- INBACDAI001I000 (Daikin domestic gateway)
Air conditioner BACnet gateway (1 indoor unit) · BACnet points list
Intesis INBACDAI001I000 (Daikin domestic gateway) BACnet points list
Updated 28 October 2026
A one-unit Intesis interface that plugs into the S21 socket on a Daikin residential indoor unit's control board and serves it as BACnet MS/TP or BACnet IP. Its member table lists 20 objects: on/off, mode, setpoint, fan, up/down and left/right louvres, room temperature, errors, run hours, remote lock and humidification.
This page lists 20 BACnet objects for the Intesis INBACDAI001I000 (Daikin domestic gateway) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- INBACDAI001I000 (Daikin domestic gateway)
- Equipment
- Air conditioner BACnet gateway (1 indoor unit)
- Equipment type
- Other equipment
- BACnet objects
- 20 (8 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 246000
- Also known as
- Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin
BMS integration notes: Intesis INBACDAI001I000 (Daikin domestic gateway)
Connect the gateway to the indoor unit (supplied 1.5 m cable into the S21 socket on the indoor control board), set the BACnet network on its DIP switches, then write the _command objects (on/off, mode, setpoint, fan) and read back the matching _status objects. One gateway serves one indoor unit (or one remote-controller group), so give each gateway its own MAC address and device instance.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 0 | OnOff_command | Start/stop the indoor unit | Command |
| MO 0 | Mode_command | Heat/cool/fan/dry/auto selection | Command |
| AO 0 | SetPoint_command | Temperature setpoint from the BMS | Command |
| MO 1 | FanSpeed_command | Fan speed selection | Command |
| BI 0 | OnOff_status | Confirm the unit is running | Read |
| AI 0 | SetPoint_status | Setpoint the unit is really using | Read |
| AI 1 | RoomTemperature_status | Room/return temperature for trending | Read |
| BI 1 | ErrorActive | Unit alarm | Read |
| AI 2 | ErrorCode | Which fault is active | Read |
Enable & remote start
No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; BV 2 LockRemoteControl locks it.
Network setup
- BACnet MS/TP or BACnet IP is chosen with a DIP switch (MS/TP is the default); switch changes need a power cycle.
- BACnet IP: factory static IP 192.168.100.246; change it (or select DHCP) with the Intesis configuration tool.
- MS/TP MAC address 0-127 is set on DIP switches; baud rate is DIP-selectable (9600-115200) with autobaud as the default, which matches the baud rate of another MS/TP device running a fixed rate.
- Default device instance 246000. In automatic mode the instance is a base (246000, changeable in the configuration tool) + the SW2 MAC address; it can also be set manually or by writing Object_Identifier.
- Do not lengthen or modify the supplied S21 cable.
Watch out for
- Every function has a separate _command (AO/BO/MO, commandable) and _status (AI/BI/MI) object; write the command, read the status.
- Temperatures follow the Celsius/Fahrenheit DIP switch; the BACnet Units property changes with it.
- The Occupancy MV and its four AVs drive built-in logic that sets mode, setpoint and on/off; leave Occupancy at 3 (Disabled) unless you use it, and any manual on/off, mode or setpoint change cancels it.
- Mode_status can show AutoHeat/AutoCool (6, 7) that are not valid Mode_command values.
Intesis INBACDAI001I000 (Daikin domestic gateway) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 0 | OnOff_status | Unit on/off status | Read | 0=Off, 1=On | |
| BOmin | 0 | OnOff_command | Start/stop command for the indoor unit | Command | 0=Off, 1=On | |
| MI | 0 | Mode_status | Operating mode currently active | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool | |
| MOmin | 0 | Mode_command | Operating mode command | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 0 | SetPoint_status | Setpoint the indoor unit is actually using | °C | Read | |
| AOmin | 0 | SetPoint_command | Temperature setpoint command from the BMS | °C | Command | |
| MI | 1 | FanSpeed_status | Current fan speed | Read | 1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5 | |
| MOmin | 1 | FanSpeed_command | Fan speed command | Command | 1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5 | |
| MI | 2 | AirDirectionUD_status | Vertical (up/down) vane position | Read | 1=Stop, 2=Swing | |
| MO | 2 | AirDirectionUD_command | Vertical (up/down) vane command | Command | 1=Stop, 2=Swing | |
| MI | 3 | AirDirectionLR_status | Horizontal (left/right) vane position | Read | 1=Stop, 2=Swing | |
| MO | 3 | AirDirectionLR_command | Horizontal (left/right) vane command | Command | 1=Stop, 2=Swing | |
| AImin | 1 | RoomTemperature_status | Room temperature used by the indoor unit | °C | Read | |
| AImin | 2 | ErrorCode | Active error code as a number | Read | ||
| MI | 4 | ErrorCodeM | Active error code as a multistate value | Read | ||
| BImin | 1 | ErrorActive | An error is active on the indoor unit | Read | 0=No, 1=Error | |
| AV | 0 | OnTimeCounter | Accumulated run time of the unit | h | Read | |
| BV | 2 | LockRemoteControl | Locks or unlocks the wired remote controller | Write | 0=Locked, 1=Unlocked | |
| MI | 8 | Humidication_status | Humidification status | Read | 1=Off, 2=Low, 3=Mid, 4=High, 5=Continous | |
| MO | 6 | Humidication_command | Humidification command | Command | 1=Off, 2=ECONAVI, 3=AutoComfort |
No points match these filters.
Integration notes
- The object-detail chapter also describes Occupancy (MV 0, AV 1-4, BV 0-1) and OutdoorTemp_status (AI 8), which are not in the 20-object member table; they are left out here.
- There is no RoomTemperature_command object on this model.
- Humidification state texts look copied from another brand (command lists ECONAVI/AutoComfort); verify on site.
- LockRemoteControl (BV 2) state texts are printed as 0=Locked, 1=Unlocked.
- Units shown as °C follow the °C/°F DIP switch.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACDAI001I000 (Daikin domestic gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis INBACDAI001I000 (Daikin domestic gateway)
How many BACnet points does the Intesis INBACDAI001I000 (Daikin domestic gateway) have?
This list has 20 BACnet objects: 3 analog inputs, 1 analog output, 1 analog value, 2 binary inputs, 1 binary output, 1 binary value, 6 multi-state inputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis INBACDAI001I000 (Daikin domestic gateway) BACnet points are writable?
8 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Intesis INBACDAI001I000 (Daikin domestic gateway) BACnet documentation?
The source is Intesis BACnet - Domestic Daikin AC User Manual (INBACDAI001I000) (DK-AC-BAC-1 (legacy code)), revision 11/2024 v1.8, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacdai001i000.pdf.
What are the minimum BACnet points to integrate the Intesis INBACDAI001I000 (Daikin domestic gateway)?
Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).
How do I enable BMS control of the Intesis INBACDAI001I000 (Daikin domestic gateway)?
No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; BV 2 LockRemoteControl locks it.
How do I check these points on the real INBACDAI001I000 (Daikin domestic gateway)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP
Source: Intesis BACnet - Domestic Daikin AC User Manual (INBACDAI001I000) · DK-AC-BAC-1 (legacy code) · rev. 11/2024 v1.8. Object names, instances and units are reproduced as published; descriptions are our own.