- Home
- BACnet points lists
- Intesis
- IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Air-to-water heat pump BACnet gateway · BACnet points list
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) BACnet points list
Updated 4 November 2026
Intesis interface for one Mitsubishi Electric Ecodan air-to-water system, plugged into CN105 and speaking BACnet MS/TP (default) or Modbus RTU. It exposes 115 objects: system and zone on/off, heat/cool mode, zone 1 and zone 2 setpoints with limits and water temperatures, DHW control (eco, boost, legionella), holiday mode, compressor, pump and backup-heater status, flow and energy counters.
This page lists 115 BACnet objects for the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
- Equipment
- Air-to-water heat pump BACnet gateway
- Equipment type
- Heat pumps
- BACnet objects
- 115 (27 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 246000
- Also known as
- IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan
- Brands covered
- Mitsubishi Electric
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Plug the gateway into CN105 on the Ecodan board, leave SW1 position 5 OFF for BACnet MS/TP and set the MAC address on SW2. Turn the system on with OnOff_command, set heat or cool with ZonesMode_command (both zones follow), and write zone and DHW setpoints to their _command objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 4 | OnOff_command | Turn the Ecodan system on/off | Command |
| MO 0 | ZonesMode_command | Heat or cool for both zones | Command |
| BO 15 | DHWOnOff_command | Domestic hot water on/off | Command |
| AO 3 | Zone1TempSetpoint_command | Zone 1 setpoint from the BMS | Command |
| AO 24 | DHWTempSetpoint_command | DHW tank setpoint | Command |
| BI 5 | OnOff_status | Confirms the system is on | Read |
| AI 74 | TempOutletWaterRef_status | Flow water temperature | Read |
| BI 1 | ErrorFlag_status | Unit alarm | Read |
| AI 2 | ErrorCode_status | Which fault is active | Read |
Enable & remote start
BO 3 RemoteControlLock_command = 1 lets only the BMS control the unit; remote-controller commands are then ignored.
Sensors & values from the BMS
Write a BMS room temperature to AO 8 Zone1TempBACnetRoomThermAmbientRef_command (AO 22 for zone 2). Once a valid value is written, the gateway's Virtual Temperature function uses it to offset the setpoint.
Network setup
- SW1 P5: OFF = BACnet MS/TP (default), ON = Modbus RTU; SW1 P6-P8 baud rate, autobaud by default.
- MS/TP MAC address on SW2 P1-P7; SW2 P8 selects °C (default) or °F.
- Default device instance 246000; in automatic mode it is 246000 + the MAC address. Writing Object_Identifier switches to manual addressing until a factory reset.
- DIP switch changes take effect after a reboot.
Watch out for
- Write the _command object and read the matching _status object; they have different object types and instance numbers.
- Custom setpoint limits cannot go past the unit's own limits (the Unit...Limit objects); the Applied...Limit objects show the range in force.
- Write 0 to CompressorOperatingTime_command or CirculationPumpOperatingTime_command to reset that run-hour counter.
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | SerialNumber | Gateway serial number | Read | ||
| AI | 86 | DIP_SW_1_status | DIP SW1 (status) | Read | ||
| AI | 87 | DIP_SW_2_status | DIP SW2 (status) | Read | ||
| AI | 1 | IndoorUnitAddress_status | Indoor unit address (status) | Read | ||
| AO | 0 | IndoorUnitAddress_command | Indoor unit address (command) | Command | ||
| BImin | 1 | ErrorFlag_status | Error flag (status) | Read | 0=No Error, 1=Error | |
| AImin | 2 | ErrorCode_status | Error code (status) | Read | 0=No error, other=error code | |
| AI | 3 | ErrorSubCode_status | Error sub code (status) | Read | 0=No error, other=error code | |
| BI | 3 | RefrigerantLeakDetectorSignalFlag_status | Refrigerant leak detector signal flag (status) | Read | 0=No Error, 1=Error | |
| AI | 8 | OperatingTimeCountHour_status | Operating time count hours (status) | h | Read | |
| BI | 4 | RemoteControlLock_status | Remote control lock (status) | Read | 0=Unlocked, 1=Locked | |
| BO | 3 | RemoteControlLock_command | Remote control lock (command) | Command | 0=Unlocked, 1=Locked | |
| BImin | 5 | OnOff_status | Unit on/off status | Read | 0=Off, 1=On | |
| BOmin | 4 | OnOff_command | Start/stop the indoor unit | Command | 0=Off, 1=On | |
| BI | 6 | Operation_status | Operation (status) | Read | 0=Not Operating, 1=Operating | |
| BI | 7 | ZonesOnOff_status | Zones on/off (status) | Read | 0=Off, 1=On | |
| BI | 8 | ZonesOperation_status | Zones operation (status) | Read | 0=Not Operating, 1=Operating | |
| MI | 0 | ZonesMode_status | Zones mode (status) | Read | 1=Heat, 2=Cool | |
| MOmin | 0 | ZonesMode_command | Zones mode (command) | Command | 1=Heat, 2=Cool | |
| BI | 10 | Zone1OnOff_status | Zone 1 on/off (status) | Read | 0=Off, 1=On | |
| BI | 11 | Zone1Operation_status | Zone 1 operation (status) | Read | 0=Not Operating, 1=Operating | |
| MI | 2 | Zone1ControlType_status | Zone 1 control type (status) | Read | 1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve | |
| MO | 1 | Zone1ControlType_command | Zone 1 control type (command) | Command | 1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve | |
| AI | 9 | Zone1TempSetpoint_status | Zone 1 temperature setpoint (status) | °C | Read | |
| AOmin | 3 | Zone1TempSetpoint_command | Zone 1 temperature setpoint (command) | °C | Command | |
| AI | 10 | Zone1TempSetpointLowCustomerLimitHeat_status | Zone 1 temperature setpoint lower customer limit heat (status) | °C | Read | |
| AO | 4 | Zone1TempSetpointLowCustomerLimitHeat_command | Zone 1 temperature setpoint lower customer limit heat (command) | °C | Command | |
| AI | 11 | Zone1TempSetpointUpCustomerLimitHeat_status | Zone 1 temperature setpoint upper customer limit heat (status) | °C | Read | |
| AO | 5 | Zone1TempSetpointUpCustomerLimitHeat_command | Zone 1 temperature setpoint upper customer limit heat (command) | °C | Command | |
| AI | 12 | Zone1TempSetpointLowCustomerLimitCool_status | Zone 1 temperature setpoint lower customer limit cool (status) | °C | Read | |
| AO | 6 | Zone1TempSetpointLowCustomerLimitCool_command | Zone 1 temperature setpoint lower customer limit cool (command) | °C | Command | |
| AI | 13 | Zone1TempSetpointUpCustomerLimitCool_status | Zone 1 temperature setpoint upper customer limit cool (status) | °C | Read | |
| AO | 7 | Zone1TempSetpointUpCustomerLimitCool_command | Zone 1 temperature setpoint upper customer limit cool (command) | °C | Command | |
| AI | 14 | Zone1TempSetpointUnitLowLimitHeat_status | Zone 1 temperature setpoint unit lower limit heat (status) | °C | Read | |
| AI | 15 | Zone1TempSetpointUnitUpLimitHeat_status | Zone 1 temperature setpoint unit upper limit heat (status) | °C | Read | |
| AI | 16 | Zone1TempSetpointUnitLowLimitCool_status | Zone 1 temperature setpoint unit lower limit cool (status) | °C | Read | |
| AI | 17 | Zone1TempSetpointUnitUpLimitCool_status | Zone 1 temperature setpoint unit upper limit cool (status) | °C | Read | |
| AI | 18 | Zone1TempSetpointAppliedLowLimitHeat_status | Zone 1 temperature setpoint applied lower limit heat (status) | °C | Read | |
| AI | 19 | Zone1TempSetpointAppliedUpLimitHeat_status | Zone 1 temperature setpoint applied upper limit heat (status) | °C | Read | |
| AI | 20 | Zone1TempSetpointAppliedLowLimitCool_status | Zone 1 temperature setpoint applied lower limit cool (status) | °C | Read | |
| AI | 21 | Zone1TempSetpointAppliedUpLimitCool_status | Zone 1 temperature setpoint applied upper limit cool (status) | °C | Read | |
| AI | 22 | Zone1TempRef_status | Zone 1 temperature reading (status) | °C | Read | |
| AO | 8 | Zone1TempBACnetRoomThermAmbientRef_command | Zone 1 temperature BMS room sensor ambient reading (command) | °C | Command | |
| AI | 24 | Zone1TempOutletWaterRef_status | Zone 1 temperature outlet water reading (status) | °C | Read | |
| AI | 25 | Zone1TempInletWaterRef_status | Zone 1 temperature inlet water reading (status) | °C | Read | |
| BI | 17 | Zone2OnOff_status | Zone 2 on/off (status) | Read | 0=Off, 1=On | |
| BI | 18 | Zone2Operation_status | Zone 2 operation (status) | Read | 0=Not Operating, 1=Operating | |
| MI | 5 | Zone2ControlType_status | Zone 2 control type (status) | Read | 1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve | |
| MO | 3 | Zone2ControlType_command | Zone 2 control type (command) | Command | 1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve | |
| AI | 43 | Zone2TempSetpoint_status | Zone 2 temperature setpoint (status) | °C | Read | |
| AO | 17 | Zone2TempSetpoint_command | Zone 2 temperature setpoint (command) | °C | Command | |
| AI | 44 | Zone2TempSetpointLowCustomerLimitHeat_status | Zone 2 temperature setpoint lower customer limit heat (status) | °C | Read | |
| AO | 18 | Zone2TempSetpointLowCustomerLimitHeat_command | Zone 2 temperature setpoint lower customer limit heat (command) | °C | Command | |
| AI | 45 | Zone2TempSetpointUpCustomerLimitHeat_status | Zone 2 temperature setpoint upper customer limit heat (status) | °C | Read | |
| AO | 19 | Zone2TempSetpointUpCustomerLimitHeat_command | Zone 2 temperature setpoint upper customer limit heat (command) | °C | Command | |
| AI | 46 | Zone2TempSetpointLowCustomerLimitCool_status | Zone 2 temperature setpoint lower customer limit cool (status) | °C | Read | |
| AO | 20 | Zone2TempSetpointLowCustomerLimitCool_command | Zone 2 temperature setpoint lower customer limit cool (command) | °C | Command | |
| AI | 47 | Zone2TempSetpointUpCustomerLimitCool_status | Zone 2 temperature setpoint upper customer limit cool (status) | °C | Read | |
| AO | 21 | Zone2TempSetpointUpCustomerLimitCool_command | Zone 2 temperature setpoint upper customer limit cool (command) | °C | Command | |
| AI | 48 | Zone2TempSetpointUnitLowLimitHeat_status | Zone 2 temperature setpoint unit lower limit heat (status) | °C | Read | |
| AI | 49 | Zone2TempSetpointUnitUpLimitHeat_status | Zone 2 temperature setpoint unit upper limit heat (status) | °C | Read | |
| AI | 50 | Zone2TempSetpointUnitLowLimitCool_status | Zone 2 temperature setpoint unit lower limit cool (status) | °C | Read | |
| AI | 51 | Zone2TempSetpointUnitUpLimitCool_status | Zone 2 temperature setpoint unit upper limit cool (status) | °C | Read | |
| AI | 52 | Zone2TempSetpointAppliedLowLimitHeat_status | Zone 2 temperature setpoint applied lower limit heat (status) | °C | Read | |
| AI | 53 | Zone2TempSetpointAppliedUpLimitHeat_status | Zone 2 temperature setpoint applied upper limit heat (status) | °C | Read | |
| AI | 54 | Zone2TempSetpointAppliedLowLimitCool_status | Zone 2 temperature setpoint applied lower limit cool (status) | °C | Read | |
| AI | 55 | Zone2TempSetpointAppliedUpLimitCool_status | Zone 2 temperature setpoint applied upper limit cool (status) | °C | Read | |
| AI | 56 | Zone2TempRef_status | Zone 2 temperature reading (status) | °C | Read | |
| AO | 22 | Zone2TempBACnetRoomThermAmbientRef_command | Zone 2 temperature BMS room sensor ambient reading (command) | °C | Command | |
| AI | 58 | Zone2TempOutletWaterRef_status | Zone 2 temperature outlet water reading (status) | °C | Read | |
| AI | 59 | Zone2TempInletWaterRef_status | Zone 2 temperature inlet water reading (status) | °C | Read | |
| BI | 22 | DHWOnOff_status | DHW on/off (status) | Read | 0=Off, 1=On | |
| BOmin | 15 | DHWOnOff_command | DHW on/off (command) | Command | 0=Off, 1=On | |
| BI | 23 | DHWOperation_status | DHW operation (status) | Read | 0=Not Operating, 1=Operating | |
| AI | 61 | DHWTempSetpoint_status | DHW temperature setpoint (status) | °C | Read | |
| AOmin | 24 | DHWTempSetpoint_command | DHW temperature setpoint (command) | °C | Command | |
| AI | 62 | DHWTempSetpointCustomLowLimit_status | DHW temperature setpoint custom lower limit (status) | °C | Read | |
| AO | 25 | DHWTempSetpointCustomLowLimit_command | DHW temperature setpoint custom lower limit (command) | °C | Command | |
| AI | 63 | DHWTempSetpointCustomUpLimit_status | DHW temperature setpoint custom upper limit (status) | °C | Read | |
| AO | 26 | DHWTempSetpointCustomUpLimit_command | DHW temperature setpoint custom upper limit (command) | °C | Command | |
| AI | 64 | DHWTempSetpointTankLowLimit_status | DHW temperature setpoint tank lower limit (status) | °C | Read | |
| AI | 65 | DHWTempSetpointTankUpLimit_status | DHW temperature setpoint tank upper limit (status) | °C | Read | |
| AI | 66 | DHWTempSetpointAppliedLowLimit_status | DHW temperature setpoint applied lower limit (status) | °C | Read | |
| AI | 67 | DHWTempSetpointAppliedUpLimit_status | DHW temperature setpoint applied upper limit (status) | °C | Read | |
| AI | 68 | DHWTempTankRef_status | DHW temperature tank reading (status) | °C | Read | |
| BI | 26 | DHWEcoMode_status | DHW eco mode (status) | Read | 0=Off, 1=On | |
| BO | 18 | DHWEcoMode_command | DHW eco mode (command) | Command | 0=Off, 1=On | |
| BI | 29 | DHWPowerfulOperation_status | DHW powerful operation (status) | Read | 0=Off, 1=On | |
| BO | 21 | DHWPowerfulOperation_command | DHW powerful operation (command) | Command | 0=Off, 1=On | |
| BI | 30 | DHWDisinfectionMode_status | DHW disinfection mode (status) | Read | 0=Off, 1=On | |
| AI | 72 | TempA2WUnitOutdoorAmbientRef_status | Temperature heatpump unit outdoor ambient reading (status) | °C | Read | |
| AI | 73 | TempRefrigerantRef_status | Temperature refrigerant reading (status) | °C | Read | |
| AImin | 74 | TempOutletWaterRef_status | Temperature outlet water reading (status) | °C | Read | |
| AI | 76 | TempInletWaterRef_status | Temperature inlet water reading (status) | °C | Read | |
| BI | 31 | HolidayMode_status | Holiday mode (status) | Read | 0=Off, 1=On | |
| BO | 23 | HolidayMode_command | Holiday mode (command) | Command | 0=Off, 1=On | |
| BI | 33 | EmergencyOperation_status | Emergency operation (status) | Read | 0=Off, 1=On | |
| BI | 34 | DefrostStartUp_status | Defrost startup (status) | Read | 0=Defrost/Start Up, 1=Hot Start | |
| BI | 36 | ThreeWayValveOperation_status | Three way valve operation (status) | Read | 0=Climatize, 1=DHW | |
| BI | 37 | BackUpHeaterOperationLevel1_status | Backup heater operation level 1 (status) | Read | 0=Off, 1=On | |
| BI | 38 | BackUpHeaterOperationLevel2_status | Backup heater operation level 2 (status) | Read | 0=Off, 1=On | |
| BI | 40 | CompressorOperation_status | Compressor operation (status) | Read | 0=Off, 1=On | |
| AI | 77 | CompressorOperatingTime_status | Compressor operating time (status) | h | Read | |
| AO | 30 | CompressorOperatingTime_command | Compressor operating time (command) | h | Command | |
| BI | 41 | CirculationPumpOperation_status | Circulation pump operation (status) | Read | 0=Off, 1=On | |
| AI | 78 | CirculationPumpOperatingTime_status | Circulation pump operating time (status) | h | Read | |
| AO | 31 | CirculationPumpOperatingTime_command | Circulation pump operating time (command) | h | Command | |
| AI | 79 | WaterFlowRate_status | Water flow rate (status) | l/h | Read | |
| AI | 81 | EnergyConsumptionTotal_status | Energy consumption total (status) | kWh | Read | |
| AI | 82 | EnergyConsumptionZonesHeat_status | Energy consumption zones heat (status) | kWh | Read | |
| AI | 83 | EnergyConsumptionZonesCool_status | Energy consumption zones cool (status) | kWh | Read | |
| AI | 84 | EnergyConsumptionDHW_status | Energy consumption DHW (status) | kWh | Read | |
| BI | 45 | ZonesHeatModeSupport_status | Zones heat mode support (status) | Read | 0=No, 1=Yes | |
| BI | 46 | ZonesCoolModeSupport_status | Zones cool mode support (status) | Read | 0=No, 1=Yes | |
| BI | 47 | DHWSupport_status | DHW support (status) | Read | 0=No, 1=Yes |
No points match these filters.
Object ID lookup: Intesis Mitsubishi Electric Ecodan Gateway IN485MIT001A000 point IDs by name
AI0SerialNumberAI86DIP_SW_1_statusAI87DIP_SW_2_statusAI1IndoorUnitAddress_statusAO0IndoorUnitAddress_commandBI1ErrorFlag_statusAI2ErrorCode_statusAI3ErrorSubCode_statusBI3RefrigerantLeakDetectorSignalFlag_statusAI8OperatingTimeCountHour_statusBI4RemoteControlLock_statusBO3RemoteControlLock_commandBI5OnOff_statusBO4OnOff_commandBI6Operation_statusBI7ZonesOnOff_statusBI8ZonesOperation_statusMI0ZonesMode_statusMO0ZonesMode_commandBI10Zone1OnOff_statusBI11Zone1Operation_statusMI2Zone1ControlType_statusMO1Zone1ControlType_commandAI9Zone1TempSetpoint_statusAO3Zone1TempSetpoint_commandAI10Zone1TempSetpointLowCustomerLimitHeat_statusAO4Zone1TempSetpointLowCustomerLimitHeat_commandAI11Zone1TempSetpointUpCustomerLimitHeat_statusAO5Zone1TempSetpointUpCustomerLimitHeat_commandAI12Zone1TempSetpointLowCustomerLimitCool_statusAO6Zone1TempSetpointLowCustomerLimitCool_commandAI13Zone1TempSetpointUpCustomerLimitCool_statusAO7Zone1TempSetpointUpCustomerLimitCool_commandAI14Zone1TempSetpointUnitLowLimitHeat_statusAI15Zone1TempSetpointUnitUpLimitHeat_statusAI16Zone1TempSetpointUnitLowLimitCool_statusAI17Zone1TempSetpointUnitUpLimitCool_statusAI18Zone1TempSetpointAppliedLowLimitHeat_statusAI19Zone1TempSetpointAppliedUpLimitHeat_statusAI20Zone1TempSetpointAppliedLowLimitCool_statusAI21Zone1TempSetpointAppliedUpLimitCool_statusAI22Zone1TempRef_statusAO8Zone1TempBACnetRoomThermAmbientRef_commandAI24Zone1TempOutletWaterRef_statusAI25Zone1TempInletWaterRef_statusBI17Zone2OnOff_statusBI18Zone2Operation_statusMI5Zone2ControlType_statusMO3Zone2ControlType_commandAI43Zone2TempSetpoint_statusAO17Zone2TempSetpoint_commandAI44Zone2TempSetpointLowCustomerLimitHeat_statusAO18Zone2TempSetpointLowCustomerLimitHeat_commandAI45Zone2TempSetpointUpCustomerLimitHeat_statusAO19Zone2TempSetpointUpCustomerLimitHeat_commandAI46Zone2TempSetpointLowCustomerLimitCool_statusAO20Zone2TempSetpointLowCustomerLimitCool_commandAI47Zone2TempSetpointUpCustomerLimitCool_statusAO21Zone2TempSetpointUpCustomerLimitCool_commandAI48Zone2TempSetpointUnitLowLimitHeat_statusAI49Zone2TempSetpointUnitUpLimitHeat_statusAI50Zone2TempSetpointUnitLowLimitCool_statusAI51Zone2TempSetpointUnitUpLimitCool_statusAI52Zone2TempSetpointAppliedLowLimitHeat_statusAI53Zone2TempSetpointAppliedUpLimitHeat_statusAI54Zone2TempSetpointAppliedLowLimitCool_statusAI55Zone2TempSetpointAppliedUpLimitCool_statusAI56Zone2TempRef_statusAO22Zone2TempBACnetRoomThermAmbientRef_commandAI58Zone2TempOutletWaterRef_statusAI59Zone2TempInletWaterRef_statusBI22DHWOnOff_statusBO15DHWOnOff_commandBI23DHWOperation_statusAI61DHWTempSetpoint_statusAO24DHWTempSetpoint_commandAI62DHWTempSetpointCustomLowLimit_statusAO25DHWTempSetpointCustomLowLimit_commandAI63DHWTempSetpointCustomUpLimit_statusAO26DHWTempSetpointCustomUpLimit_commandAI64DHWTempSetpointTankLowLimit_statusAI65DHWTempSetpointTankUpLimit_statusAI66DHWTempSetpointAppliedLowLimit_statusAI67DHWTempSetpointAppliedUpLimit_statusAI68DHWTempTankRef_statusBI26DHWEcoMode_statusBO18DHWEcoMode_commandBI29DHWPowerfulOperation_statusBO21DHWPowerfulOperation_commandBI30DHWDisinfectionMode_statusAI72TempA2WUnitOutdoorAmbientRef_statusAI73TempRefrigerantRef_statusAI74TempOutletWaterRef_statusAI76TempInletWaterRef_statusBI31HolidayMode_statusBO23HolidayMode_commandBI33EmergencyOperation_statusBI34DefrostStartUp_statusBI36ThreeWayValveOperation_statusBI37BackUpHeaterOperationLevel1_statusBI38BackUpHeaterOperationLevel2_statusBI40CompressorOperation_statusAI77CompressorOperatingTime_statusAO30CompressorOperatingTime_commandBI41CirculationPumpOperation_statusAI78CirculationPumpOperatingTime_statusAO31CirculationPumpOperatingTime_commandAI79WaterFlowRate_statusAI81EnergyConsumptionTotal_statusAI82EnergyConsumptionZonesHeat_statusAI83EnergyConsumptionZonesCool_statusAI84EnergyConsumptionDHW_statusBI45ZonesHeatModeSupport_statusBI46ZonesCoolModeSupport_statusBI47DHWSupport_status
Integration notes
- The manual's object table has no read/write column. Access is inferred: AO/BO/MO command objects as commandable, inputs as read-only.
- Footnote numbers printed after some object names in the table (for example ErrorCode_status2) are not part of the name and were removed.
- ErrorCode_status (AI 2) shows the code as a Mitsubishi centralized controller shows it; ErrorSubCode_status (AI 3) shows it as the Ecodan unit shows it.
- Run-hour and flow counters roll back to 0 at 720896; energy counters at 2147483647 kWh.
- Temperatures follow the °C/°F setting on DIP switch SW2 position 8.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
How many BACnet points does the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) have?
This list has 115 BACnet objects: 58 analog inputs, 18 analog outputs, 27 binary inputs, 6 binary outputs, 3 multi-state inputs, 3 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) BACnet points are writable?
27 of the 115 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP) BACnet documentation?
The source is IN485MIT001A000 User Manual - Mitsubishi Electric Ecodan Air-to-Water Units to BACnet MS/TP and Modbus RTU, revision 2025-12-02 v1.0.3, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in485mit001a000.pdf.
What are the minimum BACnet points to integrate the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)?
Start with BO 4 OnOff_command (Turn the Ecodan system on/off); MO 0 ZonesMode_command (Heat or cool for both zones); BO 15 DHWOnOff_command (Domestic hot water on/off); AO 3 Zone1TempSetpoint_command (Zone 1 setpoint from the BMS); AO 24 DHWTempSetpoint_command (DHW tank setpoint); BI 5 OnOff_status (Confirms the system is on); AI 74 TempOutletWaterRef_status (Flow water temperature); BI 1 ErrorFlag_status (Unit alarm); AI 2 ErrorCode_status (Which fault is active).
How do I enable BMS control of the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)?
BO 3 RemoteControlLock_command = 1 lets only the BMS control the unit; remote-controller commands are then ignored.
Can the BMS supply sensor values to the Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)?
Write a BMS room temperature to AO 8 Zone1TempBACnetRoomThermAmbientRef_command (AO 22 for zone 2). Once a valid value is written, the gateway's Virtual Temperature function uses it to offset the setpoint.
How do I check these points on the real IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: IN485MIT001A000 User Manual - Mitsubishi Electric Ecodan Air-to-Water Units to BACnet MS/TP and Modbus RTU · rev. 2025-12-02 v1.0.3. Object names, instances and units are reproduced as published; descriptions are our own.