Air conditioner BACnet gateway (1 indoor unit) · BACnet points list

Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) BACnet points list

Updated 28 October 2026

Short answer

A one-unit Intesis BACnet MS/TP interface on the R1/R2 remote-controller bus of a Panasonic ECOi or PACi indoor unit. Besides the usual on/off, mode, setpoint, fan and louvre objects it exposes outdoor demand-limit control, mode-restriction status and separate remote-controller lock objects for each function (46 objects).

This page lists 46 BACnet objects for the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Equipment
Air conditioner BACnet gateway (1 indoor unit)
Equipment type
Other equipment
BACnet objects
46 (18 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
246000
Also known as
Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L
Source document
Intesis BACnet MSTP - Panasonic AC User Manual (INBACPAN001R100) · PA-RC2-BAC-1L (legacy code) · rev. 09/2024 v1.3
Download CSV 46 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)

Integration in brief

Connect the gateway to the indoor unit (R1/R2 remote-controller bus), set the BACnet network on its DIP switches, then write the _command objects (on/off, mode, setpoint, fan) and read back the matching _status objects. One gateway serves one indoor unit (or one remote-controller group), so give each gateway its own MAC address and device instance.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0OnOff_commandStart/stop the indoor unitCommand
MO 0Mode_commandHeat/cool/fan/dry/auto selectionCommand
AO 0SetPoint_commandTemperature setpoint from the BMSCommand
MO 1FanSpeed_commandFan speed selectionCommand
BI 0OnOff_statusConfirm the unit is runningRead
AI 0SetPoint_statusSetpoint the unit is really usingRead
AI 1RoomTemperature_statusRoom/return temperature for trendingRead
BI 1ErrorActiveUnit alarmRead
AI 2ErrorCodeWhich fault is activeRead

Enable & remote start

No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; the LockRemoteControl..._command objects (BO 6-11) lock it per function.

Sensors & values from the BMS

Write the BMS room temperature to AO 1 RoomTemperature_command and keep using AO 0 SetPoint_command for the user setpoint. The gateway then runs its Virtual Temperature function: it offsets the setpoint it sends to the unit by the difference between the BMS temperature and the unit's own return temperature, so AI 0 SetPoint_status can differ from what you wrote. Until a first value is written, AO 1 shows Reliability = UNRELIABLE_OTHER and the function stays off.

Network setup

Watch out for

Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

46 of 46 shown
Type
Access
Show
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) BACnet Points List
DescriptionStates
BImin0OnOff_statusUnit on/off statusRead0=Off, 1=On
BOmin0OnOff_commandStart/stop command for the indoor unitCommand0=Off, 1=On
MI0Mode_statusOperating mode currently activeRead1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool
MOmin0Mode_commandOperating mode commandCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin0SetPoint_statusSetpoint the indoor unit is actually using°CRead
AOmin0SetPoint_commandTemperature setpoint command from the BMS°CCommand
MI1FanSpeed_statusCurrent fan speedRead1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5
MOmin1FanSpeed_commandFan speed commandCommand1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5
MI2AirDirectionUD_statusVertical (up/down) vane positionRead1=Stop, 2=Up, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Down, 7=Swing
MO2AirDirectionUD_commandVertical (up/down) vane commandCommand1=Stop, 2=Swing, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Down, 7=Swing
AImin1RoomTemperature_statusRoom temperature used by the indoor unit°CRead
AO1RoomTemperature_commandRoom temperature written by the BMS (external sensor)°CCommand
AImin2ErrorCodeActive error code as a numberRead
MI4ErrorCodeMActive error code as a multistate valueRead
BImin1ErrorActiveAn error is active on the indoor unitRead0=No, 1=Error
AI4ErrorAddressAddress of the indoor unit reporting the errorRead
AV0OnTimeCounterAccumulated run time of the unithRead
BI6FilterSignFilter-clean indicationRead0=No, 1=Yes
BO4FilterResetResets the filter signCommand0=Normal, 1=Reset
MV0OccupancyOccupancy input for the built-in occupancy logicWrite1=Occupied, 2=Unoccupied, 3=Disabled
AV1OccupiedCoolSetPointCooling setpoint used while occupied°CRead
AV2OccupiedHeatSetPointHeating setpoint used while occupied°CRead
AV3UnoccupiedCoolSetPointCooling setpoint used while unoccupied°CRead
AV4UnoccupiedHeatSetPointHeating setpoint used while unoccupied°CRead
BV0OccupancyContinuousCheckRe-run occupancy logic on every temperature changeWrite0=Disabled, 1=Enabled
BV1UnoccupiedDeadbandActionOff or stay on when unoccupied inside the deadbandWrite0=Off, 1=CurrentMode
MI7RuntimeModeRestrictionOperating mode restriction in forceRead1=None, 2=Auto, 3=Heat, 4=Heat, Auto, 5=Cool, Dry, 6=Cool, Dry, Auto, 7=Cool, Dry, Heat, Auto
MI10OutdooorDemandRate_statusOutdoor unit demand limit statusRead1=Thermo Off, 2=In range, 3=No Limit
MO7OutdooorDemandRate_commandOutdoor unit demand limit commandCommand1=Thermo Off, 2=No Limit
AI12OutdooorDemandRateValue_statusOutdoor unit demand limit value%Read
AO2OutdooorDemandRateValue_commandOutdoor unit demand limit value command%Command
BI8LockRemoteControlAll_statusRemote controller lock of all functions (status)Read0=Unlocked, 1=Locked
BO6LockRemoteControlAll_commandRemote controller lock of all functions (command)Command0=Unlocked, 1=Locked
BI9LockRemoteControlOnOff_statusRemote controller lock of on/off (status)Read0=Unlocked, 1=Locked
BO7LockRemoteControlOnOff_commandRemote controller lock of on/off (command)Command0=Unlocked, 1=Locked
BI10LockRemoteControlMode_statusRemote controller lock of mode (status)Read0=Unlocked, 1=Locked
BO8LockRemoteControlMode_commandRemote controller lock of mode (command)Command0=Unlocked, 1=Locked
BI11LockRemoteControlSetPoint_statusRemote controller lock of setpoint (status)Read0=Unlocked, 1=Locked
BO9LockRemoteControlSetPoint_commandRemote controller lock of setpoint (command)Command0=Unlocked, 1=Locked
BI12LockRemoteControlFanSpeed_statusRemote controller lock of fan speed (status)Read0=Unlocked, 1=Locked
BO10LockRemoteControlFanSpeed_commandRemote controller lock of fan speed (command)Command0=Unlocked, 1=Locked
BI13LockRemoteControlVanesUD_statusRemote controller lock of up/down vanes (status)Read0=Unlocked, 1=Locked
BO11LockRemoteControlVanesUD_commandRemote controller lock of up/down vanes (command)Command0=Unlocked, 1=Locked
AI9DIP_SW_S1_statusDIP switch SW1 position (decimal), read at bootRead
AI10DIP_SW_S2_statusDIP switch SW2 position (decimal), read at bootRead
AI11SerialNumberGateway serial numberRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACPAN001R100 (Panasonic ECOi/PACi gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)

How many BACnet points does the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) have?

This list has 46 BACnet objects: 8 analog inputs, 3 analog outputs, 5 analog values, 9 binary inputs, 8 binary outputs, 2 binary values, 6 multi-state inputs, 4 multi-state outputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) BACnet points are writable?

18 of the 46 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway) BACnet documentation?

The source is Intesis BACnet MSTP - Panasonic AC User Manual (INBACPAN001R100) (PA-RC2-BAC-1L (legacy code)), revision 09/2024 v1.3, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacpan001r100.pdf.

What are the minimum BACnet points to integrate the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)?

Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).

How do I enable BMS control of the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)?

No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; the LockRemoteControl..._command objects (BO 6-11) lock it per function.

Can the BMS supply sensor values to the Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)?

Write the BMS room temperature to AO 1 RoomTemperature_command and keep using AO 0 SetPoint_command for the user setpoint. The gateway then runs its Virtual Temperature function: it offsets the setpoint it sends to the unit by the difference between the BMS temperature and the unit's own return temperature, so AI 0 SetPoint_status can differ from what you wrote. Until a first value is written, AO 1 shows Reliability = UNRELIABLE_OTHER and the function stays off.

How do I check these points on the real INBACPAN001R100 (Panasonic ECOi/PACi gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: Intesis BACnet MSTP - Panasonic AC User Manual (INBACPAN001R100) · PA-RC2-BAC-1L (legacy code) · rev. 09/2024 v1.3. Object names, instances and units are reproduced as published; descriptions are our own.