VRF / split air conditioner BACnet gateway (1 indoor unit or group) · BACnet points list
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) BACnet points list
Updated 6 November 2026
Intesis interface for one Daikin Sky or VRV indoor unit on the P1P2 remote-controller bus that serves BACnet MS/TP or BACnet IP (selected on a DIP switch). The member table lists 31 objects: on/off, mode, setpoint, fan and up/down vane as _command/_status pairs, room temperature, error signals, run hours, filter sign and reset, occupancy logic, a remote lock, indoor coil pipe temperatures, EEV opening and thermo-on status.
This page lists 31 BACnet objects for the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
- Equipment
- VRF / split air conditioner BACnet gateway (1 indoor unit or group)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 31 (11 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 246000
- Also known as
- INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV
- Brands covered
- Daikin
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Connect the gateway anywhere on the P1P2 bus, pick BACnet MS/TP or BACnet IP on its DIP switch, set the MAC address or IP, then write the _command objects (on/off, mode, setpoint, fan) and read the _status objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 0 | OnOff_command | Start/stop the indoor unit | Command |
| MO 0 | Mode_command | Heat/cool/fan/dry/auto selection | Command |
| AO 0 | SetPoint_command | Temperature setpoint from the BMS | Command |
| MO 1 | FanSpeed_command | Fan speed selection | Command |
| BI 0 | OnOff_status | Confirm the unit is running | Read |
| AI 0 | SetPoint_status | Setpoint the unit is really using | Read |
| AI 1 | RoomTemperature_status | Room/return temperature for trending | Read |
| BI 1 | ErrorActive | Unit alarm | Read |
| AI 2 | ErrorCode | Which fault is active | Read |
Enable & remote start
No enable point is documented. BV 2 LockRemoteControl locks the wired remote.
Sensors & values from the BMS
AO 1 RoomTemperature_command only works with the gateway set as P1P2 master and SW4 set to controller reference temperature; RoomTemperature_status then follows the written value. As slave, the command object is disabled.
Network setup
- A DIP switch selects BACnet MS/TP (default) or BACnet IP; switch changes apply after a power cycle.
- BACnet IP: factory static IP 192.168.100.246; change it or select DHCP in the configuration tool.
- Default device instance 246000; in automatic mode it is a base address + the SW2 address.
- A DIP switch sets the gateway as slave (default) or master on the P1P2 bus; a Daikin wired remote must take the other role. With Daikin IR remotes the gateway must be master.
Watch out for
- The Occupancy MV drives built-in logic; leave it at 3 (Disabled) if the BMS handles scheduling.
- Write the _command object and read the _status object.
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 0 | OnOff_status | Unit on/off status | Read | 0=Off, 1=On | |
| BOmin | 0 | OnOff_command | Start/stop the indoor unit | Command | 0=Off, 1=On | |
| MI | 0 | Mode_status | Operating mode in use | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool, 8=AutoFan | |
| MOmin | 0 | Mode_command | Operating mode command | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 0 | SetPoint_status | Setpoint the indoor unit is using | °C | Read | |
| AOmin | 0 | SetPoint_command | Temperature setpoint from the BMS | °C | Command | |
| MI | 1 | FanSpeed_status | Current fan speed | Read | 1=Auto, 2=Low, 3=Mid, 4=High (legacy table: 1=Low, 2=Mid, 3=High, 6=Auto) | |
| MOmin | 1 | FanSpeed_command | Fan speed command | Command | 1=Auto, 2=Low, 3=Mid, 4=High (legacy table: 1=Low, 2=Mid, 3=High, 6=Auto) | |
| MI | 2 | AirDirectionUD_status | Up/down vane position | Read | 1=Up, 2=Mid-1, 3=Mid-2, 4=Mid-3, 5=Down, 6=Swing, 7=Stop | |
| MO | 2 | AirDirectionUD_command | Up/down vane command | Command | 1=Up, 2=Mid-1, 3=Mid-2, 4=Mid-3, 5=Down, 6=Swing | |
| AImin | 1 | RoomTemperature_status | Room temperature used by the unit | °C | Read | |
| AO | 1 | RoomTemperature_command | Room temperature written by the BMS | °C | Command | |
| AImin | 2 | ErrorCode | Active error code (number) | Read | ||
| MI | 4 | ErrorCodeM | Active error code (multistate) | Read | 156 states; Daikin error code table in the manual | |
| BImin | 1 | ErrorActive | An error is active | Read | 0=No, 1=Error | |
| AI | 4 | ErrorAddress | Address of the indoor unit reporting the error | Read | ||
| AV | 0 | OnTimeCounter | Run-hours counter | h | Read | |
| BI | 6 | FilterSign | Filter dirty signal | Read | ||
| BO | 4 | FilterReset | Reset the filter signal | Command | ||
| MV | 0 | Occupancy | Occupancy input for built-in occupancy logic | Write | 1=Occupied, 2=Unoccupied, 3=Disabled | |
| AV | 1 | OccupiedCoolSetPoint | Cooling setpoint when occupied | °C | Read | |
| AV | 2 | OccupiedHeatSetPoint | Heating setpoint when occupied | °C | Read | |
| AV | 3 | UnoccupiedCoolSetPoint | Cooling setpoint when unoccupied | °C | Read | |
| AV | 4 | UnoccupiedHeatSetPoint | Heating setpoint when unoccupied | °C | Read | |
| BV | 0 | OccupancyContinuousCheck | Re-run occupancy logic on temperature change | Write | 0=Disabled, 1=Enabled | |
| BV | 1 | UnoccupiedDeadbandAction | Unoccupied action inside the deadband | Write | 0=Off, 1=CurrentMode | |
| BV | 2 | LockRemoteControl | Lock the wired remote controller | Write | 0=Unlocked, 1=Locked | |
| AI | 5 | IndoorLiquidPipeTemp | Indoor coil liquid pipe temperature | Read | ||
| AI | 6 | IndoorGasPipeTemp | Indoor coil gas pipe temperature | Read | ||
| AI | 7 | IndoorEEVOpening | Indoor unit expansion valve opening | Read | ||
| BI | 7 | ThermostatON | Unit is actively heating or cooling (thermo on) | Read | 0=Off, 1=On |
No points match these filters.
Object ID lookup: Intesis Daikin VRV Gateway INBACDAI001R000 point IDs by name
BI0OnOff_statusBO0OnOff_commandMI0Mode_statusMO0Mode_commandAI0SetPoint_statusAO0SetPoint_commandMI1FanSpeed_statusMO1FanSpeed_commandMI2AirDirectionUD_statusMO2AirDirectionUD_commandAI1RoomTemperature_statusAO1RoomTemperature_commandAI2ErrorCodeMI4ErrorCodeMBI1ErrorActiveAI4ErrorAddressAV0OnTimeCounterBI6FilterSignBO4FilterResetMV0OccupancyAV1OccupiedCoolSetPointAV2OccupiedHeatSetPointAV3UnoccupiedCoolSetPointAV4UnoccupiedHeatSetPointBV0OccupancyContinuousCheckBV1UnoccupiedDeadbandActionBV2LockRemoteControlAI5IndoorLiquidPipeTempAI6IndoorGasPipeTempAI7IndoorEEVOpeningBI7ThermostatON
Integration notes
- The manual's property tables show Present_Value as R for every object; output objects (AO/BO/MO) have a priority array and are shown here as commandable. The occupancy setpoint AVs are shown read-only as printed; the manual describes setting them in the configuration tool.
- FilterSign, FilterReset, IndoorLiquidPipeTemp, IndoorGasPipeTemp and IndoorEEVOpening are in the member table but have no property table, so their state texts and units are not stated.
- ThermostatON is printed as 'Thermostat ON' in the member table; the name here follows Object_Name.
- Fan speed states change if 'Legacy Fan speed' is selected in the configuration tool.
- Different product from the IN485DAI001R000 (MS/TP and Modbus RTU), which is listed separately.
- Temperature objects follow the °C/°F DIP switch (SW3).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
How many BACnet points does the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) have?
This list has 31 BACnet objects: 7 analog inputs, 2 analog outputs, 5 analog values, 4 binary inputs, 2 binary outputs, 3 binary values, 4 multi-state inputs, 3 multi-state outputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) BACnet points are writable?
11 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) BACnet documentation?
The source is Intesis BACnet - SKY & VRV line User Manual (INBACDAI001R000), revision 09/2024 v1.8, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacdai001r000.pdf.
What are the minimum BACnet points to integrate the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)?
Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).
How do I enable BMS control of the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)?
No enable point is documented. BV 2 LockRemoteControl locks the wired remote.
Can the BMS supply sensor values to the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)?
AO 1 RoomTemperature_command only works with the gateway set as P1P2 master and SW4 set to controller reference temperature; RoomTemperature_status then follows the written value. As slave, the command object is disabled.
How do I check these points on the real INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: Intesis BACnet - SKY & VRV line User Manual (INBACDAI001R000) · rev. 09/2024 v1.8. Object names, instances and units are reproduced as published; descriptions are our own.