- IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
VRF BACnet IP gateway (up to 8 or 64 indoor units) · BACnet points list
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) BACnet points list
Updated 12 November 2026Unofficial source
An older IntesisBox BACnet IP server that polls one Hitachi HC-A8MB or HC-A64MB adaptor and publishes each indoor unit as a fixed block of 33 objects. HI-AC-BAC-8 handles up to 8 indoor units and HI-AC-BAC-64 up to 64. Instances are (unit number x 100) + offset, so unit 1 uses 101-133. Setup is done with the LinkBoxBACnet tool.
This page lists 35 BACnet objects for the Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Intesis’s documentation hosted by Chipkin Automation Systems, not by Intesis itself, so treat it as unofficial.
- Manufacturer
- Intesis
- Model
- IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
- Equipment
- VRF BACnet IP gateway (up to 8 or 64 indoor units)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 35 (13 writable)
- Transport
- BACnet IP
- Firmware
- 4.0.0 (PICS 2016-11-10)
- Default device instance
- 246
- Also known as
- HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway
- Source document
- IntesisBox BACnet/IP - Hitachi AC User Manual r1.1 · rev. r1.1 (PICS 2016-11-10) (unofficial copy, hosted by Chipkin Automation Systems)
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Connect the IntesisBox to the HC-A8MB/HC-A64MB adaptor and the BACnet IP LAN, set the IP and number of indoor units in LinkBoxBACnet, then map each unit's _command and _status objects from its (unit x 100) block.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 105 | IUxxx_OnOff_command | Start/stop indoor unit | Write |
| MO 107 | IUxxx_Mode_command | Mode command | Write |
| AO 111 | IUxxx_Settemp_command | Setpoint command, 17-30 °C | Write |
| MO 109 | IUxxx_Fan_command | Fan speed command (5 = auto) | Write |
| BI 104 | IUxxx_OnOff_status | Run status | Read |
| AI 110 | IUxxx_Settemp_status | Setpoint in use | Read |
| AI 119 | IUxxx_InletTemperature | Return air temperature | Read |
| BI 101 | IUxxx_IU_Exist | Unit found on the adaptor | Read |
| MI 123 | IUxxx_ErrorCode | Alarm code (255 = off) | Read |
| BI 0 | Communication error Hitachi GW | Adaptor communication lost | Read |
Enable & remote start
No enable point is documented. Remote-controller permissions can be locked per unit with the CentralSet BVs (BV 114-118).
Network setup
- Default device instance 246; device instance, name and IP are set with LinkBoxBACnet.
- One IntesisBox integrates one HC-A8MB or HC-A64MB adaptor (bought separately from Hitachi).
- The number of indoor units is set in LinkBoxBACnet; HI-AC-BAC-8 supports 8 units, HI-AC-BAC-64 supports 64.
Watch out for
- Outputs only use Priority_Array slot 16; slots 1-15 stay NULL.
- State_Text cannot be read as a whole array; read one array index at a time.
- Temperatures are °C but the Units property is no-units.
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| DEV | 246 | HI-AC BACnet Gateway | Gateway device object (instance configurable) | Read | ||
| BImin | 0 | Communication error Hitachi GW | Communication error with the HC-A8/64MB adaptor | Read | 0=No Error, 1=Error | |
| BImin | 101 | IUxxx_IU_Exist | Indoor unit present on the adaptor | Read | 0=Not Exist, 1=Exist | |
| AI | 102 | IUxxx_System_Address | H-Link refrigerant system address (0-63) | Read | ||
| AI | 103 | IUxxx_Unit_Address | Indoor unit address (0-63) | Read | ||
| BImin | 104 | IUxxx_OnOff_status | Run status | Read | 0=Stop, 1=Run | |
| BOmin | 105 | IUxxx_OnOff_command | Start/stop command | Write | 0=Stop, 1=Run | |
| MI | 106 | IUxxx_Mode_status | Operating mode | Read | 1=Cool, 2=Dry, 3=Fan, 4=Heat, 5=Auto | |
| MOmin | 107 | IUxxx_Mode_command | Mode command | Write | 1=Cool, 2=Dry, 3=Fan, 4=Heat, 5=Auto | |
| MI | 108 | IUxxx_Fan_status | Fan speed | Read | 1=Low, 2=Medium, 3=High, 4=High2, 5=Auto | |
| MOmin | 109 | IUxxx_Fan_command | Fan speed command | Write | 1=Low, 2=Medium, 3=High, 4=High2, 5=Auto | |
| AImin | 110 | IUxxx_Settemp_status | Setpoint in use, 17-30 °C | °C | Read | |
| AOmin | 111 | IUxxx_Settemp_command | Setpoint command, 17-30 °C | °C | Write | |
| MI | 112 | IUxxx_Louver_status | Louver position (8 states) | Read | ||
| MO | 113 | IUxxx_Louver_command | Louver position command (8 states) | Write | ||
| BV | 114 | IUxxx_CentralSet_OnOff | Lock on/off at the remote controller | Write | 0=On/Off from RC allowed, 1=On/Off from RC not allowed | |
| BV | 115 | IUxxx_CentralSet_Mode | Lock mode change at the remote controller | Write | 0=Mode change from RC allowed, 1=Mode change from RC not allowed | |
| BV | 116 | IUxxx_CentralSet_SetT | Lock setpoint change at the remote controller | Write | 0=Set Point Temp change from RC allowed, 1=Set Point Temp change from RC not allowed | |
| BV | 117 | IUxxx_CentralSet_Fan | Lock fan speed change at the remote controller | Write | 0=Fan Speed change from RC allowed, 1=Fan Speed change from RC not allowed | |
| BV | 118 | IUxxx_CentralSet_Louver | Lock louver change at the remote controller | Write | 0=Louver Position change from RC allowed, 1=Louver Position change from RC not allowed | |
| AImin | 119 | IUxxx_InletTemperature | Inlet (return) air temperature | °C | Read | |
| AI | 120 | IUxxx_OutletTemperature | Outlet (discharge) air temperature | °C | Read | |
| AI | 121 | IUxxx_GasPipeTemp | Gas pipe temperature | °C | Read | |
| AI | 122 | IUxxx_LiquidPipeTemp | Liquid pipe temperature | °C | Read | |
| MImin | 123 | IUxxx_ErrorCode | Alarm code (1-255) | Read | 255=Off | |
| MI | 124 | IUxxx_CompStopCause | Compressor stop cause code (1-255) | Read | 255=Operation Off, Power Off | |
| AI | 125 | IUxxx_ExpansionValveOpening | Expansion valve opening, 0-100 | Read | ||
| MI | 126 | IUxxx_OperationCond | Operating condition | Read | 1=Off, 2=Thermo Off, 3=Thermo On, 4=Alarm | |
| BI | 127 | IUxxx_Defrost | Defrost active | Read | ||
| AI | 128 | IUxxx_AmbTemp | Ambient temperature | °C | Read | |
| AI | 129 | IUxxx_RCSwitchTemp | Remote controller sensor temperature | °C | Read | |
| BV | 130 | IUxxx_RCSwitchConfiguration_Ma | Remote controller master/slave setting | Write | 0=Master, 1=Slave | |
| BV | 131 | IUxxx_RCSwitchConfiguration_RC | Remote controller present setting | Write | 0=With RCS, 1=Without RCS | |
| AV | 132 | IUxxx_RCSwitchGroup | Remote controller group (0 = no group) | Write | ||
| AI | 133 | IUxxx_RemoteSensorTemp | Remote sensor temperature | °C | Read |
No points match these filters.
Object ID lookup: Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 point IDs by name
BI0Communication error Hitachi GWBI101IUxxx_IU_ExistAI102IUxxx_System_AddressAI103IUxxx_Unit_AddressBI104IUxxx_OnOff_statusBO105IUxxx_OnOff_commandMI106IUxxx_Mode_statusMO107IUxxx_Mode_commandMI108IUxxx_Fan_statusMO109IUxxx_Fan_commandAI110IUxxx_Settemp_statusAO111IUxxx_Settemp_commandMI112IUxxx_Louver_statusMO113IUxxx_Louver_commandBV114IUxxx_CentralSet_OnOffBV115IUxxx_CentralSet_ModeBV116IUxxx_CentralSet_SetTBV117IUxxx_CentralSet_FanBV118IUxxx_CentralSet_LouverAI119IUxxx_InletTemperatureAI120IUxxx_OutletTemperatureAI121IUxxx_GasPipeTempAI122IUxxx_LiquidPipeTempMI123IUxxx_ErrorCodeMI124IUxxx_CompStopCauseAI125IUxxx_ExpansionValveOpeningMI126IUxxx_OperationCondBI127IUxxx_DefrostAI128IUxxx_AmbTempAI129IUxxx_RCSwitchTempBV130IUxxx_RCSwitchConfiguration_MaBV131IUxxx_RCSwitchConfiguration_RCAV132IUxxx_RCSwitchGroupAI133IUxxx_RemoteSensorTemp
Integration notes
- Indoor unit objects are shown for unit 1 only. Instance = (xxx x 100) + offset, xxx = indoor unit number 1-64. Object names start with IUxxx, replaced by the unit number on site.
- This is the older product that talks to Hitachi's HC-A8MB/HC-A64MB adaptor. The newer Intesis INBACHIT016O000/064O000 (also sold as HI-AC-BAC-16/64) connects straight to H-Link and uses a different object set.
- Names follow the member-objects table, except Inlet/OutletTemperature, where the section headings and detail pages agree without the underscore. Some detail pages print other variants (IUxxx_CentralSet_OnOff_command, IUxxx_RCSwitch_Configuration_Ma, IUxxx_Settempstatus); check the live object names.
- The doc gives temperature ranges in °C but sets the Units property to no-units.
- The setpoint command AO's property table marks Present_Value R; it is listed here as writable because it is the setpoint command. Louver state texts (8 states) are not printed.
- Error and compressor stop cause codes are Hitachi codes; 255 means off.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
How many BACnet points does the Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) have?
This list has 35 BACnet objects: 11 analog inputs, 1 analog output, 1 analog value, 4 binary inputs, 1 binary output, 7 binary values, 1 device, 6 multi-state inputs, 3 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) BACnet points are writable?
13 of the 35 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) BACnet documentation?
Intesis does not publish it on its own website. This list comes from IntesisBox BACnet/IP - Hitachi AC User Manual r1.1, revision r1.1 (PICS 2016-11-10), a copy hosted by Chipkin Automation Systems at https://cdn.chipkin.com/assets/uploads/2018/feb/01-01-25-53_intesisbox_hi-ac-bac-8-64_user_manual_en.pdf. Ask Intesis or its representative for the current revision.
What are the minimum BACnet points to integrate the Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)?
Start with BO 105 IUxxx_OnOff_command (Start/stop indoor unit); MO 107 IUxxx_Mode_command (Mode command); AO 111 IUxxx_Settemp_command (Setpoint command, 17-30 °C); MO 109 IUxxx_Fan_command (Fan speed command (5 = auto)); BI 104 IUxxx_OnOff_status (Run status); AI 110 IUxxx_Settemp_status (Setpoint in use); AI 119 IUxxx_InletTemperature (Return air temperature); BI 101 IUxxx_IU_Exist (Unit found on the adaptor); MI 123 IUxxx_ErrorCode (Alarm code (255 = off)); BI 0 Communication error Hitachi GW (Adaptor communication lost).
How do I enable BMS control of the Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)?
No enable point is documented. Remote-controller permissions can be locked per unit with the CentralSet BVs (BV 114-118).
How do I check these points on the real IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: IntesisBox BACnet/IP - Hitachi AC User Manual r1.1 · rev. r1.1 (PICS 2016-11-10). Object names, instances and units are reproduced as published; descriptions are our own.