- IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
VRF BACnet IP gateway (up to 64 or 128 indoor units) · BACnet points list
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) BACnet points list
Updated 12 November 2026Unofficial source
An older IntesisBox BACnet IP server that connects to one Panasonic CZ-CFUNC2 adaptor and publishes gateway-wide commands plus a fixed block of objects for each indoor unit, up to 64 or 128 units depending on model. Indoor unit instances are (unit number x 256) + offset, so unit 1 uses 256-289. Setup is done with the LinkBoxBACnet tool.
This page lists 36 BACnet objects for the Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Intesis’s documentation hosted by Chipkin Automation Systems, not by Intesis itself, so treat it as unofficial.
- Manufacturer
- Intesis
- Model
- IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
- Equipment
- VRF BACnet IP gateway (up to 64 or 128 indoor units)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 36 (19 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 246
- Also known as
- IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
- Source document
- IntesisBox BACnet/IP - Panasonic AC User Manual r2.1 (PA-AC-BAC-64/128) · rev. r2.1 (unofficial copy, hosted by Chipkin Automation Systems)
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Connect the IntesisBox to the CZ-CFUNC2 adaptor and the BACnet IP LAN, configure the indoor units in LinkBoxBACnet, then map each unit's _command and _status objects from its (unit x 256) block. Instances 18-29 act on all units at once.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 258 | IUxxx_OnOff_command | Start/stop indoor unit | Write |
| MO 260 | IUxxx_Mode_command | Mode command | Write |
| AO 262 | IUxxx_SetPoint_command | Setpoint command | Write |
| MO 265 | IUxxx_FanSpeed_command | Fan speed command (4 = auto) | Write |
| BI 257 | IUxxx_OnOff_status | Run status | Read |
| AI 261 | IUxxx_SetPoint_status | Setpoint in use | Read |
| AI 263 | IUxxx_Room_Temperature | Room temperature | Read |
| BI 256 | IUxxx_IU_Exist | Unit found on the adaptor | Read |
| MI 270 | IUxxx_ErrorCode | Fault code | Read |
Enable & remote start
No enable point is documented. Remote-controller functions can be locked per unit (MV 271) or for all units (MO 22).
Network setup
- Default device instance 246; device instance, name and IP are set with LinkBoxBACnet.
- One IntesisBox integrates one CZ-CFUNC2 adaptor (bought separately from Panasonic), which has two links of up to 30 outdoor and 64 indoor units each.
Watch out for
- OnOff_All, Mode_All, SetPoint_All, FanSpeed_All and the occupancy objects (instances 18-29) act on every indoor unit.
- Outputs only use Priority_Array slot 16; slots 1-15 stay NULL.
- State_Text cannot be read as a whole array; read one array index at a time.
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| DEV | 246 | Panasonic AC Gateway | Gateway device object (instance configurable) | Read | ||
| MI | 16 | AdaptorLink1_ErrorCode | CZ-CFUNC2 link 1 error code | Read | 1-259 = Panasonic error codes (A01...); see manual | |
| MI | 17 | AdaptorLink2_ErrorCode | CZ-CFUNC2 link 2 error code | Read | 1-259 = Panasonic error codes (A01...); see manual | |
| BO | 18 | OnOff_All | On/off for all indoor units | Write | ||
| MO | 19 | Mode_All | Mode for all indoor units | Write | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AO | 20 | SetPoint_All | Setpoint for all indoor units, -15 to 60 °C | °C / °F | Write | |
| MO | 21 | FanSpeed_All | Fan speed for all indoor units | Write | 1=Low, 2=Medium, 3=High, 4=Auto | |
| MO | 22 | RemoteControl_Lock_All | Remote controller lock for all units | Write | 1-32 = combinations of locked functions (OO on/off, OM mode, SP setpoint, AD air direction, FS fan speed); see manual table | |
| MO | 23 | Occupancy_All | Occupancy function for all units | Write | 1=Occupied, 2=Unoccupied, 3=Disabled | |
| AV | 24 | Occ_Cool_SetPoint | Occupied cooling setpoint | °C / °F | Write | |
| AV | 25 | Occ_Heat_SetPoint | Occupied heating setpoint | °C / °F | Write | |
| AV | 26 | Unocc_Cool_SetPoint | Unoccupied cooling setpoint | °C / °F | Write | |
| AV | 27 | Unocc_Heat_SetPoint | Unoccupied heating setpoint | °C / °F | Write | |
| BO | 28 | Occ_ContinuousCheck | Keep checking setpoint and occupancy continuously | Write | ||
| BO | 29 | Unocc_DeadbandAction | Action when unoccupied and inside the deadband | Write | ||
| BO | 34 | Consumption_Reset | Reset consumption counters | Write | ||
| BImin | 256 | IUxxx_IU_Exist | Indoor unit present | Read | ||
| BImin | 257 | IUxxx_OnOff_status | Run status | Read | ||
| BOmin | 258 | IUxxx_OnOff_command | Start/stop command | Write | ||
| MI | 259 | IUxxx_Mode_status | Operating mode | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=AutoHeat, 6=AutoCool | |
| MOmin | 260 | IUxxx_Mode_command | Mode command | Write | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 261 | IUxxx_SetPoint_status | Setpoint in use | °C / °F | Read | |
| AOmin | 262 | IUxxx_SetPoint_command | Setpoint command, -15 to 60 °C | °C / °F | Write | |
| AImin | 263 | IUxxx_Room_Temperature | Room temperature at the indoor unit sensor | °C / °F | Read | |
| MI | 264 | IUxxx_FanSpeed_status | Fan speed | Read | 1=Low, 2=Medium, 3=High, 4=Auto | |
| MOmin | 265 | IUxxx_FanSpeed_command | Fan speed command | Write | 1=Low, 2=Medium, 3=High, 4=Auto | |
| MI | 266 | IUxxx_AirDirection_status | Air direction (louver) | Read | 1=Horizontal, 2=Pos2, 3=Pos3, 4=Pos4, 5=Vertical, 6=Swing, 7=Off/Auto | |
| MO | 267 | IUxxx_AirDirection_command | Air direction command | Write | 1=Horizontal, 2=Pos2, 3=Pos3, 4=Pos4, 5=Vertical, 6=Swing, 7=Off/Auto | |
| BI | 268 | IUxxx_FilterSign_status | Filter sign | Read | ||
| BO | 269 | IUxxx_FilterSign_Reset_command | Filter sign reset | Write | ||
| MImin | 270 | IUxxx_ErrorCode | Indoor unit error code | Read | 1-259 = Panasonic error codes (A01...); see manual | |
| MV | 271 | IUxxx_RemoteControl_Lock | Remote controller lock for this unit | Read | 1-32 = combinations of locked functions (OO on/off, OM mode, SP setpoint, AD air direction, FS fan speed); see manual table | |
| MV | 286 | IUxxx_Occupancy | Occupancy function for this unit | Read | 1=Occupied, 2=Unoccupied, 3=Disabled | |
| AI | 287 | IUxxx_Consumption_Yesterday | Consumption yesterday | kW (as printed) | Read | |
| AI | 288 | IUxxx_Consumption_Today | Consumption today | kW (as printed) | Read | |
| AI | 289 | IUxxx_Consumption_Total | Total consumption | kW (as printed) | Read |
No points match these filters.
Object ID lookup: Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 point IDs by name
MI16AdaptorLink1_ErrorCodeMI17AdaptorLink2_ErrorCodeBO18OnOff_AllMO19Mode_AllAO20SetPoint_AllMO21FanSpeed_AllMO22RemoteControl_Lock_AllMO23Occupancy_AllAV24Occ_Cool_SetPointAV25Occ_Heat_SetPointAV26Unocc_Cool_SetPointAV27Unocc_Heat_SetPointBO28Occ_ContinuousCheckBO29Unocc_DeadbandActionBO34Consumption_ResetBI256IUxxx_IU_ExistBI257IUxxx_OnOff_statusBO258IUxxx_OnOff_commandMI259IUxxx_Mode_statusMO260IUxxx_Mode_commandAI261IUxxx_SetPoint_statusAO262IUxxx_SetPoint_commandAI263IUxxx_Room_TemperatureMI264IUxxx_FanSpeed_statusMO265IUxxx_FanSpeed_commandMI266IUxxx_AirDirection_statusMO267IUxxx_AirDirection_commandBI268IUxxx_FilterSign_statusBO269IUxxx_FilterSign_Reset_commandMI270IUxxx_ErrorCodeMV271IUxxx_RemoteControl_LockMV286IUxxx_OccupancyAI287IUxxx_Consumption_YesterdayAI288IUxxx_Consumption_TodayAI289IUxxx_Consumption_Total
Integration notes
- Indoor unit objects are shown for unit 1 only. Instance = (xxx x 256) + offset, xxx = indoor unit number 1-128. Object names start with IUxxx; the description text carries the link, outdoor and indoor address (K-OA-IA).
- This older product talks to the CZ-CFUNC2 adaptor. The newer Intesis INBACPAN016O000/064O000/128O000 (P-Link) uses a different object set. The PA-AC-BAC-64/128 names are also used for that newer product, so check the gateway model before mapping.
- Occupancy_All instance 23 and Consumption_Reset 34 come from the object-detail pages; the member-objects table prints the instance column one row off.
- The setpoint command AOs' property tables mark Present_Value R; they are listed as writable here because they are the setpoint commands. IUxxx_RemoteControl_Lock and IUxxx_Occupancy are printed R; check on site.
- Temperature units follow the gateway setting (°C or °F). Consumption units are printed as kilowatts.
- Error code states are a long Panasonic code table (A01, C12, E23 ...) in the manual and are not reproduced here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
How many BACnet points does the Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) have?
This list has 36 BACnet objects: 5 analog inputs, 2 analog outputs, 4 analog values, 3 binary inputs, 6 binary outputs, 1 device, 6 multi-state inputs, 7 multi-state outputs, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) BACnet points are writable?
19 of the 36 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) BACnet documentation?
Intesis does not publish it on its own website. This list comes from IntesisBox BACnet/IP - Panasonic AC User Manual r2.1 (PA-AC-BAC-64/128), revision r2.1, a copy hosted by Chipkin Automation Systems at https://cdn.chipkin.com/assets/uploads/2018/feb/08-02-04-48_intesisbox_pa-ac-bac-64-128_user_manual_en.pdf. Ask Intesis or its representative for the current revision.
What are the minimum BACnet points to integrate the Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)?
Start with BO 258 IUxxx_OnOff_command (Start/stop indoor unit); MO 260 IUxxx_Mode_command (Mode command); AO 262 IUxxx_SetPoint_command (Setpoint command); MO 265 IUxxx_FanSpeed_command (Fan speed command (4 = auto)); BI 257 IUxxx_OnOff_status (Run status); AI 261 IUxxx_SetPoint_status (Setpoint in use); AI 263 IUxxx_Room_Temperature (Room temperature); BI 256 IUxxx_IU_Exist (Unit found on the adaptor); MI 270 IUxxx_ErrorCode (Fault code).
How do I enable BMS control of the Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)?
No enable point is documented. Remote-controller functions can be locked per unit (MV 271) or for all units (MO 22).
How do I check these points on the real IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway
Source: IntesisBox BACnet/IP - Panasonic AC User Manual r2.1 (PA-AC-BAC-64/128) · rev. r2.1. Object names, instances and units are reproduced as published; descriptions are our own.