Split air conditioner BACnet gateway (1 indoor unit) · BACnet points list

Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP) BACnet points list

Updated 6 November 2026

Short answer

One-unit Intesis interface that plugs into the CN-CNT socket of a Panasonic Etherea/RAC indoor unit and serves it as BACnet MS/TP or BACnet IP (DIP switch). It exposes 35 objects: on/off, mode, setpoint, fan and both vane directions as _command/_status pairs, room temperature, power consumption, errors, run hours, occupancy logic, a remote lock and Panasonic extras (Powerful, Quiet, 8/10 °C freeze protection, ECONAVI/AutoComfort and the human-activity sensor).

This page lists 35 BACnet objects for the Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Equipment
Split air conditioner BACnet gateway (1 indoor unit)
Equipment type
VRF & split air conditioners
BACnet objects
35 (14 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
246000
Also known as
INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic
Brands covered
Panasonic
Source document
Intesis BACnet - Domestic Panasonic AC User Manual (INBACPAN001I000) · rev. 11/2024 v1.5
Download CSV 35 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.

BMS integration notes: Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)

Integration in brief

Plug the gateway into the indoor unit's CN-CNT socket with the supplied cable, choose BACnet MS/TP or BACnet IP on the DIP switch, set the MAC address or IP, then write the _command objects (on/off, mode, setpoint, fan) and read the _status objects. One gateway per indoor unit.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0OnOff_commandStart/stop the indoor unitCommand
MO 0Mode_commandHeat/cool/fan/dry/auto selectionCommand
AO 0SetPoint_commandTemperature setpoint from the BMSCommand
MO 1FanSpeed_commandFan speed selectionCommand
BI 0OnOff_statusConfirm the unit is runningRead
AI 0SetPoint_statusSetpoint the unit is really usingRead
AI 1RoomTemperatureRoom/return temperature for trendingRead
BI 1ErrorActiveUnit alarmRead
AI 2ErrorCodeWhich fault is activeRead

Enable & remote start

No enable point is documented. BV 2 LockRemoteControl locks the remote controller.

Network setup

Watch out for

Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

35 of 35 shown
Type
Access
Show
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP) BACnet Points List
DescriptionStates
BImin0OnOff_statusUnit on/off statusRead0=Off, 1=On
BOmin0OnOff_commandStart/stop the indoor unitCommand0=Off, 1=On
MI0Mode_statusOperating mode in useRead1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=AutoHeat, 6=AutoCool
MOmin0Mode_commandOperating mode commandCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin0SetPoint_statusSetpoint the indoor unit is using°CRead
AOmin0SetPoint_commandTemperature setpoint from the BMS°CCommand
MI1FanSpeed_statusCurrent fan speedRead1=Auto, 2=Low, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=High
MOmin1FanSpeed_commandFan speed commandCommand1=Auto, 2=Low, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=High
MI2AirDirectionUD_statusUp/down vane positionRead1=Auto, 2=Up, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Down
MO2AirDirectionUD_commandUp/down vane commandCommand1=Auto, 2=Up, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Down
MI3AirDirectionLR_statusLeft/right vane positionRead1=Auto, 2=Left, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Right
MO3AirDirectionLR_commandLeft/right vane commandCommand1=Auto, 2=Left, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Right
AImin1RoomTemperatureRoom temperature from the indoor unit sensor°CRead
AImin2ErrorCodeActive error code (number)Read
MI4ErrorCodeMActive error code (multistate)Read37 states; Panasonic error code table in the manual
BImin1ErrorActiveAn error is activeRead0=No, 1=Error
AV0OnTimeCounterRun-hours counterhRead
AI3PowerConsumptionIndoor unit power consumptionWRead
MV0OccupancyOccupancy input for built-in occupancy logicWrite1=Occupied, 2=Unoccupied, 3=Disabled
AV1OccupiedCoolSetPointCooling setpoint when occupied°CRead
AV2OccupiedHeatSetPointHeating setpoint when occupied°CRead
AV3UnoccupiedCoolSetPointCooling setpoint when unoccupied°CRead
AV4UnoccupiedHeatSetPointHeating setpoint when unoccupied°CRead
BV0OccupancyContinuousCheckRe-run occupancy logic on temperature changeWrite0=Disable, 1=Enable
BV1UnoccupiedDeadbandActionUnoccupied action inside the deadbandWrite0=Off, 1=CurrentMode
BV2LockRemoteControlLock the wired remote controllerWrite0=Locked, 1=Unlocked
BI2Powerful_statusPowerful mode statusRead0=Off, 1=On
BO1Powerful_commandPowerful mode commandCommand0=Off, 1=On
BI3Quiet_statusQuiet mode statusRead0=Off, 1=On
BO2Quiet_commandQuiet mode commandCommand0=Off, 1=On
BI4RoomFreezeProtection_status8/10 °C freeze protection statusRead0=Off, 1=On
BO3RoomFreezeProtection_command8/10 °C freeze protection commandCommand0=Off, 1=On
MI5EcoMode_statusEco mode statusRead1=Off, 2=ECONAVI, 3=AutoComfort
MO4EcoMode_commandEco mode commandCommand1=Off, 2=ECONAVI, 3=AutoComfort
BI5HumanActivityHuman activity sensorRead0=No, 1=Yes
Object ID lookup: Intesis Panasonic Gateway INBACPAN001I000 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)

How many BACnet points does the Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP) have?

This list has 35 BACnet objects: 4 analog inputs, 1 analog output, 5 analog values, 6 binary inputs, 4 binary outputs, 3 binary values, 6 multi-state inputs, 5 multi-state outputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP) BACnet points are writable?

14 of the 35 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP) BACnet documentation?

The source is Intesis BACnet - Domestic Panasonic AC User Manual (INBACPAN001I000), revision 11/2024 v1.5, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacpan001i000.pdf.

What are the minimum BACnet points to integrate the Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)?

Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).

How do I enable BMS control of the Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)?

No enable point is documented. BV 2 LockRemoteControl locks the remote controller.

How do I check these points on the real INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: Intesis BACnet - Domestic Panasonic AC User Manual (INBACPAN001I000) · rev. 11/2024 v1.5. Object names, instances and units are reproduced as published; descriptions are our own.