- Home
- BACnet points lists
- Intesis
- IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
VRF BACnet gateway (up to 64 indoor units, Samsung NASA) · BACnet points list
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway) BACnet points list
Updated 6 November 2026
Intesis 700 Series multi-protocol gateway set up for BACnet IP or BACnet MS/TP on a Samsung NASA bus. It publishes outdoor-unit alarms, gateway-wide commands and one block of objects per indoor unit at (IU x 100): on/off, mode, setpoint, fan, swing, room and discharge temperatures, error code, filter, remote restriction, ventilation, hot water, WindFree, 360 cassette airflow and energy consumption. This file shows the standard indoor unit (IU) set.
This page lists 55 BACnet objects for the Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
- Equipment
- VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 55 (23 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung
- Brands covered
- Samsung
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Connect the Samsung NASA R1/R2 bus to AC-Port B (B1 R1, B2 R2), set the outdoor and indoor units to manual addressing, pick BACnet IP or BACnet MS/TP in Intesis MAPS, scan the units, send the project, then map each indoor unit's objects from its (IU x 100) block. Check the Unit type object first: other unit types use different objects in the same block.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | OXXUXX_On/Off_C | Start/stop indoor unit | Command |
| MO 100 | OXXUXX_Mode IU/AHU_C | Mode command | Command |
| AO 100 | OXXUXX_Setpoint_C | Setpoint command | Command |
| MO 101 | OXXUXX_FanSpeed_C | Fan speed command (4 = auto) | Command |
| BI 100 | OXXUXX_On/Off_S | Run status | Read |
| AI 100 | OXXUXX_Setpoint_S | Setpoint in use | Read |
| AI 101 | OXXUXX_Room_Temperature | Indoor unit room temperature, °C | Read |
| MI 102 | OXXUXX_Communication Status | Link flags; Exist = unit found on the NASA bus | Read |
| AI 105 | OXXUXX_Unit Error code | Fault code | Read |
Enable & remote start
No enable point is documented. OXXUXX_RC Restriction_C (BO 103) restricts the unit's remote controller.
Network setup
- BACnet IP: DHCP for 30 seconds at first start-up, then the default IP 192.168.100.246.
- BACnet MS/TP uses the gateway's EIA-485 port.
- Units are found and configured in Intesis MAPS; send the project to the gateway after changes.
Watch out for
- Global objects (BO 0-3, MO 0-1, AO 0) act on all units at once.
- Samsung EHS units need an external sensor for setpoint and room temperature objects.
- Manual addressing may be needed on the outdoor units if BI 16 OU Addressing Error is active.
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 1 | OUXX_Communication Error OU | Outdoor unit communication error (OU 00) | Read | 0=No error, 1=Error | |
| BI | 16 | OU Addressing Error | OU Addressing Error | Read | 0=OU Addressing OK, 1=Manual Addr in OU required | |
| BO | 0 | On/Off (all units) | On/Off (all units) | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all units) | Mode (all units) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=Cool Storage, 7=Heat Storage | |
| MO | 1 | FanSpeed (all units) | FanSpeed (all units) | Command | 1=Low, 2=Mid, 3=High, 4=Auto | |
| BO | 1 | Vane position swing (all units) | Vane position swing (all units) | Command | 0=Swing Off, 1=Swing On | |
| AO | 0 | Temperature Setpoint (all units) | Temperature Setpoint (all units) (cool 18-30 °C, heat 16-30 °C) | °C | Command | |
| BO | 2 | Vent. On/Off (all units) | Vent. On/Off (all units) | Command | 0=Off, 1=On | |
| BO | 3 | Hot Water On/Off (all units) | Hot Water On/Off (all units) | Command | 0=Off, 1=On | |
| BImin | 100 | OXXUXX_On/Off_S | On/Off (status) | Read | 0=Off, 1=On | |
| BOmin | 100 | OXXUXX_On/Off_C | On/Off (command) | Command | 0=Off, 1=On | |
| MI | 100 | OXXUXX_Mode IU/AHU_S | Mode IU/AHU (status) | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MOmin | 100 | OXXUXX_Mode IU/AHU_C | Mode IU/AHU (command) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 100 | OXXUXX_Setpoint_S | Setpoint (status) (cool 18-30 °C, heat 16-30 °C) | °C | Read | |
| AOmin | 100 | OXXUXX_Setpoint_C | Setpoint (command) (cool 18-30 °C, heat 16-30 °C) | °C | Command | |
| MI | 101 | OXXUXX_FanSpeed_S | FanSpeed (status) | Read | 1=Low, 2=Mid, 3=High, 4=Auto | |
| MOmin | 101 | OXXUXX_FanSpeed_C | FanSpeed (command) | Command | 1=Low, 2=Mid, 3=High, 4=Auto | |
| BI | 101 | OXXUXX_Vane position swing_S | Vane position swing (status) | Read | 0=Swing Off, 1=Swing On | |
| BO | 101 | OXXUXX_Vane position swing_C | Vane position swing (command) | Command | 0=Swing Off, 1=Swing On | |
| AImin | 101 | OXXUXX_Room_Temperature | Room Temperature | °C | Read | |
| AI | 102 | OXXUXX_Disch.Setpoint Cool IU_S | Disch.Setpoint Cool IU (status) | °C | Read | |
| AO | 101 | OXXUXX_Disch.Setpoint Cool IU_C | Disch.Setpoint Cool IU (command) | °C | Command | |
| AI | 103 | OXXUXX_Disch.Setpoint Heat IU_S | Disch.Setpoint Heat IU (status) | °C | Read | |
| AO | 102 | OXXUXX_Disch.Setpoint Heat IU_C | Disch.Setpoint Heat IU (command) | °C | Command | |
| AI | 104 | OXXUXX_Disch. Current Temp. | Disch. Current Temp. | °C | Read | |
| AImin | 105 | OXXUXX_Unit Error code | Unit error code | Read | 0=No Error, 100..999=Error | |
| BI | 102 | OXXUXX_FilterSign | FilterSign | Read | 0=Normal, 1=Alarm | |
| BO | 102 | OXXUXX_FilterReset | FilterReset | Command | 0=No reset, 1=Reset | |
| MImin | 102 | OXXUXX_Communication Status | Communication Status | Read | bit flags: b0=Exist, b1=Ready, b2=Data updated, b3=Type OK | |
| BI | 103 | OXXUXX_RC Restriction_S | RC Restriction (status) | Read | 0=No restriction, 1=Restriction | |
| BO | 103 | OXXUXX_RC Restriction_C | RC Restriction (command) | Command | 0=No restriction, 1=Restriction | |
| BO | 104 | OXXUXX_Buzzer Sound | Buzzer Sound | Command | 0=Buzzer On, 1=Buzzer Off | |
| MI | 103 | OXXUXX_Unit type | Unit type | Read | 1=Not Defined, 2=IU, 3=HE, 4=HT, 5=AHU, 6=ERV, 7=ERV+, 8=EHS, 9=CHILLER | |
| BI | 104 | OXXUXX_HotWater On/Off_S | HotWater On/Off (status) | Read | 0=Off, 1=On | |
| BO | 105 | OXXUXX_HotWater On/Off_C | HotWater On/Off (command) | Command | 0=Off, 1=On | |
| BI | 105 | OXXUXX_Vent. On/Off_S | Vent. On/Off (status) | Read | 0=Off, 1=On | |
| BO | 106 | OXXUXX_Vent. On/Off_C | Vent. On/Off (command) | Command | 0=Off, 1=On | |
| MI | 105 | OXXUXX_Vent. Mode_S | Vent. Mode (status) | Read | 1=Bypass, 2=HeatEx, 3=Sleep, 4=Auto | |
| MO | 103 | OXXUXX_Vent. Mode_C | Vent. Mode (command) | Command | 1=Bypass, 2=HeatEx, 3=Sleep, 4=Auto | |
| MI | 106 | OXXUXX_Vent. FanSpeed_S | Vent. FanSpeed (status) | Read | 1=Low, 2=High, 3=Turbo | |
| MO | 104 | OXXUXX_Vent. FanSpeed_C | Vent. FanSpeed (command) | Command | 1=Low, 2=High, 3=Turbo | |
| BI | 106 | OXXUXX_WindFree_S | WindFree (status) | Read | 0=Disable, 1=Enable | |
| BO | 107 | OXXUXX_WindFree_C | WindFree (command) | Command | 0=Disable, 1=Enable | |
| BI | 107 | OXXUXX_Air Clean_S | Air Clean (status) | Read | 0=Disable, 1=Enable | |
| MI | 107 | OXXUXX_360 CST Air Flow_S | 360 CST Air Flow (status) | Read | 1=Spot, 2=Mid, 3=Wide, 4=Swing | |
| MO | 105 | OXXUXX_360 CST Air Flow_C | 360 CST Air Flow (command) | Command | 1=Spot, 2=Mid, 3=Wide, 4=Swing | |
| AI | 109 | OXXUXX_Consumption Yesterday_S | Consumption Yesterday (status) | Wh/kWh | Read | |
| AI | 110 | OXXUXX_Consumption Today_S | Consumption Today (status) | Wh/kWh | Read | |
| AI | 111 | OXXUXX_Consumption Total_S | Consumption Total (status) | Wh/kWh | Read | |
| AI | 112 | OXXUXX_Consumption Yesterday Heat_S | Consumption Yesterday Heat (status) | Wh/kWh | Read | |
| AI | 113 | OXXUXX_Consumption Today Heat_S | Consumption Today Heat (status) | Wh/kWh | Read | |
| AI | 114 | OXXUXX_Consumption Total Heat_S | Consumption Total Heat (status) | Wh/kWh | Read | |
| AI | 115 | OXXUXX_Consumption Yesterday Cool_S | Consumption Yesterday Cool (status) | Wh/kWh | Read | |
| AI | 116 | OXXUXX_Consumption Today Cool_S | Consumption Today Cool (status) | Wh/kWh | Read | |
| AI | 117 | OXXUXX_Consumption Total Cool_S | Consumption Total Cool (status) | Wh/kWh | Read |
No points match these filters.
Object ID lookup: Intesis Samsung NASA Gateway IN770 point IDs by name
BI1OUXX_Communication Error OUBI16OU Addressing ErrorBO0On/Off (all units)MO0Mode (all units)MO1FanSpeed (all units)BO1Vane position swing (all units)AO0Temperature Setpoint (all units)BO2Vent. On/Off (all units)BO3Hot Water On/Off (all units)BI100OXXUXX_On/Off_SBO100OXXUXX_On/Off_CMI100OXXUXX_Mode IU/AHU_SMO100OXXUXX_Mode IU/AHU_CAI100OXXUXX_Setpoint_SAO100OXXUXX_Setpoint_CMI101OXXUXX_FanSpeed_SMO101OXXUXX_FanSpeed_CBI101OXXUXX_Vane position swing_SBO101OXXUXX_Vane position swing_CAI101OXXUXX_Room_TemperatureAI102OXXUXX_Disch.Setpoint Cool IU_SAO101OXXUXX_Disch.Setpoint Cool IU_CAI103OXXUXX_Disch.Setpoint Heat IU_SAO102OXXUXX_Disch.Setpoint Heat IU_CAI104OXXUXX_Disch. Current Temp.AI105OXXUXX_Unit Error codeBI102OXXUXX_FilterSignBO102OXXUXX_FilterResetMI102OXXUXX_Communication StatusBI103OXXUXX_RC Restriction_SBO103OXXUXX_RC Restriction_CBO104OXXUXX_Buzzer SoundMI103OXXUXX_Unit typeBI104OXXUXX_HotWater On/Off_SBO105OXXUXX_HotWater On/Off_CBI105OXXUXX_Vent. On/Off_SBO106OXXUXX_Vent. On/Off_CMI105OXXUXX_Vent. Mode_SMO103OXXUXX_Vent. Mode_CMI106OXXUXX_Vent. FanSpeed_SMO104OXXUXX_Vent. FanSpeed_CBI106OXXUXX_WindFree_SBO107OXXUXX_WindFree_CBI107OXXUXX_Air Clean_SMI107OXXUXX_360 CST Air Flow_SMO105OXXUXX_360 CST Air Flow_CAI109OXXUXX_Consumption Yesterday_SAI110OXXUXX_Consumption Today_SAI111OXXUXX_Consumption Total_SAI112OXXUXX_Consumption Yesterday Heat_SAI113OXXUXX_Consumption Today Heat_SAI114OXXUXX_Consumption Total Heat_SAI115OXXUXX_Consumption Yesterday Cool_SAI116OXXUXX_Consumption Today Cool_SAI117OXXUXX_Consumption Total Cool_S
Integration notes
- Indoor unit instance = (IU x 100) + offset, IU 1-64; IU 1 is shown (100-117).
- Left out because they reuse instances of the IU set for other unit types: mode objects for HE, EHS/ERV+ and chiller units, AHU discharge setpoints, hot-water mode and setpoints, water temperatures and the slave-chiller error objects (see the manual).
- The outdoor communication-error object is printed with instance OU[0..15] + 1; outdoor unit 00 is shown at BI 1. As printed, OU 15 would land on BI 16, the OU Addressing Error object.
- OXXUXX_Air Clean_C (Binary Output) is printed without an instance offset and is left out; OXXUXX_Air Clean_S is BI 107.
- Mode numbering here is 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, unlike the older INBACSAM manual. Consumption is Wh or kWh as set in MAPS.
- The BACnet table has no read/write column; access is inferred from object type. Replaces the INBACSAM004O000-064O000 BACnet servers (listed separately).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
How many BACnet points does the Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway) have?
This list has 55 BACnet objects: 15 analog inputs, 4 analog outputs, 10 binary inputs, 12 binary outputs, 7 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway) BACnet points are writable?
23 of the 55 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway) BACnet documentation?
The source is 700 Series Air Gateway IN770AIR***O000 - Samsung NASA VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual, revision 2025-12-09 v1.0.19, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770samxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)?
Start with BO 100 OXXUXX_On/Off_C (Start/stop indoor unit); MO 100 OXXUXX_Mode IU/AHU_C (Mode command); AO 100 OXXUXX_Setpoint_C (Setpoint command); MO 101 OXXUXX_FanSpeed_C (Fan speed command (4 = auto)); BI 100 OXXUXX_On/Off_S (Run status); AI 100 OXXUXX_Setpoint_S (Setpoint in use); AI 101 OXXUXX_Room_Temperature (Indoor unit room temperature, °C); MI 102 OXXUXX_Communication Status (Link flags; Exist = unit found on the NASA bus); AI 105 OXXUXX_Unit Error code (Fault code).
How do I enable BMS control of the Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)?
No enable point is documented. OXXUXX_RC Restriction_C (BO 103) restricts the unit's remote controller.
How do I check these points on the real IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: 700 Series Air Gateway IN770AIR***O000 - Samsung NASA VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · rev. 2025-12-09 v1.0.19. Object names, instances and units are reproduced as published; descriptions are our own.