- INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Air conditioner BACnet gateway (1 indoor unit) · BACnet points list
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) BACnet points list
Updated 28 October 2026
A one-unit Intesis BACnet MS/TP interface on the R1/R2 remote-controller bus of a Panasonic ECOi or PACi indoor unit. Besides the usual on/off, mode, setpoint, fan and louvre objects it exposes outdoor demand-limit control, mode-restriction status and separate remote-controller lock objects for each function (46 objects).
This page lists 46 BACnet objects for the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- INBACPAN001R100 (Panasonic ECOi/PACi gateway)
- Equipment
- Air conditioner BACnet gateway (1 indoor unit)
- Equipment type
- Other equipment
- BACnet objects
- 46 (18 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 246000
- Also known as
- Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L
BMS integration notes: Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Connect the gateway to the indoor unit (R1/R2 remote-controller bus), set the BACnet network on its DIP switches, then write the _command objects (on/off, mode, setpoint, fan) and read back the matching _status objects. One gateway serves one indoor unit (or one remote-controller group), so give each gateway its own MAC address and device instance.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 0 | OnOff_command | Start/stop the indoor unit | Command |
| MO 0 | Mode_command | Heat/cool/fan/dry/auto selection | Command |
| AO 0 | SetPoint_command | Temperature setpoint from the BMS | Command |
| MO 1 | FanSpeed_command | Fan speed selection | Command |
| BI 0 | OnOff_status | Confirm the unit is running | Read |
| AI 0 | SetPoint_status | Setpoint the unit is really using | Read |
| AI 1 | RoomTemperature_status | Room/return temperature for trending | Read |
| BI 1 | ErrorActive | Unit alarm | Read |
| AI 2 | ErrorCode | Which fault is active | Read |
Enable & remote start
No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; the LockRemoteControl..._command objects (BO 6-11) lock it per function.
Sensors & values from the BMS
Write the BMS room temperature to AO 1 RoomTemperature_command and keep using AO 0 SetPoint_command for the user setpoint. The gateway then runs its Virtual Temperature function: it offsets the setpoint it sends to the unit by the difference between the BMS temperature and the unit's own return temperature, so AI 0 SetPoint_status can differ from what you wrote. Until a first value is written, AO 1 shows Reliability = UNRELIABLE_OTHER and the function stays off.
Network setup
- BACnet MS/TP only; the EIA-485 port has DIP switches for the 120-ohm terminator and bus biasing.
- MS/TP MAC address 0-127 is set on DIP switches; baud rate is DIP-selectable (9600-115200) with autobaud as the default, which matches the baud rate of another MS/TP device running a fixed rate.
- Default device instance 246000. In automatic mode the instance is 246000 + the MAC address; writing Object_Identifier from BACnet switches to manual mode until a factory reset.
Watch out for
- Every function has a separate _command (AO/BO/MO, commandable) and _status (AI/BI/MI) object; write the command, read the status.
- Temperatures follow the Celsius/Fahrenheit DIP switch; the BACnet Units property changes with it.
- The Occupancy MV and its four AVs drive built-in logic that sets mode, setpoint and on/off; leave Occupancy at 3 (Disabled) unless you use it, and any manual on/off, mode or setpoint change cancels it.
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 0 | OnOff_status | Unit on/off status | Read | 0=Off, 1=On | |
| BOmin | 0 | OnOff_command | Start/stop command for the indoor unit | Command | 0=Off, 1=On | |
| MI | 0 | Mode_status | Operating mode currently active | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool | |
| MOmin | 0 | Mode_command | Operating mode command | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 0 | SetPoint_status | Setpoint the indoor unit is actually using | °C | Read | |
| AOmin | 0 | SetPoint_command | Temperature setpoint command from the BMS | °C | Command | |
| MI | 1 | FanSpeed_status | Current fan speed | Read | 1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5 | |
| MOmin | 1 | FanSpeed_command | Fan speed command | Command | 1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5 | |
| MI | 2 | AirDirectionUD_status | Vertical (up/down) vane position | Read | 1=Stop, 2=Up, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Down, 7=Swing | |
| MO | 2 | AirDirectionUD_command | Vertical (up/down) vane command | Command | 1=Stop, 2=Swing, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Down, 7=Swing | |
| AImin | 1 | RoomTemperature_status | Room temperature used by the indoor unit | °C | Read | |
| AO | 1 | RoomTemperature_command | Room temperature written by the BMS (external sensor) | °C | Command | |
| AImin | 2 | ErrorCode | Active error code as a number | Read | ||
| MI | 4 | ErrorCodeM | Active error code as a multistate value | Read | ||
| BImin | 1 | ErrorActive | An error is active on the indoor unit | Read | 0=No, 1=Error | |
| AI | 4 | ErrorAddress | Address of the indoor unit reporting the error | Read | ||
| AV | 0 | OnTimeCounter | Accumulated run time of the unit | h | Read | |
| BI | 6 | FilterSign | Filter-clean indication | Read | 0=No, 1=Yes | |
| BO | 4 | FilterReset | Resets the filter sign | Command | 0=Normal, 1=Reset | |
| MV | 0 | Occupancy | Occupancy input for the built-in occupancy logic | Write | 1=Occupied, 2=Unoccupied, 3=Disabled | |
| AV | 1 | OccupiedCoolSetPoint | Cooling setpoint used while occupied | °C | Read | |
| AV | 2 | OccupiedHeatSetPoint | Heating setpoint used while occupied | °C | Read | |
| AV | 3 | UnoccupiedCoolSetPoint | Cooling setpoint used while unoccupied | °C | Read | |
| AV | 4 | UnoccupiedHeatSetPoint | Heating setpoint used while unoccupied | °C | Read | |
| BV | 0 | OccupancyContinuousCheck | Re-run occupancy logic on every temperature change | Write | 0=Disabled, 1=Enabled | |
| BV | 1 | UnoccupiedDeadbandAction | Off or stay on when unoccupied inside the deadband | Write | 0=Off, 1=CurrentMode | |
| MI | 7 | RuntimeModeRestriction | Operating mode restriction in force | Read | 1=None, 2=Auto, 3=Heat, 4=Heat, Auto, 5=Cool, Dry, 6=Cool, Dry, Auto, 7=Cool, Dry, Heat, Auto | |
| MI | 10 | OutdooorDemandRate_status | Outdoor unit demand limit status | Read | 1=Thermo Off, 2=In range, 3=No Limit | |
| MO | 7 | OutdooorDemandRate_command | Outdoor unit demand limit command | Command | 1=Thermo Off, 2=No Limit | |
| AI | 12 | OutdooorDemandRateValue_status | Outdoor unit demand limit value | % | Read | |
| AO | 2 | OutdooorDemandRateValue_command | Outdoor unit demand limit value command | % | Command | |
| BI | 8 | LockRemoteControlAll_status | Remote controller lock of all functions (status) | Read | 0=Unlocked, 1=Locked | |
| BO | 6 | LockRemoteControlAll_command | Remote controller lock of all functions (command) | Command | 0=Unlocked, 1=Locked | |
| BI | 9 | LockRemoteControlOnOff_status | Remote controller lock of on/off (status) | Read | 0=Unlocked, 1=Locked | |
| BO | 7 | LockRemoteControlOnOff_command | Remote controller lock of on/off (command) | Command | 0=Unlocked, 1=Locked | |
| BI | 10 | LockRemoteControlMode_status | Remote controller lock of mode (status) | Read | 0=Unlocked, 1=Locked | |
| BO | 8 | LockRemoteControlMode_command | Remote controller lock of mode (command) | Command | 0=Unlocked, 1=Locked | |
| BI | 11 | LockRemoteControlSetPoint_status | Remote controller lock of setpoint (status) | Read | 0=Unlocked, 1=Locked | |
| BO | 9 | LockRemoteControlSetPoint_command | Remote controller lock of setpoint (command) | Command | 0=Unlocked, 1=Locked | |
| BI | 12 | LockRemoteControlFanSpeed_status | Remote controller lock of fan speed (status) | Read | 0=Unlocked, 1=Locked | |
| BO | 10 | LockRemoteControlFanSpeed_command | Remote controller lock of fan speed (command) | Command | 0=Unlocked, 1=Locked | |
| BI | 13 | LockRemoteControlVanesUD_status | Remote controller lock of up/down vanes (status) | Read | 0=Unlocked, 1=Locked | |
| BO | 11 | LockRemoteControlVanesUD_command | Remote controller lock of up/down vanes (command) | Command | 0=Unlocked, 1=Locked | |
| AI | 9 | DIP_SW_S1_status | DIP switch SW1 position (decimal), read at boot | Read | ||
| AI | 10 | DIP_SW_S2_status | DIP switch SW2 position (decimal), read at boot | Read | ||
| AI | 11 | SerialNumber | Gateway serial number | Read |
No points match these filters.
Integration notes
- Object names OutdooorDemandRate... are spelled with three o's in the member table; most object-detail pages print 'OutdoorDemandRate...'; check the names on site.
- AirDirectionUD_command state 2 is printed as Swing while the status object shows 2=Up; check on site.
- Units shown as °C follow the °C/°F DIP switch.
- ErrorCodeM state texts are the Panasonic error codes listed in the manual.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACPAN001R100 (Panasonic ECOi/PACi gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
How many BACnet points does the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) have?
This list has 46 BACnet objects: 8 analog inputs, 3 analog outputs, 5 analog values, 9 binary inputs, 8 binary outputs, 2 binary values, 6 multi-state inputs, 4 multi-state outputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) BACnet points are writable?
18 of the 46 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) BACnet documentation?
The source is Intesis BACnet MSTP - Panasonic AC User Manual (INBACPAN001R100) (PA-RC2-BAC-1L (legacy code)), revision 09/2024 v1.3, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacpan001r100.pdf.
What are the minimum BACnet points to integrate the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)?
Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).
How do I enable BMS control of the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)?
No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; the LockRemoteControl..._command objects (BO 6-11) lock it per function.
Can the BMS supply sensor values to the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)?
Write the BMS room temperature to AO 1 RoomTemperature_command and keep using AO 0 SetPoint_command for the user setpoint. The gateway then runs its Virtual Temperature function: it offsets the setpoint it sends to the unit by the difference between the BMS temperature and the unit's own return temperature, so AI 0 SetPoint_status can differ from what you wrote. Until a first value is written, AO 1 shows Reliability = UNRELIABLE_OTHER and the function stays off.
How do I check these points on the real INBACPAN001R100 (Panasonic ECOi/PACi gateway)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP
Source: Intesis BACnet MSTP - Panasonic AC User Manual (INBACPAN001R100) · PA-RC2-BAC-1L (legacy code) · rev. 09/2024 v1.3. Object names, instances and units are reproduced as published; descriptions are our own.