Air conditioner BACnet gateway (1 indoor unit) · BACnet points list

Intesis INBACMID001I100 (Midea VRF gateway) BACnet points list

Updated 28 October 2026

Short answer

A one-unit Intesis BACnet MS/TP interface wired to the XYE (or D1D2 on V8) terminals of a Midea indoor unit, where it acts as a central controller. It exposes 30 fixed objects for on/off, mode, setpoint, fan, swing, room temperature, errors, occupancy logic and remote-controller lock, plus diagnostic objects for its DIP switches and the Midea protocol version.

This page lists 30 BACnet objects for the Intesis INBACMID001I100 (Midea VRF gateway) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
INBACMID001I100 (Midea VRF gateway)
Equipment
Air conditioner BACnet gateway (1 indoor unit)
Equipment type
Other equipment
BACnet objects
30 (11 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
246000
Also known as
Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea
Source document
Intesis BACnet MS/TP - Midea AC User Manual (INBACMID001I100) · rev. 3/2027 v2.8 (as printed)
Download CSV 30 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Intesis INBACMID001I100 (Midea VRF gateway)

Integration in brief

Connect the gateway to the indoor unit (XYE terminals on V4/V6, D1D2 on V8; 12 V external power), set the BACnet network on its DIP switches, then write the _command objects (on/off, mode, setpoint, fan) and read back the matching _status objects. One gateway serves one indoor unit (or one remote-controller group), so give each gateway its own MAC address and device instance.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0OnOff_commandStart/stop the indoor unitCommand
MO 0Mode_commandHeat/cool/fan/dry/auto selectionCommand
AO 0SetPoint_commandTemperature setpoint from the BMSCommand
MO 1FanSpeed_commandFan speed selectionCommand
BI 0OnOff_statusConfirm the unit is runningRead
AI 0SetPoint_statusSetpoint the unit is really usingRead
AI 1RoomTemperature_statusRoom/return temperature for trendingRead
BI 1ErrorActiveUnit alarmRead
AI 2ErrorCodeWhich fault is activeRead

Enable & remote start

No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; MO 5 RemoteControllerProhibit_command locks it.

Sensors & values from the BMS

Write the BMS room temperature to AO 1 RoomTemperature_command and keep using AO 0 SetPoint_command for the user setpoint. The gateway then runs its Virtual Temperature function: it offsets the setpoint it sends to the unit by the difference between the BMS temperature and the unit's own return temperature, so AI 0 SetPoint_status can differ from what you wrote. Until a first value is written, AO 1 shows Reliability = UNRELIABLE_OTHER and the function stays off.

Network setup

Watch out for

Intesis INBACMID001I100 (Midea VRF gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

30 of 30 shown
Type
Access
Show
Intesis INBACMID001I100 (Midea VRF gateway) BACnet Points List
DescriptionStates
BImin0OnOff_statusUnit on/off statusRead0=Off, 1=On
BOmin0OnOff_commandStart/stop command for the indoor unitCommand0=Off, 1=On
MI0Mode_statusOperating mode currently activeRead1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
MOmin0Mode_commandOperating mode commandCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin0SetPoint_statusSetpoint the indoor unit is actually using°CRead
AOmin0SetPoint_commandTemperature setpoint command from the BMS°CCommand
MI1FanSpeed_statusCurrent fan speedRead1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3
MOmin1FanSpeed_commandFan speed commandCommand1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3
MI2AirDirectionUD_statusVertical (up/down) vane positionRead1=Stop, 2=Swing
MO2AirDirectionUD_commandVertical (up/down) vane commandCommand1=Stop, 2=Swing
AImin1RoomTemperature_statusRoom temperature used by the indoor unit°CRead
AO1RoomTemperature_commandRoom temperature written by the BMS (external sensor)°CCommand
AImin2ErrorCodeActive error code as a numberRead
MI4ErrorCodeMActive error code as a multistate valueRead1=-, 2=CommError, 3=E0, 4=E1, 5=E2, 6=E3, 7=E4, 8=E5, 9=E6, 10=E7, 11=E8, 12=E9, 13=EA, 14=EB, 15=EC, 16=ED, 17=EE, 18=EF, 19=P1, 20=P2, 21=P3, 22=P4, 23=P5, 24=P6, 25=P7, 26=P8, 27=P9, 28=PA, 29=PB, 30=PC, 31=PD, 32=PE, 33=PF
BImin1ErrorActiveAn error is active on the indoor unitRead0=No, 1=Error
AV0OnTimeCounterAccumulated run time of the unithRead
MV0OccupancyOccupancy input for the built-in occupancy logicWrite1=Occupied, 2=Unoccupied, 3=Disabled
AV1OccupiedCoolSetPointCooling setpoint used while occupied°CRead
AV2OccupiedHeatSetPointHeating setpoint used while occupied°CRead
AV3UnoccupiedCoolSetPointCooling setpoint used while unoccupied°CRead
AV4UnoccupiedHeatSetPointHeating setpoint used while unoccupied°CRead
BV0OccupancyContinuousCheckRe-run occupancy logic on every temperature changeWrite0=Disabled, 1=Enabled
BV1UnoccupiedDeadbandActionOff or stay on when unoccupied inside the deadbandWrite0=Off, 1=CurrentMode
MI6RemoteControllerProhibit_statusRemote controller lock statusRead1=Unlocked, 2=Locked
MO5RemoteControllerProhibit_commandRemote controller lock commandCommand1=Unlocked, 2=Locked
AI9DIP_SW_S1_statusDIP switch SW1 position (decimal), read at bootRead
AI10DIP_SW_S2_statusDIP switch SW2 position (decimal), read at bootRead
AI11SerialNumberGateway serial numberRead
MV1AC_IU_addressThe address of the indoor unit in the Midea systemWrite1=0, 2=1, 3=2, ..., 64=63
MI11Midea_settingMidea V4/V6 protocol detection settingRead1=Auto (detecting), 2=Auto V4, 3=Auto V6, 4=V4, 5=V6

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACMID001I100 (Midea VRF gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis INBACMID001I100 (Midea VRF gateway)

How many BACnet points does the Intesis INBACMID001I100 (Midea VRF gateway) have?

This list has 30 BACnet objects: 6 analog inputs, 2 analog outputs, 5 analog values, 2 binary inputs, 1 binary output, 2 binary values, 6 multi-state inputs, 4 multi-state outputs, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis INBACMID001I100 (Midea VRF gateway) BACnet points are writable?

11 of the 30 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis INBACMID001I100 (Midea VRF gateway) BACnet documentation?

The source is Intesis BACnet MS/TP - Midea AC User Manual (INBACMID001I100), revision 3/2027 v2.8 (as printed), published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/inbacmid001i100-user-manual-en-r1-0.pdf.

What are the minimum BACnet points to integrate the Intesis INBACMID001I100 (Midea VRF gateway)?

Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).

How do I enable BMS control of the Intesis INBACMID001I100 (Midea VRF gateway)?

No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; MO 5 RemoteControllerProhibit_command locks it.

Can the BMS supply sensor values to the Intesis INBACMID001I100 (Midea VRF gateway)?

Write the BMS room temperature to AO 1 RoomTemperature_command and keep using AO 0 SetPoint_command for the user setpoint. The gateway then runs its Virtual Temperature function: it offsets the setpoint it sends to the unit by the difference between the BMS temperature and the unit's own return temperature, so AI 0 SetPoint_status can differ from what you wrote. Until a first value is written, AO 1 shows Reliability = UNRELIABLE_OTHER and the function stays off.

How do I check these points on the real INBACMID001I100 (Midea VRF gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: Intesis BACnet MS/TP - Midea AC User Manual (INBACMID001I100) · rev. 3/2027 v2.8 (as printed). Object names, instances and units are reproduced as published; descriptions are our own.