Air-to-water heat pump BACnet gateway · BACnet points list

Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) BACnet points list

Updated 4 November 2026

Short answer

Intesis interface for one Mitsubishi Electric Ecodan air-to-water system, plugged into CN105 and speaking BACnet MS/TP (default) or Modbus RTU. It exposes 115 objects: system and zone on/off, heat/cool mode, zone 1 and zone 2 setpoints with limits and water temperatures, DHW control (eco, boost, legionella), holiday mode, compressor, pump and backup-heater status, flow and energy counters.

This page lists 115 BACnet objects for the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Equipment
Air-to-water heat pump BACnet gateway
Equipment type
Heat pumps
BACnet objects
115 (27 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
246000
Also known as
IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan
Brands covered
Mitsubishi Electric
Source document
IN485MIT001A000 User Manual - Mitsubishi Electric Ecodan Air-to-Water Units to BACnet MS/TP and Modbus RTU · rev. 2025-12-02 v1.0.3
Download CSV 115 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.

BMS integration notes: Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)

Integration in brief

Plug the gateway into CN105 on the Ecodan board, leave SW1 position 5 OFF for BACnet MS/TP and set the MAC address on SW2. Turn the system on with OnOff_command, set heat or cool with ZonesMode_command (both zones follow), and write zone and DHW setpoints to their _command objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 4OnOff_commandTurn the Ecodan system on/offCommand
MO 0ZonesMode_commandHeat or cool for both zonesCommand
BO 15DHWOnOff_commandDomestic hot water on/offCommand
AO 3Zone1TempSetpoint_commandZone 1 setpoint from the BMSCommand
AO 24DHWTempSetpoint_commandDHW tank setpointCommand
BI 5OnOff_statusConfirms the system is onRead
AI 74TempOutletWaterRef_statusFlow water temperatureRead
BI 1ErrorFlag_statusUnit alarmRead
AI 2ErrorCode_statusWhich fault is activeRead

Enable & remote start

BO 3 RemoteControlLock_command = 1 lets only the BMS control the unit; remote-controller commands are then ignored.

Sensors & values from the BMS

Write a BMS room temperature to AO 8 Zone1TempBACnetRoomThermAmbientRef_command (AO 22 for zone 2). Once a valid value is written, the gateway's Virtual Temperature function uses it to offset the setpoint.

Network setup

Watch out for

Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

115 of 115 shown
Type
Access
Show
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) BACnet Points List
DescriptionStates
AI0SerialNumberGateway serial numberRead
AI86DIP_SW_1_statusDIP SW1 (status)Read
AI87DIP_SW_2_statusDIP SW2 (status)Read
AI1IndoorUnitAddress_statusIndoor unit address (status)Read
AO0IndoorUnitAddress_commandIndoor unit address (command)Command
BImin1ErrorFlag_statusError flag (status)Read0=No Error, 1=Error
AImin2ErrorCode_statusError code (status)Read0=No error, other=error code
AI3ErrorSubCode_statusError sub code (status)Read0=No error, other=error code
BI3RefrigerantLeakDetectorSignalFlag_statusRefrigerant leak detector signal flag (status)Read0=No Error, 1=Error
AI8OperatingTimeCountHour_statusOperating time count hours (status)hRead
BI4RemoteControlLock_statusRemote control lock (status)Read0=Unlocked, 1=Locked
BO3RemoteControlLock_commandRemote control lock (command)Command0=Unlocked, 1=Locked
BImin5OnOff_statusUnit on/off statusRead0=Off, 1=On
BOmin4OnOff_commandStart/stop the indoor unitCommand0=Off, 1=On
BI6Operation_statusOperation (status)Read0=Not Operating, 1=Operating
BI7ZonesOnOff_statusZones on/off (status)Read0=Off, 1=On
BI8ZonesOperation_statusZones operation (status)Read0=Not Operating, 1=Operating
MI0ZonesMode_statusZones mode (status)Read1=Heat, 2=Cool
MOmin0ZonesMode_commandZones mode (command)Command1=Heat, 2=Cool
BI10Zone1OnOff_statusZone 1 on/off (status)Read0=Off, 1=On
BI11Zone1Operation_statusZone 1 operation (status)Read0=Not Operating, 1=Operating
MI2Zone1ControlType_statusZone 1 control type (status)Read1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve
MO1Zone1ControlType_commandZone 1 control type (command)Command1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve
AI9Zone1TempSetpoint_statusZone 1 temperature setpoint (status)°CRead
AOmin3Zone1TempSetpoint_commandZone 1 temperature setpoint (command)°CCommand
AI10Zone1TempSetpointLowCustomerLimitHeat_statusZone 1 temperature setpoint lower customer limit heat (status)°CRead
AO4Zone1TempSetpointLowCustomerLimitHeat_commandZone 1 temperature setpoint lower customer limit heat (command)°CCommand
AI11Zone1TempSetpointUpCustomerLimitHeat_statusZone 1 temperature setpoint upper customer limit heat (status)°CRead
AO5Zone1TempSetpointUpCustomerLimitHeat_commandZone 1 temperature setpoint upper customer limit heat (command)°CCommand
AI12Zone1TempSetpointLowCustomerLimitCool_statusZone 1 temperature setpoint lower customer limit cool (status)°CRead
AO6Zone1TempSetpointLowCustomerLimitCool_commandZone 1 temperature setpoint lower customer limit cool (command)°CCommand
AI13Zone1TempSetpointUpCustomerLimitCool_statusZone 1 temperature setpoint upper customer limit cool (status)°CRead
AO7Zone1TempSetpointUpCustomerLimitCool_commandZone 1 temperature setpoint upper customer limit cool (command)°CCommand
AI14Zone1TempSetpointUnitLowLimitHeat_statusZone 1 temperature setpoint unit lower limit heat (status)°CRead
AI15Zone1TempSetpointUnitUpLimitHeat_statusZone 1 temperature setpoint unit upper limit heat (status)°CRead
AI16Zone1TempSetpointUnitLowLimitCool_statusZone 1 temperature setpoint unit lower limit cool (status)°CRead
AI17Zone1TempSetpointUnitUpLimitCool_statusZone 1 temperature setpoint unit upper limit cool (status)°CRead
AI18Zone1TempSetpointAppliedLowLimitHeat_statusZone 1 temperature setpoint applied lower limit heat (status)°CRead
AI19Zone1TempSetpointAppliedUpLimitHeat_statusZone 1 temperature setpoint applied upper limit heat (status)°CRead
AI20Zone1TempSetpointAppliedLowLimitCool_statusZone 1 temperature setpoint applied lower limit cool (status)°CRead
AI21Zone1TempSetpointAppliedUpLimitCool_statusZone 1 temperature setpoint applied upper limit cool (status)°CRead
AI22Zone1TempRef_statusZone 1 temperature reading (status)°CRead
AO8Zone1TempBACnetRoomThermAmbientRef_commandZone 1 temperature BMS room sensor ambient reading (command)°CCommand
AI24Zone1TempOutletWaterRef_statusZone 1 temperature outlet water reading (status)°CRead
AI25Zone1TempInletWaterRef_statusZone 1 temperature inlet water reading (status)°CRead
BI17Zone2OnOff_statusZone 2 on/off (status)Read0=Off, 1=On
BI18Zone2Operation_statusZone 2 operation (status)Read0=Not Operating, 1=Operating
MI5Zone2ControlType_statusZone 2 control type (status)Read1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve
MO3Zone2ControlType_commandZone 2 control type (command)Command1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve
AI43Zone2TempSetpoint_statusZone 2 temperature setpoint (status)°CRead
AO17Zone2TempSetpoint_commandZone 2 temperature setpoint (command)°CCommand
AI44Zone2TempSetpointLowCustomerLimitHeat_statusZone 2 temperature setpoint lower customer limit heat (status)°CRead
AO18Zone2TempSetpointLowCustomerLimitHeat_commandZone 2 temperature setpoint lower customer limit heat (command)°CCommand
AI45Zone2TempSetpointUpCustomerLimitHeat_statusZone 2 temperature setpoint upper customer limit heat (status)°CRead
AO19Zone2TempSetpointUpCustomerLimitHeat_commandZone 2 temperature setpoint upper customer limit heat (command)°CCommand
AI46Zone2TempSetpointLowCustomerLimitCool_statusZone 2 temperature setpoint lower customer limit cool (status)°CRead
AO20Zone2TempSetpointLowCustomerLimitCool_commandZone 2 temperature setpoint lower customer limit cool (command)°CCommand
AI47Zone2TempSetpointUpCustomerLimitCool_statusZone 2 temperature setpoint upper customer limit cool (status)°CRead
AO21Zone2TempSetpointUpCustomerLimitCool_commandZone 2 temperature setpoint upper customer limit cool (command)°CCommand
AI48Zone2TempSetpointUnitLowLimitHeat_statusZone 2 temperature setpoint unit lower limit heat (status)°CRead
AI49Zone2TempSetpointUnitUpLimitHeat_statusZone 2 temperature setpoint unit upper limit heat (status)°CRead
AI50Zone2TempSetpointUnitLowLimitCool_statusZone 2 temperature setpoint unit lower limit cool (status)°CRead
AI51Zone2TempSetpointUnitUpLimitCool_statusZone 2 temperature setpoint unit upper limit cool (status)°CRead
AI52Zone2TempSetpointAppliedLowLimitHeat_statusZone 2 temperature setpoint applied lower limit heat (status)°CRead
AI53Zone2TempSetpointAppliedUpLimitHeat_statusZone 2 temperature setpoint applied upper limit heat (status)°CRead
AI54Zone2TempSetpointAppliedLowLimitCool_statusZone 2 temperature setpoint applied lower limit cool (status)°CRead
AI55Zone2TempSetpointAppliedUpLimitCool_statusZone 2 temperature setpoint applied upper limit cool (status)°CRead
AI56Zone2TempRef_statusZone 2 temperature reading (status)°CRead
AO22Zone2TempBACnetRoomThermAmbientRef_commandZone 2 temperature BMS room sensor ambient reading (command)°CCommand
AI58Zone2TempOutletWaterRef_statusZone 2 temperature outlet water reading (status)°CRead
AI59Zone2TempInletWaterRef_statusZone 2 temperature inlet water reading (status)°CRead
BI22DHWOnOff_statusDHW on/off (status)Read0=Off, 1=On
BOmin15DHWOnOff_commandDHW on/off (command)Command0=Off, 1=On
BI23DHWOperation_statusDHW operation (status)Read0=Not Operating, 1=Operating
AI61DHWTempSetpoint_statusDHW temperature setpoint (status)°CRead
AOmin24DHWTempSetpoint_commandDHW temperature setpoint (command)°CCommand
AI62DHWTempSetpointCustomLowLimit_statusDHW temperature setpoint custom lower limit (status)°CRead
AO25DHWTempSetpointCustomLowLimit_commandDHW temperature setpoint custom lower limit (command)°CCommand
AI63DHWTempSetpointCustomUpLimit_statusDHW temperature setpoint custom upper limit (status)°CRead
AO26DHWTempSetpointCustomUpLimit_commandDHW temperature setpoint custom upper limit (command)°CCommand
AI64DHWTempSetpointTankLowLimit_statusDHW temperature setpoint tank lower limit (status)°CRead
AI65DHWTempSetpointTankUpLimit_statusDHW temperature setpoint tank upper limit (status)°CRead
AI66DHWTempSetpointAppliedLowLimit_statusDHW temperature setpoint applied lower limit (status)°CRead
AI67DHWTempSetpointAppliedUpLimit_statusDHW temperature setpoint applied upper limit (status)°CRead
AI68DHWTempTankRef_statusDHW temperature tank reading (status)°CRead
BI26DHWEcoMode_statusDHW eco mode (status)Read0=Off, 1=On
BO18DHWEcoMode_commandDHW eco mode (command)Command0=Off, 1=On
BI29DHWPowerfulOperation_statusDHW powerful operation (status)Read0=Off, 1=On
BO21DHWPowerfulOperation_commandDHW powerful operation (command)Command0=Off, 1=On
BI30DHWDisinfectionMode_statusDHW disinfection mode (status)Read0=Off, 1=On
AI72TempA2WUnitOutdoorAmbientRef_statusTemperature heatpump unit outdoor ambient reading (status)°CRead
AI73TempRefrigerantRef_statusTemperature refrigerant reading (status)°CRead
AImin74TempOutletWaterRef_statusTemperature outlet water reading (status)°CRead
AI76TempInletWaterRef_statusTemperature inlet water reading (status)°CRead
BI31HolidayMode_statusHoliday mode (status)Read0=Off, 1=On
BO23HolidayMode_commandHoliday mode (command)Command0=Off, 1=On
BI33EmergencyOperation_statusEmergency operation (status)Read0=Off, 1=On
BI34DefrostStartUp_statusDefrost startup (status)Read0=Defrost/Start Up, 1=Hot Start
BI36ThreeWayValveOperation_statusThree way valve operation (status)Read0=Climatize, 1=DHW
BI37BackUpHeaterOperationLevel1_statusBackup heater operation level 1 (status)Read0=Off, 1=On
BI38BackUpHeaterOperationLevel2_statusBackup heater operation level 2 (status)Read0=Off, 1=On
BI40CompressorOperation_statusCompressor operation (status)Read0=Off, 1=On
AI77CompressorOperatingTime_statusCompressor operating time (status)hRead
AO30CompressorOperatingTime_commandCompressor operating time (command)hCommand
BI41CirculationPumpOperation_statusCirculation pump operation (status)Read0=Off, 1=On
AI78CirculationPumpOperatingTime_statusCirculation pump operating time (status)hRead
AO31CirculationPumpOperatingTime_commandCirculation pump operating time (command)hCommand
AI79WaterFlowRate_statusWater flow rate (status)l/hRead
AI81EnergyConsumptionTotal_statusEnergy consumption total (status)kWhRead
AI82EnergyConsumptionZonesHeat_statusEnergy consumption zones heat (status)kWhRead
AI83EnergyConsumptionZonesCool_statusEnergy consumption zones cool (status)kWhRead
AI84EnergyConsumptionDHW_statusEnergy consumption DHW (status)kWhRead
BI45ZonesHeatModeSupport_statusZones heat mode support (status)Read0=No, 1=Yes
BI46ZonesCoolModeSupport_statusZones cool mode support (status)Read0=No, 1=Yes
BI47DHWSupport_statusDHW support (status)Read0=No, 1=Yes
Object ID lookup: Intesis Mitsubishi Electric Ecodan Gateway IN485MIT001A000 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)

How many BACnet points does the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) have?

This list has 115 BACnet objects: 58 analog inputs, 18 analog outputs, 27 binary inputs, 6 binary outputs, 3 multi-state inputs, 3 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) BACnet points are writable?

27 of the 115 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) BACnet documentation?

The source is IN485MIT001A000 User Manual - Mitsubishi Electric Ecodan Air-to-Water Units to BACnet MS/TP and Modbus RTU, revision 2025-12-02 v1.0.3, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in485mit001a000.pdf.

What are the minimum BACnet points to integrate the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)?

Start with BO 4 OnOff_command (Turn the Ecodan system on/off); MO 0 ZonesMode_command (Heat or cool for both zones); BO 15 DHWOnOff_command (Domestic hot water on/off); AO 3 Zone1TempSetpoint_command (Zone 1 setpoint from the BMS); AO 24 DHWTempSetpoint_command (DHW tank setpoint); BI 5 OnOff_status (Confirms the system is on); AI 74 TempOutletWaterRef_status (Flow water temperature); BI 1 ErrorFlag_status (Unit alarm); AI 2 ErrorCode_status (Which fault is active).

How do I enable BMS control of the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)?

BO 3 RemoteControlLock_command = 1 lets only the BMS control the unit; remote-controller commands are then ignored.

Can the BMS supply sensor values to the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)?

Write a BMS room temperature to AO 8 Zone1TempBACnetRoomThermAmbientRef_command (AO 22 for zone 2). Once a valid value is written, the gateway's Virtual Temperature function uses it to offset the setpoint.

How do I check these points on the real IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: IN485MIT001A000 User Manual - Mitsubishi Electric Ecodan Air-to-Water Units to BACnet MS/TP and Modbus RTU · rev. 2025-12-02 v1.0.3. Object names, instances and units are reproduced as published; descriptions are our own.