Split air conditioner BACnet gateway (1 indoor unit) · BACnet points list

Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP) BACnet points list

Updated 11 November 2026

Short answer

One-unit Intesis interface that plugs into the CN105 socket of a Mitsubishi Electric indoor unit and exposes it on BACnet MS/TP as 31 fixed objects. Each function has a _command object to write and a _status object to read back. It includes left/right vane control, occupancy logic, a remote-controller lock and a virtual-temperature function that uses a BMS room sensor.

This page lists 31 BACnet objects for the Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Equipment
Split air conditioner BACnet gateway (1 indoor unit)
Equipment type
VRF & split air conditioners
BACnet objects
31 (16 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
246000
Also known as
IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP
Brands covered
Mitsubishi Electric
Source document
IN485MIT001I000 Gateway - Mitsubishi Electric Residential, Mr. Slim, and City Multi Systems to BACnet MS/TP - User Manual · rev. 2024-09-17 v1.2.7
Download CSV 31 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.

BMS integration notes: Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)

Integration in brief

Plug the gateway into the indoor unit's CN105 socket (CN92 on some units), set the MS/TP MAC address and baud rate on the DIP switches, then write the _command objects (on/off, mode, setpoint, fan, vanes) and read the matching _status objects. One gateway serves one indoor unit.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0OnOff_commandStart/stop the indoor unitCommand
MO 0Mode_commandHeat/cool/fan/dry/auto selectionCommand
AO 0SetPoint_commandTemperature setpoint from the BMSCommand
MO 1FanSpeed_commandFan speed selectionCommand
BI 0OnOff_statusConfirm the unit is runningRead
AI 0SetPoint_statusSetpoint the unit is really usingRead
AI 1RoomTemperature_statusRoom/return temperature for trendingRead
BI 1ErrorActiveUnit alarmRead
AI 2ErrorCodeWhich fault is activeRead

Enable & remote start

No enable point is documented; the gateway accepts commands as soon as it talks to the unit. BV 2 LockRemoteControl can lock out the wired remote.

Sensors & values from the BMS

Write the BMS room temperature to AO 1 RoomTemperature_command and the setpoint to AO 0. The gateway then runs its Virtual Temperature function and recalculates the setpoint it sends to the unit; BI 14 VirtualTempActive shows it is active and AI 17 UserSetPoint_status shows the BMS setpoint.

Network setup

Watch out for

Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

31 of 31 shown
Type
Access
Show
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP) BACnet Points List
DescriptionStates
BImin0OnOff_statusUnit on/off statusRead0=Off, 1=On
BOmin0OnOff_commandStart/stop the indoor unitCommand0=Off, 1=On
MI0Mode_statusOperating mode in useRead1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
MOmin0Mode_commandOperating mode commandCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin0SetPoint_statusSetpoint the indoor unit is using°CRead
AI17UserSetPoint_statusBMS setpoint while virtual temperature is active°CRead
AOmin0SetPoint_commandTemperature setpoint from the BMS°CCommand
BI14VirtualTempActiveVirtual temperature function in useRead0=No, 1=Yes
MI1FanSpeed_statusCurrent fan speedRead1=Auto, 2=Fan Speed 1 (Silent), 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5
MOmin1FanSpeed_commandFan speed commandCommand1=Auto, 2=Fan Speed 1 (Silent), 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5
MI2AirDirectionUD_statusUp/down vane positionRead1=Auto, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing
MO2AirDirectionUD_commandUp/down vane commandCommand1=Auto, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing
MI3AirDirectionLR_statusLeft/right vane positionRead1=Pos1, 2=Pos2, 3=Pos3, 4=Pos4, 5=Pos5, 6=Pos6 (Wide), 7=Swing
MO3AirDirectionLR_commandLeft/right vane commandCommand1=Pos1, 2=Pos2, 3=Pos3, 4=Pos4, 5=Pos5, 6=Pos6 (Wide), 7=Swing
AImin1RoomTemperature_statusRoom temperature used by the unit°CRead
AO1RoomTemperature_commandRoom temperature written by the BMS°CCommand
AImin2ErrorCodeActive error code (number)Read
MI4ErrorCodeMActive error code (multistate)Read1=-, 2=CommError, 3=1102, ... (full error code table in the manual)
BImin1ErrorActiveAn error is activeRead0=No, 1=Error
AV0OnTimeCounterRun-hours counterhWrite
MV0OccupancyOccupancy input for built-in occupancy logicWrite1=Occupied, 2=Unoccupied, 3=Disabled
AV1OccupiedCoolSetPointCooling setpoint when occupied°CWrite
AV2OccupiedHeatSetPointHeating setpoint when occupied°CWrite
AV3UnoccupiedCoolSetPointCooling setpoint when unoccupied°CWrite
AV4UnoccupiedHeatSetPointHeating setpoint when unoccupied°CWrite
BV0OccupancyContinuousCheckRe-run occupancy logic on temperature changeWrite0=Disabled, 1=Enabled
BV1UnoccupiedDeadbandActionUnoccupied action inside the deadbandWrite0=Off, 1=CurrentMode
BV2LockRemoteControlLock the wired remote controllerWrite0=Unlocked, 1=Locked
AI9DIP_SW_S1_statusDIP switch SW1 value (decimal)Read
AI10DIP_SW_S2_statusDIP switch SW2 value (decimal)Read
AI11SerialNumberGateway serial numberRead
Object ID lookup: Intesis Mitsubishi Gateway IN485MIT001I000 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)

How many BACnet points does the Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP) have?

This list has 31 BACnet objects: 7 analog inputs, 2 analog outputs, 5 analog values, 3 binary inputs, 1 binary output, 3 binary values, 5 multi-state inputs, 4 multi-state outputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP) BACnet points are writable?

16 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP) BACnet documentation?

The source is IN485MIT001I000 Gateway - Mitsubishi Electric Residential, Mr. Slim, and City Multi Systems to BACnet MS/TP - User Manual, revision 2024-09-17 v1.2.7, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user_manual_in485mit001i000.pdf.

What are the minimum BACnet points to integrate the Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)?

Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).

How do I enable BMS control of the Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)?

No enable point is documented; the gateway accepts commands as soon as it talks to the unit. BV 2 LockRemoteControl can lock out the wired remote.

Can the BMS supply sensor values to the Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)?

Write the BMS room temperature to AO 1 RoomTemperature_command and the setpoint to AO 0. The gateway then runs its Virtual Temperature function and recalculates the setpoint it sends to the unit; BI 14 VirtualTempActive shows it is active and AI 17 UserSetPoint_status shows the BMS setpoint.

How do I check these points on the real IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists