Easy BACnet
  1. Home
  2. BACnet points lists
  3. Intesis
  4. INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)

VRF / split air conditioner BACnet gateway (1 indoor unit or group) · BACnet points list

Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) BACnet points list

Updated 6 November 2026

Short answer

Intesis interface for one Daikin Sky or VRV indoor unit on the P1P2 remote-controller bus that serves BACnet MS/TP or BACnet IP (selected on a DIP switch). The member table lists 31 objects: on/off, mode, setpoint, fan and up/down vane as _command/_status pairs, room temperature, error signals, run hours, filter sign and reset, occupancy logic, a remote lock, indoor coil pipe temperatures, EEV opening and thermo-on status.

This page lists 31 BACnet objects for the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Equipment
VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Equipment type
VRF & split air conditioners
BACnet objects
31 (11 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
246000
Also known as
INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV
Brands covered
Daikin
Source document
Intesis BACnet - SKY & VRV line User Manual (INBACDAI001R000) · rev. 09/2024 v1.8
Download CSV 31 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.

BMS integration notes: Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)

Integration in brief

Connect the gateway anywhere on the P1P2 bus, pick BACnet MS/TP or BACnet IP on its DIP switch, set the MAC address or IP, then write the _command objects (on/off, mode, setpoint, fan) and read the _status objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0OnOff_commandStart/stop the indoor unitCommand
MO 0Mode_commandHeat/cool/fan/dry/auto selectionCommand
AO 0SetPoint_commandTemperature setpoint from the BMSCommand
MO 1FanSpeed_commandFan speed selectionCommand
BI 0OnOff_statusConfirm the unit is runningRead
AI 0SetPoint_statusSetpoint the unit is really usingRead
AI 1RoomTemperature_statusRoom/return temperature for trendingRead
BI 1ErrorActiveUnit alarmRead
AI 2ErrorCodeWhich fault is activeRead

Enable & remote start

No enable point is documented. BV 2 LockRemoteControl locks the wired remote.

Sensors & values from the BMS

AO 1 RoomTemperature_command only works with the gateway set as P1P2 master and SW4 set to controller reference temperature; RoomTemperature_status then follows the written value. As slave, the command object is disabled.

Network setup

Watch out for

Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

31 of 31 shown
Type
Access
Show
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) BACnet Points List
DescriptionStates
BImin0OnOff_statusUnit on/off statusRead0=Off, 1=On
BOmin0OnOff_commandStart/stop the indoor unitCommand0=Off, 1=On
MI0Mode_statusOperating mode in useRead1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool, 8=AutoFan
MOmin0Mode_commandOperating mode commandCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin0SetPoint_statusSetpoint the indoor unit is using°CRead
AOmin0SetPoint_commandTemperature setpoint from the BMS°CCommand
MI1FanSpeed_statusCurrent fan speedRead1=Auto, 2=Low, 3=Mid, 4=High (legacy table: 1=Low, 2=Mid, 3=High, 6=Auto)
MOmin1FanSpeed_commandFan speed commandCommand1=Auto, 2=Low, 3=Mid, 4=High (legacy table: 1=Low, 2=Mid, 3=High, 6=Auto)
MI2AirDirectionUD_statusUp/down vane positionRead1=Up, 2=Mid-1, 3=Mid-2, 4=Mid-3, 5=Down, 6=Swing, 7=Stop
MO2AirDirectionUD_commandUp/down vane commandCommand1=Up, 2=Mid-1, 3=Mid-2, 4=Mid-3, 5=Down, 6=Swing
AImin1RoomTemperature_statusRoom temperature used by the unit°CRead
AO1RoomTemperature_commandRoom temperature written by the BMS°CCommand
AImin2ErrorCodeActive error code (number)Read
MI4ErrorCodeMActive error code (multistate)Read156 states; Daikin error code table in the manual
BImin1ErrorActiveAn error is activeRead0=No, 1=Error
AI4ErrorAddressAddress of the indoor unit reporting the errorRead
AV0OnTimeCounterRun-hours counterhRead
BI6FilterSignFilter dirty signalRead
BO4FilterResetReset the filter signalCommand
MV0OccupancyOccupancy input for built-in occupancy logicWrite1=Occupied, 2=Unoccupied, 3=Disabled
AV1OccupiedCoolSetPointCooling setpoint when occupied°CRead
AV2OccupiedHeatSetPointHeating setpoint when occupied°CRead
AV3UnoccupiedCoolSetPointCooling setpoint when unoccupied°CRead
AV4UnoccupiedHeatSetPointHeating setpoint when unoccupied°CRead
BV0OccupancyContinuousCheckRe-run occupancy logic on temperature changeWrite0=Disabled, 1=Enabled
BV1UnoccupiedDeadbandActionUnoccupied action inside the deadbandWrite0=Off, 1=CurrentMode
BV2LockRemoteControlLock the wired remote controllerWrite0=Unlocked, 1=Locked
AI5IndoorLiquidPipeTempIndoor coil liquid pipe temperatureRead
AI6IndoorGasPipeTempIndoor coil gas pipe temperatureRead
AI7IndoorEEVOpeningIndoor unit expansion valve openingRead
BI7ThermostatONUnit is actively heating or cooling (thermo on)Read0=Off, 1=On
Object ID lookup: Intesis Daikin VRV Gateway INBACDAI001R000 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)

How many BACnet points does the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) have?

This list has 31 BACnet objects: 7 analog inputs, 2 analog outputs, 5 analog values, 4 binary inputs, 2 binary outputs, 3 binary values, 4 multi-state inputs, 3 multi-state outputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) BACnet points are writable?

11 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP) BACnet documentation?

The source is Intesis BACnet - SKY & VRV line User Manual (INBACDAI001R000), revision 09/2024 v1.8, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacdai001r000.pdf.

What are the minimum BACnet points to integrate the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)?

Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).

How do I enable BMS control of the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)?

No enable point is documented. BV 2 LockRemoteControl locks the wired remote.

Can the BMS supply sensor values to the Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)?

AO 1 RoomTemperature_command only works with the gateway set as P1P2 master and SW4 set to controller reference temperature; RoomTemperature_status then follows the written value. As slave, the command object is disabled.

How do I check these points on the real INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: Intesis BACnet - SKY & VRV line User Manual (INBACDAI001R000) · rev. 09/2024 v1.8. Object names, instances and units are reproduced as published; descriptions are our own.