VRF BACnet gateway (up to 16, 64 or 128 indoor units) · BACnet points list

Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) BACnet points list

Updated 28 October 2026

Short answer

An Intesis BACnet server connected to the Panasonic P-Link bus that publishes each configured outdoor and indoor unit as BACnet objects, plus 'all units' commands. The 16 and 64 unit models support BACnet IP and MS/TP; the 128 unit model is BACnet IP only. Instance numbers come from fixed formulas on line, outdoor and indoor address.

This page lists 55 BACnet objects for the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Equipment
VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Equipment type
VRF & split air conditioners
BACnet objects
55 (20 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
246
Also known as
Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF
Source document
Intesis BACnet Server - Panasonic VRF User's Manual · rev. 04/2020 r1.2
Download CSV 55 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)

Integration in brief

Wire Port A to the P-Link terminals of the outdoor unit (on the 128 model Port B takes a second P-Link line), configure the units in Intesis MAPS and send the project, then map each indoor unit's _C/_S objects from its FI block. Use the 'all units' objects for global commands.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 100LXOXXUXX_On/Off_CStart/stop indoor unitCommand
MO 100LXOXXUXX_Mode_CMode commandCommand
AO 100LXOXXUXX_Setpoint_CSetpoint commandCommand
MO 101LXOXXUXX_FanSpeed_CFan speed command (1 = auto)Command
BI 100LXOXXUXX_On/Off_SRun statusRead
AI 100LXOXXUXX_Setpoint_SSetpoint in useRead
AI 101LXOXXUXX_Room TemperatureRoom (return air) temperatureRead
BI 103LXOXXUXX_Communication Error IUUnit offline alarmRead
AI 114LXOXXUXX_Unit Error CodeFault codeRead

Enable & remote start

No enable point is documented; remote-controller permissions can be removed with the Allow ... from RC_C objects.

Sensors & values from the BMS

Enable virtual temperature for the unit in Intesis MAPS, then write the BMS room temperature to LXOXXUXX_Bacnet ambient temperature (AO FI+3). The gateway recalculates the setpoint it sends, so Setpoint_S can differ from Setpoint_C. Intesis advises using this only when the gateway is the sole source of setpoint changes.

Network setup

Watch out for

Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

55 of 55 shown
Type
Access
Show
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) BACnet Points List
DescriptionStates
BO0On/Off (all units)On/Off (all units)Command0=Off, 1=On
MO0Mode (all units)Mode (all units)Command1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
MO1FanSpeed (all units)FanSpeed (all units)Command1=Auto, 2=Low, 3=Med, 4=High
MO2Vane Position swing (all units)Vane Position swing (all units)Command1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing
AO0Temperature Setpoint (all units)Temperature Setpoint (all units)°CCommand
BI10025LXOUXX_Communication Error OUCommunication Error outdoor unitRead0=No Error, 1=Error
AI10025LXOUXX_Demand Limit. Ratio_SDemand Limit. Ratio (status) (range 1-0%, 2-100%, 3- 200%, 4-No Limit)Read
AO10025LXOUXX_Demand Limit. Ratio_CDemand Limit. Ratio (command) (range 1-0%, 2-100%, 3- 200%, 4-No Limit)Command
AI10026LXOUXX_High Pressure SensorHigh Pressure SensorbarRead
AI10027LXOUXX_Low Pressure SensorLow Pressure SensorbarRead
AI10028LXOUXX_Working TimeWorking TimehRead
BImin100LXOXXUXX_On/Off_SOn/Off (status)Read0=Off, 1=On
BOmin100LXOXXUXX_On/Off_COn/Off (command)Command0=Off, 1=On
MI100LXOXXUXX_Mode_SMode (status)Read1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool
MOmin100LXOXXUXX_Mode_CMode (command)Command1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin100LXOXXUXX_Setpoint_SSetpoint (status)°CRead
AOmin100LXOXXUXX_Setpoint_CSetpoint (command)°CCommand
MI101LXOXXUXX_FanSpeed_SFanSpeed (status)Read1=Auto, 2=Low, 3=Low+, 4=Med, 5=Med+, 6=High
MOmin101LXOXXUXX_FanSpeed_CFanSpeed (command)Command1=Auto, 2=Low, 3=Med, 4=High
MI102LXOXXUXX_Vane Position_SVane Position (status)Read1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing
MO102LXOXXUXX_Vane Position_CVane Position (command)Command1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing
AImin101LXOXXUXX_Room TemperatureRoom Temperature°CRead
AO103LXOXXUXX_Bacnet ambient temperatureBacnet ambient temperature°CCommand
BI101LXOXXUXX_Wired Remote Controller_SWired Remote Controller (status)Read0=Body sensor, 1=Remote control sensor
BO101LXOXXUXX_Wired Remote Controller_CWired Remote Controller (command)Command0=Body sensor, 1=Remote control sensor
AI102LXOXXUXX_Disch.Setpoint Cool_SDischarge Setpoint Cool (status)°CRead
AO101LXOXXUXX_Disch.Setpoint Cool_CDischarge Setpoint Cool (command)°CCommand
AI103LXOXXUXX_Disch.Setpoint Heat_SDischarge Setpoint Heat (status)°CRead
AO102LXOXXUXX_Disch.Setpoint Heat_CDischarge Setpoint Heat (command)°CCommand
AI104LXOXXUXX_Disch.Current Temp.Discharge Current temperature°CRead
AI105LXOXXUXX_Heat Exchanger Temp.Heat Exchanger temperature°CRead
AI106LXOXXUXX_Heat Setpoint Up LimitHeat Setpoint Up Limit°CRead
AI107LXOXXUXX_Heat Setpoint Low LimitHeat Setpoint Low Limit°CRead
AI108LXOXXUXX_Cool Setpoint Up LimitCool Setpoint Up Limit°CRead
AI109LXOXXUXX_Cool Setpoint Low LimitCool Setpoint Low Limit°CRead
AI110LXOXXUXX_Dry Setpoint Up LimitDry Setpoint Up Limit°CRead
AI111LXOXXUXX_Dry Setpoint Low LimitDry Setpoint Low Limit°CRead
AI112LXOXXUXX_Auto Setpoint Up LimitAuto Setpoint Up Limit°CRead
AI113LXOXXUXX_Auto Setpoint Low LimitAuto Setpoint Low Limit°CRead
AImin114LXOXXUXX_Unit Error CodeUnit Error CodeRead
BI102LXOXXUXX_Filter SignFilter SignRead0=Normal, 1=Alarm
BO102LXOXXUXX_Filter ResetFilter ResetCommand0=No reset, 1=Reset
BImin103LXOXXUXX_Communication Error IUCommunication Error indoor unitRead0=No error, 1=Error
BI104LXOXXUXX_Allow On/Off from RC_SAllow On/Off from remote controller (status)Read0=Allow, 1=Not allow
BO103LXOXXUXX_Allow On/Off from RC_CAllow On/Off from remote controller (command)Command0=Allow, 1=Not allow
BI105LXOXXUXX_Allow Mode from RC_SAllow Mode from remote controller (status)Read0=Allow, 1=Not allow
BO104LXOXXUXX_Allow Mode from RC_CAllow Mode from remote controller (command)Command0=Allow, 1=Not allow
BI106LXOXXUXX_Allow Setpoint from RC_SAllow Setpoint from remote controller (status)Read0=Allow, 1=Not allow
BO105LXOXXUXX_Allow Setpoint from RC_CAllow Setpoint from remote controller (command)Command0=Allow, 1=Not allow
MI103LXOXXUXX_Unit TypeUnit TypeRead1=Not Defined, 2=TBD, 3=GHP, 4=PAC, 5=VRF
MI104LXOXXUXX_Occupancy_SOccupancy (status)Read1=Occupied, 2=Unoccupied, 3=Disable
MO103LXOXXUXX_Occupancy_COccupancy (command)Command1=Occupied, 2=Unoccupied, 3=Disable
AI115LXOXXUXX_Consumption YesterdayConsumption YesterdaykWhRead
AI116LXOXXUXX_Consumption TodayConsumption TodaykWhRead
AI117LXOXXUXX_Consumption TotalConsumption TotalkWhRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)

How many BACnet points does the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) have?

This list has 55 BACnet objects: 22 analog inputs, 6 analog outputs, 8 binary inputs, 7 binary outputs, 5 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) BACnet points are writable?

20 of the 55 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server) BACnet documentation?

The source is Intesis BACnet Server - Panasonic VRF User's Manual, revision 04/2020 r1.2, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacpanxxxo000.pdf.

What are the minimum BACnet points to integrate the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)?

Start with BO 100 LXOXXUXX_On/Off_C (Start/stop indoor unit); MO 100 LXOXXUXX_Mode_C (Mode command); AO 100 LXOXXUXX_Setpoint_C (Setpoint command); MO 101 LXOXXUXX_FanSpeed_C (Fan speed command (1 = auto)); BI 100 LXOXXUXX_On/Off_S (Run status); AI 100 LXOXXUXX_Setpoint_S (Setpoint in use); AI 101 LXOXXUXX_Room Temperature (Room (return air) temperature); BI 103 LXOXXUXX_Communication Error IU (Unit offline alarm); AI 114 LXOXXUXX_Unit Error Code (Fault code).

How do I enable BMS control of the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)?

No enable point is documented; remote-controller permissions can be removed with the Allow ... from RC_C objects.

Can the BMS supply sensor values to the Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)?

Enable virtual temperature for the unit in Intesis MAPS, then write the BMS room temperature to LXOXXUXX_Bacnet ambient temperature (AO FI+3). The gateway recalculates the setpoint it sends, so Setpoint_S can differ from Setpoint_C. Intesis advises using this only when the gateway is the sole source of setpoint changes.

How do I check these points on the real INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: Intesis BACnet Server - Panasonic VRF User's Manual · rev. 04/2020 r1.2. Object names, instances and units are reproduced as published; descriptions are our own.