 "manufacturer": "Vertiv",
 "manufacturer_slug": "vertiv",
 "model": "Liebert Mini-Mate2 1-5 ton and 8 ton (IntelliSlot Unity card)",
 "model_slug": "mini-mate2-unity",
 "aliases": [
  "Liebert Mini-Mate2",
  "Mini-Mate2 8 ton",
  "IS-UNITY-DP",
  "SL-28170"
 ],
 "equipment_type": "Ceiling-mounted precision split cooling unit",
 "applies_to": "Liebert Mini-Mate2 1-ton to 5-ton and 8-ton units read through a Liebert IntelliSlot Unity card.",
 "summary": "The Liebert Mini-Mate2 1-5 ton and 8 ton map is a short legacy list: unit status, temperature and humidity readings and setpoints, an on/off control word and alarm words where several alarms share one object as bits. Only use it with the card variant named in the title.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Tables 5.62, 5.63, 5.64, pdf pages 1602-1605 of the 2024 guide (printed page numbers are 4 lower).",
  "Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.",
  "The guide prints the same instance twice for: AV 22 (bc25_1 and bc25_1_deg_F); only the first is listed.",
  "For AV 5, AV 9 and AV 11 the guide prints a second name ending _deg_F in the same row (°F reading); only the first name is listed."
 ],
 "source": {
  "title": "Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP)",
  "doc_number": "SL-28170",
  "revision_date": "2024-04 (Rev 29)",
  "url": "https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf"
 },
 "integration": {
  "summary": "Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.",
  "minimum_points": [
   {
    "ref": "AV 4",
    "name": "bc01_1",
    "why": "Control word: unit on/off and lockouts (bit-coded)"
   },
   {
    "ref": "AV 9",
    "name": "bs10_1",
    "why": "Return air temperature setpoint, °C"
   },
   {
    "ref": "AV 10",
    "name": "bs12_1",
    "why": "Humidity setpoint, %RH"
   },
   {
    "ref": "AV 5",
    "name": "bs01_1",
    "why": "Inlet air temperature, °C"
   },
   {
    "ref": "AV 6",
    "name": "bs02_1",
    "why": "Return humidity, %RH"
   },
   {
    "ref": "AV 8",
    "name": "bs09_1",
    "why": "Temperature control capacity, %"
   },
   {
    "ref": "AV 1",
    "name": "ba01_1",
    "why": "Alarm word 1 (bit-coded)"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The card needs a unique Device Instance Number; the device object represents the card, not the unit.",
   "The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).",
   "IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports."
  ],
  "gotchas": [
   "Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.",
   "No segmented responses: large ReadPropertyMultiple requests can fail, so split them.",
   "Only data the managed unit actually has is created on the card, so object counts vary by model and options."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 1,
   "name": "ba21_1",
   "description": "Internal Communications Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "ba27_1",
   "description": "High Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "ba28_1",
   "description": "Low Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "ba29_1",
   "description": "High Return Humidity",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "ba30_1",
   "description": "Low Return Humidity",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "ba31_1",
   "description": "Humidifier Problem",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "ba24_1",
   "description": "Loss of Air Flow",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "ba26_1",
   "description": "Clogged Air Filter",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "ba32_1",
   "description": "Smoke Detected",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "ba25_1",
   "description": "Ext Standby Glycol Pump On",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "ba34_1",
   "description": "Ext Standby Unit On (Not in 1-5 ton unit)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "ba33_1",
   "description": "Supply Chilled Water Loss of Flow",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "ba36_1",
   "description": "Loss Of Power",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "ba37_1",
   "description": "Custom Alarm #1",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "ba38_1",
   "description": "Custom Alarm #2",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "ba39_1",
   "description": "Custom Alarm #3 (Not in 1-5 ton unit)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "ba40_1",
   "description": "Custom Alarm #4 (Not in 1-5 ton unit)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "ba22_1",
   "description": "Compressor 1 High Pressure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "ba23_1",
   "description": "Compressor 2 High Pressure (Not in 1-5 ton unit)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "ba35_1",
   "description": "Compressor Short Cycle",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "ba01_1",
   "description": "Bit-packed: Combined Data",
   "units": "",
   "access": "R",
   "states": "Communications Failure: Bit 0; Local Off: Bit 1; Remote Off: Bit 2; High Head Pressure 1: Bit 3 This event is not latching; High Head Pressure 2 (Not in 1-5 ton unit): Bit 4 This event is not latching; Loss of Air Flow: Bit 5; Standby Glycol Unit On (Not in 1-5 ton unit): Bit 6; Clogged Air Filter: Bit 8; High Temperature: Bit 9; Low Temperature: Bit 10"
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "ba02_1",
   "description": "Bit-packed: Combined Data",
   "units": "",
   "access": "R",
   "states": "High Humidity: Bit 0; Low Humidity: Bit 1; Humidifier Problem: Bit 2; Compressor 1 Thermal Overload: Bit 4; Compressor 2 Thermal Overload (Not in 1-5 ton unit): Bit 5; Main Fan Overload: Bit 6; Smoke Detected: Bit 8; Loss of Water: Bit 9; Standby Unit On (Not in 1-5 ton unit): Bit 10"
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "ba03_1",
   "description": "Bit-packed: Combined Data",
   "units": "",
   "access": "R",
   "states": "Low Suction Pressure: Bit 0; Short Cycle: Bit 1; Loss of Power: Bit 2; Local Alarm 1: Bit 6; Local Alarm 2: Bit 7; EPO Shutdown: Bit 8; High Water (1-5 Ton) Local Alarm 3 (8 Ton): Bit 9; High Water (8 Ton) (Not in 1-5 ton unit): Bit 10"
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "bc01_1",
   "description": "Bit-packed: Combined Data",
   "units": "",
   "access": "W",
   "states": "Unit On/Off: Bit 0 On=unit Off Bit 1 On= Unit ON (W); Reheat Lockout: Bit 2 On=RH Off Bit 3 On=RH On; Humidifier Lockout: Bit 4 On= HL Off Bit 5 On=HL On; Temperature and Tolerance: 0=No change (W); Humidity and Tolerance: 0=No change (W)"
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "bs03_1",
   "description": "Cooling State",
   "units": "",
   "access": "R",
   "states": "1=On /, 0=Off"
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "bs04_1",
   "description": "Heating State",
   "units": "",
   "access": "R",
   "states": "1=On /, 0=Off"
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "bs05_1",
   "description": "Humidifier State (Combined Data)",
   "units": "",
   "access": "R",
   "states": "1=On /, 0=Off"
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "bs06_1",
   "description": "Dehumidifier State (Combined Data)",
   "units": "",
   "access": "R",
   "states": "1=On /, 0=Off"
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "bs01_1",
   "description": "Inlet Air Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "bs02_1",
   "description": "Return Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "bs09_1",
   "description": "Temperature Control Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "bs08_1",
   "description": "Cool/Heat Stages",
   "units": "",
   "access": "R",
   "states": "0=None, 1=Stage 1, 2=Stage 2"
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "bs07_1",
   "description": "Glyco Pump On (System)",
   "units": "",
   "access": "R",
   "states": "0=off, 1=on"
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "bs10_1",
   "description": "Return Air Temperature Set Point (Settings)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "bc02_1",
   "description": "Return Air Temperature Set Point (Settings)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "bc25_1",
   "description": "Air Temperature Proportional Band",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "bs12_1",
   "description": "Humidity Set Point (Settings)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "bc03_1",
   "description": "Humidity Set Point (Settings)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "bc27_1",
   "description": "Humidity Proportional Band",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "bs18_1",
   "description": "System On/Off Control (Settings)",
   "units": "",
   "access": "W",
   "states": "0: off 1: on"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "bs23_1",
   "description": "Temp Control State",
   "units": "",
   "access": "R",
   "states": "1=Idle, 2=Heating, 3=Cooling"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "bs26_1",
   "description": "Glyco Pump On (System)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "bs27_1",
   "description": "Managed Device Operation State",
   "units": "",
   "access": "R",
   "states": "1=UnitOn, 2=Reboot, 3=Unit Power Off, 4=RsdOff, 5=CommsOff"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "bs24_1",
   "description": "Humidifier State (System)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "bs25_1",
   "description": "Dehumidifier State (System)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "bc21_1",
   "description": "System On/Off Control (Settings)",
   "units": "",
   "access": "W",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "bc22_1",
   "description": "Reheater Lockout",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "bc23_1",
   "description": "Humidifier Lockout",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/vertiv/mini-mate2-unity",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}