Air conditioner BACnet gateway (1 indoor unit) · BACnet points list

Intesis INBACTOS001R100 (Toshiba gateway) BACnet points list

Updated 28 October 2026

Short answer

A one-unit Intesis BACnet MS/TP interface on a Toshiba indoor unit's A/B remote-controller bus. It exposes 42 fixed objects: the standard on/off, mode, setpoint, fan and louvre set, errors, filter, occupancy logic, mode-restriction status and per-function remote-controller lock objects.

This page lists 42 BACnet objects for the Intesis INBACTOS001R100 (Toshiba gateway) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
INBACTOS001R100 (Toshiba gateway)
Equipment
Air conditioner BACnet gateway (1 indoor unit)
Equipment type
Other equipment
BACnet objects
42 (16 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
246000
Also known as
Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP
Source document
Intesis BACnet MSTP - Toshiba AC User Manual (INBACTOS001R100) · TO-RC-BAC-1L (legacy code) · rev. 9/2024 v1.2
Download CSV 42 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Intesis INBACTOS001R100 (Toshiba gateway)

Integration in brief

Connect the gateway to the indoor unit (A/B remote-controller bus, no polarity), set the BACnet network on its DIP switches, then write the _command objects (on/off, mode, setpoint, fan) and read back the matching _status objects. One gateway serves one indoor unit (or one remote-controller group), so give each gateway its own MAC address and device instance.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0OnOff_commandStart/stop the indoor unitCommand
MO 0Mode_commandHeat/cool/fan/dry/auto selectionCommand
AO 0SetPoint_commandTemperature setpoint from the BMSCommand
MO 1FanSpeed_commandFan speed selectionCommand
BI 0OnOff_statusConfirm the unit is runningRead
AI 0SetPoint_statusSetpoint the unit is really usingRead
AI 1RoomTemperature_statusRoom/return temperature for trendingRead
BI 1ErrorActiveUnit alarmRead
AI 2ErrorCodeWhich fault is activeRead

Enable & remote start

No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; the LockRemoteControl..._command objects (BO 6-11) lock it per function.

Sensors & values from the BMS

Write the BMS room temperature to AO 1 RoomTemperature_command and keep using AO 0 SetPoint_command for the user setpoint. The gateway then runs its Virtual Temperature function: it offsets the setpoint it sends to the unit by the difference between the BMS temperature and the unit's own return temperature, so AI 0 SetPoint_status can differ from what you wrote. Until a first value is written, AO 1 shows Reliability = UNRELIABLE_OTHER and the function stays off.

Network setup

Watch out for

Intesis INBACTOS001R100 (Toshiba gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

42 of 42 shown
Type
Access
Show
Intesis INBACTOS001R100 (Toshiba gateway) BACnet Points List
DescriptionStates
BImin0OnOff_statusUnit on/off statusRead0=Off, 1=On
BOmin0OnOff_commandStart/stop command for the indoor unitCommand0=Off, 1=On
MI0Mode_statusOperating mode currently activeRead1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool
MOmin0Mode_commandOperating mode commandCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin0SetPoint_statusSetpoint the indoor unit is actually using°CRead
AOmin0SetPoint_commandTemperature setpoint command from the BMS°CCommand
MI1FanSpeed_statusCurrent fan speedRead1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5
MOmin1FanSpeed_commandFan speed commandCommand1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5
MI2AirDirectionUD_statusVertical (up/down) vane positionRead1=Stop, 2=Up, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Down, 7=Swing
MO2AirDirectionUD_commandVertical (up/down) vane commandCommand1=Stop, 2=Swing, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Down, 7=Swing
AImin1RoomTemperature_statusRoom temperature used by the indoor unit°CRead
AO1RoomTemperature_commandRoom temperature written by the BMS (external sensor)°CCommand
AImin2ErrorCodeActive error code as a numberRead
MI4ErrorCodeMActive error code as a multistate valueRead
BImin1ErrorActiveAn error is active on the indoor unitRead0=No, 1=Error
AI4ErrorAddressAddress of the indoor unit reporting the errorRead
AV0OnTimeCounterAccumulated run time of the unithRead
BI6FilterSignFilter-clean indicationRead0=No, 1=Yes
BO4FilterResetResets the filter signCommand0=Normal, 1=Reset
MV0OccupancyOccupancy input for the built-in occupancy logicWrite1=Occupied, 2=Unoccupied, 3=Disabled
AV1OccupiedCoolSetPointCooling setpoint used while occupied°CRead
AV2OccupiedHeatSetPointHeating setpoint used while occupied°CRead
AV3UnoccupiedCoolSetPointCooling setpoint used while unoccupied°CRead
AV4UnoccupiedHeatSetPointHeating setpoint used while unoccupied°CRead
BV0OccupancyContinuousCheckRe-run occupancy logic on every temperature changeWrite0=Disabled, 1=Enabled
BV1UnoccupiedDeadbandActionOff or stay on when unoccupied inside the deadbandWrite0=Off, 1=CurrentMode
MI7RuntimeModeRestrictionOperating mode restriction in forceRead1=None, 2=Auto, 3=Heat, 4=Heat, Auto, 5=Cool, Dry, 6=Cool, Dry, Auto, 7=Cool, Dry, Heat, Auto
BI8LockRemoteControlAll_statusRemote controller lock of all functions (status)Read0=Unlocked, 1=Locked
BO6LockRemoteControlAll_commandRemote controller lock of all functions (command)Command0=Unlocked, 1=Locked
BI9LockRemoteControlOnOff_statusRemote controller lock of on/off (status)Read0=Unlocked, 1=Locked
BO7LockRemoteControlOnOff_commandRemote controller lock of on/off (command)Command0=Unlocked, 1=Locked
BI10LockRemoteControlMode_statusRemote controller lock of mode (status)Read0=Unlocked, 1=Locked
BO8LockRemoteControlMode_commandRemote controller lock of mode (command)Command0=Unlocked, 1=Locked
BI11LockRemoteControlSetPoint_statusRemote controller lock of setpoint (status)Read0=Unlocked, 1=Locked
BO9LockRemoteControlSetPoint_commandRemote controller lock of setpoint (command)Command0=Unlocked, 1=Locked
BI12LockRemoteControlFanSpeed_statusRemote controller lock of fan speed (status)Read0=Unlocked, 1=Locked
BO10LockRemoteControlFanSpeed_commandRemote controller lock of fan speed (command)Command0=Unlocked, 1=Locked
BI13LockRemoteControlVanesUD_statusRemote controller lock of up/down vanes (status)Read0=Unlocked, 1=Locked
BO11LockRemoteControlVanesUD_commandRemote controller lock of up/down vanes (command)Command0=Unlocked, 1=Locked
AI9DIP_SW_S1_statusDIP switch SW1 position (decimal), read at bootRead
AI10DIP_SW_S2_statusDIP switch SW2 position (decimal), read at bootRead
AI11SerialNumberGateway serial numberRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACTOS001R100 (Toshiba gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis INBACTOS001R100 (Toshiba gateway)

How many BACnet points does the Intesis INBACTOS001R100 (Toshiba gateway) have?

This list has 42 BACnet objects: 7 analog inputs, 2 analog outputs, 5 analog values, 9 binary inputs, 8 binary outputs, 2 binary values, 5 multi-state inputs, 3 multi-state outputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis INBACTOS001R100 (Toshiba gateway) BACnet points are writable?

16 of the 42 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis INBACTOS001R100 (Toshiba gateway) BACnet documentation?

The source is Intesis BACnet MSTP - Toshiba AC User Manual (INBACTOS001R100) (TO-RC-BAC-1L (legacy code)), revision 9/2024 v1.2, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbactos001r100.pdf.

What are the minimum BACnet points to integrate the Intesis INBACTOS001R100 (Toshiba gateway)?

Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).

How do I enable BMS control of the Intesis INBACTOS001R100 (Toshiba gateway)?

No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; the LockRemoteControl..._command objects (BO 6-11) lock it per function.

Can the BMS supply sensor values to the Intesis INBACTOS001R100 (Toshiba gateway)?

Write the BMS room temperature to AO 1 RoomTemperature_command and keep using AO 0 SetPoint_command for the user setpoint. The gateway then runs its Virtual Temperature function: it offsets the setpoint it sends to the unit by the difference between the BMS temperature and the unit's own return temperature, so AI 0 SetPoint_status can differ from what you wrote. Until a first value is written, AO 1 shows Reliability = UNRELIABLE_OTHER and the function stays off.

How do I check these points on the real INBACTOS001R100 (Toshiba gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: Intesis BACnet MSTP - Toshiba AC User Manual (INBACTOS001R100) · TO-RC-BAC-1L (legacy code) · rev. 9/2024 v1.2. Object names, instances and units are reproduced as published; descriptions are our own.