 "manufacturer": "Intesis",
 "manufacturer_slug": "intesis",
 "model": "IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)",
 "model_slug": "pa-ac-bac-64-128-cz-cfunc2",
 "aliases": [
  "IntesisBox BACnet/IP Panasonic AC",
  "CZ-CFUNC2 BACnet",
  "Panasonic CZ-CFUNC2 BACnet gateway"
 ],
 "equipment_type": "VRF BACnet IP gateway (up to 64 or 128 indoor units)",
 "applies_to": "Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).",
 "summary": "An older IntesisBox BACnet IP server that connects to one Panasonic CZ-CFUNC2 adaptor and publishes gateway-wide commands plus a fixed block of objects for each indoor unit, up to 64 or 128 units depending on model. Indoor unit instances are (unit number x 256) + offset, so unit 1 uses 256-289. Setup is done with the LinkBoxBACnet tool.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": 246,
 "access_inferred": false,
 "notes": [
  "Indoor unit objects are shown for unit 1 only. Instance = (xxx x 256) + offset, xxx = indoor unit number 1-128. Object names start with IUxxx; the description text carries the link, outdoor and indoor address (K-OA-IA).",
  "This older product talks to the CZ-CFUNC2 adaptor. The newer Intesis INBACPAN016O000/064O000/128O000 (P-Link) uses a different object set. The PA-AC-BAC-64/128 names are also used for that newer product, so check the gateway model before mapping.",
  "Occupancy_All instance 23 and Consumption_Reset 34 come from the object-detail pages; the member-objects table prints the instance column one row off.",
  "The setpoint command AOs' property tables mark Present_Value R; they are listed as writable here because they are the setpoint commands. IUxxx_RemoteControl_Lock and IUxxx_Occupancy are printed R; check on site.",
  "Temperature units follow the gateway setting (°C or °F). Consumption units are printed as kilowatts.",
  "Error code states are a long Panasonic code table (A01, C12, E23 ...) in the manual and are not reproduced here."
 ],
 "source": {
  "title": "IntesisBox BACnet/IP - Panasonic AC User Manual r2.1 (PA-AC-BAC-64/128)",
  "doc_number": null,
  "revision_date": "r2.1",
  "url": "https://cdn.chipkin.com/assets/uploads/2018/feb/08-02-04-48_intesisbox_pa-ac-bac-64-128_user_manual_en.pdf",
  "unofficial": true,
  "host": "Chipkin Automation Systems"
 },
 "integration": {
  "summary": "Connect the IntesisBox to the CZ-CFUNC2 adaptor and the BACnet IP LAN, configure the indoor units in LinkBoxBACnet, then map each unit's _command and _status objects from its (unit x 256) block. Instances 18-29 act on all units at once.",
  "minimum_points": [
   {
    "ref": "BO 258",
    "name": "IUxxx_OnOff_command",
    "why": "Start/stop indoor unit"
   },
   {
    "ref": "MO 260",
    "name": "IUxxx_Mode_command",
    "why": "Mode command"
   },
   {
    "ref": "AO 262",
    "name": "IUxxx_SetPoint_command",
    "why": "Setpoint command"
   },
   {
    "ref": "MO 265",
    "name": "IUxxx_FanSpeed_command",
    "why": "Fan speed command (4 = auto)"
   },
   {
    "ref": "BI 257",
    "name": "IUxxx_OnOff_status",
    "why": "Run status"
   },
   {
    "ref": "AI 261",
    "name": "IUxxx_SetPoint_status",
    "why": "Setpoint in use"
   },
   {
    "ref": "AI 263",
    "name": "IUxxx_Room_Temperature",
    "why": "Room temperature"
   },
   {
    "ref": "BI 256",
    "name": "IUxxx_IU_Exist",
    "why": "Unit found on the adaptor"
   },
   {
    "ref": "MI 270",
    "name": "IUxxx_ErrorCode",
    "why": "Fault code"
   }
  ],
  "enable": "No enable point is documented. Remote-controller functions can be locked per unit (MV 271) or for all units (MO 22).",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Default device instance 246; device instance, name and IP are set with LinkBoxBACnet.",
   "One IntesisBox integrates one CZ-CFUNC2 adaptor (bought separately from Panasonic), which has two links of up to 30 outdoor and 64 indoor units each."
  ],
  "gotchas": [
   "OnOff_All, Mode_All, SetPoint_All, FanSpeed_All and the occupancy objects (instances 18-29) act on every indoor unit.",
   "Outputs only use Priority_Array slot 16; slots 1-15 stay NULL.",
   "State_Text cannot be read as a whole array; read one array index at a time."
  ]
 },
 "points": [
  {
   "type": "DEV",
   "instance": 246,
   "name": "Panasonic AC Gateway",
   "description": "Gateway device object (instance configurable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 16,
   "name": "AdaptorLink1_ErrorCode",
   "description": "CZ-CFUNC2 link 1 error code",
   "units": "",
   "access": "R",
   "states": "1-259 = Panasonic error codes (A01...); see manual"
  },
  {
   "type": "MI",
   "instance": 17,
   "name": "AdaptorLink2_ErrorCode",
   "description": "CZ-CFUNC2 link 2 error code",
   "units": "",
   "access": "R",
   "states": "1-259 = Panasonic error codes (A01...); see manual"
  },
  {
   "type": "BO",
   "instance": 18,
   "name": "OnOff_All",
   "description": "On/off for all indoor units",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MO",
   "instance": 19,
   "name": "Mode_All",
   "description": "Mode for all indoor units",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto"
  },
  {
   "type": "AO",
   "instance": 20,
   "name": "SetPoint_All",
   "description": "Setpoint for all indoor units, -15 to 60 °C",
   "units": "°C / °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "MO",
   "instance": 21,
   "name": "FanSpeed_All",
   "description": "Fan speed for all indoor units",
   "units": "",
   "access": "W",
   "states": "1=Low, 2=Medium, 3=High, 4=Auto"
  },
  {
   "type": "MO",
   "instance": 22,
   "name": "RemoteControl_Lock_All",
   "description": "Remote controller lock for all units",
   "units": "",
   "access": "W",
   "states": "1-32 = combinations of locked functions (OO on/off, OM mode, SP setpoint, AD air direction, FS fan speed); see manual table"
  },
  {
   "type": "MO",
   "instance": 23,
   "name": "Occupancy_All",
   "description": "Occupancy function for all units",
   "units": "",
   "access": "W",
   "states": "1=Occupied, 2=Unoccupied, 3=Disabled"
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Occ_Cool_SetPoint",
   "description": "Occupied cooling setpoint",
   "units": "°C / °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Occ_Heat_SetPoint",
   "description": "Occupied heating setpoint",
   "units": "°C / °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Unocc_Cool_SetPoint",
   "description": "Unoccupied cooling setpoint",
   "units": "°C / °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Unocc_Heat_SetPoint",
   "description": "Unoccupied heating setpoint",
   "units": "°C / °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 28,
   "name": "Occ_ContinuousCheck",
   "description": "Keep checking setpoint and occupancy continuously",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 29,
   "name": "Unocc_DeadbandAction",
   "description": "Action when unoccupied and inside the deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 34,
   "name": "Consumption_Reset",
   "description": "Reset consumption counters",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 256,
   "name": "IUxxx_IU_Exist",
   "description": "Indoor unit present",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 257,
   "name": "IUxxx_OnOff_status",
   "description": "Run status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 258,
   "name": "IUxxx_OnOff_command",
   "description": "Start/stop command",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 259,
   "name": "IUxxx_Mode_status",
   "description": "Operating mode",
   "units": "",
   "access": "R",
   "states": "1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=AutoHeat, 6=AutoCool"
  },
  {
   "type": "MO",
   "instance": 260,
   "name": "IUxxx_Mode_command",
   "description": "Mode command",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto"
  },
  {
   "type": "AI",
   "instance": 261,
   "name": "IUxxx_SetPoint_status",
   "description": "Setpoint in use",
   "units": "°C / °F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 262,
   "name": "IUxxx_SetPoint_command",
   "description": "Setpoint command, -15 to 60 °C",
   "units": "°C / °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 263,
   "name": "IUxxx_Room_Temperature",
   "description": "Room temperature at the indoor unit sensor",
   "units": "°C / °F",
   "access": "R",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 264,
   "name": "IUxxx_FanSpeed_status",
   "description": "Fan speed",
   "units": "",
   "access": "R",
   "states": "1=Low, 2=Medium, 3=High, 4=Auto"
  },
  {
   "type": "MO",
   "instance": 265,
   "name": "IUxxx_FanSpeed_command",
   "description": "Fan speed command",
   "units": "",
   "access": "W",
   "states": "1=Low, 2=Medium, 3=High, 4=Auto"
  },
  {
   "type": "MI",
   "instance": 266,
   "name": "IUxxx_AirDirection_status",
   "description": "Air direction (louver)",
   "units": "",
   "access": "R",
   "states": "1=Horizontal, 2=Pos2, 3=Pos3, 4=Pos4, 5=Vertical, 6=Swing, 7=Off/Auto"
  },
  {
   "type": "MO",
   "instance": 267,
   "name": "IUxxx_AirDirection_command",
   "description": "Air direction command",
   "units": "",
   "access": "W",
   "states": "1=Horizontal, 2=Pos2, 3=Pos3, 4=Pos4, 5=Vertical, 6=Swing, 7=Off/Auto"
  },
  {
   "type": "BI",
   "instance": 268,
   "name": "IUxxx_FilterSign_status",
   "description": "Filter sign",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 269,
   "name": "IUxxx_FilterSign_Reset_command",
   "description": "Filter sign reset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 270,
   "name": "IUxxx_ErrorCode",
   "description": "Indoor unit error code",
   "units": "",
   "access": "R",
   "states": "1-259 = Panasonic error codes (A01...); see manual"
  },
  {
   "type": "MV",
   "instance": 271,
   "name": "IUxxx_RemoteControl_Lock",
   "description": "Remote controller lock for this unit",
   "units": "",
   "access": "R",
   "states": "1-32 = combinations of locked functions (OO on/off, OM mode, SP setpoint, AD air direction, FS fan speed); see manual table"
  },
  {
   "type": "MV",
   "instance": 286,
   "name": "IUxxx_Occupancy",
   "description": "Occupancy function for this unit",
   "units": "",
   "access": "R",
   "states": "1=Occupied, 2=Unoccupied, 3=Disabled"
  },
  {
   "type": "AI",
   "instance": 287,
   "name": "IUxxx_Consumption_Yesterday",
   "description": "Consumption yesterday",
   "units": "kW (as printed)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 288,
   "name": "IUxxx_Consumption_Today",
   "description": "Consumption today",
   "units": "kW (as printed)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 289,
   "name": "IUxxx_Consumption_Total",
   "description": "Total consumption",
   "units": "kW (as printed)",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/intesis/pa-ac-bac-64-128-cz-cfunc2",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}