Air conditioner BACnet gateway (1 indoor unit) · BACnet points list

Intesis INBACHIT001R000 (Hitachi VRF gateway) BACnet points list

Updated 28 October 2026

Short answer

A one-unit Intesis interface that sits on a Hitachi indoor unit's remote-controller bus and serves it as a BACnet MS/TP or BACnet IP device. It exposes 31 fixed objects (on/off, mode, setpoint, fan, louvre, room temperature, errors, filter, occupancy logic and remote-controller lock). Several indoor units on the same remote-controller bus can be connected but they are all driven as one group.

This page lists 31 BACnet objects for the Intesis INBACHIT001R000 (Hitachi VRF gateway) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
INBACHIT001R000 (Hitachi VRF gateway)
Equipment
Air conditioner BACnet gateway (1 indoor unit)
Equipment type
Other equipment
BACnet objects
31 (12 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
246000
Also known as
Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000
Source document
Intesis BACnet IP/MSTP - Hitachi VRF User Manual (INBACHIT001R000) · rev. 09/2024 v1.4
Download CSV 31 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Intesis INBACHIT001R000 (Hitachi VRF gateway)

Integration in brief

Connect the gateway to the indoor unit (two-wire A/B remote-controller bus, gateway port RC2, up to 500 m), set the BACnet network on its DIP switches, then write the _command objects (on/off, mode, setpoint, fan) and read back the matching _status objects. One gateway serves one indoor unit (or one remote-controller group), so give each gateway its own MAC address and device instance.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0OnOff_commandStart/stop the indoor unitCommand
MO 0Mode_commandHeat/cool/fan/dry/auto selectionCommand
AO 0SetPoint_commandTemperature setpoint from the BMSCommand
MO 1FanSpeed_commandFan speed selectionCommand
BI 0OnOff_statusConfirm the unit is runningRead
AI 0SetPoint_statusSetpoint the unit is really usingRead
AI 1RoomTemperature_statusRoom/return temperature for trendingRead
BI 1ErrorActiveUnit alarmRead
AI 2ErrorCodeWhich fault is activeRead

Enable & remote start

No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; BV 2 LockRemoteControl locks it.

Sensors & values from the BMS

Write a BMS room temperature to AO 1 RoomTemperature_command. BI 14 VirtualTempActive shows whether the gateway is using it, and AI 17 UserSetPoint_status shows the user setpoint written from BACnet while it is active (AI 0 then shows the setpoint actually applied).

Network setup

Watch out for

Intesis INBACHIT001R000 (Hitachi VRF gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

31 of 31 shown
Type
Access
Show
Intesis INBACHIT001R000 (Hitachi VRF gateway) BACnet Points List
DescriptionStates
BImin0OnOff_statusUnit on/off statusRead0=Off, 1=On
BOmin0OnOff_commandStart/stop command for the indoor unitCommand0=Off, 1=On
MI0Mode_statusOperating mode currently activeRead1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
MOmin0Mode_commandOperating mode commandCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin0SetPoint_statusSetpoint the indoor unit is actually using°CRead
AOmin0SetPoint_commandTemperature setpoint command from the BMS°CCommand
MI1FanSpeed_statusCurrent fan speedRead1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4
MOmin1FanSpeed_commandFan speed commandCommand1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4
MI2AirDirectionUD_statusVertical (up/down) vane positionRead1=POS1, 2=POS2, 3=POS3, 4=POS4, 5=POS5, 6=POS6, 7=POS7, 8=SWING
MO2AirDirectionUD_commandVertical (up/down) vane commandCommand1=POS1, 2=POS2, 3=POS3, 4=POS4, 5=POS5, 6=POS6, 7=POS7, 8=SWING
AImin1RoomTemperature_statusRoom temperature used by the indoor unit°CRead
AO1RoomTemperature_commandRoom temperature written by the BMS (external sensor)°CCommand
AImin2ErrorCodeActive error code as a numberRead
MI4ErrorCodeMActive error code as a multistate valueRead
BImin1ErrorActiveAn error is active on the indoor unitRead0=No, 1=Error
AI4ErrorAddressAddress of the indoor unit reporting the errorRead
BO5ErrorResetResets the error indicationCommand0=Normal, 1=Reset
AV0OnTimeCounterAccumulated run time of the unithRead
BI6FilterSignFilter-clean indicationRead
BO4FilterResetResets the filter signCommand
MV0OccupancyOccupancy input for the built-in occupancy logicWrite1=Occupied, 2=Unoccupied, 3=Disabled (default)
AV1OccupiedCoolSetPointCooling setpoint used while occupied°CRead
AV2OccupiedHeatSetPointHeating setpoint used while occupied°CRead
AV3UnoccupiedCoolSetPointCooling setpoint used while unoccupied°CRead
AV4UnoccupiedHeatSetPointHeating setpoint used while unoccupied°CRead
BV0OccupancyContinuousCheckRe-run occupancy logic on every temperature changeWrite0=Disabled, 1=Enabled
BV1UnoccupiedDeadbandActionOff or stay on when unoccupied inside the deadbandWrite0=Off, 1=CurrentMode
BV2LockRemoteControlLocks or unlocks the wired remote controllerWrite0=Unlocked, 1=Locked
AI17UserSetPoint_statusUser setpoint from BACnet while virtual temperature is active°CRead
BI14VirtualTempActiveVirtual temperature function is in useRead0=No, 1=Yes
AI18FilterSignAddressAddress of the indoor unit reporting the filter signRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACHIT001R000 (Hitachi VRF gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis INBACHIT001R000 (Hitachi VRF gateway)

How many BACnet points does the Intesis INBACHIT001R000 (Hitachi VRF gateway) have?

This list has 31 BACnet objects: 6 analog inputs, 2 analog outputs, 5 analog values, 4 binary inputs, 3 binary outputs, 3 binary values, 4 multi-state inputs, 3 multi-state outputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis INBACHIT001R000 (Hitachi VRF gateway) BACnet points are writable?

12 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis INBACHIT001R000 (Hitachi VRF gateway) BACnet documentation?

The source is Intesis BACnet IP/MSTP - Hitachi VRF User Manual (INBACHIT001R000), revision 09/2024 v1.4, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbachit001r000-r1-0-en.pdf.

What are the minimum BACnet points to integrate the Intesis INBACHIT001R000 (Hitachi VRF gateway)?

Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).

How do I enable BMS control of the Intesis INBACHIT001R000 (Hitachi VRF gateway)?

No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; BV 2 LockRemoteControl locks it.

Can the BMS supply sensor values to the Intesis INBACHIT001R000 (Hitachi VRF gateway)?

Write a BMS room temperature to AO 1 RoomTemperature_command. BI 14 VirtualTempActive shows whether the gateway is using it, and AI 17 UserSetPoint_status shows the user setpoint written from BACnet while it is active (AI 0 then shows the setpoint actually applied).

How do I check these points on the real INBACHIT001R000 (Hitachi VRF gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: Intesis BACnet IP/MSTP - Hitachi VRF User Manual (INBACHIT001R000) · rev. 09/2024 v1.4. Object names, instances and units are reproduced as published; descriptions are our own.