- IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Air-to-water heat pump BACnet gateway · BACnet points list
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP) BACnet points list
Updated 4 November 2026
Intesis interface for one Daikin Altherma 3 air-to-water heat pump on the P1/P2 bus, speaking BACnet MS/TP or Modbus RTU (Modbus is the factory setting). It exposes 100 objects for zone on/off and heat/cool mode, zone 1 and room 1 setpoints with their limits, DHW tank control, water and refrigerant temperatures, compressor and pump run times, flow and pressure.
This page lists 100 BACnet objects for the Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP) — 28 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
- Equipment
- Air-to-water heat pump BACnet gateway
- Equipment type
- Heat pumps
- BACnet objects
- 100 (28 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 246000
- Also known as
- IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma
- Brands covered
- Daikin
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Connect the gateway to the Altherma P1/P2 bus and the EIA-485 network, then set SW1 position 5 OFF: the gateway ships set for Modbus RTU. Start/stop space heating or cooling with ZonesOnOff_command, pick heat or cool with ZonesMode_command, and write zone 1, room 1 and DHW setpoints to their _command objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 5 | ZonesOnOff_command | Start/stop space heating/cooling | Command |
| MO 0 | ZonesMode_command | Heat or cool | Command |
| BO 15 | DHWOnOff_command | Domestic hot water on/off | Command |
| AO 3 | Zone1TempSetpoint_command | Zone 1 setpoint from the BMS | Command |
| AO 24 | DHWTempSetpoint_command | DHW tank setpoint | Command |
| BI 7 | ZonesOnOff_status | Confirms space heating/cooling is on | Read |
| AI 74 | TempOutletWaterRef_status | Leaving water temperature | Read |
| BI 1 | ErrorFlag_status | Unit alarm | Read |
| AI 2 | ErrorCode_status | Which fault is active | Read |
Enable & remote start
SW1 position 5 must be OFF for BACnet MS/TP (ON = Modbus RTU, the default). BO 3 RemoteControlLock_command = 1 lets only the BMS control the unit; commands from the Daikin remote are then ignored.
Sensors & values from the BMS
Write a BMS room temperature to AO 15 Room1TempBACnetRoomThermAmbientRef_command. Once a valid value is written, the gateway's Virtual Temperature function uses it to offset the setpoint so the living area reaches the requested temperature.
Network setup
- SW1 P5: OFF = BACnet MS/TP, ON = Modbus RTU (default); SW1 P6-P8 baud rate, autobaud by default.
- MS/TP MAC address on SW2 P1-P7; SW2 P8 selects °C (default) or °F.
- Default device instance 246000; in automatic mode it is 246000 + the MAC address. Writing Object_Identifier switches to manual addressing until a factory reset.
- SW3 enables the 120-ohm terminator and bus biasing.
- DIP switch changes take effect after a reboot.
Watch out for
- Write the _command object and read the matching _status object; they have different object types and instance numbers.
- Custom setpoint limits cannot go past the unit's own limits (the Unit...Limit objects); the Applied...Limit objects show the range in force.
- Several Altherma units on one gateway act as one unit.
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | SerialNumber | Gateway serial number | Read | ||
| AI | 86 | DIP_SW_1_status | DIP SW1 (status) | Read | ||
| AI | 87 | DIP_SW_2_status | DIP SW2 (status) | Read | ||
| BImin | 1 | ErrorFlag_status | Error flag (status) | Read | 0=No error, 1=Error | |
| AImin | 2 | ErrorCode_status | Error code (status) | Read | 0=No error, other=error code | |
| AI | 3 | ErrorSubCode_status | Error sub code (status) | Read | 0=No error, other=error code | |
| AO | 1 | OperatingTimeCountSec_command | Operating time count seconds (command) | s | Command | |
| AI | 7 | OperatingTimeCountSec_status | Operating time count seconds (status) | s | Read | |
| AO | 2 | OperatingTimeCountHour_command | Operating time count hours (command) | h | Command | |
| AI | 8 | OperatingTimeCountHour_status | Operating time count hours (status) | h | Read | |
| BO | 3 | RemoteControlLock_command | Remote control lock (command) | Command | 0=Unlocked, 1=Locked | |
| BI | 4 | RemoteControlLock_status | Remote control lock (status) | Read | 0=Unlocked, 1=Locked | |
| BI | 6 | Operation_status | Operation (status) | Read | 0=Not operating, 1=Operating | |
| BOmin | 5 | ZonesOnOff_command | Zones on/off (command) | Command | 0=Off, 1=On | |
| BImin | 7 | ZonesOnOff_status | Zones on/off (status) | Read | 0=Off, 1=On | |
| BI | 8 | ZonesOperation_status | Zones operation (status) | Read | 0=Not operating, 1=Operating | |
| MOmin | 0 | ZonesMode_command | Zones mode (command) | Command | 1=Heat, 2=Cool | |
| MI | 0 | ZonesMode_status | Zones mode (status) | Read | 1=Heat, 2=Cool | |
| MI | 2 | Zone1ControlType_status | Zone 1 control type (status) | Read | 1=Outlet Water Temperature, 2=External Ambient Temperature, 3=Room Thermostat Ambient Temperature | |
| MO | 2 | Zone1SetpointMode_command | Zone 1 setpoint mode (command) | Command | 1=Fixed, 2=Weather Dependent | |
| MI | 3 | Zone1SetpointMode_status | Zone 1 setpoint mode (status) | Read | 1=Fixed, 2=Weather Dependent | |
| BI | 12 | Zone1SetpointModeType_status | Zone 1 setpoint mode type (status) | Read | 0=Weather- dependent Heating, Fixed Cooling, 1=Weather- dependent Heating and Cooling | |
| AOmin | 3 | Zone1TempSetpoint_command | Zone 1 temperature setpoint (command) | °C | Command | |
| AI | 9 | Zone1TempSetpoint_status | Zone 1 temperature setpoint (status) | °C | Read | |
| AO | 4 | Zone1TempSetpointLowCustomerLimitHeat_command | Zone 1 temperature setpoint lower customer limit heat (command) | °C | Command | |
| AI | 10 | Zone1TempSetpointLowCustomerLimitHeat_status | Zone 1 temperature setpoint lower customer limit heat (status) | °C | Read | |
| AO | 5 | Zone1TempSetpointUpCustomerLimitHeat_command | Zone 1 temperature setpoint upper customer limit heat (command) | °C | Command | |
| AI | 11 | Zone1TempSetpointUpCustomerLimitHeat_status | Zone 1 temperature setpoint upper customer limit heat (status) | °C | Read | |
| AO | 6 | Zone1TempSetpointLowCustomerLimitCool_command | Zone 1 temperature setpoint lower customer limit cool (command) | °C | Command | |
| AI | 12 | Zone1TempSetpointLowCustomerLimitCool_status | Zone 1 temperature setpoint lower customer limit cool (status) | °C | Read | |
| AO | 7 | Zone1TempSetpointUpCustomerLimitCool_command | Zone 1 temperature setpoint upper customer limit cool (command) | °C | Command | |
| AI | 13 | Zone1TempSetpointUpCustomerLimitCool_status | Zone 1 temperature setpoint upper customer limit cool (status) | °C | Read | |
| AI | 14 | Zone1TempSetpointUnitLowLimitHeat_status | Zone 1 temperature setpoint unit lower limit heat (status) | °C | Read | |
| AI | 15 | Zone1TempSetpointUnitUpLimitHeat_status | Zone 1 temperature setpoint unit upper limit heat (status) | °C | Read | |
| AI | 16 | Zone1TempSetpointUnitLowLimitCool_status | Zone 1 temperature setpoint unit lower limit cool (status) | °C | Read | |
| AI | 17 | Zone1TempSetpointUnitUpLimitCool_status | Zone 1 temperature setpoint unit upper limit cool (status) | °C | Read | |
| AI | 18 | Zone1TempSetpointAppliedLowLimitHeat_status | Zone 1 temperature setpoint applied lower limit heat (status) | °C | Read | |
| AI | 19 | Zone1TempSetpointAppliedUpLimitHeat_status | Zone 1 temperature setpoint applied upper limit heat (status) | °C | Read | |
| AI | 20 | Zone1TempSetpointAppliedLowLimitCool_status | Zone 1 temperature setpoint applied lower limit cool (status) | °C | Read | |
| AI | 21 | Zone1TempSetpointAppliedUpLimitCool_status | Zone 1 temperature setpoint applied upper limit cool (status) | °C | Read | |
| BO | 9 | Zone1ScheduledMode_command | Zone 1 scheduled mode (command) | Command | 0=Off, 1=On | |
| BI | 14 | Zone1ScheduledMode_status | Zone 1 scheduled mode (status) | Read | 0=Off, 1=On | |
| AO | 10 | Room1TempSetpoint_command | Room 1 temperature setpoint (command) | °C | Command | |
| AI | 27 | Room1TempSetpoint_status | Room 1 temperature setpoint (status) | °C | Read | |
| AO | 11 | Room1TempSetpointCustomLowLimitHeat_command | Room 1 temperature setpoint custom lower limit heat (command) | °C | Command | |
| AI | 28 | Room1TempSetpointCustomLowLimitHeat_status | Room 1 temperature setpoint custom lower limit heat (status) | °C | Read | |
| AO | 12 | Room1TempSetpointCustomUpLimitHeat_command | Room 1 temperature setpoint custom upper limit heat (command) | °C | Command | |
| AI | 29 | Room1TempSetpointCustomUpLimitHeat_status | Room 1 temperature setpoint custom upper limit heat (status) | °C | Read | |
| AO | 13 | Room1TempSetpointCustomLowLimitCool_command | Room 1 temperature setpoint custom lower limit cool (command) | °C | Command | |
| AI | 30 | Room1TempSetpointCustomLowLimitCool_status | Room 1 temperature setpoint custom lower limit cool (status) | °C | Read | |
| AO | 14 | Room1TempSetpointCustomUpLimitCool_command | Room 1 temperature setpoint custom upper limit cool (command) | °C | Command | |
| AI | 31 | Room1TempSetpointCustomUpLimitCool_status | Room 1 temperature setpoint custom upper limit cool (status) | °C | Read | |
| AI | 32 | Room1TempSetpointUnitLowLimitHeat_status | Room 1 temperature setpoint unit lower limit heat (status) | °C | Read | |
| AI | 33 | Room1TempSetpointUnitUpLimitHeat_status | Room 1 temperature setpoint unit upper limit heat (status) | °C | Read | |
| AI | 34 | Room1TempSetpointUnitLowLimitCool_status | Room 1 temperature setpoint unit lower limit cool (status) | °C | Read | |
| AI | 35 | Room1TempSetpointUnitUpLimitCool_status | Room 1 temperature setpoint unit upper limit cool (status) | °C | Read | |
| AI | 36 | Room1TempSetpointAppliedLowLimitHeat_status | Room 1 temperature setpoint applied lower limit heat (status) | °C | Read | |
| AI | 37 | Room1TempSetpointAppliedUpLimitHeat_status | Room 1 temperature setpoint applied upper limit heat (status) | °C | Read | |
| AI | 38 | Room1TempSetpointAppliedLowLimitCool_status | Room 1 temperature setpoint applied lower limit cool (status) | °C | Read | |
| AI | 39 | Room1TempSetpointAppliedUpLimitCool_status | Room 1 temperature setpoint applied upper limit cool (status) | °C | Read | |
| AO | 15 | Room1TempBACnetRoomThermAmbientRef_command | Room 1 temperature BMS room sensor ambient reading (command) | °C | Command | |
| AI | 41 | Room1TempBACnetRoomThermAmbientRef_status | Room 1 temperature BMS room sensor ambient reading (status) | °C | Read | |
| BO | 10 | Room1AntifrostMode_command | Room 1 antifrost mode (command) | Command | 0=Off, 1=On | |
| BI | 15 | Room1Antifrost_status | Room 1 antifrost (status) | Read | 0=0ff, 1=On | |
| AO | 16 | Room1AntifrostRoomSetpointTempHeat_command | Room 1 antifrost room setpoint temperature heat (command) | °C | Command | |
| AI | 42 | Room1AntifrostRoomSetpointTempHeat_status | Room 1 antifrost room setpoint temperature heat (status) | °C | Read | |
| BOmin | 15 | DHWOnOff_command | DHW on/off (command) | Command | 0=Off, 1=On | |
| BI | 22 | DHWOnOff_status | DHW on/off (status) | Read | 0=Off, 1=On | |
| BI | 23 | DHWOperation_status | DHW operation (status) | Read | 0=Not Operating, 1=Operating | |
| BO | 16 | DHWSetpointMode_command | DHW setpoint mode (command) | Command | 0=Fixed, 1=Weather Dependent | |
| BI | 24 | DHWSetpointMode_status | DHW setpoint mode (status) | Read | 0=Fixed, 1=Weather Dependent | |
| AOmin | 24 | DHWTempSetpoint_command | DHW temperature setpoint (command) | °C | Command | |
| AI | 61 | DHWTempSetpoint_status | DHW temperature setpoint (status) | °C | Read | |
| AO | 25 | DHWTempSetpointCustomLowLimit_command | DHW temperature setpoint custom lower limit (command) | °C | Command | |
| AI | 62 | DHWTempSetpointCustomLowLimit_status | DHW temperature setpoint custom lower limit (status) | °C | Read | |
| AO | 26 | DHWTempSetpointCustomUpLimit_command | DHW temperature setpoint custom upper limit (command) | °C | Command | |
| AI | 63 | DHWTempSetpointCustomUpLimit_status | DHW temperature setpoint custom upper limit (status) | °C | Read | |
| AI | 64 | DHWTempSetpointTankLowLimit_status | DHW temperature setpoint tank lower limit (status) | °C | Read | |
| AI | 65 | DHWTempSetpointTankUpLimit_status | DHW temperature setpoint tank upper limit (status) | °C | Read | |
| AI | 66 | DHWTempSetpointAppliedLowLimit_status | DHW temperature setpoint applied lower limit (status) | °C | Read | |
| AI | 67 | DHWTempSetpointappliedUpLimit_status | DHW temperature setpoint applied upper limit (status) | °C | Read | |
| AI | 68 | DHWTempTankRef_status | DHW temperature tank reading (status) | °C | Read | |
| BI | 28 | DHWScheduledMode_status | DHW scheduled mode (status) | Read | 0=Off, 1=On | |
| BO | 21 | DHWPowerfulOperation_command | DHW powerful operation (command) | Command | 0=Off, 1=On | |
| BI | 29 | DHWPowerfulOperation_status | DHW powerful operation (status) | Read | 0=Off, 1=On | |
| BI | 30 | DHWDisinfectionMode_status | DHW disinfection mode (status) | Read | 0=Off, 1=On | |
| AI | 72 | TempA2WUnitOutdoorAmbientRef_status | Temperature heatpump unit outdoor ambient reading (status) | °C | Read | |
| AI | 73 | TempRefrigerantRef_status | Temperature refrigerant reading (status) | °C | Read | |
| AImin | 74 | TempOutletWaterRef_status | Temperature outlet water reading (status) | °C | Read | |
| AI | 75 | TempOutletWaterRefPlateHeatExchanger_status | Temperature outlet water reading plate heat exchanger (status) | °C | Read | |
| AI | 76 | TempInletWaterRef_status | Temperature inlet water reading (status) | °C | Read | |
| BI | 32 | QuietModeLowNoiseOperation_status | Quiet mode lower noise operation (status) | Read | 0=Off, 1=On | |
| BI | 40 | CompressorOperation_status | Compressor operation (status) | Read | 0=Off, 1=On | |
| AO | 30 | CompressorOperatingTime_command | Compressor operating time (command) | h | Command | |
| AI | 77 | CompressorOperatingTime_status | Compressor operating time (status) | h | Read | |
| BI | 41 | CirculationPumpOperation_status | Circulation pump operation (status) | Read | 0=Off, 1=On | |
| AO | 31 | CirculationPumpOperatingTime_command | Circulation pump operating time (command) | h | Command | |
| AI | 78 | CirculationPumpOperatingTime_status | Circulation pump operating time (status) | h | Read | |
| AI | 79 | WaterFlowRate_status | Water flow rate (status) | l/h | Read | |
| AI | 80 | WaterPressureDHW_status | Water pressure DHW (status) | Pa | Read |
No points match these filters.
Object ID lookup: Intesis Daikin Altherma 3 Gateway IN485DAI001A000 point IDs by name
AI0SerialNumberAI86DIP_SW_1_statusAI87DIP_SW_2_statusBI1ErrorFlag_statusAI2ErrorCode_statusAI3ErrorSubCode_statusAO1OperatingTimeCountSec_commandAI7OperatingTimeCountSec_statusAO2OperatingTimeCountHour_commandAI8OperatingTimeCountHour_statusBO3RemoteControlLock_commandBI4RemoteControlLock_statusBI6Operation_statusBO5ZonesOnOff_commandBI7ZonesOnOff_statusBI8ZonesOperation_statusMO0ZonesMode_commandMI0ZonesMode_statusMI2Zone1ControlType_statusMO2Zone1SetpointMode_commandMI3Zone1SetpointMode_statusBI12Zone1SetpointModeType_statusAO3Zone1TempSetpoint_commandAI9Zone1TempSetpoint_statusAO4Zone1TempSetpointLowCustomerLimitHeat_commandAI10Zone1TempSetpointLowCustomerLimitHeat_statusAO5Zone1TempSetpointUpCustomerLimitHeat_commandAI11Zone1TempSetpointUpCustomerLimitHeat_statusAO6Zone1TempSetpointLowCustomerLimitCool_commandAI12Zone1TempSetpointLowCustomerLimitCool_statusAO7Zone1TempSetpointUpCustomerLimitCool_commandAI13Zone1TempSetpointUpCustomerLimitCool_statusAI14Zone1TempSetpointUnitLowLimitHeat_statusAI15Zone1TempSetpointUnitUpLimitHeat_statusAI16Zone1TempSetpointUnitLowLimitCool_statusAI17Zone1TempSetpointUnitUpLimitCool_statusAI18Zone1TempSetpointAppliedLowLimitHeat_statusAI19Zone1TempSetpointAppliedUpLimitHeat_statusAI20Zone1TempSetpointAppliedLowLimitCool_statusAI21Zone1TempSetpointAppliedUpLimitCool_statusBO9Zone1ScheduledMode_commandBI14Zone1ScheduledMode_statusAO10Room1TempSetpoint_commandAI27Room1TempSetpoint_statusAO11Room1TempSetpointCustomLowLimitHeat_commandAI28Room1TempSetpointCustomLowLimitHeat_statusAO12Room1TempSetpointCustomUpLimitHeat_commandAI29Room1TempSetpointCustomUpLimitHeat_statusAO13Room1TempSetpointCustomLowLimitCool_commandAI30Room1TempSetpointCustomLowLimitCool_statusAO14Room1TempSetpointCustomUpLimitCool_commandAI31Room1TempSetpointCustomUpLimitCool_statusAI32Room1TempSetpointUnitLowLimitHeat_statusAI33Room1TempSetpointUnitUpLimitHeat_statusAI34Room1TempSetpointUnitLowLimitCool_statusAI35Room1TempSetpointUnitUpLimitCool_statusAI36Room1TempSetpointAppliedLowLimitHeat_statusAI37Room1TempSetpointAppliedUpLimitHeat_statusAI38Room1TempSetpointAppliedLowLimitCool_statusAI39Room1TempSetpointAppliedUpLimitCool_statusAO15Room1TempBACnetRoomThermAmbientRef_commandAI41Room1TempBACnetRoomThermAmbientRef_statusBO10Room1AntifrostMode_commandBI15Room1Antifrost_statusAO16Room1AntifrostRoomSetpointTempHeat_commandAI42Room1AntifrostRoomSetpointTempHeat_statusBO15DHWOnOff_commandBI22DHWOnOff_statusBI23DHWOperation_statusBO16DHWSetpointMode_commandBI24DHWSetpointMode_statusAO24DHWTempSetpoint_commandAI61DHWTempSetpoint_statusAO25DHWTempSetpointCustomLowLimit_commandAI62DHWTempSetpointCustomLowLimit_statusAO26DHWTempSetpointCustomUpLimit_commandAI63DHWTempSetpointCustomUpLimit_statusAI64DHWTempSetpointTankLowLimit_statusAI65DHWTempSetpointTankUpLimit_statusAI66DHWTempSetpointAppliedLowLimit_statusAI67DHWTempSetpointappliedUpLimit_statusAI68DHWTempTankRef_statusBI28DHWScheduledMode_statusBO21DHWPowerfulOperation_commandBI29DHWPowerfulOperation_statusBI30DHWDisinfectionMode_statusAI72TempA2WUnitOutdoorAmbientRef_statusAI73TempRefrigerantRef_statusAI74TempOutletWaterRef_statusAI75TempOutletWaterRefPlateHeatExchanger_statusAI76TempInletWaterRef_statusBI32QuietModeLowNoiseOperation_statusBI40CompressorOperation_statusAO30CompressorOperatingTime_commandAI77CompressorOperatingTime_statusBI41CirculationPumpOperation_statusAO31CirculationPumpOperatingTime_commandAI78CirculationPumpOperatingTime_statusAI79WaterFlowRate_statusAI80WaterPressureDHW_status
Integration notes
- The manual's object table has no read/write column. Access is inferred: AO/BO/MO command objects as commandable, inputs as read-only.
- Footnote numbers printed after some object names in the table (for example DIP_SW_1_status2) are not part of the name and were removed.
- DHWTempSetpointappliedUpLimit_status is printed with a lower-case 'a'; kept as printed.
- Room1Antifrost_status lists its states as '0: 0ff, 1: On' in the manual (typo for Off).
- Temperatures follow the °C/°F setting on DIP switch SW2 position 8.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
How many BACnet points does the Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP) have?
This list has 100 BACnet objects: 52 analog inputs, 19 analog outputs, 17 binary inputs, 7 binary outputs, 3 multi-state inputs, 2 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP) BACnet points are writable?
28 of the 100 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP) BACnet documentation?
The source is IN485DAI001A000 User Manual - Daikin Altherma 3 Air-to-water Heat Pumps to BACnet MS/TP and Modbus RTU, revision 2025-07-18 v1.0.2, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in485dai001a000.pdf.
What are the minimum BACnet points to integrate the Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)?
Start with BO 5 ZonesOnOff_command (Start/stop space heating/cooling); MO 0 ZonesMode_command (Heat or cool); BO 15 DHWOnOff_command (Domestic hot water on/off); AO 3 Zone1TempSetpoint_command (Zone 1 setpoint from the BMS); AO 24 DHWTempSetpoint_command (DHW tank setpoint); BI 7 ZonesOnOff_status (Confirms space heating/cooling is on); AI 74 TempOutletWaterRef_status (Leaving water temperature); BI 1 ErrorFlag_status (Unit alarm); AI 2 ErrorCode_status (Which fault is active).
How do I enable BMS control of the Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)?
SW1 position 5 must be OFF for BACnet MS/TP (ON = Modbus RTU, the default). BO 3 RemoteControlLock_command = 1 lets only the BMS control the unit; commands from the Daikin remote are then ignored.
Can the BMS supply sensor values to the Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)?
Write a BMS room temperature to AO 15 Room1TempBACnetRoomThermAmbientRef_command. Once a valid value is written, the gateway's Virtual Temperature function uses it to offset the setpoint so the living area reaches the requested temperature.
How do I check these points on the real IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: IN485DAI001A000 User Manual - Daikin Altherma 3 Air-to-water Heat Pumps to BACnet MS/TP and Modbus RTU · rev. 2025-07-18 v1.0.2. Object names, instances and units are reproduced as published; descriptions are our own.