- Home
- BACnet points lists
- Intesis
- IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)
VRF BACnet gateway (Fujitsu, multi-unit) · BACnet points list
Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet) BACnet points list
Updated 12 November 2026
The IN775FGL***O000 is a multi-protocol Intesis 700 Series gateway that reads a Fujitsu VRF network and serves it as BACnet IP or BACnet MS/TP objects (the same map for both). It has gateway/batch objects, a block per outdoor unit and a block per indoor unit; instance numbers come from fixed formulas on the unit number.
This page lists 64 BACnet objects for the Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet) — 25 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)
- Equipment
- VRF BACnet gateway (Fujitsu, multi-unit)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 64 (25 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- IN775FGL, IN775FGLO000, IN775FGL***O000, 700 Series Air Fujitsu, Intesis Fujitsu VRF BACnet gateway, HMS Intesis Fujitsu VRF, Fujitsu Airstage VRF BACnet
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)
Connect the gateway to the Fujitsu VRF bus, scan and configure the units in Intesis MAPS, then map each indoor unit's _C/_S objects from its block (U x 100). Use the Batch_ objects for all-unit commands.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | IUXX_Operation_C | Start/stop indoor unit | Command |
| MO 100 | IUXX_OperationMode_C | Mode command | Command |
| AO 100 | IUXX_SetTemp_C | Setpoint command | Command |
| MO 101 | IUXX_FanSpeed_C | Fan speed command | Command |
| BI 101 | IUXX_Operation_S | Run status | Read |
| AI 100 | IUXX_SetTemp_S | Setpoint in use | Read |
| AI 101 | IUXX_SpaceTemp_S | Room temperature | Read |
| BI 105 | IUXX_Error_S | Unit alarm | Read |
| MI 105 | IUXX_ErrorCode_S | Fault code (1 = no error) | Read |
| BI 1 | Gateway_Error_S | Gateway fault | Read |
Enable & remote start
No enable point is documented; remote-controller use can be restricted with IUXX_RC_Prohibit_C.
Network setup
- BACnet IP or BACnet MS/TP is selected in Intesis MAPS; the object map is the same for both.
- Out of the box DHCP is tried; with no DHCP server the gateway falls back to 192.168.100.246.
Watch out for
- Instances are formula-based: indoor unit n uses n x 100 + offset, outdoor unit n uses n x 25 + 10000 + offset.
- Batch_ commands act on all units at once.
Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 0 | Gateway_ES_C | Command | 0=Not used, 1=Energy saving | ||
| BI | 0 | Gateway_ES_S | Read | 0=Not used, 1=Energy saving | ||
| BImin | 1 | Gateway_Error_S | Read | 0=Normal, 1=Abnormal | ||
| MI | 0 | Gateway_ErrorCode_S | Read | 1=No error, 2=Hardware Comm. Error, 3=No Config Error | ||
| BO | 1 | Batch_Operation_C | Command | 0=Off, 1=On | ||
| MO | 0 | Batch_OperationMode_C | Command | 1=Cool, 2=Heat, 3=Fan, 4=Dry, 5=Auto | ||
| MO | 1 | Batch_Fanspeed_C | Command | 1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet, 6=Med_Low, 7=Med_High | ||
| AO | 0 | Batch_SetTemp_C | °C/°F | Command | ||
| MO | 2 | Batch_RC_Prohibition_C | Command | 0=Disabled, 1=No disabled | ||
| MO | 10000 | OUXX_CapacitySave_C | Command | 1=Not set, 2=100%, 3=90%, 4=80%, 5=70%, 6=60%, 7=50%, 8=40% | ||
| MI | 10000 | OUXX_CapacitySave_S | Read | 1=Not set, 2=100%, 3=90%, 4=80%, 5=70%, 6=60%, 7=50%, 8=40% | ||
| BO | 10000 | OUXX_ForcedOff_C | Command | 0=Reset, 1=Set | ||
| BI | 10000 | OUXX_ForcedOff_S | Read | 0=Reset, 1=Set | ||
| MO | 10001 | OUXX_LowNoiseOp_C | Command | 1=Stop, 2=Lev1_Quiet, 3=Lev1_Ability, 4=Lev2_Quiet, 5=Lev2_Ability, 6=Lev3_Quiet, 7=Lev3_Ability | ||
| MI | 10001 | OUXX_LowNoiseOp_S | Values per the AC manual (1-16) | Read | ||
| BI | 10001 | OUXX_Error_S | Read | 0=Normal, 1=Fault | ||
| MI | 10002 | OUXX_ErrorCode_S | 1 = no error, other values = error code | Read | ||
| BI | 100 | IUXX_Exists_S | Read | 0=Not Exist, 1=Exist | ||
| BOmin | 100 | IUXX_Operation_C | Command | 0=Off, 1=On | ||
| BImin | 101 | IUXX_Operation_S | Read | 0=Off, 1=On | ||
| MOmin | 100 | IUXX_OperationMode_C | Command | 1=Cool, 2=Heat, 3=Fan, 4=Dry, 5=Auto | ||
| MI | 100 | IUXX_OperationMode_S | Read | 1=Cool, 2=Heat, 3=Fan, 4=Dry, 5=Auto | ||
| MOmin | 101 | IUXX_FanSpeed_C | Second printed state set: 1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet | Command | 1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet, 6=Med_Low, 7=Med_High | |
| MI | 101 | IUXX_FanSpeed_S | Second printed state set: 1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet | Read | 1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet, 6=Med_Low, 7=Med_High | |
| MO | 102 | IUXX_AirFlowDirVT_C | Command | 1=Pos1, 2=Pos2, 3=Pos3, 4=Pos4, 5=Swing | ||
| MI | 102 | IUXX_AirFlowDirVT_S | Read | 1=Pos1, 2=Pos2, 3=Pos3, 4=Pos4, 5=Swing | ||
| MO | 103 | IUXX_AirFlowDirHZ_C | Command | 1=Pos1, 2=Pos2, 3=Pos3, 4=Pos4, 5=Pos5, 6=Swing | ||
| MI | 103 | IUXX_AirFlowDirHZ_S | Read | 1=Pos1, 2=Pos2, 3=Pos3, 4=Pos4, 5=Pos5, 6=Swing | ||
| AOmin | 100 | IUXX_SetTemp_C | °C/°F | Command | ||
| AImin | 100 | IUXX_SetTemp_S | °C/°F | Read | ||
| AImin | 101 | IUXX_SpaceTemp_S | °C/°F | Read | ||
| MO | 104 | IUXX_RC_Prohibit_C | Values per the AC manual (1-65) | Command | ||
| MI | 104 | IUXX_RC_Prohibit_S | Values per the AC manual (1-65) | Read | ||
| BO | 101 | IUXX_ThermostatOFF_C | Command | 0=Reset, 1=Set | ||
| BI | 102 | IUXX_ThermostatOFF_S | Read | 0=Reset, 1=Set | ||
| BO | 102 | IUXX_Reset_Filter_C | Command | 0=No Reset, 1=Reset | ||
| BI | 103 | IUXX_FilterSign_S | Read | 0=No Sign, 1=Sign | ||
| BI | 104 | IUXX_Emergency_S | Read | 0=Normal, 1=Stop | ||
| BImin | 105 | IUXX_Error_S | Read | 0=Normal, 1=Fault | ||
| MImin | 105 | IUXX_ErrorCode_S | 1 = no error, other values = error code | Read | ||
| BO | 103 | IUXX_TempLimValid_C | Command | 0=Invalid, 1=Valid | ||
| BI | 106 | IUXX_TempLimValid_S | Read | 0=Invalid, 1=Valid | ||
| AO | 101 | IUXX_AutoTempLoLim_C | °C/°F | Command | ||
| AI | 102 | IUXX_AutoTempLoLim_S | °C/°F | Read | ||
| AO | 102 | IUXX_AutoTempHiLim_C | °C/°F | Command | ||
| AI | 103 | IUXX_AutoTempHiLim_S | °C/°F | Read | ||
| AO | 103 | IUXX_CoolTempLoLim_C | °C/°F | Command | ||
| AI | 104 | IUXX_CoolTempLoLim_S | °C/°F | Read | ||
| AO | 104 | IUXX_CoolTempHiLim_C | °C/°F | Command | ||
| AI | 105 | IUXX_CoolTempHiLim_S | °C/°F | Read | ||
| AO | 105 | IUXX_HeatTempLoLim_C | °C/°F | Command | ||
| AI | 106 | IUXX_HeatTempLoLim_S | °C/°F | Read | ||
| AO | 106 | IUXX_HeatTempHiLim_C | °C/°F | Command | ||
| AI | 107 | IUXX_HeatTempHiLim_S | °C/°F | Read | ||
| MI | 106 | IUXX_Managed_Mode_S | Read | 1=None, 2=Master, 3=Slave, 4=External | ||
| AI | 108 | IUXX_Consumption Yesterday | Wh/kWh | Read | ||
| AI | 109 | IUXX_Consumption Today | Wh/kWh | Read | ||
| AI | 110 | IUXX_Consumption Total | Wh/kWh | Read | ||
| AI | 111 | IUXX_Consumption Yesterday Heat | Wh/kWh | Read | ||
| AI | 112 | IUXX_Consumption Today Heat | Wh/kWh | Read | ||
| AI | 113 | IUXX_Consumption Total Heat | Wh/kWh | Read | ||
| AI | 114 | IUXX_Consumption Yesterday Cool | Wh/kWh | Read | ||
| AI | 115 | IUXX_Consumption Today Cool | Wh/kWh | Read | ||
| AI | 116 | IUXX_Consumption Total Cool | Wh/kWh | Read |
No points match these filters.
Object ID lookup: Intesis IN775FGL***O000 point IDs by name
BO0Gateway_ES_CBI0Gateway_ES_SBI1Gateway_Error_SMI0Gateway_ErrorCode_SBO1Batch_Operation_CMO0Batch_OperationMode_CMO1Batch_Fanspeed_CAO0Batch_SetTemp_CMO2Batch_RC_Prohibition_CMO10000OUXX_CapacitySave_CMI10000OUXX_CapacitySave_SBO10000OUXX_ForcedOff_CBI10000OUXX_ForcedOff_SMO10001OUXX_LowNoiseOp_CMI10001OUXX_LowNoiseOp_SBI10001OUXX_Error_SMI10002OUXX_ErrorCode_SBI100IUXX_Exists_SBO100IUXX_Operation_CBI101IUXX_Operation_SMO100IUXX_OperationMode_CMI100IUXX_OperationMode_SMO101IUXX_FanSpeed_CMI101IUXX_FanSpeed_SMO102IUXX_AirFlowDirVT_CMI102IUXX_AirFlowDirVT_SMO103IUXX_AirFlowDirHZ_CMI103IUXX_AirFlowDirHZ_SAO100IUXX_SetTemp_CAI100IUXX_SetTemp_SAI101IUXX_SpaceTemp_SMO104IUXX_RC_Prohibit_CMI104IUXX_RC_Prohibit_SBO101IUXX_ThermostatOFF_CBI102IUXX_ThermostatOFF_SBO102IUXX_Reset_Filter_CBI103IUXX_FilterSign_SBI104IUXX_Emergency_SBI105IUXX_Error_SMI105IUXX_ErrorCode_SBO103IUXX_TempLimValid_CBI106IUXX_TempLimValid_SAO101IUXX_AutoTempLoLim_CAI102IUXX_AutoTempLoLim_SAO102IUXX_AutoTempHiLim_CAI103IUXX_AutoTempHiLim_SAO103IUXX_CoolTempLoLim_CAI104IUXX_CoolTempLoLim_SAO104IUXX_CoolTempHiLim_CAI105IUXX_CoolTempHiLim_SAO105IUXX_HeatTempLoLim_CAI106IUXX_HeatTempLoLim_SAO106IUXX_HeatTempHiLim_CAI107IUXX_HeatTempHiLim_SMI106IUXX_Managed_Mode_SAI108IUXX_Consumption YesterdayAI109IUXX_Consumption TodayAI110IUXX_Consumption TotalAI111IUXX_Consumption Yesterday HeatAI112IUXX_Consumption Today HeatAI113IUXX_Consumption Total HeatAI114IUXX_Consumption Yesterday CoolAI115IUXX_Consumption Today CoolAI116IUXX_Consumption Total Cool
Integration notes
- Points are listed for the global/batch objects, outdoor unit 0 (OU block = (OU x 25) + 10000, OU 0-11) and indoor unit 1 (IU block = U x 100, U 1-64). Names keep the printed XX placeholder.
- The manual has no access column: _C (command) objects are taken as commandable, _S (status) objects as read-only.
- Batch_SetTemp_C is printed as object type "1-Analog Input". The manual's own type codes use 0 = Analog Input and 1 = Analog Output (every other _C setpoint is printed "1-Analog Output"), and it is a command, so AO 0 is used here.
- IUXX_FanSpeed_C/_S are printed twice with different state lists (7 speeds and 5 speeds) at the same instance; the 7-speed list is shown and the 5-speed list is in the description. Check which applies to your indoor units.
- Only the objects for units configured in the gateway exist; use IUXX_Exists_S to check.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)
How many BACnet points does the Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet) have?
This list has 64 BACnet objects: 17 analog inputs, 8 analog outputs, 11 binary inputs, 7 binary outputs, 11 multi-state inputs, 10 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet) BACnet points are writable?
25 of the 64 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet) BACnet documentation?
The source is 700 Series Air Gateway - IN775FGL***O000, Fujitsu VRF systems, User Manual (section 7.3 Integration into BACnet systems), revision Version 1.0.15 (2025-12-09), published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user_manual_in775fglxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)?
Start with BO 100 IUXX_Operation_C (Start/stop indoor unit); MO 100 IUXX_OperationMode_C (Mode command); AO 100 IUXX_SetTemp_C (Setpoint command); MO 101 IUXX_FanSpeed_C (Fan speed command); BI 101 IUXX_Operation_S (Run status); AI 100 IUXX_SetTemp_S (Setpoint in use); AI 101 IUXX_SpaceTemp_S (Room temperature); BI 105 IUXX_Error_S (Unit alarm); MI 105 IUXX_ErrorCode_S (Fault code (1 = no error)); BI 1 Gateway_Error_S (Gateway fault).
How do I enable BMS control of the Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)?
No enable point is documented; remote-controller use can be restricted with IUXX_RC_Prohibit_C.
How do I check these points on the real IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - VRF BACnet gateway (Mitsubishi Heavy Industries, multi-unit)
Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)
Mitsubishi Heavy Industries VRF systems (up to 128 indoor units, or 80 with up to 12 monitored outdoor units on the large license) through the Intesis 700 Series Air gateway IN776MHI***O000.
Also known as: IN776MHI, IN776MHIO000, IN776MHI***O000, IN776MHI00LO000, 700 Series Air MHI, Intesis MHI VRF BACnet gateway, Mitsubishi Heavy Industries VRF BACnet, MHI KX VRF BACnet - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: 700 Series Air Gateway - IN775FGL***O000, Fujitsu VRF systems, User Manual (section 7.3 Integration into BACnet systems) · rev. Version 1.0.15 (2025-12-09). Object names, instances and units are reproduced as published; descriptions are our own.