Easy BACnet
  1. Home
  2. BACnet points lists
  3. Intesis
  4. IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)

VRF BACnet gateway (multiple indoor units, P-Link/S-Link) · BACnet points list

Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) BACnet points list

Updated 6 November 2026

Short answer

Intesis 700 Series multi-protocol gateway set up for BACnet IP or BACnet MS/TP on a Panasonic U1U2 P-Link/S-Link bus. It publishes occupancy settings, gateway-wide commands, an outdoor-unit block (demand limit, pressures, compressor hours) and an indoor-unit block per unit: on/off, mode, setpoint, fan, vane, room temperature, a BMS ambient-temperature input, discharge setpoints, setpoint limits, error code, filter, remote-controller permissions, occupancy and energy consumption.

This page lists 69 BACnet objects for the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Equipment
VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Equipment type
VRF & split air conditioners
BACnet objects
69 (26 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic
Brands covered
Panasonic
Source document
700 Series Air Gateway IN770AIR***O000 - Panasonic Systems (U1U2 P-Link/S-Link) to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · rev. 2025-12-09 v1.1.7
Download CSV 69 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.

BMS integration notes: Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)

Integration in brief

Wire the P-Link/S-Link U1U2 bus to AC-Port A (A1 U1, A2 U2), pick BACnet IP or BACnet MS/TP in Intesis MAPS, configure the units, send the project, then map each indoor unit's _C commands and _S status objects from its block.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 100LXOXXUXX_On/Off_CStart/stop indoor unitCommand
MO 100LXOXXUXX_Mode_CMode commandCommand
AO 100LXOXXUXX_Setpoint_CSetpoint commandCommand
MO 101LXOXXUXX_FanSpeed_CFan speed command (1 = auto)Command
BI 100LXOXXUXX_On/Off_SRun statusRead
AI 100LXOXXUXX_Setpoint_SSetpoint in useRead
AI 101LXOXXUXX_Room TemperatureIndoor unit room temperature, °CRead
BI 103LXOXXUXX_Communication Error IUUnit offline on the Panasonic busRead
AI 114LXOXXUXX_Unit Error CodeFault code (0 = no error)Read

Enable & remote start

No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 103-105).

Sensors & values from the BMS

AO 103 Bacnet ambient temperature takes a room temperature from the BMS; BI/BO 101 Wired Remote Controller select body sensor or remote-controller sensor.

Network setup

Watch out for

Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

69 of 69 shown
Type
Access
Show
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) BACnet Points List
DescriptionStates
AV0Occupancy Cool SetpointOccupancy Cool Setpoint°CWrite
AV1Occupancy Heat SetpointOccupancy Heat Setpoint°CWrite
AV2Unoccupancy Cool SetpointUnoccupancy Cool Setpoint°CWrite
AV3Unoccupancy Heat SetpointUnoccupancy Heat Setpoint°CWrite
BV0Occupancy Continuous CheckOccupancy Continuous CheckWrite0=Disabled, 1=Enabled
BV1Unoccupancy Deadband ActionUnoccupancy Deadband ActionWrite0=Off, 1=Current mode
BO0On/Off (all units)On/Off (all units)Command0=Off, 1=On
MO0Mode (all units)Mode (all units)Command1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
MO1FanSpeed (all units)FanSpeed (all units)Command1=Auto, 2=Low, 3=Med, 4=High
MO2Vane Position (all units)Vane Position (all units)Command1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing
AO0Temperature Setpoint (all units)Temperature Setpoint (all units)°CCommand
BI10025LXOUXX_Communication Error OUCommunication Error OURead0=No error, 1=Error
AI10025LXOUXX_Demand Limit. Ratio_SOutdoor unit demand limit ratio, 0-200 % (status)%Read255=No limit
AO10025LXOUXX_Demand Limit. Ratio_COutdoor unit demand limit ratio, 0-200 % (command)%Command255=No limit
AI10026LXOUXX_High Pressure SensorHigh Pressure SensorbarRead
AI10027LXOUXX_Low Pressure SensorLow Pressure SensorbarRead
AI10028LXOUXX_Compressor_1_Working TimeCompressor 1 run hourshRead
AI10029LXOUXX_Compressor_2_Working TimeCompressor 2 run hourshRead
AI10030LXOUXX_Compressor_3_Working TimeCompressor 3 run hourshRead
BImin100LXOXXUXX_On/Off_SOn/Off (status)Read0=Off, 1=On
BOmin100LXOXXUXX_On/Off_COn/Off (command)Command0=Off, 1=On
MI100LXOXXUXX_Mode_SMode (status)Read1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool
MOmin100LXOXXUXX_Mode_CMode (command)Command1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin100LXOXXUXX_Setpoint_SSetpoint (status)°CRead
AOmin100LXOXXUXX_Setpoint_CSetpoint (command)°CCommand
MI101LXOXXUXX_FanSpeed_SFanSpeed (status)Read1=Auto, 2=Low, 3=Low+, 4=Med, 5=Med+, 6=High
MOmin101LXOXXUXX_FanSpeed_CFanSpeed (command)Command1=Auto, 2=Low, 3=Med, 4=High
MI102LXOXXUXX_Vane Position_SVane Position (status)Read1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing
MO102LXOXXUXX_Vane Position_CVane Position (command)Command1=Stop, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Swing
AImin101LXOXXUXX_Room TemperatureRoom Temperature°CRead
AO103LXOXXUXX_Bacnet ambient temperatureRoom temperature written by the BMS°CCommand
BI101LXOXXUXX_Wired Remote Controller_SWired Remote Controller (status)Read0=Body sensor, 1=Remote control sensor
BO101LXOXXUXX_Wired Remote Controller_CWired Remote Controller (command)Command0=Body sensor, 1=Remote control sensor
AI102LXOXXUXX_Disch.Setpoint Cool_SDisch.Setpoint Cool (status)°CRead
AO101LXOXXUXX_Disch.Setpoint Cool_CDisch.Setpoint Cool (command)°CCommand
AI103LXOXXUXX_Disch.Setpoint Heat_SDisch.Setpoint Heat (status)°CRead
AO102LXOXXUXX_Disch.Setpoint Heat_CDisch.Setpoint Heat (command)°CCommand
AI104LXOXXUXX_Disch.Current Temp.Disch.Current Temp.°CRead
AI105LXOXXUXX_Heat Exchanger Temp.Heat Exchanger Temp.°CRead
AI106LXOXXUXX_Heat Setpoint Up LimitHeat Setpoint Up Limit°CRead
AI107LXOXXUXX_Heat Setpoint Low LimitHeat Setpoint Low Limit°CRead
AI108LXOXXUXX_Cool Setpoint Up LimitCool Setpoint Up Limit°CRead
AI109LXOXXUXX_Cool Setpoint Low LimitCool Setpoint Low Limit°CRead
AI110LXOXXUXX_Dry Setpoint Up LimitDry Setpoint Up Limit°CRead
AI111LXOXXUXX_Dry Setpoint Low LimitDry Setpoint Low Limit°CRead
AI112LXOXXUXX_Auto Setpoint Up LimitAuto Setpoint Up Limit°CRead
AI113LXOXXUXX_Auto Setpoint Low LimitAuto Setpoint Low Limit°CRead
AImin114LXOXXUXX_Unit Error CodeUnit error codeRead0=No Error, 1..255=Error
BI102LXOXXUXX_Filter SignFilter SignRead0=Normal, 1=Alarm
BO102LXOXXUXX_Filter ResetFilter ResetCommand0=No reset, 1=Reset
BImin103LXOXXUXX_Communication Error IUCommunication Error IURead0=No error, 1=Error
BI104LXOXXUXX_Allow On/Off from RC_SAllow On/Off from RC (status)Read0=Not allow, 1=Allow
BO103LXOXXUXX_Allow On/Off from RC_CAllow On/Off from RC (command)Command0=Not allow, 1=Allow
BI105LXOXXUXX_Allow Mode from RC_SAllow Mode from RC (status)Read0=Not allow, 1=Allow
BO104LXOXXUXX_Allow Mode from RC_CAllow Mode from RC (command)Command0=Not allow, 1=Allow
BI106LXOXXUXX_Allow Setpoint from RC_SAllow Setpoint from RC (status)Read0=Not allow, 1=Allow
BO105LXOXXUXX_Allow Setpoint from RC_CAllow Setpoint from RC (command)Command0=Not allow, 1=Allow
MI103LXOXXUXX_Unit TypeUnit TypeRead1=Not Defined, 2=TBD, 3=GHP, 4=PAC, 5=VRF
MI104LXOXXUXX_Occupancy_SOccupancy (status)Read1=Occupied, 2=Unoccupied, 3=Disable
MO103LXOXXUXX_Occupancy_COccupancy (command)Command1=Occupied, 2=Unoccupied, 3=Disable
AI115LXOXXUXX_Consumption YesterdayConsumption YesterdayWh/kWhRead
AI116LXOXXUXX_Consumption TodayConsumption TodayWh/kWhRead
AI117LXOXXUXX_Consumption TotalConsumption TotalWh/kWhRead
AI118LXOXXUXX_Consumption Yesterday HeatConsumption Yesterday HeatWh/kWhRead
AI119LXOXXUXX_Consumption Today HeatConsumption Today HeatWh/kWhRead
AI120LXOXXUXX_Consumption Total HeatConsumption Total HeatWh/kWhRead
AI121LXOXXUXX_Consumption Yesterday CoolConsumption Yesterday CoolWh/kWhRead
AI122LXOXXUXX_Consumption Today CoolConsumption Today CoolWh/kWhRead
AI123LXOXXUXX_Consumption Total CoolConsumption Total CoolWh/kWhRead
Object ID lookup: Intesis Panasonic VRF Gateway IN770 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)

How many BACnet points does the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) have?

This list has 69 BACnet objects: 30 analog inputs, 6 analog outputs, 4 analog values, 8 binary inputs, 7 binary outputs, 2 binary values, 5 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) BACnet points are writable?

26 of the 69 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway) BACnet documentation?

The source is 700 Series Air Gateway IN770AIR***O000 - Panasonic Systems (U1U2 P-Link/S-Link) to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual, revision 2025-12-09 v1.1.7, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770panxxxo000.pdf.

What are the minimum BACnet points to integrate the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)?

Start with BO 100 LXOXXUXX_On/Off_C (Start/stop indoor unit); MO 100 LXOXXUXX_Mode_C (Mode command); AO 100 LXOXXUXX_Setpoint_C (Setpoint command); MO 101 LXOXXUXX_FanSpeed_C (Fan speed command (1 = auto)); BI 100 LXOXXUXX_On/Off_S (Run status); AI 100 LXOXXUXX_Setpoint_S (Setpoint in use); AI 101 LXOXXUXX_Room Temperature (Indoor unit room temperature, °C); BI 103 LXOXXUXX_Communication Error IU (Unit offline on the Panasonic bus); AI 114 LXOXXUXX_Unit Error Code (Fault code (0 = no error)).

How do I enable BMS control of the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)?

No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 103-105).

Can the BMS supply sensor values to the Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)?

AO 103 Bacnet ambient temperature takes a room temperature from the BMS; BI/BO 101 Wired Remote Controller select body sensor or remote-controller sensor.

How do I check these points on the real IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: 700 Series Air Gateway IN770AIR***O000 - Panasonic Systems (U1U2 P-Link/S-Link) to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · rev. 2025-12-09 v1.1.7. Object names, instances and units are reproduced as published; descriptions are our own.