage (Battery String 2 Battery Cell In String 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378758,
   "name": "8569_2_2",
   "description": "Battery Cell Temperature (Battery String 2 Battery Cell In String 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 878758,
   "name": "8569_2_2_deg_F",
   "description": "Battery Cell Temperature (Battery String 2 Battery Cell In String 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 379933,
   "name": "8568_2_100",
   "description": "Battery Cell Voltage (Battery String 2 Battery Cell In String 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 379934,
   "name": "8569_2_100",
   "description": "Battery Cell Temperature (Battery String 2 Battery Cell In String 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 879934,
   "name": "8569_2_100_deg_F",
   "description": "Battery Cell Temperature (Battery String 2 Battery Cell In String 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386035,
   "name": "4900_8",
   "description": "String Overall Voltage (Battery String 8)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386036,
   "name": "4901_8",
   "description": "String Current (Battery String 8)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386037,
   "name": "8549_8",
   "description": "Battery String Temperature (Battery String 8)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 886037,
   "name": "8549_8_deg_F",
   "description": "Battery String Temperature (Battery String 8)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386038,
   "name": "8550_8",
   "description": "Battery String State Of Charge (Battery String 8)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386039,
   "name": "8551_8",
   "description": "Battery String Max Cell Voltage (Battery String 8)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386040,
   "name": "8552_8",
   "description": "Battery String Min Cell Voltage (Battery String 8)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386041,
   "name": "8553_8",
   "description": "Battery String Highest Cell Temperature (Battery String 8)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 886041,
   "name": "8553_8_deg_F",
   "description": "Battery String Highest Cell Temperature (Battery String 8)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386042,
   "name": "8554_8",
   "description": "Battery String Lowest Cell Temperature (Battery String 8)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 886042,
   "name": "8554_8_deg_F",
   "description": "Battery String Lowest Cell Temperature (Battery String 8)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386053,
   "name": "8568_8_1",
   "description": "Battery Cell Voltage (Battery String 8 Battery Cell In String 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386054,
   "name": "8569_8_1",
   "description": "Battery Cell Temperature (Battery String 8 Battery Cell In String 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 886054,
   "name": "8569_8_1_deg_F",
   "description": "Battery Cell Temperature (Battery String 8 Battery Cell In String 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386065,
   "name": "8568_8_2",
   "description": "Battery Cell Voltage (Battery String 8 Battery Cell In String 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386066,
   "name": "8569_8_2",
   "description": "Battery Cell Temperature (Battery String 8 Battery Cell In String 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 886066,
   "name": "8569_8_2_deg_F",
   "description": "Battery Cell Temperature (Battery String 8 Battery Cell In String 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 387241,
   "name": "8568_8_100",
   "description": "Battery Cell Voltage (Battery String 8 Battery Cell In String 100)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 387242,
   "name": "8569_8_100",
   "description": "Battery Cell Temperature (Battery String 8 Battery Cell In String 100)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 887242,
   "name": "8569_8_100_deg_F",
   "description": "Battery Cell Temperature (Battery String 8 Battery Cell In String 100)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "4771_1",
   "description": "Rectifier Isolation Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "4770_1",
   "description": "Bypass Isolation Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "4772_1",
   "description": "Maintenance Bypass Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 24,
   "name": "4775_1",
   "description": "Module Output Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 25,
   "name": "4773_1",
   "description": "Maintenance Isolation Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 36,
   "name": "8493_1",
   "description": "System Control Card Operating Status (System Control Card 1)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 47,
   "name": "8493_2",
   "description": "System Control Card Operating Status (System Control Card 2)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 58,
   "name": "8500_1",
   "description": "Bypass Module Operating Status",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 59,
   "name": "4736_1",
   "description": "Static Bypass Switch",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 70,
   "name": "5833_1",
   "description": "Module Operating Status (Power Module 1)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 71,
   "name": "6437_1",
   "description": "Power Module Sleep Status (Power Module 1)",
   "units": "",
   "access": "R",
   "states": "1=Sleeping, 2=Not Sleeping"
  },
  {
   "type": "MV",
   "instance": 82,
   "name": "4748_1_1",
   "description": "Rectifier Status (Power Module 1 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 93,
   "name": "5864_1_1",
   "description": "Inverter Status (Power Module 1 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "1=Inverter Inactive, 2=Inverter Active"
  },
  {
   "type": "MV",
   "instance": 104,
   "name": "6256_1_1",
   "description": "Charger On/Off State (Power Module 1 Charger 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 115,
   "name": "8509_1_1",
   "description": "Discharger On/Off Status (Power Module 1 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 126,
   "name": "5833_2",
   "description": "Module Operating Status (Power Module 2)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 127,
   "name": "6437_2",
   "description": "Power Module Sleep Status (Power Module 2)",
   "units": "",
   "access": "R",
   "states": "1=Sleeping, 2=Not Sleeping"
  },
  {
   "type": "MV",
   "instance": 138,
   "name": "4748_2_1",
   "description": "Rectifier Status (Power Module 2 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 149,
   "name": "5864_2_1",
   "description": "Inverter Status (Power Module 2 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "1=Inverter Inactive, 2=Inverter Active"
  },
  {
   "type": "MV",
   "instance": 160,
   "name": "6256_2_1",
   "description": "Charger On/Off State (Power Module 2 Charger 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 171,
   "name": "8509_2_1",
   "description": "Discharger On/Off Status (Power Module 2 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 574,
   "name": "5833_10",
   "description": "Module Operating Status (Power Module 10)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 575,
   "name": "6437_10",
   "description": "Power Module Sleep Status (Power Module 10)",
   "units": "",
   "access": "R",
   "states": "1=Sleeping, 2=Not Sleeping"
  },
  {
   "type": "MV",
   "instance": 586,
   "name": "4748_10_1",
   "description": "Rectifier Status (Power Module 10 Rectifier 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 597,
   "name": "5864_10_1",
   "description": "Inverter Status (Power Module 10 Inverter 1)",
   "units": "",
   "access": "R",
   "states": "1=Inverter Inactive, 2=Inverter Active"
  },
  {
   "type": "MV",
   "instance": 608,
   "name": "6256_10_1",
   "description": "Charger On/Off State (Power Module 10 Charger 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 619,
   "name": "8509_10_1",
   "description": "Discharger On/Off Status (Power Module 10 Discharger 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 630,
   "name": "8594_1",
   "description": "MMS UPS Loading Status",
   "units": "",
   "access": "R",
   "states": "1=Load on Other Module, 2=Load Off, 3=Load on Inverter, 4=Load on Bypass, 5=Load on Maintenance Bypass, 6=Load on Battery, 7=Load on Shared Source"
  },
  {
   "type": "MV",
   "instance": 641,
   "name": "8275_1",
   "description": "Application Mode For UPS",
   "units": "",
   "access": "R",
   "states": "1=UPS Mode, 2=Frequency Converter Mode, 3=Intelligent Paralleling Mode, 4=Intelligent Paralleling Mode Demo, 5=ECO Mode, 6=Intelligent ECO Mode, 7=Intelligent ECO Mode Demo, 8=Testing Mode, 9=Regen Mode, 10=Power Conditioner Mode, 11=Frequency Converter Mode without Battery, 12=Dynamic Online Mode, 13=Dynamic Online Mode Demo"
  },
  {
   "type": "MV",
   "instance": 642,
   "name": "8595_1",
   "description": "UPS Loading Status",
   "units": "",
   "access": "R",
   "states": "1=Load on Other Module, 2=Load Off, 3=Load on Inverter, 4=Load on Bypass, 5=Load on Maintenance Bypass, 6=Load on Battery, 7=Load on Shared Source"
  },
  {
   "type": "MV",
   "instance": 643,
   "name": "4123_1",
   "description": "System Status",
   "units": "",
   "access": "R",
   "states": "1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation"
  },
  {
   "type": "MV",
   "instance": 654,
   "name": "8330_1",
   "description": "Battery type",
   "units": "",
   "access": "R",
   "states": "1=VRLA, 2=Lithium Battery"
  },
  {
   "type": "MV",
   "instance": 655,
   "name": "4871_1",
   "description": "UPS Battery Status",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Normal, 3=Low, 4=Depleted"
  },
  {
   "type": "MV",
   "instance": 656,
   "name": "5799_1",
   "description": "Battery is",
   "units": "",
   "access": "R",
   "states": "1=fully charged, 2=charging, 3=discharging, 4=not charging (charger off)"
  },
  {
   "type": "MV",
   "instance": 657,
   "name": "5803_1",
   "description": "Automatic Battery Test",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 668,
   "name": "8607_1",
   "description": "Battery Cabinet Type (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "1=Internal, 2=External"
  },
  {
   "type": "MV",
   "instance": 669,
   "name": "8533_1",
   "description": "Battery Cabinet Operating Status (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 670,
   "name": "8534_1",
   "description": "Battery Cabinet Circuit Breaker Status (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 671,
   "name": "8535_1",
   "description": "Battery Cabinet Charge Disconnect Status (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 672,
   "name": "8536_1",
   "description": "Battery Cabinet Discharge Disconnect Status (Battery Cabinet 1)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 683,
   "name": "5834_1_1",
   "description": "Module Operating Status (Battery Cabinet 1 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 684,
   "name": "8578_1_1",
   "description": "Battery Module Disconnect Status (Battery Cabinet 1 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 695,
   "name": "5834_1_2",
   "description": "Module Operating Status (Battery Cabinet 1 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 696,
   "name": "8578_1_2",
   "description": "Battery Module Disconnect Status (Battery Cabinet 1 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 1055,
   "name": "5834_1_32",
   "description": "Module Operating Status (Battery Cabinet 1 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 1056,
   "name": "8578_1_32",
   "description": "Battery Module Disconnect Status (Battery Cabinet 1 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 1067,
   "name": "8607_2",
   "description": "Battery Cabinet Type (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "1=Internal, 2=External"
  },
  {
   "type": "MV",
   "instance": 1068,
   "name": "8533_2",
   "description": "Battery Cabinet Operating Status (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 1069,
   "name": "8534_2",
   "description": "Battery Cabinet Circuit Breaker Status (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 1070,
   "name": "8535_2",
   "description": "Battery Cabinet Charge Disconnect Status (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 1071,
   "name": "8536_2",
   "description": "Battery Cabinet Discharge Disconnect Status (Battery Cabinet 2)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 1082,
   "name": "5834_2_1",
   "description": "Module Operating Status (Battery Cabinet 2 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 1083,
   "name": "8578_2_1",
   "description": "Battery Module Disconnect Status (Battery Cabinet 2 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 1094,
   "name": "5834_2_2",
   "description": "Module Operating Status (Battery Cabinet 2 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 1095,
   "name": "8578_2_2",
   "description": "Battery Module Disconnect Status (Battery Cabinet 2 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 1454,
   "name": "5834_2_32",
   "description": "Module Operating Status (Battery Cabinet 2 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 1455,
   "name": "8578_2_32",
   "description": "Battery Module Disconnect Status (Battery Cabinet 2 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 3860,
   "name": "8607_9",
   "description": "Battery Cabinet Type (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "1=Internal, 2=External"
  },
  {
   "type": "MV",
   "instance": 3861,
   "name": "8533_9",
   "description": "Battery Cabinet Operating Status (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 3862,
   "name": "8534_9",
   "description": "Battery Cabinet Circuit Breaker Status (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 3863,
   "name": "8535_9",
   "description": "Battery Cabinet Charge Disconnect Status (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 3864,
   "name": "8536_9",
   "description": "Battery Cabinet Discharge Disconnect Status (Battery Cabinet 9)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 3875,
   "name": "5834_9_1",
   "description": "Module Operating Status (Battery Cabinet 9 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 3876,
   "name": "8578_9_1",
   "description": "Battery Module Disconnect Status (Battery Cabinet 9 Battery Module 1)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 3887,
   "name": "5834_9_2",
   "description": "Module Operating Status (Battery Cabinet 9 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 3888,
   "name": "8578_9_2",
   "description": "Battery Module Disconnect Status (Battery Cabinet 9 Battery Module 2)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 4247,
   "name": "5834_9_32",
   "description": "Module Operating Status (Battery Cabinet 9 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 4248,
   "name": "8578_9_32",
   "description": "Battery Module Disconnect Status (Battery Cabinet 9 Battery Module 32)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 4259,
   "name": "8555_1",
   "description": "Battery String Operating Status (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 4260,
   "name": "8556_1",
   "description": "Battery String Charge Disconnect Status (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 4261,
   "name": "8557_1",
   "description": "Battery String Discharge Disconnect Status (Battery String 1)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 4272,
   "name": "8555_2",
   "description": "Battery String Operating Status (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 4273,
   "name": "8556_2",
   "description": "Battery String Charge Disconnect Status (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 4274,
   "name": "8557_2",
   "description": "Battery String Discharge Disconnect Status (Battery String 2)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 4350,
   "name": "8555_8",
   "description": "Battery String Operating Status (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Fault"
  },
  {
   "type": "MV",
   "instance": 4351,
   "name": "8556_8",
   "description": "Battery String Charge Disconnect Status (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 4352,
   "name": "8557_8",
   "description": "Battery String Discharge Disconnect Status (Battery String 8)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/vertiv/apm2",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}