VRF BACnet IP gateway (up to 8 or 64 indoor units) · BACnet points list

Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

An older IntesisBox BACnet IP server that polls one Hitachi HC-A8MB or HC-A64MB adaptor and publishes each indoor unit as a fixed block of 33 objects. HI-AC-BAC-8 handles up to 8 indoor units and HI-AC-BAC-64 up to 64. Instances are (unit number x 100) + offset, so unit 1 uses 101-133. Setup is done with the LinkBoxBACnet tool.

This page lists 35 BACnet objects for the Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Intesis’s documentation hosted by Chipkin Automation Systems, not by Intesis itself, so treat it as unofficial.

Manufacturer
Intesis
Model
IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Equipment
VRF BACnet IP gateway (up to 8 or 64 indoor units)
Equipment type
VRF & split air conditioners
BACnet objects
35 (13 writable)
Transport
BACnet IP
Firmware
4.0.0 (PICS 2016-11-10)
Default device instance
246
Also known as
HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway
Source document
IntesisBox BACnet/IP - Hitachi AC User Manual r1.1 · rev. r1.1 (PICS 2016-11-10) (unofficial copy, hosted by Chipkin Automation Systems)
Download CSV 35 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.

BMS integration notes: Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)

Integration in brief

Connect the IntesisBox to the HC-A8MB/HC-A64MB adaptor and the BACnet IP LAN, set the IP and number of indoor units in LinkBoxBACnet, then map each unit's _command and _status objects from its (unit x 100) block.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 105IUxxx_OnOff_commandStart/stop indoor unitWrite
MO 107IUxxx_Mode_commandMode commandWrite
AO 111IUxxx_Settemp_commandSetpoint command, 17-30 °CWrite
MO 109IUxxx_Fan_commandFan speed command (5 = auto)Write
BI 104IUxxx_OnOff_statusRun statusRead
AI 110IUxxx_Settemp_statusSetpoint in useRead
AI 119IUxxx_InletTemperatureReturn air temperatureRead
BI 101IUxxx_IU_ExistUnit found on the adaptorRead
MI 123IUxxx_ErrorCodeAlarm code (255 = off)Read
BI 0Communication error Hitachi GWAdaptor communication lostRead

Enable & remote start

No enable point is documented. Remote-controller permissions can be locked per unit with the CentralSet BVs (BV 114-118).

Network setup

Watch out for

Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

35 of 35 shown
Type
Other
Access
Show
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) BACnet Points List
DescriptionStates
DEV246HI-AC BACnet GatewayGateway device object (instance configurable)Read
BImin0Communication error Hitachi GWCommunication error with the HC-A8/64MB adaptorRead0=No Error, 1=Error
BImin101IUxxx_IU_ExistIndoor unit present on the adaptorRead0=Not Exist, 1=Exist
AI102IUxxx_System_AddressH-Link refrigerant system address (0-63)Read
AI103IUxxx_Unit_AddressIndoor unit address (0-63)Read
BImin104IUxxx_OnOff_statusRun statusRead0=Stop, 1=Run
BOmin105IUxxx_OnOff_commandStart/stop commandWrite0=Stop, 1=Run
MI106IUxxx_Mode_statusOperating modeRead1=Cool, 2=Dry, 3=Fan, 4=Heat, 5=Auto
MOmin107IUxxx_Mode_commandMode commandWrite1=Cool, 2=Dry, 3=Fan, 4=Heat, 5=Auto
MI108IUxxx_Fan_statusFan speedRead1=Low, 2=Medium, 3=High, 4=High2, 5=Auto
MOmin109IUxxx_Fan_commandFan speed commandWrite1=Low, 2=Medium, 3=High, 4=High2, 5=Auto
AImin110IUxxx_Settemp_statusSetpoint in use, 17-30 °C°CRead
AOmin111IUxxx_Settemp_commandSetpoint command, 17-30 °C°CWrite
MI112IUxxx_Louver_statusLouver position (8 states)Read
MO113IUxxx_Louver_commandLouver position command (8 states)Write
BV114IUxxx_CentralSet_OnOffLock on/off at the remote controllerWrite0=On/Off from RC allowed, 1=On/Off from RC not allowed
BV115IUxxx_CentralSet_ModeLock mode change at the remote controllerWrite0=Mode change from RC allowed, 1=Mode change from RC not allowed
BV116IUxxx_CentralSet_SetTLock setpoint change at the remote controllerWrite0=Set Point Temp change from RC allowed, 1=Set Point Temp change from RC not allowed
BV117IUxxx_CentralSet_FanLock fan speed change at the remote controllerWrite0=Fan Speed change from RC allowed, 1=Fan Speed change from RC not allowed
BV118IUxxx_CentralSet_LouverLock louver change at the remote controllerWrite0=Louver Position change from RC allowed, 1=Louver Position change from RC not allowed
AImin119IUxxx_InletTemperatureInlet (return) air temperature°CRead
AI120IUxxx_OutletTemperatureOutlet (discharge) air temperature°CRead
AI121IUxxx_GasPipeTempGas pipe temperature°CRead
AI122IUxxx_LiquidPipeTempLiquid pipe temperature°CRead
MImin123IUxxx_ErrorCodeAlarm code (1-255)Read255=Off
MI124IUxxx_CompStopCauseCompressor stop cause code (1-255)Read255=Operation Off, Power Off
AI125IUxxx_ExpansionValveOpeningExpansion valve opening, 0-100Read
MI126IUxxx_OperationCondOperating conditionRead1=Off, 2=Thermo Off, 3=Thermo On, 4=Alarm
BI127IUxxx_DefrostDefrost activeRead
AI128IUxxx_AmbTempAmbient temperature°CRead
AI129IUxxx_RCSwitchTempRemote controller sensor temperature°CRead
BV130IUxxx_RCSwitchConfiguration_MaRemote controller master/slave settingWrite0=Master, 1=Slave
BV131IUxxx_RCSwitchConfiguration_RCRemote controller present settingWrite0=With RCS, 1=Without RCS
AV132IUxxx_RCSwitchGroupRemote controller group (0 = no group)Write
AI133IUxxx_RemoteSensorTempRemote sensor temperature°CRead
Object ID lookup: Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)

How many BACnet points does the Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) have?

This list has 35 BACnet objects: 11 analog inputs, 1 analog output, 1 analog value, 4 binary inputs, 1 binary output, 7 binary values, 1 device, 6 multi-state inputs, 3 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) BACnet points are writable?

13 of the 35 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor) BACnet documentation?

Intesis does not publish it on its own website. This list comes from IntesisBox BACnet/IP - Hitachi AC User Manual r1.1, revision r1.1 (PICS 2016-11-10), a copy hosted by Chipkin Automation Systems at https://cdn.chipkin.com/assets/uploads/2018/feb/01-01-25-53_intesisbox_hi-ac-bac-8-64_user_manual_en.pdf. Ask Intesis or its representative for the current revision.

What are the minimum BACnet points to integrate the Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)?

Start with BO 105 IUxxx_OnOff_command (Start/stop indoor unit); MO 107 IUxxx_Mode_command (Mode command); AO 111 IUxxx_Settemp_command (Setpoint command, 17-30 °C); MO 109 IUxxx_Fan_command (Fan speed command (5 = auto)); BI 104 IUxxx_OnOff_status (Run status); AI 110 IUxxx_Settemp_status (Setpoint in use); AI 119 IUxxx_InletTemperature (Return air temperature); BI 101 IUxxx_IU_Exist (Unit found on the adaptor); MI 123 IUxxx_ErrorCode (Alarm code (255 = off)); BI 0 Communication error Hitachi GW (Adaptor communication lost).

How do I enable BMS control of the Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)?

No enable point is documented. Remote-controller permissions can be locked per unit with the CentralSet BVs (BV 114-118).

How do I check these points on the real IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: IntesisBox BACnet/IP - Hitachi AC User Manual r1.1 · rev. r1.1 (PICS 2016-11-10). Object names, instances and units are reproduced as published; descriptions are our own.