Air conditioner BACnet gateway (1 indoor unit) · BACnet points list

Intesis INBACDAI001I000 (Daikin domestic gateway) BACnet points list

Updated 28 October 2026

Short answer

A one-unit Intesis interface that plugs into the S21 socket on a Daikin residential indoor unit's control board and serves it as BACnet MS/TP or BACnet IP. Its member table lists 20 objects: on/off, mode, setpoint, fan, up/down and left/right louvres, room temperature, errors, run hours, remote lock and humidification.

This page lists 20 BACnet objects for the Intesis INBACDAI001I000 (Daikin domestic gateway) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
INBACDAI001I000 (Daikin domestic gateway)
Equipment
Air conditioner BACnet gateway (1 indoor unit)
Equipment type
Other equipment
BACnet objects
20 (8 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
246000
Also known as
Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin
Source document
Intesis BACnet - Domestic Daikin AC User Manual (INBACDAI001I000) · DK-AC-BAC-1 (legacy code) · rev. 11/2024 v1.8
Download CSV 20 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Intesis INBACDAI001I000 (Daikin domestic gateway)

Integration in brief

Connect the gateway to the indoor unit (supplied 1.5 m cable into the S21 socket on the indoor control board), set the BACnet network on its DIP switches, then write the _command objects (on/off, mode, setpoint, fan) and read back the matching _status objects. One gateway serves one indoor unit (or one remote-controller group), so give each gateway its own MAC address and device instance.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0OnOff_commandStart/stop the indoor unitCommand
MO 0Mode_commandHeat/cool/fan/dry/auto selectionCommand
AO 0SetPoint_commandTemperature setpoint from the BMSCommand
MO 1FanSpeed_commandFan speed selectionCommand
BI 0OnOff_statusConfirm the unit is runningRead
AI 0SetPoint_statusSetpoint the unit is really usingRead
AI 1RoomTemperature_statusRoom/return temperature for trendingRead
BI 1ErrorActiveUnit alarmRead
AI 2ErrorCodeWhich fault is activeRead

Enable & remote start

No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; BV 2 LockRemoteControl locks it.

Network setup

Watch out for

Intesis INBACDAI001I000 (Daikin domestic gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

20 of 20 shown
Type
Access
Show
Intesis INBACDAI001I000 (Daikin domestic gateway) BACnet Points List
DescriptionStates
BImin0OnOff_statusUnit on/off statusRead0=Off, 1=On
BOmin0OnOff_commandStart/stop command for the indoor unitCommand0=Off, 1=On
MI0Mode_statusOperating mode currently activeRead1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool
MOmin0Mode_commandOperating mode commandCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin0SetPoint_statusSetpoint the indoor unit is actually using°CRead
AOmin0SetPoint_commandTemperature setpoint command from the BMS°CCommand
MI1FanSpeed_statusCurrent fan speedRead1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5
MOmin1FanSpeed_commandFan speed commandCommand1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5
MI2AirDirectionUD_statusVertical (up/down) vane positionRead1=Stop, 2=Swing
MO2AirDirectionUD_commandVertical (up/down) vane commandCommand1=Stop, 2=Swing
MI3AirDirectionLR_statusHorizontal (left/right) vane positionRead1=Stop, 2=Swing
MO3AirDirectionLR_commandHorizontal (left/right) vane commandCommand1=Stop, 2=Swing
AImin1RoomTemperature_statusRoom temperature used by the indoor unit°CRead
AImin2ErrorCodeActive error code as a numberRead
MI4ErrorCodeMActive error code as a multistate valueRead
BImin1ErrorActiveAn error is active on the indoor unitRead0=No, 1=Error
AV0OnTimeCounterAccumulated run time of the unithRead
BV2LockRemoteControlLocks or unlocks the wired remote controllerWrite0=Locked, 1=Unlocked
MI8Humidication_statusHumidification statusRead1=Off, 2=Low, 3=Mid, 4=High, 5=Continous
MO6Humidication_commandHumidification commandCommand1=Off, 2=ECONAVI, 3=AutoComfort

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACDAI001I000 (Daikin domestic gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis INBACDAI001I000 (Daikin domestic gateway)

How many BACnet points does the Intesis INBACDAI001I000 (Daikin domestic gateway) have?

This list has 20 BACnet objects: 3 analog inputs, 1 analog output, 1 analog value, 2 binary inputs, 1 binary output, 1 binary value, 6 multi-state inputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis INBACDAI001I000 (Daikin domestic gateway) BACnet points are writable?

8 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis INBACDAI001I000 (Daikin domestic gateway) BACnet documentation?

The source is Intesis BACnet - Domestic Daikin AC User Manual (INBACDAI001I000) (DK-AC-BAC-1 (legacy code)), revision 11/2024 v1.8, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacdai001i000.pdf.

What are the minimum BACnet points to integrate the Intesis INBACDAI001I000 (Daikin domestic gateway)?

Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).

How do I enable BMS control of the Intesis INBACDAI001I000 (Daikin domestic gateway)?

No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; BV 2 LockRemoteControl locks it.

How do I check these points on the real INBACDAI001I000 (Daikin domestic gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: Intesis BACnet - Domestic Daikin AC User Manual (INBACDAI001I000) · DK-AC-BAC-1 (legacy code) · rev. 11/2024 v1.8. Object names, instances and units are reproduced as published; descriptions are our own.