VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units) · BACnet points list

Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) BACnet points list

Updated 28 October 2026

Short answer

An Intesis BACnet server on the Samsung NASA R1/R2 bus that serves BACnet IP and BACnet MS/TP. It publishes outdoor-unit communication alarms, gateway-wide commands and one block of objects per indoor unit at (identifier x 100). The manual also defines different object sets for hot-water (HE/HT/EHS), AHU, ERV/ERV+ and chiller unit types; this file shows the standard indoor unit (IU) set.

This page lists 54 BACnet objects for the Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Equipment
VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Equipment type
VRF & split air conditioners
BACnet objects
54 (20 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
246
Also known as
Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA
Source document
Intesis BACnet Server - Samsung NASA AC User's Manual · rev. 01/2022 r1.3
Download CSV 54 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)

Integration in brief

Connect the NASA R1/R2 bus to Port A (A3 R1/+, A4 R2/-), scan the bus in Intesis MAPS, assign each unit an identifier and send the project; then map each indoor unit's objects from its (identifier x 100) block. Gateway-wide objects at low instances command all units.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 100OxxUxx_On/Off_CStart/stop indoor unitCommand
MO 100OxxUxx_Mode IU/AHU_CMode commandCommand
AO 100OxxUxx_Setpoint_CSetpoint commandCommand
MO 101OxxUxx_FanSpeed_CFan speed command (4 = auto)Command
BI 100OxxUxx_On/Off_SRun statusRead
AI 100OxxUxx_Setpoint_SSetpoint in useRead
AI 101OxxUxx_Room_TemperatureIndoor unit room temperature, °CRead
MI 102OxxUxx_Communication StatusLink flags; EXST = unit found on the NASA busRead
AI 105OxxUxx_Unit Error codeFault codeRead

Enable & remote start

No enable point is documented. OxxUxx_RC Restriction_C (BO 103) restricts the unit's remote controller.

Network setup

Watch out for

Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

54 of 54 shown
Type
Access
Show
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) BACnet Points List
DescriptionStates
BI0OU00_Communication Error OUOutdoor unit00 Communication Error outdoor unitRead0=No Error, 1=Error
BI1OU01_Communication Error OUOutdoor unit01 Communication Error outdoor unitRead0=No Error, 1=Error
BI2OU02_Communication Error OUOutdoor unit02 Communication Error outdoor unitRead0=No Error, 1=Error
BI3OU03_Communication Error OUOutdoor unit03 Communication Error outdoor unitRead0=No Error, 1=Error
BI4OU04_Communication Error OUOutdoor unit04 Communication Error outdoor unitRead0=No Error, 1=Error
BI5OU05_Communication Error OUOutdoor unit05 Communication Error outdoor unitRead0=No Error, 1=Error
BI6OU06_Communication Error OUOutdoor unit06 Communication Error outdoor unitRead0=No Error, 1=Error
BI7OU07_Communication Error OUOutdoor unit07 Communication Error outdoor unitRead0=No Error, 1=Error
BI8OU08_Communication Error OUOutdoor unit08 Communication Error outdoor unitRead0=No Error, 1=Error
BI9OU09_Communication Error OUOutdoor unit09 Communication Error outdoor unitRead0=No Error, 1=Error
BI10OU10_Communication Error OUOutdoor unit10 Communication Error outdoor unitRead0=No Error, 1=Error
BI11OU11_Communication Error OUOutdoor unit11 Communication Error outdoor unitRead0=No Error, 1=Error
BI12OU12_Communication Error OUOutdoor unit12 Communication Error outdoor unitRead0=No Error, 1=Error
BI13OU13_Communication Error OUOutdoor unit13 Communication Error outdoor unitRead0=No Error, 1=Error
BI14OU14_Communication Error OUOutdoor unit14 Communication Error outdoor unitRead0=No Error, 1=Error
BI15OU15_Communication Error OUOutdoor unit15 Communication Error outdoor unitRead0=No Error, 1=Error
BI16OU Addressing ErrorOutdoor unit Addressing ErrorRead0=OU Addressing OK, 1=Manual Addr in OU required
BO0On/Off (all units)On/Off (all units)Command0=Off, 1=On
MO0Mode (all units)Mode (all units)Command1=Heat, 2=Dry, 3=Fan, 4=Cool, 5=Auto, 6=Cool Storage, 7=Hot Water
MO1FanSpeed (all units)FanSpeed (all units)Command1=Low, 2=Mid, 3=High, 4=Auto
BO1Vane position swing (all units)Vane position swing (all units)Command0=Swing Off, 1=Swing On
AO0Temperature Setpoint (all units)Temperature Setpoint (all units)°CCommand
BO2Vent. On/Off (all units)Vent. On/Off (all units)Command0=Off, 1=On
BO3Hot Water On/Off (all units)Hot Water On/Off (all units)Command0=Off, 1=On
BImin100OxxUxx_On/Off_SOn/Off (status)Read0=Off, 1=On
BOmin100OxxUxx_On/Off_COn/Off (command)Command0=Off, 1=On
MI100OxxUxx_Mode IU/AHU_SMode indoor unit/AHU (status)Read1=Heat, 2=Dry, 3=Fan, 4=Cool, 5=Auto, 6=Not Valid, 7=Not Valid
MOmin100OxxUxx_Mode IU/AHU_CMode indoor unit/AHU (command)Command1=Heat, 2=Dry, 3=Fan, 4=Cool, 5=Auto, 6=Not Valid, 7=Not Valid
AImin100OxxUxx_Setpoint_SSetpoint (status)°CRead
AOmin100OxxUxx_Setpoint_CSetpoint (command)°CCommand
MI101OxxUxx_FanSpeed_SFanSpeed (status)Read1=Low, 2=Mid, 3=High, 4=Auto
MOmin101OxxUxx_FanSpeed_CFanSpeed (command)Command1=Low, 2=Mid, 3=High, 4=Auto
BI101OxxUxx_Vane position swing_SVane position swing (status)Read0=Off, 1=On
BO101OxxUxx_Vane position swing_CVane position swing (command)Command0=Off, 1=On
AImin101OxxUxx_Room_TemperatureRoom Temperature°CRead
AI102OxxUxx_Disch.Setpoint Cool IU_SDischarge Setpoint Cool indoor unit (status)°CRead
AO101OxxUxx_Disch.Setpoint Cool IU_CDischarge Setpoint Cool indoor unit (command)°CCommand
AI103OxxUxx_Disch.Setpoint Heat IU_SDischarge Setpoint Heat indoor unit (status)°CRead
AO102OxxUxx_Disch.Setpoint Heat IU_CDischarge Setpoint Heat indoor unit (command)°CCommand
AI104OxxUxx_Disch. Current Temp.Discharge Current temperature°CRead
AImin105OxxUxx_Unit Error codeUnit Error codeRead
BI102OxxUxx_FilterSignFilterSignRead0=Normal, 1=Alarm
BO102OxxUxx_FilterResetFilterResetCommand0=No reset, 1=Reset
MImin102OxxUxx_Communication StatusCommunication StatusRead1=-/-/-/-, 2=-/-/-/EXST, 3=-/-/RDY/-, 4=-/-/RDY/EXST, 5=-/DTUP/-/-, 6=-/DTUP/-/EXST, 7=-/DTUP/RDY/-, 8=-/DTUP/RDY/EXST, 9=TPOK/-/-/-, 10=TPOK/-/-/EXST, 11=TPOK/-/RDY/-, 12=TPOK/-/RDY/EXST, 13=TPOK/DTUP/-/-, 14=TPOK/DTUP/-/EXST, 15=TPOK/DTUP/RDY/-, 16=TPOK/DTUP/RDY/EXST
BI103OxxUxx_RC Restriction_SRemote controller Restriction (status)Read0=No restriction, 1=Restriction
BO103OxxUxx_RC Restriction_CRemote controller Restriction (command)Command0=No restriction, 1=Restriction
BO104OxxUxx_Buzzer SoundBuzzer SoundCommand0=Buzzer On, 1=Buzzer Off
MI103OxxUxx_Unit typeUnit typeRead1=Not Defined, 2=IU, 3=HE, 4=HT, 5=AHU, 6=ERV, 7=ERV+, 8=EHS, 9=CHILLER
BI106OXXUXX_WindFree_SWindFree (status)Read0=Disable, 1=Enable
BO107OXXUXX_WindFree_CWindFree (command)Command0=Disable, 1=Enable
BI107OXXUXX_Air Clean_SAir Clean (status)Read0=Disable, 1=Enable
BO108OXXUXX_Air Clean_CAir Clean (command)Command0=Disable, 1=Enable
MI107OXXUXX_360 CST Air Flow_S360 CST Air Flow (status)Read1=Spot, 2=Mid, 3=Wide, 4=Swing
MO105OXXUXX_360 CST Air Flow_C360 CST Air Flow (command)Command1=Spot, 2=Mid, 3=Wide, 4=Swing

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)

How many BACnet points does the Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) have?

This list has 54 BACnet objects: 6 analog inputs, 4 analog outputs, 23 binary inputs, 11 binary outputs, 5 multi-state inputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) BACnet points are writable?

20 of the 54 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) BACnet documentation?

The source is Intesis BACnet Server - Samsung NASA AC User's Manual, revision 01/2022 r1.3, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacsamxxxo000.pdf.

What are the minimum BACnet points to integrate the Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)?

Start with BO 100 OxxUxx_On/Off_C (Start/stop indoor unit); MO 100 OxxUxx_Mode IU/AHU_C (Mode command); AO 100 OxxUxx_Setpoint_C (Setpoint command); MO 101 OxxUxx_FanSpeed_C (Fan speed command (4 = auto)); BI 100 OxxUxx_On/Off_S (Run status); AI 100 OxxUxx_Setpoint_S (Setpoint in use); AI 101 OxxUxx_Room_Temperature (Indoor unit room temperature, °C); MI 102 OxxUxx_Communication Status (Link flags; EXST = unit found on the NASA bus); AI 105 OxxUxx_Unit Error code (Fault code).

How do I enable BMS control of the Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)?

No enable point is documented. OxxUxx_RC Restriction_C (BO 103) restricts the unit's remote controller.

How do I check these points on the real INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: Intesis BACnet Server - Samsung NASA AC User's Manual · rev. 01/2022 r1.3. Object names, instances and units are reproduced as published; descriptions are our own.