 "manufacturer": "Intesis",
 "manufacturer_slug": "intesis",
 "model": "INBACHIT001R000 (Hitachi VRF gateway)",
 "model_slug": "inbachit001r000",
 "aliases": [
  "Hitachi BACnet gateway",
  "Hitachi VRF BACnet",
  "Hitachi BACnet points list",
  "Intesis Hitachi BACnet IP MS/TP",
  "IN485HIT001R000"
 ],
 "equipment_type": "Air conditioner BACnet gateway (1 indoor unit)",
 "applies_to": "Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.",
 "summary": "A one-unit Intesis interface that sits on a Hitachi indoor unit's remote-controller bus and serves it as a BACnet MS/TP or BACnet IP device. It exposes 31 fixed objects (on/off, mode, setpoint, fan, louvre, room temperature, errors, filter, occupancy logic and remote-controller lock). Several indoor units on the same remote-controller bus can be connected but they are all driven as one group.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": 246000,
 "access_inferred": false,
 "notes": [
  "The member-object table lists ErrorReset as BI 5 but its object section is a Binary Output; it is listed here as BO 5.",
  "The capacity table says 33 objects; the member table lists 31 plus the Device object.",
  "Units shown as °C follow the °C/°F DIP switch.",
  "ErrorCodeM state texts are the Hitachi error codes listed in the manual's error-code chapter.",
  "UserSetPoint_status and VirtualTempActive report the virtual-temperature function driven by RoomTemperature_command."
 ],
 "source": {
  "title": "Intesis BACnet IP/MSTP - Hitachi VRF User Manual (INBACHIT001R000)",
  "doc_number": null,
  "revision_date": "09/2024 v1.4",
  "url": "https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbachit001r000-r1-0-en.pdf"
 },
 "integration": {
  "summary": "Connect the gateway to the indoor unit (two-wire A/B remote-controller bus, gateway port RC2, up to 500 m), set the BACnet network on its DIP switches, then write the _command objects (on/off, mode, setpoint, fan) and read back the matching _status objects. One gateway serves one indoor unit (or one remote-controller group), so give each gateway its own MAC address and device instance.",
  "minimum_points": [
   {
    "ref": "BO 0",
    "name": "OnOff_command",
    "why": "Start/stop the indoor unit"
   },
   {
    "ref": "MO 0",
    "name": "Mode_command",
    "why": "Heat/cool/fan/dry/auto selection"
   },
   {
    "ref": "AO 0",
    "name": "SetPoint_command",
    "why": "Temperature setpoint from the BMS"
   },
   {
    "ref": "MO 1",
    "name": "FanSpeed_command",
    "why": "Fan speed selection"
   },
   {
    "ref": "BI 0",
    "name": "OnOff_status",
    "why": "Confirm the unit is running"
   },
   {
    "ref": "AI 0",
    "name": "SetPoint_status",
    "why": "Setpoint the unit is really using"
   },
   {
    "ref": "AI 1",
    "name": "RoomTemperature_status",
    "why": "Room/return temperature for trending"
   },
   {
    "ref": "BI 1",
    "name": "ErrorActive",
    "why": "Unit alarm"
   },
   {
    "ref": "AI 2",
    "name": "ErrorCode",
    "why": "Which fault is active"
   }
  ],
  "enable": "No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; BV 2 LockRemoteControl locks it.",
  "heartbeat": null,
  "remote_sensors": "Write a BMS room temperature to AO 1 RoomTemperature_command. BI 14 VirtualTempActive shows whether the gateway is using it, and AI 17 UserSetPoint_status shows the user setpoint written from BACnet while it is active (AI 0 then shows the setpoint actually applied).",
  "setup": [
   "BACnet MS/TP or BACnet IP is chosen with a DIP switch (MS/TP is the default); switch changes need a power cycle.",
   "BACnet IP: factory static IP 192.168.100.246; change it (or select DHCP) with the Intesis configuration tool.",
   "MS/TP MAC address 0-127 is set on DIP switches; baud rate is DIP-selectable (9600-115200) with autobaud as the default.",
   "Default device instance 246000. In automatic mode the instance is a base (246000, changeable in the configuration tool) + the SW2 MAC address; it can also be set manually or by writing Object_Identifier.",
   "SW4 sets the gateway as slave (default) or master on the Hitachi A/B bus.",
   "The gateway is normally powered from the AC unit; a mini-USB port can power it for bench testing."
  ],
  "gotchas": [
   "Every function has a separate _command (AO/BO/MO, commandable) and _status (AI/BI/MI) object; write the command, read the status.",
   "Temperatures follow the Celsius/Fahrenheit DIP switch; the BACnet Units property changes with it.",
   "The Occupancy MV and its four AVs drive built-in logic that sets mode, setpoint and on/off; leave Occupancy at 3 (Disabled) unless you use it, and any manual on/off, mode or setpoint change cancels it.",
   "Several indoor units on one A/B bus are commanded together; individual commands to them are not possible."
  ]
 },
 "points": [
  {
   "type": "BI",
   "instance": 0,
   "name": "OnOff_status",
   "description": "Unit on/off status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "OnOff_command",
   "description": "Start/stop command for the indoor unit",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "MI",
   "instance": 0,
   "name": "Mode_status",
   "description": "Operating mode currently active",
   "units": "",
   "access": "R",
   "states": "1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto"
  },
  {
   "type": "MO",
   "instance": 0,
   "name": "Mode_command",
   "description": "Operating mode command",
   "units": "",
   "access": "C",
   "states": "1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto"
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "SetPoint_status",
   "description": "Setpoint the indoor unit is actually using",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "SetPoint_command",
   "description": "Temperature setpoint command from the BMS",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "FanSpeed_status",
   "description": "Current fan speed",
   "units": "",
   "access": "R",
   "states": "1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4"
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "FanSpeed_command",
   "description": "Fan speed command",
   "units": "",
   "access": "C",
   "states": "1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4"
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "AirDirectionUD_status",
   "description": "Vertical (up/down) vane position",
   "units": "",
   "access": "R",
   "states": "1=POS1, 2=POS2, 3=POS3, 4=POS4, 5=POS5, 6=POS6, 7=POS7, 8=SWING"
  },
  {
   "type": "MO",
   "instance": 2,
   "name": "AirDirectionUD_command",
   "description": "Vertical (up/down) vane command",
   "units": "",
   "access": "C",
   "states": "1=POS1, 2=POS2, 3=POS3, 4=POS4, 5=POS5, 6=POS6, 7=POS7, 8=SWING"
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "RoomTemperature_status",
   "description": "Room temperature used by the indoor unit",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "RoomTemperature_command",
   "description": "Room temperature written by the BMS (external sensor)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "ErrorCode",
   "description": "Active error code as a number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 4,
   "name": "ErrorCodeM",
   "description": "Active error code as a multistate value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "ErrorActive",
   "description": "An error is active on the indoor unit",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Error"
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "ErrorAddress",
   "description": "Address of the indoor unit reporting the error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "ErrorReset",
   "description": "Resets the error indication",
   "units": "",
   "access": "C",
   "states": "0=Normal, 1=Reset"
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "OnTimeCounter",
   "description": "Accumulated run time of the unit",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "FilterSign",
   "description": "Filter-clean indication",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "FilterReset",
   "description": "Resets the filter sign",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "Occupancy",
   "description": "Occupancy input for the built-in occupancy logic",
   "units": "",
   "access": "W",
   "states": "1=Occupied, 2=Unoccupied, 3=Disabled (default)"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "OccupiedCoolSetPoint",
   "description": "Cooling setpoint used while occupied",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "OccupiedHeatSetPoint",
   "description": "Heating setpoint used while occupied",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "UnoccupiedCoolSetPoint",
   "description": "Cooling setpoint used while unoccupied",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "UnoccupiedHeatSetPoint",
   "description": "Heating setpoint used while unoccupied",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "OccupancyContinuousCheck",
   "description": "Re-run occupancy logic on every temperature change",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "UnoccupiedDeadbandAction",
   "description": "Off or stay on when unoccupied inside the deadband",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=CurrentMode"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "LockRemoteControl",
   "description": "Locks or unlocks the wired remote controller",
   "units": "",
   "access": "W",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "UserSetPoint_status",
   "description": "User setpoint from BACnet while virtual temperature is active",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "VirtualTempActive",
   "description": "Virtual temperature function is in use",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "FilterSignAddress",
   "description": "Address of the indoor unit reporting the filter sign",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "covers_brands": [
  "Hitachi"
 ],
 "short_model": "Hitachi Gateway INBACHIT001R000",
 "page": "https://easybacnet.com/bacnet-points-lists/intesis/inbachit001r000",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}