VRF BACnet gateway (multiple indoor units, P-Link/S-Link) · BACnet points list
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) BACnet points list
Updated 6 November 2026
Intesis 700 Series multi-protocol gateway set up for BACnet IP or BACnet MS/TP on a Panasonic U1U2 P-Link/S-Link bus. It publishes occupancy settings, gateway-wide commands, an outdoor-unit block (demand limit, pressures, compressor hours) and an indoor-unit block per unit: on/off, mode, setpoint, fan, vane, room temperature, a BMS ambient-temperature input, discharge setpoints, setpoint limits, error code, filter, remote-controller permissions, occupancy and energy consumption.
This page lists 69 BACnet objects for the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
- Equipment
- VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 69 (26 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic
- Brands covered
- Panasonic
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Wire the P-Link/S-Link U1U2 bus to AC-Port A (A1 U1, A2 U2), pick BACnet IP or BACnet MS/TP in Intesis MAPS, configure the units, send the project, then map each indoor unit's _C commands and _S status objects from its block.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | LXOXXUXX_On/Off_C | Start/stop indoor unit | Command |
| MO 100 | LXOXXUXX_Mode_C | Mode command | Command |
| AO 100 | LXOXXUXX_Setpoint_C | Setpoint command | Command |
| MO 101 | LXOXXUXX_FanSpeed_C | Fan speed command (1 = auto) | Command |
| BI 100 | LXOXXUXX_On/Off_S | Run status | Read |
| AI 100 | LXOXXUXX_Setpoint_S | Setpoint in use | Read |
| AI 101 | LXOXXUXX_Room Temperature | Indoor unit room temperature, °C | Read |
| BI 103 | LXOXXUXX_Communication Error IU | Unit offline on the Panasonic bus | Read |
| AI 114 | LXOXXUXX_Unit Error Code | Fault code (0 = no error) | Read |
Enable & remote start
No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 103-105).
Sensors & values from the BMS
AO 103 Bacnet ambient temperature takes a room temperature from the BMS; BI/BO 101 Wired Remote Controller select body sensor or remote-controller sensor.
Network setup
- BACnet IP: DHCP for 30 seconds at first start-up, then the default IP 192.168.100.246.
- BACnet MS/TP uses the gateway's EIA-485 port.
- Set up the units and the protocol in Intesis MAPS and send the project to the gateway.
Watch out for
- Gateway-wide objects (BO 0, MO 0-2, AO 0) act on all units at once.
- The occupancy AV/BV objects at instances 0-3 drive built-in occupancy logic together with each unit's Occupancy_C.
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 0 | Occupancy Cool Setpoint | Occupancy Cool Setpoint | °C | Write | |
| AV | 1 | Occupancy Heat Setpoint | Occupancy Heat Setpoint | °C | Write | |
| AV | 2 | Unoccupancy Cool Setpoint | Unoccupancy Cool Setpoint | °C | Write | |
| AV | 3 | Unoccupancy Heat Setpoint | Unoccupancy Heat Setpoint | °C | Write | |
| BV | 0 | Occupancy Continuous Check | Occupancy Continuous Check | Write | 0=Disabled, 1=Enabled | |
| BV | 1 | Unoccupancy Deadband Action | Unoccupancy Deadband Action | Write | 0=Off, 1=Current mode | |
| BO | 0 | On/Off (all units) | On/Off (all units) | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all units) | Mode (all units) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MO | 1 | FanSpeed (all units) | FanSpeed (all units) | Command | 1=Auto, 2=Low, 3=Med, 4=High | |
| MO | 2 | Vane Position (all units) | Vane Position (all units) | Command | 1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing | |
| AO | 0 | Temperature Setpoint (all units) | Temperature Setpoint (all units) | °C | Command | |
| BI | 10025 | LXOUXX_Communication Error OU | Communication Error OU | Read | 0=No error, 1=Error | |
| AI | 10025 | LXOUXX_Demand Limit. Ratio_S | Outdoor unit demand limit ratio, 0-200 % (status) | % | Read | 255=No limit |
| AO | 10025 | LXOUXX_Demand Limit. Ratio_C | Outdoor unit demand limit ratio, 0-200 % (command) | % | Command | 255=No limit |
| AI | 10026 | LXOUXX_High Pressure Sensor | High Pressure Sensor | bar | Read | |
| AI | 10027 | LXOUXX_Low Pressure Sensor | Low Pressure Sensor | bar | Read | |
| AI | 10028 | LXOUXX_Compressor_1_Working Time | Compressor 1 run hours | h | Read | |
| AI | 10029 | LXOUXX_Compressor_2_Working Time | Compressor 2 run hours | h | Read | |
| AI | 10030 | LXOUXX_Compressor_3_Working Time | Compressor 3 run hours | h | Read | |
| BImin | 100 | LXOXXUXX_On/Off_S | On/Off (status) | Read | 0=Off, 1=On | |
| BOmin | 100 | LXOXXUXX_On/Off_C | On/Off (command) | Command | 0=Off, 1=On | |
| MI | 100 | LXOXXUXX_Mode_S | Mode (status) | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool | |
| MOmin | 100 | LXOXXUXX_Mode_C | Mode (command) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 100 | LXOXXUXX_Setpoint_S | Setpoint (status) | °C | Read | |
| AOmin | 100 | LXOXXUXX_Setpoint_C | Setpoint (command) | °C | Command | |
| MI | 101 | LXOXXUXX_FanSpeed_S | FanSpeed (status) | Read | 1=Auto, 2=Low, 3=Low+, 4=Med, 5=Med+, 6=High | |
| MOmin | 101 | LXOXXUXX_FanSpeed_C | FanSpeed (command) | Command | 1=Auto, 2=Low, 3=Med, 4=High | |
| MI | 102 | LXOXXUXX_Vane Position_S | Vane Position (status) | Read | 1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing | |
| MO | 102 | LXOXXUXX_Vane Position_C | Vane Position (command) | Command | 1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing | |
| AImin | 101 | LXOXXUXX_Room Temperature | Room Temperature | °C | Read | |
| AO | 103 | LXOXXUXX_Bacnet ambient temperature | Room temperature written by the BMS | °C | Command | |
| BI | 101 | LXOXXUXX_Wired Remote Controller_S | Wired Remote Controller (status) | Read | 0=Body sensor, 1=Remote control sensor | |
| BO | 101 | LXOXXUXX_Wired Remote Controller_C | Wired Remote Controller (command) | Command | 0=Body sensor, 1=Remote control sensor | |
| AI | 102 | LXOXXUXX_Disch.Setpoint Cool_S | Disch.Setpoint Cool (status) | °C | Read | |
| AO | 101 | LXOXXUXX_Disch.Setpoint Cool_C | Disch.Setpoint Cool (command) | °C | Command | |
| AI | 103 | LXOXXUXX_Disch.Setpoint Heat_S | Disch.Setpoint Heat (status) | °C | Read | |
| AO | 102 | LXOXXUXX_Disch.Setpoint Heat_C | Disch.Setpoint Heat (command) | °C | Command | |
| AI | 104 | LXOXXUXX_Disch.Current Temp. | Disch.Current Temp. | °C | Read | |
| AI | 105 | LXOXXUXX_Heat Exchanger Temp. | Heat Exchanger Temp. | °C | Read | |
| AI | 106 | LXOXXUXX_Heat Setpoint Up Limit | Heat Setpoint Up Limit | °C | Read | |
| AI | 107 | LXOXXUXX_Heat Setpoint Low Limit | Heat Setpoint Low Limit | °C | Read | |
| AI | 108 | LXOXXUXX_Cool Setpoint Up Limit | Cool Setpoint Up Limit | °C | Read | |
| AI | 109 | LXOXXUXX_Cool Setpoint Low Limit | Cool Setpoint Low Limit | °C | Read | |
| AI | 110 | LXOXXUXX_Dry Setpoint Up Limit | Dry Setpoint Up Limit | °C | Read | |
| AI | 111 | LXOXXUXX_Dry Setpoint Low Limit | Dry Setpoint Low Limit | °C | Read | |
| AI | 112 | LXOXXUXX_Auto Setpoint Up Limit | Auto Setpoint Up Limit | °C | Read | |
| AI | 113 | LXOXXUXX_Auto Setpoint Low Limit | Auto Setpoint Low Limit | °C | Read | |
| AImin | 114 | LXOXXUXX_Unit Error Code | Unit error code | Read | 0=No Error, 1..255=Error | |
| BI | 102 | LXOXXUXX_Filter Sign | Filter Sign | Read | 0=Normal, 1=Alarm | |
| BO | 102 | LXOXXUXX_Filter Reset | Filter Reset | Command | 0=No reset, 1=Reset | |
| BImin | 103 | LXOXXUXX_Communication Error IU | Communication Error IU | Read | 0=No error, 1=Error | |
| BI | 104 | LXOXXUXX_Allow On/Off from RC_S | Allow On/Off from RC (status) | Read | 0=Not allow, 1=Allow | |
| BO | 103 | LXOXXUXX_Allow On/Off from RC_C | Allow On/Off from RC (command) | Command | 0=Not allow, 1=Allow | |
| BI | 105 | LXOXXUXX_Allow Mode from RC_S | Allow Mode from RC (status) | Read | 0=Not allow, 1=Allow | |
| BO | 104 | LXOXXUXX_Allow Mode from RC_C | Allow Mode from RC (command) | Command | 0=Not allow, 1=Allow | |
| BI | 106 | LXOXXUXX_Allow Setpoint from RC_S | Allow Setpoint from RC (status) | Read | 0=Not allow, 1=Allow | |
| BO | 105 | LXOXXUXX_Allow Setpoint from RC_C | Allow Setpoint from RC (command) | Command | 0=Not allow, 1=Allow | |
| MI | 103 | LXOXXUXX_Unit Type | Unit Type | Read | 1=Not Defined, 2=TBD, 3=GHP, 4=PAC, 5=VRF | |
| MI | 104 | LXOXXUXX_Occupancy_S | Occupancy (status) | Read | 1=Occupied, 2=Unoccupied, 3=Disable | |
| MO | 103 | LXOXXUXX_Occupancy_C | Occupancy (command) | Command | 1=Occupied, 2=Unoccupied, 3=Disable | |
| AI | 115 | LXOXXUXX_Consumption Yesterday | Consumption Yesterday | Wh/kWh | Read | |
| AI | 116 | LXOXXUXX_Consumption Today | Consumption Today | Wh/kWh | Read | |
| AI | 117 | LXOXXUXX_Consumption Total | Consumption Total | Wh/kWh | Read | |
| AI | 118 | LXOXXUXX_Consumption Yesterday Heat | Consumption Yesterday Heat | Wh/kWh | Read | |
| AI | 119 | LXOXXUXX_Consumption Today Heat | Consumption Today Heat | Wh/kWh | Read | |
| AI | 120 | LXOXXUXX_Consumption Total Heat | Consumption Total Heat | Wh/kWh | Read | |
| AI | 121 | LXOXXUXX_Consumption Yesterday Cool | Consumption Yesterday Cool | Wh/kWh | Read | |
| AI | 122 | LXOXXUXX_Consumption Today Cool | Consumption Today Cool | Wh/kWh | Read | |
| AI | 123 | LXOXXUXX_Consumption Total Cool | Consumption Total Cool | Wh/kWh | Read |
No points match these filters.
Object ID lookup: Intesis Panasonic VRF Gateway IN770 point IDs by name
AV0Occupancy Cool SetpointAV1Occupancy Heat SetpointAV2Unoccupancy Cool SetpointAV3Unoccupancy Heat SetpointBV0Occupancy Continuous CheckBV1Unoccupancy Deadband ActionBO0On/Off (all units)MO0Mode (all units)MO1FanSpeed (all units)MO2Vane Position (all units)AO0Temperature Setpoint (all units)BI10025LXOUXX_Communication Error OUAI10025LXOUXX_Demand Limit. Ratio_SAO10025LXOUXX_Demand Limit. Ratio_CAI10026LXOUXX_High Pressure SensorAI10027LXOUXX_Low Pressure SensorAI10028LXOUXX_Compressor_1_Working TimeAI10029LXOUXX_Compressor_2_Working TimeAI10030LXOUXX_Compressor_3_Working TimeBI100LXOXXUXX_On/Off_SBO100LXOXXUXX_On/Off_CMI100LXOXXUXX_Mode_SMO100LXOXXUXX_Mode_CAI100LXOXXUXX_Setpoint_SAO100LXOXXUXX_Setpoint_CMI101LXOXXUXX_FanSpeed_SMO101LXOXXUXX_FanSpeed_CMI102LXOXXUXX_Vane Position_SMO102LXOXXUXX_Vane Position_CAI101LXOXXUXX_Room TemperatureAO103LXOXXUXX_Bacnet ambient temperatureBI101LXOXXUXX_Wired Remote Controller_SBO101LXOXXUXX_Wired Remote Controller_CAI102LXOXXUXX_Disch.Setpoint Cool_SAO101LXOXXUXX_Disch.Setpoint Cool_CAI103LXOXXUXX_Disch.Setpoint Heat_SAO102LXOXXUXX_Disch.Setpoint Heat_CAI104LXOXXUXX_Disch.Current Temp.AI105LXOXXUXX_Heat Exchanger Temp.AI106LXOXXUXX_Heat Setpoint Up LimitAI107LXOXXUXX_Heat Setpoint Low LimitAI108LXOXXUXX_Cool Setpoint Up LimitAI109LXOXXUXX_Cool Setpoint Low LimitAI110LXOXXUXX_Dry Setpoint Up LimitAI111LXOXXUXX_Dry Setpoint Low LimitAI112LXOXXUXX_Auto Setpoint Up LimitAI113LXOXXUXX_Auto Setpoint Low LimitAI114LXOXXUXX_Unit Error CodeBI102LXOXXUXX_Filter SignBO102LXOXXUXX_Filter ResetBI103LXOXXUXX_Communication Error IUBI104LXOXXUXX_Allow On/Off from RC_SBO103LXOXXUXX_Allow On/Off from RC_CBI105LXOXXUXX_Allow Mode from RC_SBO104LXOXXUXX_Allow Mode from RC_CBI106LXOXXUXX_Allow Setpoint from RC_SBO105LXOXXUXX_Allow Setpoint from RC_CMI103LXOXXUXX_Unit TypeMI104LXOXXUXX_Occupancy_SMO103LXOXXUXX_Occupancy_CAI115LXOXXUXX_Consumption YesterdayAI116LXOXXUXX_Consumption TodayAI117LXOXXUXX_Consumption TotalAI118LXOXXUXX_Consumption Yesterday HeatAI119LXOXXUXX_Consumption Today HeatAI120LXOXXUXX_Consumption Total HeatAI121LXOXXUXX_Consumption Yesterday CoolAI122LXOXXUXX_Consumption Today CoolAI123LXOXXUXX_Consumption Total Cool
Integration notes
- Indoor unit instance = (IU x 100) + ((L - 1) x 20000) + offset, IU 1-64; IU 1 on L = 1 is shown (100-123).
- Outdoor unit instance = (OU x 25) + ((L - 1) x 1000) + 10000 + offset, OU 1-30; OU 1 on L = 1 is shown (10025-10030).
- The manual lists LXOUXX_Demand Limit. Ratio_C with type code 0 but labels it Analog Output; it is shown as AO here.
- The BACnet table has no read/write column; access is inferred from object type.
- Consumption objects report Wh or kWh as set in Intesis MAPS.
- Replaces the older INBACPAN016O000/064O000 BACnet server (listed separately), which uses a different object map.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
How many BACnet points does the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) have?
This list has 69 BACnet objects: 30 analog inputs, 6 analog outputs, 4 analog values, 8 binary inputs, 7 binary outputs, 2 binary values, 5 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) BACnet points are writable?
26 of the 69 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) BACnet documentation?
The source is 700 Series Air Gateway IN770AIR***O000 - Panasonic Systems (U1U2 P-Link/S-Link) to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual, revision 2025-12-09 v1.1.7, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770panxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)?
Start with BO 100 LXOXXUXX_On/Off_C (Start/stop indoor unit); MO 100 LXOXXUXX_Mode_C (Mode command); AO 100 LXOXXUXX_Setpoint_C (Setpoint command); MO 101 LXOXXUXX_FanSpeed_C (Fan speed command (1 = auto)); BI 100 LXOXXUXX_On/Off_S (Run status); AI 100 LXOXXUXX_Setpoint_S (Setpoint in use); AI 101 LXOXXUXX_Room Temperature (Indoor unit room temperature, °C); BI 103 LXOXXUXX_Communication Error IU (Unit offline on the Panasonic bus); AI 114 LXOXXUXX_Unit Error Code (Fault code (0 = no error)).
How do I enable BMS control of the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)?
No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 103-105).
Can the BMS supply sensor values to the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)?
AO 103 Bacnet ambient temperature takes a room temperature from the BMS; BI/BO 101 Wired Remote Controller select body sensor or remote-controller sensor.
How do I check these points on the real IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: 700 Series Air Gateway IN770AIR***O000 - Panasonic Systems (U1U2 P-Link/S-Link) to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · rev. 2025-12-09 v1.1.7. Object names, instances and units are reproduced as published; descriptions are our own.