- INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
VRF BACnet gateway (up to 16, 64 or 128 indoor units) · BACnet points list
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) BACnet points list
Updated 28 October 2026
An Intesis BACnet server connected to the Panasonic P-Link bus that publishes each configured outdoor and indoor unit as BACnet objects, plus 'all units' commands. The 16 and 64 unit models support BACnet IP and MS/TP; the 128 unit model is BACnet IP only. Instance numbers come from fixed formulas on line, outdoor and indoor address.
This page lists 55 BACnet objects for the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
- Equipment
- VRF BACnet gateway (up to 16, 64 or 128 indoor units)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 55 (20 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 246
- Also known as
- Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF
BMS integration notes: Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Wire Port A to the P-Link terminals of the outdoor unit (on the 128 model Port B takes a second P-Link line), configure the units in Intesis MAPS and send the project, then map each indoor unit's _C/_S objects from its FI block. Use the 'all units' objects for global commands.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | LXOXXUXX_On/Off_C | Start/stop indoor unit | Command |
| MO 100 | LXOXXUXX_Mode_C | Mode command | Command |
| AO 100 | LXOXXUXX_Setpoint_C | Setpoint command | Command |
| MO 101 | LXOXXUXX_FanSpeed_C | Fan speed command (1 = auto) | Command |
| BI 100 | LXOXXUXX_On/Off_S | Run status | Read |
| AI 100 | LXOXXUXX_Setpoint_S | Setpoint in use | Read |
| AI 101 | LXOXXUXX_Room Temperature | Room (return air) temperature | Read |
| BI 103 | LXOXXUXX_Communication Error IU | Unit offline alarm | Read |
| AI 114 | LXOXXUXX_Unit Error Code | Fault code | Read |
Enable & remote start
No enable point is documented; remote-controller permissions can be removed with the Allow ... from RC_C objects.
Sensors & values from the BMS
Enable virtual temperature for the unit in Intesis MAPS, then write the BMS room temperature to LXOXXUXX_Bacnet ambient temperature (AO FI+3). The gateway recalculates the setpoint it sends, so Setpoint_S can differ from Setpoint_C. Intesis advises using this only when the gateway is the sole source of setpoint changes.
Network setup
- Default device instance 246, configurable in MAPS.
- With factory settings DHCP runs for 30 s after power-up; with no DHCP answer the IP falls back to 192.168.100.246.
- Outdoor units are addressed 1-31 per line, indoor units 1-64 per line.
Watch out for
- The 128-unit model has no MS/TP.
- Room Temperature is printed as AI FI+0 (clashing with Setpoint_S) in the summary tables but AI FI+1 on its detail page; discover the device to confirm.
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 0 | On/Off (all units) | On/Off (all units) | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all units) | Mode (all units) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MO | 1 | FanSpeed (all units) | FanSpeed (all units) | Command | 1=Auto, 2=Low, 3=Med, 4=High | |
| MO | 2 | Vane Position swing (all units) | Vane Position swing (all units) | Command | 1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing | |
| AO | 0 | Temperature Setpoint (all units) | Temperature Setpoint (all units) | °C | Command | |
| BI | 10025 | LXOUXX_Communication Error OU | Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| AI | 10025 | LXOUXX_Demand Limit. Ratio_S | Demand Limit. Ratio (status) (range 1-0%, 2-100%, 3- 200%, 4-No Limit) | Read | ||
| AO | 10025 | LXOUXX_Demand Limit. Ratio_C | Demand Limit. Ratio (command) (range 1-0%, 2-100%, 3- 200%, 4-No Limit) | Command | ||
| AI | 10026 | LXOUXX_High Pressure Sensor | High Pressure Sensor | bar | Read | |
| AI | 10027 | LXOUXX_Low Pressure Sensor | Low Pressure Sensor | bar | Read | |
| AI | 10028 | LXOUXX_Working Time | Working Time | h | Read | |
| BImin | 100 | LXOXXUXX_On/Off_S | On/Off (status) | Read | 0=Off, 1=On | |
| BOmin | 100 | LXOXXUXX_On/Off_C | On/Off (command) | Command | 0=Off, 1=On | |
| MI | 100 | LXOXXUXX_Mode_S | Mode (status) | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool | |
| MOmin | 100 | LXOXXUXX_Mode_C | Mode (command) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 100 | LXOXXUXX_Setpoint_S | Setpoint (status) | °C | Read | |
| AOmin | 100 | LXOXXUXX_Setpoint_C | Setpoint (command) | °C | Command | |
| MI | 101 | LXOXXUXX_FanSpeed_S | FanSpeed (status) | Read | 1=Auto, 2=Low, 3=Low+, 4=Med, 5=Med+, 6=High | |
| MOmin | 101 | LXOXXUXX_FanSpeed_C | FanSpeed (command) | Command | 1=Auto, 2=Low, 3=Med, 4=High | |
| MI | 102 | LXOXXUXX_Vane Position_S | Vane Position (status) | Read | 1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing | |
| MO | 102 | LXOXXUXX_Vane Position_C | Vane Position (command) | Command | 1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing | |
| AImin | 101 | LXOXXUXX_Room Temperature | Room Temperature | °C | Read | |
| AO | 103 | LXOXXUXX_Bacnet ambient temperature | Bacnet ambient temperature | °C | Command | |
| BI | 101 | LXOXXUXX_Wired Remote Controller_S | Wired Remote Controller (status) | Read | 0=Body sensor, 1=Remote control sensor | |
| BO | 101 | LXOXXUXX_Wired Remote Controller_C | Wired Remote Controller (command) | Command | 0=Body sensor, 1=Remote control sensor | |
| AI | 102 | LXOXXUXX_Disch.Setpoint Cool_S | Discharge Setpoint Cool (status) | °C | Read | |
| AO | 101 | LXOXXUXX_Disch.Setpoint Cool_C | Discharge Setpoint Cool (command) | °C | Command | |
| AI | 103 | LXOXXUXX_Disch.Setpoint Heat_S | Discharge Setpoint Heat (status) | °C | Read | |
| AO | 102 | LXOXXUXX_Disch.Setpoint Heat_C | Discharge Setpoint Heat (command) | °C | Command | |
| AI | 104 | LXOXXUXX_Disch.Current Temp. | Discharge Current temperature | °C | Read | |
| AI | 105 | LXOXXUXX_Heat Exchanger Temp. | Heat Exchanger temperature | °C | Read | |
| AI | 106 | LXOXXUXX_Heat Setpoint Up Limit | Heat Setpoint Up Limit | °C | Read | |
| AI | 107 | LXOXXUXX_Heat Setpoint Low Limit | Heat Setpoint Low Limit | °C | Read | |
| AI | 108 | LXOXXUXX_Cool Setpoint Up Limit | Cool Setpoint Up Limit | °C | Read | |
| AI | 109 | LXOXXUXX_Cool Setpoint Low Limit | Cool Setpoint Low Limit | °C | Read | |
| AI | 110 | LXOXXUXX_Dry Setpoint Up Limit | Dry Setpoint Up Limit | °C | Read | |
| AI | 111 | LXOXXUXX_Dry Setpoint Low Limit | Dry Setpoint Low Limit | °C | Read | |
| AI | 112 | LXOXXUXX_Auto Setpoint Up Limit | Auto Setpoint Up Limit | °C | Read | |
| AI | 113 | LXOXXUXX_Auto Setpoint Low Limit | Auto Setpoint Low Limit | °C | Read | |
| AImin | 114 | LXOXXUXX_Unit Error Code | Unit Error Code | Read | ||
| BI | 102 | LXOXXUXX_Filter Sign | Filter Sign | Read | 0=Normal, 1=Alarm | |
| BO | 102 | LXOXXUXX_Filter Reset | Filter Reset | Command | 0=No reset, 1=Reset | |
| BImin | 103 | LXOXXUXX_Communication Error IU | Communication Error indoor unit | Read | 0=No error, 1=Error | |
| BI | 104 | LXOXXUXX_Allow On/Off from RC_S | Allow On/Off from remote controller (status) | Read | 0=Allow, 1=Not allow | |
| BO | 103 | LXOXXUXX_Allow On/Off from RC_C | Allow On/Off from remote controller (command) | Command | 0=Allow, 1=Not allow | |
| BI | 105 | LXOXXUXX_Allow Mode from RC_S | Allow Mode from remote controller (status) | Read | 0=Allow, 1=Not allow | |
| BO | 104 | LXOXXUXX_Allow Mode from RC_C | Allow Mode from remote controller (command) | Command | 0=Allow, 1=Not allow | |
| BI | 106 | LXOXXUXX_Allow Setpoint from RC_S | Allow Setpoint from remote controller (status) | Read | 0=Allow, 1=Not allow | |
| BO | 105 | LXOXXUXX_Allow Setpoint from RC_C | Allow Setpoint from remote controller (command) | Command | 0=Allow, 1=Not allow | |
| MI | 103 | LXOXXUXX_Unit Type | Unit Type | Read | 1=Not Defined, 2=TBD, 3=GHP, 4=PAC, 5=VRF | |
| MI | 104 | LXOXXUXX_Occupancy_S | Occupancy (status) | Read | 1=Occupied, 2=Unoccupied, 3=Disable | |
| MO | 103 | LXOXXUXX_Occupancy_C | Occupancy (command) | Command | 1=Occupied, 2=Unoccupied, 3=Disable | |
| AI | 115 | LXOXXUXX_Consumption Yesterday | Consumption Yesterday | kWh | Read | |
| AI | 116 | LXOXXUXX_Consumption Today | Consumption Today | kWh | Read | |
| AI | 117 | LXOXXUXX_Consumption Total | Consumption Total | kWh | Read |
No points match these filters.
Integration notes
- Points shown for the 'all units' commands, line 1 outdoor unit 1 and line 1 indoor unit 1 only.
- Outdoor unit base FO = (O x 25) + ((L - 1) x 1000) + 10000; line 1 outdoor unit 1 gives 10025.
- Indoor unit base FI = (U x 100) + ((L - 1) x 20000); line 1 indoor unit 1 gives 100.
- Room Temperature is printed as AI FI+0 in the summary tables, but its object-detail page gives AI FI+1 (the only free AI offset); FI+1 is used here, verify on site.
- LXOXXUXX_Bacnet ambient temperature (AO FI+3) only appears when virtual temperature is enabled in MAPS.
- The cover says r1.2; page headers say r1.1.
- The object-detail chapter also lists gateway occupancy objects (AV 0-3 setpoints, BV 0 OccupancyContinuousCheck, Unoccupancy Deadband Action with an inconsistent object type) that are not in the member tables; they are left out here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
How many BACnet points does the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) have?
This list has 55 BACnet objects: 22 analog inputs, 6 analog outputs, 8 binary inputs, 7 binary outputs, 5 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) BACnet points are writable?
20 of the 55 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) BACnet documentation?
The source is Intesis BACnet Server - Panasonic VRF User's Manual, revision 04/2020 r1.2, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacpanxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)?
Start with BO 100 LXOXXUXX_On/Off_C (Start/stop indoor unit); MO 100 LXOXXUXX_Mode_C (Mode command); AO 100 LXOXXUXX_Setpoint_C (Setpoint command); MO 101 LXOXXUXX_FanSpeed_C (Fan speed command (1 = auto)); BI 100 LXOXXUXX_On/Off_S (Run status); AI 100 LXOXXUXX_Setpoint_S (Setpoint in use); AI 101 LXOXXUXX_Room Temperature (Room (return air) temperature); BI 103 LXOXXUXX_Communication Error IU (Unit offline alarm); AI 114 LXOXXUXX_Unit Error Code (Fault code).
How do I enable BMS control of the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)?
No enable point is documented; remote-controller permissions can be removed with the Allow ... from RC_C objects.
Can the BMS supply sensor values to the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)?
Enable virtual temperature for the unit in Intesis MAPS, then write the BMS room temperature to LXOXXUXX_Bacnet ambient temperature (AO FI+3). The gateway recalculates the setpoint it sends, so Setpoint_S can differ from Setpoint_C. Intesis advises using this only when the gateway is the sole source of setpoint changes.
How do I check these points on the real INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP
Source: Intesis BACnet Server - Panasonic VRF User's Manual · rev. 04/2020 r1.2. Object names, instances and units are reproduced as published; descriptions are our own.